Schneider Electric MNA01M001EN User Manual

Page 1

LXM32

Common DC bus Application note
MNA01M001EN, V1.01, 08.2014
MNA01M001EN, V1.01, 08.2014
www.schneider-electric.com
Page 2
LXM32
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or relia­bility of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any sugges­tions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety require­ments, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operat­ing results.
Failure to observe this information can result in injury or equipment damage.
© 2013 Schneider Electric. All rights reserved.
2 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 3
LXM32 Table of contents

Table of contents

Table of contents 3
Safety Information 5
Hazard categories 5
Qualification of personnel 6
Intended use 6
Basic information 7
DC bus voltage measurement 9
Standards and terminology 9
About the book 11
1 Introduction 13
1.1 Permissible device types for common DC bus 14
2 Technical Data 15
2.1 Firmware version 15
2.2 DC bus data 16
2.3 Braking resistor 17
2.3.1 External braking resistors (accessories) 19
2.4 Cables for the DC bus 20
3 Engineering 21
3.1 Energy balance 22
3.1.1 Energy balance basics 22
3.2 Electromagnetic compatibility (EMC) 24
3.3 DC bus connection 24
3.4 Fuses 25
3.4.1 DC bus connection of single-phase drives 25
3.4.2 DC bus connection of three-phase drives 27
3.4.3 Supply via the DC bus 29
3.5 Braking resistors 32
3.5.1 Rating the braking resistor 32
3.5.2 Rating information 34
3.6 Mains reactor 36
3.7 Mains filter 38
3.8 Mains reactor and external mains filter 39
4 Installation 41
MNA01M001EN, V1.01, 08.2014
Common DC bus 3
Page 4
Table of contents LXM32
4.1 Assembling cables 42
4.2 Wiring the DC bus 45
4.2.1 Drives with connectors 45
4.2.2 Drives with terminals 47
4.2.3 Connecting the DC bus 48
4.3 Verifying installation 49
5 Commissioning 51
5.1 Commissioning procedure 52
5.1.1 DC bus connection LXM32 to LXM32 52
5.1.2 Supply via the DC bus 53
5.2 LXM32: Setting the braking resistor parameters 54
6 Accessories and spare parts 55
6.1 DC bus accessories 55
6.2 DC fuses 55
6.3 External braking resistors 56
Glossary 57
Units and conversion tables 57
Length 57 Mass 57 Force 57 Power 57 Rotation 58 Torque 58 Moment of inertia 58 Temperature 58 Conductor cross section 58
Terms and Abbreviations 59
Table of figures 61
Index 63
4 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 5
LXM32

Safety Information

Safety Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a proce­dure.
The addition of this symbol to a Danger safety label indi­cates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

Hazard categories

Safety instructions to the user are highlighted by safety alert symbols in the manual. In addition, labels with symbols and/or instructions are attached to the product that alert you to potential hazards.
Depending on the seriousness of the hazard, the safety instructions are divided into 4 hazard categories.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
NOTICE
NOTICE indicates a potentially hazardous situation, which, if not avoided, can result in equipment damage.
MNA01M001EN, V1.01, 08.2014
Common DC bus 5
Page 6
Safety Information

Qualification of personnel

Intended use

LXM32
Only appropriately trained persons who are familiar with and under­stand the contents of this manual and all other pertinent product docu­mentation are authorized to work on and with this product. In addition, these persons must have received safety training to recognize and avoid hazards involved. These persons must have sufficient technical training, knowledge and experience and be able to foresee and detect potential hazards that may be caused by using the product, by chang­ing the settings and by the mechanical, electrical and electronic equip­ment of the entire system in which the product is used.
All persons working on and with the product must be fully familiar with all applicable standards, directives, and accident prevention regula­tions when performing such work.
The functions described in this document are only intended for use for the products described in this document.
The product may only be used in compliance with all applicable safety regulations and directives, the specified requirements and the techni­cal data.
Prior to using the product, you must perform a risk assessment in view of the planned application. Based on the results, the appropriate safety measures must be implemented.
Since the product is used as a component in an entire system, you must ensure the safety of persons by means of the design of this entire system (for example, machine design).
Operate the product only with the specified cables and accessories. Use only genuine accessories and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in hazards.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
6 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 7
LXM32
Safety Information

Basic information

DANGER
HAZARD DUE TO ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.
Many components of the product, including the printed circuit board, operate with mains voltage. Do not touch. Use only electri­cally insulated tools.
Do not touch unshielded components or terminals with voltage present.
The motor itself generates voltage when the motor shaft is rota­ted. Block the motor shaft to prevent rotation prior to performing any type of work on the drive system.
AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
Do not short across the DC bus terminals or the DC bus capaci­tors.
Before performing work on the drive system:
- Disconnect all power, including external control power that
may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge.
Measure the voltage on the DC bus as per chapter "DC bus voltage measurement" and verify the voltage is <42 Vdc. The DC bus LED is not an indicator of the absence of DC bus volt­age.
Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or seri­ous injury.
MNA01M001EN, V1.01, 08.2014
Common DC bus 7
Page 8
Safety Information
LXM32
WARNING
LOSS OF CONTROL
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop, overtravel stop, power outage and restart.
Separate or redundant control paths must be provided for critical functions.
System control paths may include communication links. Consider­ation must be given to the implication of unanticipated transmis­sion delays or failures of the link.
Observe all accident prevention regulations and local safety guidelines.
Each implementation of the product must be individually and thor­oughly tested for proper operation before being placed into serv­ice.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1)
1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems”.
8 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 9
LXM32
Safety Information

DC bus voltage measurement

The DC bus voltage can exceed 800 Vdc. The DC bus LED is not an indicator of the absence of DC bus voltage.
DANGER
ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect the voltage supply to all connections.
Wait 15 minutes to allow the DC bus capacitors to discharge.
Use a properly rated voltage-sensing device for measuring (>800 Vdc).
Measure the DC bus voltage between the DC bus terminals (PA/+ and PC/-) to verify that the voltage is less than 42 Vdc.
Contact your local Schneider Electric representative if the DC bus capacitors do not discharge to less than 42 Vdc within a period of 15 minutes.
Do not operate the product if the DC bus capacitors do not dis­charge properly.
Do not attempt to repair the product if the DC bus capacitors do not discharge properly.
Failure to follow these instructions will result in death or seri­ous injury.

Standards and terminology

Technical terms, terminology and the corresponding descriptions in this manual are intended to use the terms or definitions of the perti­nent standards.
In the area of drive systems, this includes, but is not limited to, terms such as "safety function", "safe state", "fault", "fault reset", "failure", "error", "error message", "warning", etc.
Among others, these standards include:
IEC 61800 series: "Adjustable speed electrical power drive sys­tems"
IEC 61158 series: "Digital data communications for measurement and control – Fieldbus for use in industrial control systems"
IEC 61784 series: "Industrial communication networks – Profiles"
IEC 61508 series: "Functional safety of electrical/electronic/ programmable electronic safety-related systems"
Also see the glossary at the end of this manual.
MNA01M001EN, V1.01, 08.2014
Common DC bus 9
Page 10
Safety Information
LXM32
10 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 11
LXM32

