Schneider Electric Lexium 62 ILM Hardware Guide

Lexium 62 ILM

EIO0000001351 02/2020
Lexium 62 ILM
Hardware Guide
Original instructions
02/2020
EIO0000001351.07
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage. © 2020 Schneider Electric. All rights reserved.

Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Specific Safety Information . . . . . . . . . . . . . . . . . . . . . . . 13
Product Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualification of Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
System Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 Connection Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 Distribution Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 ILM Integrated Servo Drive . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 ILM Digital I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lexium 62 ILM Safety Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ILM Daisy Chain Connector Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Engineering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.1 Electromagnetic Compatibility, EMC . . . . . . . . . . . . . . . . . . . . . . . . . .
Electromagnetic Compatibility, EMC . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Control Cabinet Planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Degree of Protection (IP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and Climatic Environmental Conditions in the Control
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Cooling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Information about Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information about Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ESD Protection Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conditions for UL / CSA Compliant Use . . . . . . . . . . . . . . . . . . . . . . .
Fusing the Mains Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mains Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mains Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mains Line Reactor (Choke) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of the Lexium 62 Power Supply . . . . . . . . . . . . . . . . . . . .
Leakage (Touch) Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Residual Current Operated Protective Device. . . . . . . . . . . . . . . . . . .
14 18 20
22 24 27 29 31 34 36 38
42 42 46 47
48 49 51 52 53 55 56 58 60 61 62 63 64 65
EIO0000001351 02/2020 3
3.4 Functional Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process Minimizing Risks Associated with the Machine . . . . . . . . . . .
Designated Safety Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup, Installation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
Perform Muting with the Optional Modules DIS1 . . . . . . . . . . . . . . . . .
Application Proposals for Hardware-Based Safety Functions . . . . . . .
Application Proposals for Software-Based Safety Functions . . . . . . . .
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Special Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low Air Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66 67 69 77 79 82 85 86 87 89 90 91 93 93
Chapter 4 Installation and Maintenance . . . . . . . . . . . . . . . . . . . . . . 97
4.1 Prerequisites for Installation and Maintenance . . . . . . . . . . . . . . . . . .
Prerequisites for Maintenance and Installation . . . . . . . . . . . . . . . . . .
4.2 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prerequisites for Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grinding the Holding Brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing the Control Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring the Lexium 62 Connection Module in Linear or Tree Topologies Wiring from the Lexium 62 Connection Module in a Daisy Chain
Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Maintenance, Repair, Cleaning, Replacement Equipment Inventory. .
Prerequisites for Maintenance, Repair, and Cleaning . . . . . . . . . . . . .
Fuse Replacement Lexium 62 Connection Module . . . . . . . . . . . . . . .
