Schneider Electric MK-4800 Series Installation Instructions

Application
The MK-4800 series pneumatic valve actuator has an
2
(71 cm2) effective diaphragm area and is used to
11 in control 1-1/2" to 2" VB-9XXX series valves.
Rugged, die-cast aluminum housing
11 in
2
(71 cm2) effective area
Replaceable, beaded, molded neoprene diaphragm
Applicable Literature
MK-4800 Series
Pneumatic Valve Actuator
General Instructions
Cross-Reference Guide F-23638
Reference Manual F-21683
Application Manual F-21335
General Instructions Sheet F-23325, for Valve
Linkage AV-420
Printed in U.S.A. 6-10 © Copyright 2010 Schneider Electric All Rights Reserved. F-23326-6
INSTALLATION
C A U T I O N
Inspection
Requirements
Valve Mounting
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return dam­aged products.
Piping diagrams
Tools (not provided):
Appropriate screwdriver or wrench for field service
Appropriate pliers or equivalent to assemble the linkage kit
Training: Installer must be a qualified, experienced technician
Appropriate accessories and valve body
Disconnect the air supply before installation, to prevent equipment damage.
Make all connections in accordance with the piping diagram, and national and local
codes.
Do not exceed the ratings of the device(s).
Avoid locations where excessive moisture, corrosive fumes, or vibration is present.
Mount the actuator on a valve so that it conforms to the following, as applicable:
1. Install all two-way valves so that they close against the flow. An arrow on the valve body or tag indicates proper flow direction.
2. Always install three-way mixing valves with two inlets and one outlet.
3. Always install three-way diverting valves with one inlet and two outlets.
4. Allow sufficient room above the actuator valve assembly for removal and reatt of the actuator to the installed valve.
5. The valve actuator is generally mounted in an upright position, above the center line of the valve body. Do not mount the valve actuator below the center line of the valve.
6. The actuator may be swiveled, on a valve, to align the air connection with the control piping.
7. The actuator can be removed from the valve without disturbing the spring setting.
8. For steam applications only, position the valve body at least at 45° from the vertical.
so the valve stem and actuator are
achment
Assembly Instructions
For instructions on the installation of the actuator on a valve bod y, using the AV-420 valve linkage assembly, refer to the AV-420 General Instructions F-23325.
F-23326-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3