About the book

Source manuals The latest versions of the manuals can be downloaded from the Inter-
Work steps If work steps must be performed consecutively, this sequence of steps
About the book
This document describes how several Schneider Electric drives type LXM32 can share a common DC bus. This application note replaces application note MNA01D001.
The information provided in this document supplements the manuals. Before beginning, fully read and understand the manuals of the prod­ucts used.
net at:
http://www.schneider-electric.com
is represented as follows:
Special prerequisites for the following work steps
Step 1
Specific response to this work step
Step 2
If a response to a work step is indicated, this allows you to verify that the work step has been performed correctly.
Unless otherwise stated, the individual steps must be performed in the specified sequence.
Making work easier Information on making work easier is highlighted by this symbol:
Sections highlighted this way provide supplementary information on making work easier.
SI units Technical data are specified in SI units. Converted units are shown in
parentheses behind the SI unit; they may be rounded.
Example: Minimum conductor cross section: 1.5 mm2 (AWG 14)
Glossary Explanations of special technical terms and abbreviations.
Index List of keywords with references to the corresponding page numbers.
MNA01M001EN, V1.01, 08.2014
Common DC bus 11
Page 12
About the book
LXM32
12 Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 13
LXM32
1 Introduction
Use of electrical energy If an application operates with multiple drive systems, it may be useful
Common DC bus Whether or not a common DC bus makes sense depends on the

1 Introduction

A drive system requires energy for acceleration or constant movement that must be supplied to the system.
During deceleration, a motor acts as a generator. A considerable por­tion of the kinetic energy is re-generated as electrical energy.
Since electrical energy can only be stored to a limited extent in a sin­gle drive, a drive uses a braking resistor to transform the excess energy into thermal energy.
to employ a common DC bus. By sharing a common DC bus, the energy regenerated by one drive can be supplied to another drive.
acceleration and deceleration cycles of the drive systems.
A common DC bus is useful, for example, if one drive systems accel­erates while another drive system decelerates.
If the drive systems accelerate and decelerate at the same time, a common DC bus does not make sense.
MNA01M001EN, V1.01, 08.2014
Common DC bus 13
Page 14
1 Introduction

1.1 Permissible device types for common DC bus

The DC bus of drives with identical numbers of mains phases can be connected.
Single-phase drives:
LXM32∙∙∙∙M2 with LXM32∙∙∙∙M2
Three-phase drives:
LXM32∙∙∙∙N4 with LXM32∙∙∙∙N4
LXM32
14
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 15
LXM32
2 Technical Data

2.1 Firmware version

2 Technical Data

A common DC bus requires the devices to have at least the specified firmware versions:
Drive Firmware version
LXM32C, LXM32A V01.04.00
LXM32M V01.02.00
MNA01M001EN, V1.01, 08.2014
Common DC bus
15
Page 16
2 Technical Data
LXM32

2.2 DC bus data

Single-phase drives
LXM32... U45M2 U90M2 D18M2 D30M2
Nominal voltage (1 ) V 115 230 115 230 115 230 115 230
Nominal voltage DC bus V 163 325 163 325 163 325 163 325
Undervoltage limit V 55 130 55 130 55 130 55 130
Voltage limit: activation of Quick Stop V 60 140 60 140 60 140 60 140
Overvoltage limit V 450 450 450 450 450 450 450 450
Maximum continuous power via DC bus kW 0.2 0.5 0.4 0.9 0.8 1.6 0.8 2.2
Maximum continuous current via DC bus A 1.5 1.5 3.2 3.2 6.0 6.0 10.0 10.0
Three-phase drives
LXM32... U60N4 D12N4 D18N4 D30N4 D72N4 D85N4 C10N4
Nominal voltage (3 ) V 208 208 208 208 208 208 208
Nominal voltage DC bus V 294 294 294 294 294 294 294
Undervoltage limit V 150 150 150 150 150 150 150
Voltage limit: activation of Quick Stop V 160 160 160 160 160 160 160
Overvoltage limit V 820 820 820 820 820 820 820
Maximum continuous power via DC bus kW 0.4 0.8 1.7 2.8 6.5 7.0 11.0
Maximum continuous current via DC bus A 1.5 3.2 6.0 10.0 22.0 28.0 40.0
LXM32... U60N4 D12N4 D18N4 D30N4 D72N4 D85N4 C10N4
Nominal voltage (3 ) V 400 400 400 400 400 400 400
Nominal voltage DC bus V 566 566 566 566 566 566 566
Undervoltage limit V 350 350 350 350 350 350 350
Voltage limit: activation of Quick Stop V 360 360 360 360 360 360 360
Overvoltage limit V 820 820 820 820 820 820 820
Maximum continuous power via DC bus kW 0.8 1.6 3.3 5.6 13.0 15.0 22.0
Maximum continuous current via DC bus A 1.5 3.2 6.0 10.0 22.0 28.0 40.0
LXM32... U60N4 D12N4 D18N4 D30N4 D72N4 D85N4 C10N4
Nominal voltage (3 ) V 480 480 480 480 480 480 480
Nominal voltage DC bus V 679 679 679 679 679 679 679
Undervoltage limit V 350 350 350 350 350 350 350
Voltage limit: activation of Quick Stop V 360 360 360 360 360 360 360
Overvoltage limit V 820 820 820 820 820 820 820
Maximum continuous power via DC bus kW 0.8 1.6 3.3 5.6 13.0 15.0 22.0
Maximum continuous current via DC bus A 1.5 3.2 6.0 10.0 22.0 28.0 40.0
16
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 17
LXM32
2 Technical Data

2.3 Braking resistor

LXM32 drives have an internal braking resistor and a connection for an external braking resistor. If the internal braking resistor is insuffi­cient for the dynamics of the application, one or more external braking resistors must be connected.
Single-phase drives
LXM32... U45M2 U90M2 D18M2 D30M2
Resistance value of internal braking resistor
Continuous power internal braking resis­tor P
PR
Peak energy E
CR
External braking resistor minimum
External braking resistor maximum
1)
Maximum continuous power external braking resistor
Capacitance of internal capacitor μF 390 780 1170 1560
Parameter DCbus_compat = 0 (default value)
Switch-on voltage braking resistor V 430 430 430 430
Energy absorption of internal capacitors E
at nominal voltage 115 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 200 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 230 V +10%
var
Parameter DCbus_compat = 1 (reduced switch-on voltage)
Switch-on voltage braking resistor V 395 395 395 395
Energy absorption of internal capacitors E
at nominal voltage 115 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 200 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 230 V +10%
var
1) The maximum specified braking resistor can derate the peak power of the device. Depending on the application, it is possible to use a higher ohm resistor.
Ω
94 47 20 10
W 10 20 40 60
Ws 82 166 330 550
Ω
68 36 20 10
Ω
110 55 27 16
W 200 400 600 800
Ws 30 60 89 119
Ws 17 34 52 69
Ws 11 22 33 44
Ws 24 48 73 97
Ws 12 23 35 46
Ws 5 11 16 22
MNA01M001EN, V1.01, 08.2014
Common DC bus
17
Page 18
2 Technical Data
LXM32
Three-phase drives
LXM32... U60N4 D12N4 D18N4 D30N4 D72N4 D85N4 C10N4
Resistance value of internal braking resis­tor
Continuous power internal braking resis­tor P
PR
Peak energy E
CR
External braking resistor minimum
External braking resistor maximum
1)
Maximum continuous power external braking resistor
Capacitance of internal capacitor μF 110 195 390 560 1120 1230 1230
Parameter DCbus_compat
2)
Switch-on voltage V 780 780 780 780 780 780 780
Energy absorption of internal capacitors E
at nominal voltage 208 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 380 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 400 V +10%
var
Energy absorption of internal capacitors E
at nominal voltage 480 V +10%
var
1) The maximum specified braking resistor can derate the peak power of the device. Depending on the application, it is possible to use a higher ohm resistor.
2) Parameter DCbus_compat has no effect in the case of three-phase devices
Ω
132 60 30 30 10 10 10
W 20 40 60 100 150 150 150
Ws 200 400 600 1000 2400 2400 2400
Ω
70 47 25 15 8 8 8
Ω
145 73 50 30 12 11 11
W 200 500 800 1500 3000 4500 5500
Ws 28 49 98 141 282 310 310
Ws 14 25 50 73 145 159 159
Ws 12 22 43 62 124 136 136
Ws 3 5 10 14 28 31 31
18
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 19
LXM32