Machine Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacement Equipment Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Replacing Components and Cables. . . . . . . . . . . . . . . . . . . . . . . . . . .
Prerequisites for Replacing Components and Cables . . . . . . . . . . . . .
Replacement of the Lexium 62 Connection Module . . . . . . . . . . . . . .
Replacement of the Lexium 62 Distribution Box . . . . . . . . . . . . . . . . .
Replacement of the Lexium 62 ILM Integrated Servo Drive . . . . . . . .
98 98
99 100 101 103 104 108 114
120 124 125 127 131 132 133 134 135 138 141 145
Chapter 5 Indicators and Control Elements. . . . . . . . . . . . . . . . . . . 149
Indicators of the Lexium 62 Power Supply . . . . . . . . . . . . . . . . . . . . .
Indicators of the Lexium 62 Connection Module . . . . . . . . . . . . . . . . .
Indicators of the Lexium 62 Distribution Box . . . . . . . . . . . . . . . . . . . .
Indicators of the Lexium 62 ILM Integrated Servo Drive . . . . . . . . . . .
150 153 155 157
Chapter 6 Electrical Power Connections . . . . . . . . . . . . . . . . . . . . . 161
Electrical Connections for the Lexium 62 Power Supply . . . . . . . . . . .
Electrical Connections for the Lexium 62 Connection Module . . . . . .
Electrical Connections for the Lexium 62 Distribution Box . . . . . . . . .
Electrical Connections for the Lexium 62 ILM Integrated Servo Drive
Electrical Connections for the ILM Daisy Chain Connector Box . . . . .
162 168 174 177 179
Chapter 7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Standards and Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and Electrical Data for the Lexium 62 Power Supply . . . .
Mechanical and Electrical Data for the Lexium 62 Connection Module Mechanical and Electrical Data for the Lexium 62 Distribution Box . . Mechanical and Electrical Data for the
ILM Daisy Chain Connector Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and Electrical Data for the Lexium 62 ILM Integrated Servo
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and Electrical Data for the ILM070 Servo Motor . . . . . . .
Mechanical and Electrical Data for the ILM100 Servo Motor . . . . . . .
Mechanical and Electrical Data for the ILM140 Servo Motor . . . . . . .
Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Shaft and Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Holding Brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Arrangement and Degree of Protection. . . . . . . . . . . . . . . .
Torque / Speed Characteristic Curves . . . . . . . . . . . . . . . . . . . . . . . .
186 187 188 191 194
197
202 205 208 211 214 215 217 219 220
Chapter 8 Lexium 62 ILM Digital I/O Module. . . . . . . . . . . . . . . . . . 227
Lexium 62 ILM Digital I/O Module - Description . . . . . . . . . . . . . . . . .
Lexium 62 ILM Digital I/O Module - Technical Data . . . . . . . . . . . . . .
Lexium 62 ILM Digital I/O Module - Installation. . . . . . . . . . . . . . . . . .
Lexium 62 ILM Digital I/O Module - Electrical Connections. . . . . . . . .
Lexium 62 ILM Digital I/O Module - Wiring . . . . . . . . . . . . . . . . . . . . .
228 229 231 234 238
Chapter 9 Lexium 62 ILM Safety Module . . . . . . . . . . . . . . . . . . . . 239
Lexium 62 ILM Safety Module - Description . . . . . . . . . . . . . . . . . . . .
Lexium 62 ILM Safety Module - Technical Data . . . . . . . . . . . . . . . . .
Lexium 62 ILM Safety Module - Installation. . . . . . . . . . . . . . . . . . . . .
240 241 243
EIO0000001351 02/2020 5
Chapter 10 Hybrid Connector HCN-2 Adapter . . . . . . . . . . . . . . . . . . 247
Hybrid Connector HCN-2 Adapter - Description . . . . . . . . . . . . . . . . .
Hybrid Connector HCN-2 Adapter - Technical Data . . . . . . . . . . . . . .
Hybrid Connector HCN-2 Adapter- Installation . . . . . . . . . . . . . . . . . .
Hybrid Connector HCN-2 Adapter - Electrical Connections. . . . . . . . .
Hybrid Connector HCN-2 Adapter - Dimensions . . . . . . . . . . . . . . . . .
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
248 249 251 253 255
257
259 261 263

