Schneider Electric MNB-300 Installation Instructions

MNB-300
Dimensions shown are in inches (mm).
2
(50.8)
4
(101.6)
7 (177.8)
2
(50.8)
3-1/2 (88.9)
MicroNet BACnet
Unitary Controller
Installation Instructions
Application
The I/A Series® MicroNet™ BACnet an interoperable controller with native BACnet, IP, and MS/TP communications support. The controller features Sensor Link (S-Link) support, LED status and output indication, screw terminal blocks, as well as a panel mount sub-base with removable electronics module.
When programmed using WorkPlace Tech Tool, the Unitary Controller provides a wide range of control strategies for packaged rooftop, heat pump, fan coil, unit ventilator, and similar applications.
®
Unitary Controller is
Model Chart
Model
Number
MNB‑300 6 3 6
Inputs and Outputs
UI UO DO (Triacs)
Installation
Inspection
Inspect carton for damage. If damaged, notify carrier immediately. Inspect controllers for damage upon receipt.
Precautions
When installing the MNB-300 controller, be sure to follow the guidelines outlined in “Precautions” on page 4.
Location
The MNB-300 controller is suitable for indoor use only. The mounting location must clear the maximum dimensions of the
controller case and allow sufcient clearance for access to
wiring terminals.
Caution:
Avoid locations where excessive moisture, corrosive
fumes, vibration, or explosive vapors are present.
Avoid electrical noise interference. Do not install near
large contactors, electrical machinery, or welding equipment.
Locate where ambient temperatures do not exceed
140°F (60°C) or fall below -40°F (-40°C) and relative humidity does not exceed 85% or fall below 5%, non­condensing.
Dimensions
Mounting dimensions for the MNB-300 controller are shown in Figure-1. Refer to Figure-3 for mounting dimensions for optional enclosure MNB-300-ENC.
Requirements
Installer must be a qualied technician
The following items are not provided.
Job wiring diagrams
Tools:
– Drill and bits for mounting screws – Screw drivers – Nut drivers – Digital Volt-ohm meter (DVM) – Static protection wrist strap
MNB-300-ENC enclosure for wall-mounting (optional)
Class 2 power transformer supplying a nominal 12 VA at
24 Vac plus DO load; in European Community, transformer must conform to EN 60742
Four #10 pan head screws for wall-mounting
Four #10 pan head screws for panel-mounting
If needed, end-of-line termination resistor, 120 W ±5%,
part number 40-1758
Schneider Electric
F-27345 -4 May 2014
Figure-1 Mounting Dimensions.
Input
Board
Controller
Base Plate
Mounting Hole (1 of 4)
Base of Optional
Enclosure
MNB-300-ENC
Threaded Studs for
Mounting Controller
(1 of 4)
(part of enclosure base)
#10 Pan Head
Screw (1 of 4)
(not supplied)
#10 Pan Head
Screw (1 of 4) (not supplied)
Mounting Hole
(1 of 4)
Thumb Screws
(1 of 4)
Output Board
7 Tighten the four thumb screws
CW to secure the input and output boards in place.
6 Press on the aluminum tabs to slide the input and output boards
into the controller, making sure the mating connectors engage fully.
Note: The connectors are properly
engaged when the gap between the controller and the input and output boards is even and minimal from top to bottom.
5 Position the controller onto the
base plate.
4 Be sure the input and output
boards are spread apart as far as possible. If needed, loosen the four thumb screws by turning them CCW and then reposition the boards.
1 Select a mounting location. The MNB-300 may be panel-
mounted or, optionally, enclosure-mounted. To panel­mount the MNB-300, go to Step 2. To mount the MNB-300 inside optional Enclosure MNB-300-ENC, go to Step 3.
Note: The MNB-300 may be mounted in any orientation.
2 To mount the MNB-300 to a panel, proceed as follows:
a. Holding the controller's base plate in position, mark
the locations of the four mounting holes on the panel
.
b. Set the base plate aside and drill the marked
mounting holes, using a drill bit sized to the mounting screws.
c.
Secure the base plate to the panel, using four #10 screws (not supplied).
d.
Continue at Step 4.