2.3.1 External braking resistors (accessories)

The resistance values for external braking resistors must not be below the minimum resistance specified for the drives.
2 Technical Data
VW3A760... 1Rxx
Resistance
Continuous power W 400 100 200 400 100 200 400
Maximum time in braking at 115 V / 230 V
Peak power at 115 V / 230 V kW 18.5 6.8 6.8 6.8 2.6 2.6 2.6
Maximum peak energy at 115 V / 230 V Ws 13300 3800 7400 18100 3700 9600 24700
Maximum time in braking at 400 V / 480 V
Peak power at 400 V / 480 V kW 60.8 22.5 22.5 22.5 8.5 8.5 8.5
Maximum peak energy at 400 V / 480 V Ws 7300 1900 4900 11400 2500 6600 16200
Degree of protection IP65 IP65 IP65 IP65 IP65 IP65 IP65
UL approval (file no.) - E233422 E233422 - E233422 E233422 -
1) Resistors with a continuous power of 400 W are not UL/CSA-approved.
VW3A77... 04 05
Resistance
Continuous power W 1000 1000
Maximum time in braking at 115 V / 230 V
Peak power at 115 V / 230 V kW 12.3 18.5
Maximum peak energy at 115 V / 230 V Ws 43100 36500
Maximum time in braking at 400 V / 480 V
Peak power at 400 V / 480 V kW 40.6 60.8
Maximum peak energy at 400 V / 480 V Ws 26500 22500
Degree of protection IP20 IP20
UL approval (file no.) E221095 E221095
Ω
s 0.72 0.552 1.08 2.64 1.44 3.72 9.6
s 0.12 0.084 0.216 0.504 0.3 0.78 1.92
Ω
s 3.5 1.98
s 0.65 0.37
1)
2Rxx 3Rxx 4Rxx
10 27 27 27 72 72 72
15 10
1)
5Rxx 6Rxx 7Rxx
1)
MNA01M001EN, V1.01, 08.2014
Common DC bus
19
Page 20
2 Technical Data

2.4 Cables for the DC bus

Minimum requirement A cable for the common DC bus must meet the following require-
ments.
Shield: Shielded at cable lengths of > 0.2 m
Twisted Pair: Twisted pair at cable lengths of >
Cable: Two wires, shielded
Maximum cable length between 2 drives:
Special characteristics: Insulation must be rated for the
The connection of the fuses for the DC bus must be rated for the total maximum continuous current on the DC bus of all drives connected via the DC bus. Analyze the most critical case in your application (for example EMERGENCY STOP) and select an appropriate conductor cross section.
LXM32
0.2 m
3 m
DC bus voltage
Conductor cross section accord­ing to the calculated current, but at least 2* 6 mm2 (2* AWG 10)
20
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 21
LXM32
3 Engineering

3 Engineering

This chapter provides engineering information for a common DC bus for several drives.
Incorrect use of the DC bus may permanently damage the drives either immediately or over time.
WARNING
DESTRUCTION OF SYSTEM COMPONENTS AND LOSS OF CONTROL
Verify that all requirements for using the DC bus are met.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
DESTRUCTION OF SYSTEM COMPONENTS
Connect only drives with identical nominal voltages.
Connect single-phase drives only to single-phase drives. Connect single-phase drives to the same phase.
Connect three-phase drives only to three-phase drives.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
MNA01M001EN, V1.01, 08.2014
Common DC bus
21
Page 22
3 Engineering

3.1 Energy balance

3.1.1 Energy balance basics

LXM32
To be able to estimate the effect of an interconnection of drives via a common DC bus, create an energy balance of the individual drives over a movement cycle. A movement cycle typically consists of the fol­lowing phases: acceleration, continuous movement and deceleration.
The energy generated during deceleration can be used by other drives connected via a common DC bus. Excess energy can be absorbed by the braking resistors.
The assessment of the energy balances of the individual drives per movement cycle and of the cyclic sequence of the movement cycles allows you to draw a conclusion regarding the efficiency of a common DC bus.
The energy balance is influenced by the following factors:
Energy absorption of the capaci-
tors E
var
Electrical losses EelThe electrical losses Eel of the drive system can be estimated on the
Mechanical losses E
mech
Energy absorption of capacitors E
Electrical losses of the drive system E
Mechanical losses of the facility and the drive system E
Braking resistor E
B
in the drive
var
el
mech
The higher the mains voltage, the lower the energy absorption of the capacitors E
. In your calculation, use the values for the highest
var
mains voltage that is used in your application, see chapter "2.3 Braking resistor".
The energy absorption of the capacitors E
is the square difference
var
between the voltage prior to the start of the deceleration and the switch-on voltage of the braking resistor.
basis of the peak power of the drive. The maximum power dissipation is approximately 10% of the peak power at a typical efficiency of 90%. If the current during deceleration is lower, the power dissipation is reduced accordingly.
The mechanical losses result from friction during operation of the sys­tem. Mechanical losses are negligible if the time required by the sys­tem to coast to a stop without a driving force is considerably longer than the time required to decelerate the system. The mechanical los­ses can be calculated from the load torque and the velocity from which the motor is to stop.
22
Braking resistor EBTwo characteristic values determine the energy absorption of a brak-
ing resistor:
The continuous power PPR is the amount of energy that can be continuously absorbed without overloading the braking resistor.
The maximum energy ECR limits the maximum short-term power that can be absorbed.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 23
v
I
t
t
D
i
n
i
2
60
ω
i
2
= Ei =J
t
1 2
J
t
1 2
LXM32
3 Engineering
Rating
Figure 1: Movement cycle: Profile for energy assessment
This profile with velocity (v) and motor current (I) is also used for rating the motor and the braking resistor. The deceleration segment to be considered is labeled Di.
Calculation of the energy at constant deceleration:
The total inertia (Jt) must be known.
Jt with:
Jt = Jm + J
c
Jm: Motor inertia with or without holding brake
Jc: Load inertia
The energy for each deceleration segment is calculated as follows:
Units: Ei in Ws (wattseconds), Jt in kgm2, ω in rad and ni in min-1.
See the technical data for the energy absorption E (without consideration of an internal or external braking resistor).
In the next calculation steps, only consider those segments Di, whose energy Ei exceeds the energy absorption of the device (see chapter
of the devices
var
"2.2 DC bus data"). These excess energies EDi must be diverted by means of the braking resistor (internal or external).
MNA01M001EN, V1.01, 08.2014
Common DC bus
EDi is calculated using the following formula:
EDi = Ei - E
(in Ws)
var
The continuous power Pc is calculated for each machine cycle:
23
Page 24
Pc =
Σ
E
Di
Cycletime
3 Engineering
Units: Pc in W, EDi in Ws and cycle time T in s
These calculations allow you to select the required braking resistor.

3.2 Electromagnetic compatibility (EMC)

If drives are to be operated via a common DC bus, the following aspects must be considered in terms of EMC:
Keep DC bus cables as short as possible.
Shielded DC bus cables must be used at a cable length of > 0.2 m. In the case of shielded DC bus cables, connect the cable shield to the shield connection (large surface area contact).

3.3 DC bus connection

LXM32
The DC bus is connected by means of a plug and socket connection or screw terminals. See the manual of the respective product for tightening torque of the screw terminals.
Cable specifications See chapter "2.4 Cables for the DC bus", page 20 for the cable speci-
fications. Connector kits and pre-assembled cables can be found in chapter "6 Accessories and spare parts", page 55.
24
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 25
PC/- PA/+ PC/- PA/+ PC/- PA/+
DC+ DC
-
N/L2
L1
N/L2 L1 N/L2 L1 N/L2 L1
LXM32

3.4 Fuses

The number of mains fuses depends on the input current of all drives connected via the common DC bus.
Choose fuse ratings as low as possible according to the power of the drive as well as the conductor cross section.
See manual of the respective product for more information.
The maximum permissible fuse ratings must not be exceeded.