Safety Information

Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
EIO0000001351 02/2020 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.

About the Book

At a Glance
Document Scope
Read and understand the material contained in this manual before you work on Lexium 62 ILM drive for the first time. Take particular note of the chapter
(see page 13) (see page 20)
A copy of this manual must be available for personnel who work with the Lexium 62 ILM drive. This manual is to help you use the capabilities of the Lexium 62 ILM drive safely and properly. Follow the instructions within this manual to help:
Reduce risksReduce repair costs and downtime of the Lexium 62 ILM components.Increase the service life of the Lexium 62 ILM components.Increase reliability of the Lexium 62 ILM components.
Validity Note
This document has been updated for the release of EcoStruxureTM Machine Expert V1.2. The technical characteristics of the devices described in the present document also appear online.
To access the information online, go to the Schneider Electric home page
electric.com
Specific Safety Information
. Only those persons who meet the criteria described in are allowed to work with the Lexium 62 ILM components.
.
Qualification of Personnel
www.schneider-
Related Documents
Document title Reference EcoStruxure Machine Expert Programming Guide
LXM62LT00A01000 Lexium 62 DC Link Terminal, Instruction Sheet
SH3 Servo Motor - User Guide
EIO0000001351 02/2020 9
EIO0000002854 (ENG) EIO0000002855 (FRE) EIO0000002856 (GER) EIO0000002857 (ITA) EIO0000002858 (SPA) EIO0000002859 (CHS)
NVE50846 (ENG)
0198441113987 (ENG)
;
;
Terminology Derived from Standards
The technical terms, terminology, symbols and the corresponding descriptions in this manual, or that appear in or on the products themselves, are generally derived from the terms or definitions of international standards.
In the area of functional safety systems, drives and general automation, this may include, but is not limited to, terms such as
safety, safety function, safe state, fault, fault reset, malfunction, failure
error, error message, dangerous
Among others, these standards include:
Standard Description IEC 61131-2:2007 Programmable controllers, part 2: Equipment requirements and tests. ISO 13849-1:2015 Safety of machinery: Safety related parts of control systems.
EN 61496-1:2013 Safety of machinery: Electro-sensitive protective equipment.
ISO 12100:2010 Safety of machinery - General principles for design - Risk assessment and risk
EN 60204-1:2006 Safety of machinery - Electrical equipment of machines - Part 1: General
ISO 14119:2013 Safety of machinery - Interlocking devices associated with guards - Principles
ISO 13850:2015 Safety of machinery - Emergency stop - Principles for design IEC 62061:2015 Safety of machinery - Functional safety of safety-related electrical, electronic,
IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety-
IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety-
IEC 61508-3:2010 Functional safety of electrical/electronic/programmable electronic safety-
IEC 61784-3:2016 Industrial communication networks - Profiles - Part 3: Functional safety
2006/42/EC Machinery Directive 2014/30/EU Electromagnetic Compatibility Directive 2014/35/EU Low Voltage Directive
General principles for design.
Part 1: General requirements and tests.
reduction
requirements
for design and selection
and electronic programmable control systems
related systems: General requirements.
related systems: Requirements for electrical/electronic/programmable electronic safety-related systems.
related systems: Software requirements.
fieldbuses - General rules and profile definitions.
,
, etc.
In addition, terms used in the present document may tangentially be used as they are derived from other standards such as:
Standard Description IEC 60034 series Rotating electrical machines IEC 61800 series Adjustable speed electrical power drive systems IEC 61158 series Digital data communications for measurement and control – Fieldbus for use in
industrial control systems
Finally, the term hazards, and is defined as it is for a
2006/42/EC
(
zone of operation
) and
ISO 12100:2010
may be used in conjunction with the description of specific
hazard zone
or
danger zone
in the
Machinery Directive
.
NOTE: The aforementioned standards may or may not apply to the specific products cited in the present documentation. For more information concerning the individual standards applicable to the products described herein, see the characteristics tables for those product references.
EIO0000001351 02/2020 11
Lexium 62 ILM Specific Safety Information EIO0000001351 02/2020

Specific Safety Information

Chapter 1
Specific Safety Information
Overview
This chapter contains important safety information regarding working with the Lexium 62 ILM.
What Is in This Chapter?
This chapter contains the following topics:
Product Related Information 14 Intended Use 18 Qualification of Personnel 20
Topic Page
EIO0000001351 02/2020 13
Specific Safety Information