3 Optional To mount the MNB-300 inside Enclosure
MNB-300-ENC, proceed as follows:
a. Separate the enclosure cover from the enclosure
base.
b. Holding the enclosure's base in position on the
wall, mark the locations of the four mounting holes.
c. Set the enclosure base aside and drill the marked
mounting holes, using a drill bit sized to the mounting screws
.
d.
Secure the enclosure base to the wall, using four #10 screws (not supplied).
e.
Mount the controller's base plate onto the four threaded studs on the enclosure's base. Secure the base plate, using four #6-32 nuts (provided)
.
f.
Continue at Step 4.
Aluminum
Tab (1 of 2)
Connectors
Tab
Slot
Mounting
2
Mount the controller to the wall according to Figure-2.
Warning: Electrical shock hazard! Disconnect power before installing or removing the cover.
Schneider Electric
F-27345 -4 May 2014
Figure-2 MNB-300 Mounting.
Dimensions shown are in inches (mm).
10-1/2 (267)
2-1/4
(57)
6-1/8
(156)
3
(76)
9-1/4 (235)
Enclosure
Cover
Enclosure
Base
I/A Series
®
1 1
1
1 Outside dimensions of the enclosure cover.
Optional Enclosure
3
Optionally, the MNB-300 may be mounted inside an enclosure. Refer to Figure-3 for mounting dimensions for enclosure MNB-300-ENC.
Figure-3 Enclosure MNB-300-ENC Mounting Dimensions.
DIP Switch
Each MicroNet BACnet controller is equipped with a DIP switch for setting the controller’s MS/ TP network address. Once the address is set, the network is properly wired, and all routers are
congured, WorkPlace Tech Tool (must be version 5.0 or greater) and other Schneider Electric
tools will be able to “see” and work with all the networked BACnet devices. For guidance in assigning a DIP switch setting that will optimize system performance, refer to the WorkPlace Tech Tool 5.0 Engineering Guide Supplement, F-27356.
Other BACnet Devices
The UNC and other BACnet devices on the network can work with the MicroNet BACnet
controller once they are assigned unique identiers and names. MicroNet BACnet controllers are congured in this way through the Commissioning Tool.
Note: The logical addressing of devices (i.e. the assignment of unique identiers and names) is
not a prerequisite for using Invensys network management tools. It is, however, a prerequisite for using the UNC and third-party BACnet devices with MicroNet BACnet controllers.
EOL Termination
The MNB-300 is equipped with a jumper-selectable end-of-line (EOL) termination resistor. The default position for the EOL jumper is “EOL termination not present.” If the controller is at the end-of-line, set termination according to the MicroNet BACnet Wiring and Networking Practices Guide, F-27360.
Note: If another device is at the end-of-line on the MS/TP trunk, use an end-of-line termination resistor, 120 W ±5%, part number 40-1758.
Schneider Electric
F-27345 -4 May 2014
Installation Completion
Finish installing the MNB‑300 controller by performing the wiring and network conguration
tasks outlined in the MicroNet BACnet Wiring and Networking Practices Guide, F-27360. Information covered in this Guide include:
Communications wiring Logical addressing of devices
– MicroNet BACnet wiring
– Sensor Link (S-Link) wiring
Conguration of routers
Communications hardware checkout
Input/Output wiring Troubleshooting
Power supply wiring A list of related documentation
Mechanical hardware checkout
Precautions
General
Warning: Electrical shock hazard! Disconnect power before installing or removing the cover.
Follow Static Precautions (below) when installing this equipment.
Use copper conductors that are suitable for 167°F (75°C).
Make all connections according to electrical wiring diagram, national and local electrical
codes.
Static Precautions
Static charges damage electronic components. The microprocessor and associated circuitry are extremely sensitive to static discharge. Use the following precautions when installing, servicing, or operating the system.
Work in a static-free area.
Discharge static electricity by touching a known, securely grounded object.
Use a wrist strap connected to earth ground when handling the controller’s printed circuit
board.
Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a resdential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
Canadian Department of Communications (DOC)
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
European Community Directives
This equipment meets all requirements of European Community Directives for Low Voltage (72/23/EEC), General Safety (92/59/EEC), and Electromagnetic Compatibility (89/336/EEC).
Schneider Electric
F-27345 -4 May 2014
© 2014 Schneider Electric. All rights reserved.
Loading...