3.4.1 DC bus connection of single-phase drives

Single mains fuse A single mains fuse is sufficient if the total input current of all drives
connected via the common DC bus is less than the maximum fuse rat­ing shown in the table below.
Single mains fuse Maximum fuse rating
LXM32∙∙∙∙M2 A 25
3 Engineering
MNA01M001EN, V1.01, 08.2014
Common DC bus
Figure 2: Single mains fuse for single-phase drives
25
Page 26
N/L2 L1
N/L2
L1
N/L2 L1N/L2 L1
PC/- PA/+ PC/- PA/+ PC/- PA/+
DC+ DC
-
3 Engineering
Multiple mains fuses Multiple mains fuses are required if the total input current of all drives
LXM32
connected via the common DC bus exceeds the maximum fuse rating shown in the table below.
Multiple mains fuses Maximum fuse rating
LXM32∙∙∙∙M2 A 25
If multiple mains fuses are required, additional DC bus fuses must be used upstream of each drive. The DC bus fuses must be suitable for 600 Vdc.
DC bus fuses Maximum fuse rating
LXM32∙∙∙∙M2 A 25
26
Figure 3: Multiple mains fuses for single-phase drives
See chapter "6.2 DC fuses" for fuses for the DC bus.
The use of mains reactors can reduce the input current. Due to the lower input current, it may be possible to operate the drives with just a single mains fuse.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 27
PC/- PA/+ PC/- PA/+ PC/- PA/+
DC+ DC
-
L3
L2
L1
L2 L1L3 L2 L1L3L2 L1L3
LXM32

3.4.2 DC bus connection of three-phase drives

Single mains fuse A single fuse is sufficient if the total input current of all drives connec-
ted via the common DC bus is less than the maximum fuse rating shown in the table below.
Single mains fuse Maximum fuse rating
LXM32U60N4, LXM32D12N4, LXM32D18N4, LXM32D30N4, LXM32D72N4
LXM32D85N4, LXM32C10N4 A 63
3 Engineering
A 32
MNA01M001EN, V1.01, 08.2014
Common DC bus
Figure 4: Single mains fuse for three-phase drives
27
Page 28
PC/- PA/+ PC/- PA/+ PC/- PA/+
L3
L2
L1
L2 L1L3 L2 L1L3L2 L1L3
DC+ DC
-
3 Engineering
Multiple mains fuses Multiple mains fuses are required A single fuse is sufficient if the total
LXM32
input current of all drives connected via the common DC bus is less than the maximum fuse rating shown in the table below.
Multiple mains fuses Maximum fuse rating
LXM32U60N4, LXM32D12N4, LXM32D18N4, LXM32D30N4, LXM32D72N4
LXM32D85N4, LXM32C10N4 A 63
If multiple mains fuses are required, additional DC bus fuses must be used upstream of each drive. The DC bus fuses must be suitable for 600 Vdc.
DC bus fuses Maximum fuse rating
LXM32U60N4, LXM32D12N4, LXM32D18N4, LXM32D30N4, LXM32D72N4
LXM32D85N4, LXM32C10N4 A 63
A 32
A 32
28
Figure 5: Multiple mains fuses for three-phase drives
See chapter "6.2 DC fuses" for fuses for the DC bus.
The use of mains reactors can reduce the input current. Due to the lower input current, it may be possible to operate the drives with just a single mains fuse.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 29
LXM32

3.4.3 Supply via the DC bus

3 Engineering
A single or multiple drives can be supplied directly via the DC bus.
The supply is provided by a correspondingly sized drive or by a DC power supply unit.
In the case of supply via the DC bus, DC bus fuses must be used. The DC bus fuses must be suitable for 600 Vdc.
The number of DC bus fuses depends on the total maximum continu­ous current on the DC bus of all drives connected via the common DC bus.
Single-phase drives
Three-phase drives
DC bus fuses Maximum fuse rating
LXM32∙∙∙∙M2 A 25
DC bus fuses Maximum fuse rating
LXM32U60N4, LXM32D12N4, LXM32D18N4, LXM32D30N4, LXM32D72N4
LXM32D85N4, LXM32C10N4 A 63
A 32
MNA01M001EN, V1.01, 08.2014
Common DC bus
29
Page 30
L3
L2
L1
L2 L1L3
PC/- PA/+ PC/- PA/+ PC/- PA/+
PC/- PA/+
L2 L1L3 L2 L1L3 L2 L1L3
L2 L1L3 L2 L1L3 L2 L1L3
~
+-
PC/- PA/+ PC/- PA/+ PC/- PA/+
L3
L2
L1
3 Engineering
Single DC bus fuse If the total maximum continuous current on the DC bus of all drives
LXM32
connected via the common DC bus does not exceed the maximum fuse rating of a drive, a single DC bus fuse is sufficient.
Figure 6: Supply via the DC bus by a drive
Figure 7: Supply via the DC bus by a DC power supply unit
30
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 31
L2 L1L3 L2 L1L3 L2 L1L3
L3
L2
L1
L2 L1L3
PC/- PA/+ PC/- PA/+ PC/- PA/+
PC/- PA/+
L2 L1L3 L2 L1L3 L2 L1L3
~
+-
PC/- PA/+ PC/- PA/+ PC/- PA/+
L3
L2
L1
LXM32
3 Engineering
Multiple DC bus fuses If the total maximum continuous current on the DC bus of all drives
connected via the common DC bus exceeds the maximum fuse rating of a drive, DC bus fuses are required at each drive.
Figure 8: Supply via the DC bus by a drive
Figure 9: Supply via the DC bus by a DC power supply unit
MNA01M001EN, V1.01, 08.2014
Common DC bus
31
Page 32
3 Engineering

3.5 Braking resistors

Excess energy in the common DC bus must be absorbed by the brak­ing resistors. Depending on the application, one or more braking resis­tors can be connected. Consider the internal braking resistors of LXM32 drives in your calculations.
If drives with a different nominal power are connected via the DC bus, you must connect braking resistors to the drive with the highest nomi­nal power. See the manual of the respective product for more informa­tion.