Product Related Information

Overview
Health and safety risks arising from the Lexium 62 ILM have been reduced. However residual risks remain, since the Lexium 62 ILM components work with electrical voltage and electrical currents as well as initiation of movement that may be hazardous depending on your machine design.
If activities involve residual risks, a safety message is made at the appropriate points. This includes potential hazard(s) that may arise, their possible consequences, and describes preventive measures to avoid the hazard(s).
Electrical Parts
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.Measure the voltage on the DC bus with a properly rated voltage sensing device and verify
that the voltage is less than 42.4 Vdc.
Do not assume that the DC bus is voltage-free when the DC bus LED is off.Block the motor shaft to prevent rotation prior to performing any type of work on the drive
system.
Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
DANGER
14
EIO0000001351 02/2020
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operate electrical components only with a connected protective ground (earth) cable.After the installation, verify the secure connection of the protective ground (earth) cable to all
electrical devices to ensure that connection complies with the connection diagram.
Before enabling the device, safely cover the live components to prevent contact.Do not touch the electrical connection points of the components when the module is
energized.
Provide protection against indirect contact.Connect and disconnect cables and terminals only after you have verified that the power has
been removed from the system.
Failure to follow these instructions will result in death or serious injury.
Assembly and Handling
This product has a leakage (touch) current greater than 3.5 mA. If the protective ground connection is interrupted, a hazardous leakage (touch) current may flow if the housing is touched.
INSUFFICIENT GROUNDING
Use a protective ground copper conductor with at least 10 mm
ground copper conductors with the same or larger cross section of the conductors supplying the power terminals.
Verify compliance with all local and national electrical code requirements as well as all other
applicable regulations with respect to grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
DANGER
DANGER
Specific Safety Information
2
(AWG 6) or two protective
WARNING
CRUSHING, SHEARING, CUTTING AND HITTING DURING HANDLING
Observe the general construction and safety regulations for handling and assembly.Use appropriate mounting and transport equipment and use appropriate tools.Prevent clamping and crushing by taking appropriate precautions.Cover edges and angles to protect against cutting damage.Wear appropriate protective clothing (for example, protective goggles, protective boots,
protective gloves).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001351 02/2020 15
Specific Safety Information
Hazardous Movements
There can be different sources of hazardous movements:
No, or incorrect, homing of the driveWiring or cabling errorsErrors in the application programComponent errorsError in the measured value and signal transmitter
NOTE: Provide for personal safety by primary equipment monitoring or measures. Do not rely only on the internal monitoring of the drive components. Adapt the monitoring or other arrangements and measures to the specific conditions of the installation in accordance with a risk and error analysis.
UNAVAILABLE OR INADEQUATE PROTECTION DEVICE(S)
Prevent entry to a zone of operation with, for example, protective fencing, mesh guards,
protective coverings, or light barriers.
Dimension the protective devices properly and do not remove them.Do not make any modifications that can degrade, incapacitate, or in any way invalidate
protection devices.
Before accessing the drives or entering the zone of operation, bring the drives and the motors
they control to a stop.
Protect existing workstations and operating terminals against unauthorized operation.Position EMERGENCY STOP switches so that they are easily accessible and can be reached
quickly.
Validate the functionality of EMERGENCY STOP equipment before start-up and during
maintenance periods.
Prevent unintentional start-up by disconnecting the power connection of the drive using the
EMERGENCY STOP circuit or using an appropriate lock-out tag-out sequence.
Validate the system and installation before the initial start-up.Avoid operating high-frequency, remote control, and radio devices close to the system
electronics and their feed lines, and perform, if necessary, an EMC validation of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
16
EIO0000001351 02/2020
Drive systems may perform unanticipated movements because of incorrect wiring, incorrect settings, incorrect data or other errors.
UNINTENDED MOVEMENT OR MACHINE OPERATION
Carefully install the wiring in accordance with the EMC requirements.Do not operate the product with undetermined settings and data.Perform comprehensive commissioning tests that include verification of configuration settings
and data that determine position and movement.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
PELV Circuits
ELECTRIC SHOCK DUE TO INADEQUATE PROTECTIVE SEPARATION Only connect devices, electrical components, or lines to the signal voltage connectors of these
products that feature a sufficient, protective separation from the connected circuits in accordance with the standards (IEC 61800-5-1: Adjustable speed electrical power drive systems - safety requirements).
Failure to follow these instructions will result in death or serious injury.
Specific Safety Information
WARNING
DANGER
EIO0000001351 02/2020 17
Specific Safety Information

Intended Use

Installation
Install and operate this equipment in a control cabinet (enclosure) appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
The Lexium 62 ILM and the Lexium 62 Distribution Box are intended for the installation in a machine.
Provide for Protective Measures
Before installing the device, provide for appropriate protective devices in compliance with local and national standards. Do not commission components without appropriate protective devices. After installation, commissioning, or repair, test the protective devices used.
Perform a risk evaluation concerning the specific use before operating the product and take appropriate safety measures.
UNINTENDED EQUIPMENT OPERATION Ensure that a risk assessment is conducted and respected according to EN/ISO 12100 during
the design of your machine. Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
18
If circumstances occur that affect the safety or cause changes to the operating behavior of the Lexium 62 ILM components, then immediately shut down the Lexium 62 ILM components and contact your Schneider Electric representative.
EIO0000001351 02/2020
Use Original Equipment Only
Use only the accessories and mounting parts specified in the documentation and no third-party devices or components that have not been expressly approved by Schneider Electric.
There are no user-serviceable parts in the Lexium 62 ILM system. Do not attempt to modify the Lexium 62 ILM in any way. Refer to Schneider Electric for all repairs and replacements.
UNINTENDED EQUIPMENT OPERATION
Only use software and hardware components approved by Schneider Electric for use with this
equipment.
Do not attempt to service this equipment outside of authorized Schneider Electric service
centers.
Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Environment Restrictions
The components must not be used in the following environments:
In hazardous (explosive) atmospheres In mobile, movable, or floating systems In life support systemsIn domestic appliancesUnderground
This equipment has been designed to operate outside of any hazardous location. Only install this equipment in zones known to be free of a hazardous atmosphere.
Specific Safety Information
WARNING
DANGER
POTENTIAL FOR EXPLOSION Install and use this equipment in non-hazardous locations only. Failure to follow these instructions will result in death or serious injury.
EIO0000001351 02/2020 19
Specific Safety Information

Qualification of Personnel

Target Audience for This Manual
Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Qualified Person
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved.
The qualified personnel must be able to detect possible hazards that may arise from parameter­ization, changing parameter values and generally from mechanical, electrical, or electronic equipment. The qualified personnel must be familiar with the standards, provisions, and regulations for the prevention of industrial accidents, which they must observe when working on the drive system.
Designated Safety Functions
Qualified personnel that work with designated safety functions must be trained according to the complexity of the machines and the requirements of the ISO 13849-1. The training has to include the production process and the relation between the designated safety function and the machine.
Qualification guidelines are available in the following publication:
Commitment: Competency Guidelines for Safety-Related System Practitioners
IEEE Publications, ISBN 0 85296 787 X, 1999.
Safety, Competency and
.
20
EIO0000001351 02/2020
Lexium 62 ILM System Overview EIO0000001351 02/2020

System Overview

Chapter 2
System Overview
What Is in This Chapter?
This chapter contains the following topics:
System Overview 22 Lexium 62 Power Supply 24 Lexium 62 Connection Module 27 Lexium 62 Distribution Box 29 Lexium 62 ILM Integrated Servo Drive 31 Lexium 62 ILM Digital I/O Module 34 Lexium 62 ILM Safety Module 36 ILM Daisy Chain Connector Box 38
Topic Page
EIO0000001351 02/2020 21

System Overview

System Overview
System Overview
The control system consists of several components, depending on its application. PacDrive 3 system overview:
22
(1) EcoStruxure Machine Expert Software (2) Safety Logic Controller according to IEC 61508:2010 and EN ISO 13849:2008
EIO0000001351 02/2020
Lexium 62 ILM system overview:
1 Lexium 62 Connection Module 2 Lexium 62 Distribution Box 3 Lexium 62 ILM Integrated Servo Drive 4 Lexium 62 ILM with Safety Module 5 Hybrid Cable
System Overview
EIO0000001351 02/2020 23
System Overview