3.5.1 Rating the braking resistor

An insufficiently rated braking resistor can cause overvoltage on the DC bus. Overvoltage on the DC bus causes the power stage to be disabled. The motor is no longer actively decelerated.
MOTOR WITHOUT BRAKING EFFECT
Verify that the braking resistor has a sufficient rating.
Verify that the parameter settings for the braking resistor are cor­rect.
Verify that the I2t value for temperature monitoring does not exceed 100% by performing a test run under maximum load con­ditions.
Verify that the calculations and the test run take into account the fact that the DC bus capacitors can absorb less braking energy at higher mains voltages.
LXM32
WARNING
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The temperature of the braking resistor may exceed 250 °C (482 °F) during operation.
WARNING
HOT SURFACES
Ensure that any contact with a hot braking resistor is avoided.
Do not allow flammable or heat-sensitive parts in the immediate vicinity of the braking resistor.
Verify that the heat dissipation is sufficient by performing a test run under maximum load conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Braking resistors are required for dynamic applications. During decel­eration, the kinetic energy is transformed into electrical energy in the motor. The electrical energy increases the DC bus voltage. The brak­ing resistor is activated when the defined threshold value is exceeded. The braking resistor transforms electrical energy into heat. If highly dynamic deceleration is required, the braking resistor must be well adapted to the system.
32
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 33
R =
P
max
U
2
LXM32
3 Engineering
Further information on the subject Page
Technical data chapter "2.3 Braking resistor" 17
Commissioning chapter "5.2 LXM32: Setting the braking resistor parameters"
See also chapter "3.1 Energy balance", page 22 for rating information.
Internal braking resistor A braking resistor to absorb braking energy is integrated in LXM32
drives. The device is shipped with the internal braking resistor active.
If the braking energy of all drives sharing a common DC bus is greater than the energy the internal braking resistors can absorb, you must use an external braking resistor. Consider the most extreme case of your application in calculating the braking energy. Example: In the case of an EMERGENCY STOP, all drives decelerate simultaneously; the braking resistors must be able to absorb the entire braking energy.
External braking resistor An external braking resistor is required in applications in which the
braking energy is greater than the energy that can be absorbed by the drives sharing a common DC bus. Consider the most extreme case of your application in calculating the braking energy. Example: In the case of an EMERGENCY STOP, all drives decelerate simultaneously; the braking resistors must be able to absorb the entire braking energy.
54
LXM32: Monitoring LXM32 drives monitor the load on the connected braking resistor. The
Selection of the external braking
resistor
load on the braking resistor can be read out. The connection of the external braking resistor is short-circuit protec­ted. A ground fault of the braking resistor is not detected.
The rating of an external braking resistor depends on the required peak power and continuous power with which the braking resistor can be operated.
The resistance R is derived from the required peak power and the DC bus voltage.
R = Resistance value in Ω U = Switch-on voltage braking resistor in V P
= Required peak power in W
max
If 2 or more braking resistors are connected to one drive, note the fol­lowing criteria:
The braking resistors must be connected in parallel or in series so the required resistance is reached. Only connect resistors with identical resistance in parallel in order to evenly distribute the load to all braking resistors.
The total resistance of all external braking resistors connected to one drive must not fall below a lower limit.
The continuous power of the network of connected braking resis­tors must be calculated. The result must be greater than or equal to the actually required continuous power.
MNA01M001EN, V1.01, 08.2014
Common DC bus
33
Page 34
3 Engineering
Use only resistors that are specified as braking resistors. See chapter "2.3 Braking resistor", page 17 for suitable braking resistors.
Connection of braking resistor Braking resistors with degree of protection IP65 may be installed out-
side the control cabinet in an appropriate environment in order to decrease the temperature in the control cabinet. The external braking resistors listed in the Accessories chapter are shipped with an information sheet that provides details on installation.
Further procedure:
Connect the braking resistors to the drive.
LXM32: Check the parameter RESint_ext during commissioning. This parameter allows you to switch between internal and external braking resistor.
LXM32: If you have connected an external braking resistor to an LXM32 drive, you must set the parameters for the external braking resistor during commissioning.
During commissioning, test the braking resistors under realistic conditions, see page 54.
Wire ferrules: If you use wire ferrules, use only wire ferrules with col­lars for these terminals.
LXM32

3.5.2 Rating information

To rate the braking resistor, calculate the proportion contributing to absorbing braking energy.
An external braking resistor is required if the kinetic energy that must be absorbed exceeds the total of the internal proportions, including the internal braking resistor.
The energy E the deceleration process and the response threshold.
The voltage prior to the deceleration process depends on the mains voltage. The energy absorption by the DC bus capacitors is lowest when the mains voltage is highest. In the calculation, use the values for the highest mains voltage.
Energy absorption braking resistor Two characteristic values determine the energy absorption of the
braking resistor:
The continuous power PPR is the amount of energy that can be continuously absorbed without overloading the braking resistor.
The maximum energy ECR limits the maximum short-term power that can be absorbed.
If the continuous power was exceeded for a specific time, the braking resistor must remain without load for a corresponding period.
is the square difference between the voltage before
var
34
The characteristic values PPR and ECR of the internal braking resistor can be found in chapter "2 Technical Data".
See page 22 for information on assessing the electrical and mechani­cal losses.
Example: LXM32 drive Deceleration of a rotary motor with the following data:
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 35
LXM32
3 Engineering
Selecting an external braking
resistor
Initial speed of rotation: n = 4000 min
Rotor inertia: JR = 4 kgcm
Load inertia: JL = 6 kgcm
2
2
-1
Calculation of the energy to be absorbed:
EB = 1/2 * J * (2*π*n * 1/60)
2
to 88 Ws
Electrical and mechanical losses are ignored.
In this example, the DC bus capacitors absorb 23 Ws (the value depends on the device type, see chapter "2 Technical Data").
The internal braking resistor must absorb the remaining 65 Ws. It can absorb a pulse of 80 Ws. If the load is decelerated once, the internal braking resistor is sufficient.
If the deceleration process is repeated cyclically, the continuous out­put must be considered. If the cycle time is longer than the ratio of the energy to be absorbed EB and the continuous power PPR, the internal braking resistor is sufficient. If the system decelerates more frequently, the internal braking resistor is not sufficient.
In the example, the ratio EB/PPR is 1.3 s. If the cycle time is shorter, an external braking resistor is required.
The selection is made in two steps:
The maximum energy during deceleration must be less than the peak energy that the internal braking resistor can absorb: (EDi)<(ECr). In addition, the continuous power of the internal braking resistor must not be exceeded: (PC)<(PPr). If these conditions are met, then the internal braking resistor is sufficient.
If one of the conditions is not met, you must use an external brak­ing resistor. The braking resistor must be rated in such a way that the conditions are met. The resistance of the braking resistor must be between the specified minimum and maximum values, since otherwise the load can no longer be decelerated or the product might be destroyed.
MNA01M001EN, V1.01, 08.2014
Common DC bus
See chapter "2.3 Braking resistor", page 17 for technical data on the external braking resistors.
35
Page 36
PC/- PA/+ PC/- PA/+
DC+ DC
-
L3
L2
L1
L2 L1L3 L2 L1L3
S2 S3
S1
E3
E2
E1
3 Engineering

3.6 Mains reactor

LXM32
A mains reactor is required if at least one of the following criteria is met:
The output power of the drive is to be increased.
The short-circuit current rating (SCCR) of the supplying mains is greater than specified for the drives.
Current harmonics are to be reduced.
If one drive requires a mains reactor, then all drives connected via the DC bus must be equipped with mains reactors.
The mains reactor for several drives with a common AC fuse must be rated in such a way that the nominal current of the mains reactor is greater than the total of the input current of the drives.
The fuse rating of the fuse upstream of the mains reactor must not be greater than the nominal current of the mains reactor.
36
Figure 10: Wiring of drives with common AC fuse and a mains reactor, exam­ple shows three-phase drives.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 37
N/L2
L1
S2
S1
E2
E1
PC/- PA/+
DC+ DC
-
N/L2 L1
S2
S1
E2
E1
PC/- PA/+
N/L2 L1
LXM32
3 Engineering
Figure 11: Wiring of drives with individual AC fuses and mains reactors, example shows singe-phase drives.
See the manual of the respective product for information on mains reactors.
MNA01M001EN, V1.01, 08.2014
Common DC bus
37
Page 38
PC/- PA/+ PC/- PA/+
DC+ DC
-
L3
L2
L1
L2 L1L3 L2 L1L3
L3
L2
L1
L3'
L2'
L1'
3 Engineering

3.7 Mains filter

LXM32
The emission depends on the length of the motor cables. If the required limit value is not reached with the internal mains filter, you must use an external mains filter.
See manual of the respective product for information on mains filters.
The mains filter for several drives with a common AC fuse must be rated in such a way that the nominal current of the external mains filter is greater than the total of the input current of the drives.
The fuse rating of the fuse upstream of the external mains filter must not be greater than the nominal current of the external mains filter.
Mount the external mains filter in such a way that the lines from the mains filter to the drives are as short as possible. For EMC reasons, route the cables from the mains filter to the drives separately from the line to the mains filter.
External three-phase mains filters do not have a neutral conductor connection; they are only approved for three-phase devices.
38
Figure 12: Wiring of an external mains filter, example shows three-phase drives.
See the manual of the respective product for information on external mains filters.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 39
PC/- PA/+ PC/- PA/+ PC/- PA/+
DC+ DC
-
L3
L2
L1
L2 L1L3 L2 L1L3
S2 S3
S1
E3
E2
E1
L3
L2
L1
L3'
L2'
L1'
L2 L1L3
LXM32