Lexium 62 Power Supply

Overview
Product Description
The central Lexium 62 Power Supply, using a common DC bus, supplies the connected Lexium 62 servo drive(s) with the required power. For further information, refer to:
Installation and Maintenance (see page 97)
Indicators of the Lexium 62 Power Supply (see page 150)
Electrical Connections for the Lexium 62 Power Supply (see page 162)
Mechanical and Electrical Data for the Lexium 62 Power Supply (see page 188)
References
Product Reference Power supply LXM62PD20A11000
24
LXM62PD84A11000
EIO0000001351 02/2020
Type Code
Item Meaning Product
family Size 62 = Lexium 62 Type P = Power Module Peak
current Variants A = Power Supply Module Options 1 = 1 or 3 Phases x 208...480 Vac Hardware
release Internal 0 = Serial production Customer 00 = Standard Type code
(example)
Technical Nameplate
The technical nameplate is located laterally on housing.
System Overview
LXM = Lexium
D84 = 84 A D20 = 20 A
1
LXM 62 P D84 A 1 1 0 00
Label Meaning LXM62PDxxxxxxx Device type and Unicode Input ac/dc Input voltage and/or input current (rated- and/or peak
Output dc Output voltage and output current (rated and/or peak
IP20 Degree of protection Symbols This field displays the symbols of declarations and
EIO0000001351 02/2020 25
value per input)
value per output)
certifications
System Overview
Logistic Nameplate
The technical nameplate is located on top of the housing.
Label Meaning LXM62PDxxxxxxx Device type and Unicode 2528044067 Serial number RS:01 Hardware revision DOM Date of manufacture Symbols This field displays the symbols of declarations and
certifications
26
EIO0000001351 02/2020

Lexium 62 Connection Module

Overview
The Lexium 62 Connection Module simplifies the wiring of the devices. With the Lexium 62 Connection Module you can connect up to 45 servo drives.
Product Description
System Overview
The Lexium 62 Connection Module supplies the Lexium 62 ILMs with DC voltage from the DC bus via a hybrid cable or a power cable (daisy chain wiring). Additionally, the Lexium 62 Connection Module provides the Inverter Enable and Sercos interface. For further information, refer to:
Installation and Maintenance (see page 97)
Indicators of the Lexium 62 Connection Module (see page 153)
Electrical Power Connection of the Lexium 62 Connection Module (see page 168)
Mechanical and Electrical Data for the Lexium 62 Connection Module (see page 191)
References
Product Reference Lexium 62 Connection Module ILM62CMD20A000
EIO0000001351 02/2020 27
System Overview
Type Code
Item Meaning Product family ILM = Integrated Lexium Servo Module Size 62 = Lexium 62 Type CM = Connection Module Power
(cont. DC Bus current)
Variants A Internal 0 = Serial production Customer 00 = Standard Type code
(example)
Technical Nameplate
The technical nameplate is located laterally on housing.
Label Meaning ILM62CMxxxxxxx Device type and Unicode Input dc Input voltage and/or input current (rated- and/or peak
Output ac/dc Output voltage and output current (rated and/or peak
IP20 Degree of protection Symbols This field displays the symbols of declarations and
D20
ILM 62 CM D20 A 0 00
value per input)
value per output)
certifications
Logistic Nameplate
The technical nameplate is located on top of the housing.
Label Meaning ILM62xxxxxxxxxx Device type and Unicode 2528044067 Serial number RS:01 Hardware revision DOM Date of manufacture Symbols This field displays the symbols of declarations and
28
certifications
EIO0000001351 02/2020