3.8 Mains reactor and external mains filter

If a mains reactor and an external mains filter are required, the mains reactor and external mains filter must be arranged according to the following illustrations for EMC reasons.
3 Engineering
Figure 13: Wiring of drives with common mains fuse, mains reactor and mains filter, example shows three-phase drives.
MNA01M001EN, V1.01, 08.2014
Common DC bus
39
Page 40
3 Engineering
LXM32
40
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 41
LXM32
4 Installation

4 Installation

An engineering phase is mandatory prior to mechanical and electrical installation. See chapter "3 EngineeringInstallation", page 21, for basic information.
Incorrect use of the DC bus may permanently damage the drives either immediately or over time.
WARNING
DESTRUCTION OF SYSTEM COMPONENTS AND LOSS OF CONTROL
Verify that all requirements for using the DC bus are met.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
DESTRUCTION OF SYSTEM COMPONENTS
Connect only drives with identical nominal voltages.
Connect single-phase drives only to single-phase drives. Connect single-phase drives to the same phase.
Connect three-phase drives only to three-phase drives.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
DESTRUCTION DUE TO INCORRECT OPERATION
Verify that the power stage supplies of the drives connected via a common DC bus are switched on simultaneously.
Failure to follow these instructions can result in equipment damage.
MNA01M001EN, V1.01, 08.2014
Common DC bus
41
Page 42
L1
N/L2
L1
N/L2
M2
M2
L1
L3
L2
L1
L3
L2
N4
N4
L1
L3
L2
N
L1
L3
L2
N
M2
M2
L1
L3
L2
N
L1
L3
L2
N
N4
M2
4 Installation
LXM32
Figure 14: Specifications for drives with mains supply

4.1 Assembling cables

Pre-assembled cables are available for common DC bus. If the pre­assembled cables do not have the required length, use cables and crimp contacts, see chapter "6.1 DC bus accessories", page 55.
Properties of the DC bus cable Note the DC bus cable properties, see chapter
Assembling DC bus cables The following instructions apply to drives with plug connections for the
"2.4 Cables for the DC bus" , page 20.
DC bus.
42
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 43
4
3
A
1
2
5
C
B
PC/-PA/+
PC/-
PA/+
LXM32
4 Installation
Part Length in mm (inches)
A Cable jacket 130 (5.2)
B Length of shield connection 60 (2.5)
C Stripping length 6 (0.25)
Diameter ring-type cable lug / fork-type cable lug
For M5 screw
(1) Strip the cable jacket, length A.
(2) Slide back the shield braiding. Open the shield braiding and twist it to form a shield connection wire.
(3) Shorten the twisted shield connection wire to length B and insu­late the shield braiding with heat shrink tube. Crimp the crimp contacts to the two stripped conductors. The strip­ping length is C. See chapter "6.1 DC bus accessories", page 55 for information on the crimping tool.
(4) Crimp a fork-type cable lug to the shield connection wire. Push the crimp contacts into the connector housing. Polarity: the red wire is PA/+, the black wire is PC/-.
(5) Secure the shield with heat shrink tube.
MNA01M001EN, V1.01, 08.2014
Common DC bus
43
Page 44
3
A
B
1
2
C
4 Installation
LXM32
The following instructions apply to drives with screw terminals for the DC bus.
LXM32... D85, C10
A mm (in) 220 (8.66)
B mm (in) 50 (1.97)
C mm (in) 18 (0.71)
(1) Strip the cable jacket, length A. (2) Slide the shield braiding back over the cable jacket. (3) Secure the shield braiding with a heat shrink tube. The
shield must have at least length D. Verify that a large surface area of the shield braiding is connected to the EMC shield clamp.
44
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 45
PA/+
PC/-
LXM32

4.2 Wiring the DC bus

The DC bus is connected by means of a plug and socket connection or screw terminals.
Cable specifications See chapter "2.4 Cables for the DC bus", page 20 for the cable speci-
fications. Pre-assembled cables and connector kits can be found in chapter "6 Accessories and spare parts", page 55.

4.2.1 Drives with connectors

Connector coding The connectors are coded. If you do not use pre-assembled cables,
verify that the crimp contacts properly snap into the connector. Verify that PA/+ is connected to PA/+ and PC/- is connected to PC/-. Incor­rect wiring will destroy the devices.
4 Installation
NOTICE
EQUIPMENT DAMAGE CAUSED BY INCORRECT POLARITY
Verify correct polarity during installation.
Failure to follow these instructions can result in equipment damage.
Connector lock The connector has a snap lock mechanism. Pull the connector hous-
MNA01M001EN, V1.01, 08.2014
Common DC bus
Figure 15: Connector coding
ing to unlock the connector.
Both wires in the connector housing must be able to move independ­ently for unlocking.
If you want to remove the DC bus connection cable, you must open the connector lock by pulling at the housing. The connection cable is easier to remove if you remove the motor connector first.
45
Page 46
PC/-PA/+
PC/-PA/+
4 Installation
LXM32
Figure 16: Unlocking the DC bus connector, step 1: Push cables towards con­nector.
46
Figure 17: Unlocking the DC bus connector, step 2: Push cables towards con­nector, at the same time remove the connector with the other hand.
If the two wires cannot move freely, the DC bus connector will not unlock.
Push the two wires towards the connector (see Figure 16).
While pushing the wires towards the connector, pull the connector at the connector housing with the other hand.The connector is unlocked and you can remove the DC bus connection cable (see ). The connector is unlocked and you can remove the DC bus con­nection cable (see Figure 17).
Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 47
BR+BR-
L3/TL2/SL1/R
CN9
U/T1 W/T3V/T2PA/+ PC/-PBU/T
1
W/T3
V/T2
PB
LXM32

4.2.2 Drives with terminals

4 Installation
This chapter describes LXM32 drives with screw terminals.
Properties of the connection termi-
nals CN9
Wiring diagram
LXM32... D85, C10
Connection cross section mm2
(AWG)
Tightening torque for terminal screws
Stripping length mm
Nm (lb.in)
(in)
6 ... 25 (10 ... 4)
3.8 (33.6)
18 (0.71)
The terminals are approved for fine wire conductors and rigid conduc­tors. Observe the maximum permissible connection cross section. Take into account the fact that wire ferrules increase the conductor cross section.
Figure 18: Wiring diagram DC bus
Connecting the DC bus
Switch off all supply voltages. Observe the safety instructions con­cerning electrical installation.
Connect the DC bus to the device. Connect PA/+ to PA/+ (red) and PC/- to PC/- (black). Note the tightening torque specified for the terminal screws.
Connect the cable shield with a shield clamp to an EMC rail (large surface area contact).
Verify that the individual wires are in the individual guides.
Mount the cable guide.
MNA01M001EN, V1.01, 08.2014
Common DC bus
47
Page 48
CN9 DC Bus
PC/- PA/+
ESC
W
V
U
ESC
CN9 DC Bus
PC/- PA/+
W
V
U
4 Installation

4.2.3 Connecting the DC bus

LXM32
Figure 19: DC bus connection, example with connector
Verify that the requirements concerning the DC bus are met, see chapter "3 EngineeringInstallation".
Use pre-assembled cables whenever possible (page 55) to reduce the risk of wiring errors.
Only connect the devices with the specified accessories. The con­nectors are coded. Connect PA/+ to PA/+ (red) and PC/- to PC/­(black).
48
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 49
LXM32