Lexium 62 Distribution Box

Overview
Product Description
The highlights:
1...4 connections for Lexium 62 ILMs or daisy chain lines or further Lexium 62 distribution
boxes.
Pre-assembled hybrid cables or power cables (Daisy Chain wiring).
System Overview
The Lexium 62 Distribution Box is the link between Lexium 62 Connection Module and Lexium 62 ILM. Depending on the number of drives, 1 to 4 Lexium 62 ILMs or daisy chain lines can be connected. When operating more than four drives, expand the system by using more Lexium 62 distribution boxes. For further information, refer to:
Installation and Maintenance (see page 97)
Indicators of the Lexium 62 Distribution Box (see page 155)
Electrical Connections for the Lexium 62 Distribution Box (see page 174)
Mechanical and Electrical Data for the Lexium 62 Distribution Box (see page 194)
References
Product Reference Lexium 62 Distribution Box ILM62DB4A000 Sercos bridge plug VW3E6023
EIO0000001351 02/2020 29
System Overview
Type Code
Item Meaning Product family ILM = Integrated Lexium Servo Module Size 62 = Lexium 62 Type DB = Distribution Box Hybrid outputs 4 Variants A Internal 0 Customer 0 Type code (example) ILM 62 DB 4 A000
Technical Nameplate
The technical nameplate is located laterally on housing:
Label Meaning ILM62DBxxxxx Device type and Unicode Input dc Input voltage and/or input current (rated- and/or peak
Output ac/dc Output voltage and output current (rated and/or peak
IP65 Degree of protection Symbols This field displays the symbols of declarations and
value per input)
value per output)
certifications
Logistic Nameplate
Label Meaning ILM62DBxxxxx Device type and Unicode 2328234578 Serial number RS:01 Hardware revision DOM Date of manufacture
30
EIO0000001351 02/2020

Lexium 62 ILM Integrated Servo Drive

Overview
Product Description
The Lexium 62 ILMs are available in three different flange sizes:
ILM070 (70 mm / 2.76 in.)ILM100 (100 mm / 3.94 in.)ILM140 (140 mm / 5.51 in.)
The Lexium 62 ILMs have been derived from the Schneider Electric SH3 family of motors, and therefore share many characteristics. For instance, when it comes to mounting the motor, the Lexium 62 ILMs are equivalent.
The highlights:
Compact design3.5 times peak torqueIntegrated Sercos interfaceHigh-resolution single or multi-turn encoderDegree of protection IP65 (depending on the reference and/or options)
System Overview
The Lexium 62 ILM combines motor, power stage, and digital servo controller for an axis in a space­saving housing. Due to its compact design with the integrated drive, it is suitable for decentralized, distributed architectures. It is available with single­turn or multi-turn encoders, and simplifies configuration with the aid of the electronic nameplate in the Lexium 62 ILM. For further information, refer to:
Installation and Maintenance (see page 98)
Indicators of the Lexium 62 ILM Integrated Servo Drive (see page 157)
Electrical Connections for the Lexium 62 ILM Integrated Servo Drive (see page 177)
Mechanical and Electrical Data for the Lexium 62 ILM Integrated Servo Drive (see page 202)
EIO0000001351 02/2020 31
System Overview
References
Device Reference Lexium 62 ILM Integrated Servo Drive
Type Code
Item Meaning Product family ILM = Integrated Lexium Servo Module Flange size 070 = 70 mm / 2.76 in.
Number of stacks
Winding type P = Standard
Shaft
(see page 215)
Encoder
(see page 214)
Holding brake
(see page 217)
Variants 0 Internal 0 = Standard production Costumer 00 = Standard Type code
(example)
ILM0701PILM0702PILM0703PILM1001PILM1002PILM1003PILM1401PILM1401MILM1402P
100 = 100 mm / 3.94 in. 140 = 140 mm / 5.51 in.
1 = 1 Stack 2 = 2 Stacks 3 = 3 Stacks
M = Optimized in terms of torque (available only with ILM1401)
0 = Smooth shaft, without shaft seal 1 = Parallel key, without shaft seal 2 = Smooth shaft, with shaft seal, IP65 3 = Parallel key, with shaft seal, IP65
1 = Absolute single-turn 128 SinCos periods per revolution 2 = Absolute multi-turn 128 SinCos periods per revolution
A = Without holding brake F = With holding brake
ILM 070 1 P 0 1 A 0 0 00
32
EIO0000001351 02/2020
Technical/Logistic Nameplate
Label Meaning ILMxxxxxxxxxxxx Device type, see type code SN Serial number Input 1 Rated voltage and rated current of the power supply Input 2 Rated voltage and rated current of the electronics Type rating Degree of protection of the housing in accordance with NEMA 250 and
HW Hardware version SW Software version IPxx Degree of protection Th-Cl Insulation material class of the motor M0 Standstill torque Mmax Peak torque nN Nominal speed of rotation DOM Date of manufacture Symbols This field displays the symbols of declarations and certifications.
System Overview
UL 50.
EIO0000001351 02/2020 33
System Overview