4.3 Verifying installation

4 Installation
Verify that the wiring complies with the specifications as per chap­ter "3 EngineeringInstallation".
Verify that the fuses used do not exceed the maximum permissible fuse rating.
Verify that PA/+ is only connected to PA/+ and that PC/- is only connected to PC/-.
Verify that the connector locks are properly snapped in.
MNA01M001EN, V1.01, 08.2014
Common DC bus
49
Page 50
4 Installation
LXM32
50
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 51
LXM32
5 Commissioning

5 Commissioning

For commissioning, follow the commissioning instructions for the indi­vidual devices in the manual of the respective product.
Incorrect use of the DC bus may permanently damage the drives either immediately or over time.
WARNING
DESTRUCTION OF SYSTEM COMPONENTS AND LOSS OF CONTROL
Verify that all requirements for using the DC bus are met.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
DESTRUCTION DUE TO INCORRECT OPERATION
Verify that the drives connected via a common DC bus are switched on simultaneously.
Failure to follow these instructions can result in equipment damage.
MNA01M001EN, V1.01, 08.2014
Common DC bus
51
Page 52
5 Commissioning

5.1 Commissioning procedure

5.1.1 DC bus connection LXM32 to LXM32

Commissioning steps:
Verify proper installation of the drives and the connections for the common DC bus, see chapter "4.3 Verifying installation", page 49.
Switch on the controller supply for all devices.
Set the parameters for the braking resistors, see chapter "5.2 LXM32: Setting the braking resistor parameters".
Commission the drives, see the descriptions in the manuals for the individual products.
LXM32
52
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 53
LXM32

5.1.2 Supply via the DC bus

5 Commissioning
Commissioning steps:
Verify proper installation of the drives and the connections for the common DC bus, see chapter "4.3 Verifying installation", page 49.
Switch on the controller supply for all devices.
LXM32: Set the parameter MON_MainsVolt to "DC-Bus Only" for LXM32.
Parameters Value
MON_MainsVolt
LXM32: Set the parameters for the braking resistors of LXM32 drives, see chapter "5.2 LXM32: Setting the braking resistor parameters".
Commission the drives, see the descriptions in the manuals for the individual products.
DC-Bus Only
MNA01M001EN, V1.01, 08.2014
Common DC bus
53
Page 54
5 Commissioning

5.2 LXM32: Setting the braking resistor parameters

An insufficiently rated braking resistor can cause overvoltage on the DC bus. Overvoltage on the DC bus causes the power stage to be disabled. The motor is no longer actively decelerated.
WARNING
MOTOR WITHOUT BRAKING EFFECT
Verify that the braking resistor has a sufficient rating.
Verify that the parameter settings for the braking resistor are cor­rect.
Verify that the I2t value for temperature monitoring does not exceed 100% by performing a test run under maximum load con­ditions.
Verify that the calculations and the test run take into account the fact that the DC bus capacitors can absorb less braking energy at higher mains voltages.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
LXM32
The temperature of the braking resistor may exceed 250 °C (482 °F) during operation.
WARNING
HOT SURFACES
Ensure that any contact with a hot braking resistor is avoided.
Do not allow flammable or heat-sensitive parts in the immediate vicinity of the braking resistor.
Verify that the heat dissipation is sufficient by performing a test run under maximum load conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Check the parameter RESint_ext. If you have connected an external braking resistor, you must set the parameter to "external".
If you have connected an external braking resistor, (value of the parameter RESint_ext is set to "external"), you must assign the appropriate values to the parameters RESext_P, RESext_R and RESext_ton. Verify that the selected external braking resistor is really connected.
Test the function of the braking resistor under realistic, worst case conditions.
54
If the regenerated power becomes greater than the power that can be absorbed by the braking resistor, an error message is generated and the power stage is disabled.
See the product manual for a description of the parameters.
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 55
LXM32

6 Accessories and spare parts

6 Accessories and spare parts

6.1 DC bus accessories

Description Order no.
DC bus connection cable, 2 * 6 mm2 (2 * AWG 10), pre-assembled, 0.1 m, 5 pieces VW3M7101R01
DC bus connection cable, 2 * 6 mm2 (2 * AWG 10), Twisted Pair, shielded, 15 m VW3M7102R150
DC bus connector kit, connector housing and crimp contacts for 3 ... 6 mm2 (AWG 12 ... 10), 10 pieces
A crimping tool is required for the crimp contacts of the connector kit. Manufacturer: Tyco Electronics, Heavy Head Hand Tool, Tool Pt. No 180250

6.2 DC fuses

VW3M2207
The following DC fuses are offered by SIBA.
http://www.siba-fuses.com
Description SIBA order no.
DC fuse, DC 700V 10A 5020106.10
DC fuse, DC 700V 16A 5020106.16
DC fuse, DC 700V 25A 5020106.25
DC fuse, DC 700V 32A 5020106.32
DC fuse, DC 700V 40A 5020106.40
DC fuse, DC 700V 50A 5020106.50
DC fuse, DC 700V 63A 5020106.63
MNA01M001EN, V1.01, 08.2014
Common DC bus
55
Page 56
6 Accessories and spare parts

6.3 External braking resistors

Description Order no.
Braking resistor IP65; 10 Ω; maximum continuous power 400 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 10 Ω; maximum continuous power 400 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 10 Ω; maximum continuous power 400 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 100 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 100 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 100 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 200 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 200 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 200 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 400 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 400 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 27 Ω; maximum continuous power 400 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 100 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 100 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 100 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 200 W; 0.75 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 200 W; 2 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 200 W; 3 m connection cable (2.1 mm2), UL
Braking resistor IP65; 72 Ω; maximum continuous power 400 W; 0.75 m connection cable VW3A7607R07
Braking resistor IP65; 72 Ω; maximum continuous power 400 W; 2 m connection cable VW3A7607R20
Braking resistor IP65; 72 Ω; maximum continuous power 400 W; 3 m connection cable VW3A7607R30
Braking resistor IP65; 100 Ω; maximum continuous power 100 W; 0.75 m connection cable VW3A7608R07
Braking resistor IP65; 100 Ω; maximum continuous power 100 W; 2 m connection cable VW3A7608R20
Braking resistor IP65; 100 Ω; maximum continuous power 100 W; 3 m connection cable VW3A7608R30
Braking resistor IP20; 15 Ω; maximum continuous power 1000 W; M6 terminals, UL VW3A7704
Braking resistor IP20; 10 Ω; maximum continuous power 1000 W; M6 terminals, UL VW3A7705
VW3A7601R07
VW3A7601R20
VW3A7601R30
VW3A7602R07
VW3A7602R20
VW3A7602R30
VW3A7603R07
VW3A7603R20
VW3A7603R30
VW3A7604R07
VW3A7604R20
VW3A7604R30
VW3A7605R07
VW3A7605R20
VW3A7605R30
VW3A7606R07
VW3A7606R20
VW3A7606R30
LXM32
56
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 57
LXM32

Glossary

Glossary

Units and conversion tables

The value in the specified unit (left column) is calculated for the desired unit (top row) with the formula (in the field).
Example: conversion of 5 meters (m) to yards (yd) 5 m / 0.9144 = 5.468 yd

Length

in ft yd m cm mm
in - / 12 / 36 * 0.0254 * 2.54 * 25.4
ft * 12 - / 3 * 0.30479 * 30.479 * 304.79
yd * 36 * 3 - * 0.9144 * 91.44 * 914.4
m / 0.0254 / 0.30479 / 0.9144 - * 100 * 1000
cm / 2.54 / 30.479 / 91.44 / 100 - * 10
mm / 25.4 / 304.79 / 914.4 / 1000 / 10 -

Mass

lb oz slug kg g
lb - * 16 * 0.03108095 * 0.4535924 * 453.5924
oz / 16 - * 1.942559*10
slug / 0.03108095 / 1.942559*10
kg / 0.45359237 / 0.02834952 / 14.5939 - * 1000
g / 453.59237 / 28.34952 / 14593.9 / 1000 -
-3
- * 14.5939 * 14593.9
-3
* 0.02834952 * 28.34952

Force

lb oz p N
lb - * 16 * 453.55358 * 4.448222
oz / 16 - * 28.349524 * 0.27801
p / 453.55358 / 28.349524 - * 9.807*10
N / 4.448222 / 0.27801 / 9.807*10
-3
-
-3

Power

HP W
HP - * 746
W / 746 -
MNA01M001EN, V1.01, 08.2014
Common DC bus
57
Page 58
Glossary
LXM32

Rotation

min-1 (RPM) rad/s deg./s
min-1 (RPM) - * π / 30 * 6
rad/s * 30 / π - * 57.295
deg./s / 6 / 57.295 -

Torque

lbin lbft ozin Nm kpm kpcm dynecm
lbin - / 12 * 16 * 0.112985 * 0.011521 * 1.1521 * 1.129*10
lbft * 12 - * 192 * 1.355822 * 0.138255 * 13.8255 * 13.558*10
ozin / 16 / 192 - * 7.0616*10-3* 720.07*10-6* 72.007*10-3* 70615.5
Nm / 0.112985 / 1.355822 / 7.0616*10-3- * 0.101972 * 10.1972 * 10*10
6
kpm / 0.011521 / 0.138255 / 720.07*10-6/ 0.101972 - * 100 * 98.066*10
kpcm / 1.1521 / 13.8255 / 72.007*10-3/ 10.1972 / 100 - * 0.9806*10
dynecm / 1.129*106/ 13.558*106/ 70615.5 / 10*10
6
/ 98.066*106/ 0.9806*106-

Moment of inertia

6
6
6
6
2
lbin
2
lbft
2
kgm
2
kgcm
kpcms
2
ozin
2
lbin
- / 144 / 3417.16 / 0.341716 / 335.109 * 16
* 144 - * 0.04214 * 421.4 * 0.429711 * 2304
* 3417.16 / 0.04214 - * 10*10
* 0.341716 / 421.4 / 10*10
2
* 335.109 / 0.429711 / 10.1972 * 980.665 - * 5361.74
/ 16 / 2304 / 54674 / 5.46 / 5361.74 -
lbft
2
kgm
2
3
kgcm
2
3
kpcms
* 10.1972 * 54674
2
ozin
- / 980.665 * 5.46
2

Temperature

°F °C K
°F - (°F - 32) * 5/9 (°F - 32) * 5/9 + 273.15
°C °C * 9/5 + 32 - °C + 273.15
K (K - 273.15) * 9/5 + 32 K - 273.15 -

Conductor cross section

AWG 1 2 3 4 5 6 7 8 9 10 11 12 13
2
mm
42.4 33.6 26.7 21.2 16.8 13.3 10.5 8.4 6.6 5.3 4.2 3.3 2.6
AWG 14 15 16 17 18 19 20 21 22 23 24 25 26
2
mm
58
2.1 1.7 1.3 1.0 0.82 0.65 0.52 0.41 0.33 0.26 0.20 0.16 0.13
Common DC bus
MNA01M001EN, V1.01, 08.2014
Page 59
LXM32
Glossary

Terms and Abbreviations

See chapter " Standards and terminology" for information on the perti­nent standards on which many terms are based. Some terms and abbreviations may have specific meanings with regard to the stand­ards.
AC Alternating current
DC Direct current
DC bus Circuit that supplies the power stage with energy (direct voltage).
Drive system System consisting of controller, drive and motor.
EMC Electromagnetic compatibility
Error Discrepancy between a detected (computed, measured or signaled)
value or condition and the specified or theoretically correct value or condition.
Error class Classification of errors into groups. The different error classes allow
for specific responses to errors, for example by severity.
Factory setting Factory settings when the product is shipped
Fault Fault is an operating state. If the monitoring functions detect an error,
a transition to this operating state is triggered, depending on the error class. A "Fault Reset" is required to exit this operating state after the cause of the detected error has been removed. Further information can be found in the pertinent standards such as IEC 61800-7, ODVA Common Industrial Protocol (CIP).
Fault Reset A function used to restore the drive to an operational state after a
detected error is cleared by removing the cause of the error so that the error is no longer active.
Parameter Device data and values that can be read and set (to a certain extent)
by the user.
PELV Protective Extra Low Voltage, low voltage with isolation. For more
information: IEC 60364-4-41
Persistent Indicates whether the value of the parameter remains in the memory
after the device is switched off.
Power stage The power stage controls the motor. The power stage generates cur-
rent for controlling the motor on the basis of the motion signals from the controller.
Quick Stop The Quick Stop function can be used for fast deceleration of a move-
ment as a response to a detected error or via a command.
Warning If the term is used outside the context of safety instructions, a warning
alerts to a potential problem that was detected by a monitoring func­tion. A warning does not cause a transition of the operating state.
MNA01M001EN, V1.01, 08.2014
Common DC bus
59
Page 60
Glossary
LXM32
60
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 61
LXM32

Table of figures

Table of figures
1) Movement cycle: Profile for energy assessment 23
2) Single mains fuse for single-phase drives 25
3) Multiple mains fuses for single-phase drives 26
4) Single mains fuse for three-phase drives 27
5) Multiple mains fuses for three-phase drives 28
6) Supply via the DC bus by a drive 30
7) Supply via the DC bus by a DC power supply unit 30
8) Supply via the DC bus by a drive 31
9) Supply via the DC bus by a DC power supply unit 31
10) Wiring of drives with common AC fuse and a mains reactor, example shows three-phase drives. 36
11) Wiring of drives with individual AC fuses and mains reactors, example shows singe-phase drives. 37
12) Wiring of an external mains filter, example shows three-phase drives. 38
13) Wiring of drives with common mains fuse, mains reactor and mains filter, example shows three-phase drives. 39
14) Specifications for drives with mains supply 42
15) Connector coding 45
16) Unlocking the DC bus connector, step 1: Push cables towards connector. 46
17) Unlocking the DC bus connector, step 2: Push cables towards connector, at the same time remove the connector with the other hand. 46
18) Wiring diagram DC bus 47
19) DC bus connection, example with connector 48
MNA01M001EN, V1.01, 08.2014
Common DC bus
61
Page 62
Table of figures
LXM32
62
MNA01M001EN, V1.01, 08.2014
Common DC bus
Page 63
LXM32

Index

Index
A
Abbreviations 59
Accessories
External braking resistor, data 19
Accessories and spare parts 55
B
Braking resistor 17
External 19
Monitoring 33
Rating 32
Selection 33
Braking resistors common DC bus 32
C
E
EMC 24
Energy balance 22
External braking resistors 19
G
Glossary 57
H
Hazard categories 5
I
Installation of common DC bus 45
Intended use 6
Introduction 13
Commissioning 51
Parameters for braking resistor 54
steps 52
Common DC bus
Braking resistors 32
Common DC-Bus
Installation 45
Connector
Coding 45
Lock 45
D
DC bus
Braking resistors 32
M
Manuals
Source 11
Monitoring
Braking resistor 33
P
Parameters for braking resistor 54
Q
Qualification of personnel 6
R
Rating
Energy balance 22
MNA01M001EN, V1.01, 08.2014
Common DC bus
63
Page 64
Index
LXM32
Rating information
Braking resistor 34
Rating of braking resistor 32
S
Safety Information 5
Source
Manuals 11
T
Technical data 15
Terms 59
U
Units and conversion tables 57
W
Wiring 45
Wiring diagram
External braking resistor 47
64
MNA01M001EN, V1.01, 08.2014
Common DC bus
Loading...