Lexium 62 ILM Digital I/O Module

Overview
Option Module for Lexium 62 ILM Integrated Servo Drive.
Product Description
Reference
Product Reference Digital I/O Module VW3E702100000
Type Code
Lexium 62 ILM Digital I/O Module with 8 digital inputs or outputs. For further information, refer to the chapter
ILM 62 Digital I/O Module (see page 227)
Lexium
.
Item Meaning Product family VW3 = Integrated Lexium Size E = PacDrive 3 Type 7 = Option Modules Drawing reference 021 = I/O Option Module for
Internal 00000 Type code (example) VW3 E 7 021 00000
34
Lexium 62 ILM 022 = Safety Option Module for Lexium 62 ILM
EIO0000001351 02/2020
Technical/Logistic Nameplate Description
Label Meaning ILM62-iSH-DIO8 I/O module Device type and Unicode VW3E702100000 Commercial reference 2910229412 Serial number DOM Date of manufacture HW Hardware version FW Firmware version
System Overview
EIO0000001351 02/2020 35
System Overview

Lexium 62 ILM Safety Module

Overview
Option module for Lexium 62 ILM integrated servo drive.
Product Description
Reference
Product Reference Safety Module VW3E702200000
Lexium 62 ILM Safety Module manages the safe motion functions via Sercos bus.
Safe Torque off (STO)Safe Stop 1 (SS1)Safe Operating Stop (SOS)Safe Stop 2 (SS2)Safe Maximum Speed (SMS)Safely-Limited Speed (SLS)Safe Direction Indication (SDI)
For further information, refer to the chapter
62 ILM Safety Module (see page 239)
Lexium
.
Type Code
Item Meaning Product family VW3 = Integrated Lexium Size E = PacDrive 3 Type 7 = Option Modules Drawing reference 021 = I/O Option Module for
Lexium 62 ILM 022 = Safety Option Module for
Lexium 62 ILM Internal 00000 Type code (example) VW3 E 7 022 00000
36
EIO0000001351 02/2020
Technical/Logistic Nameplate Description
Label Meaning Lexium 62 ILM safety option module Device type and Unicode VW3E702200000 Commercial reference 2910171253 Serial number DOM Date of manufacture HW Hardware version FW Firmware version
System Overview
EIO0000001351 02/2020 37
System Overview

ILM Daisy Chain Connector Box

Overview
Product Description Type A The ILM Daisy Chain Connector Box is mounted on
Type B Power (DC bus voltage/24 V/Inverter Enable signals)
Type C
a Lexium 62 ILM in order to enable a daisy chain wiring. The Lexium 62 ILMs can be either directly connected to the Lexium 62 Distribution Box or via a Lexium 62 Connection Module. Refer to
Wiring from the Lexium 62 Connection Module in a Daisy Chain Topology (see page 120)
When connecting via a Lexium 62 Distribution Box, a larger number of drives can be connected.
and Sercos signals are distributed via separate cables. Each Lexium 62 ILM must be extended by a Daisy Chain Connector Box (refer to
(see page 108)
Box is used, then up to four daisy chain lines can be connected to it. If several Lexium 62 distribution boxes are used, then from the first Lexium 62 Distribution Box up to and including the second last Lexium 62 Distribution Box respectively up to three daisy chain lines and on the last Lexium 62 Distribution Box up to four daisy chain lines can be connected. A daisy chain line can consist of up to nine Lexium 62 ILMs.
). If only one Lexium 62 Distribution
.
Mounting
38
EIO0000001351 02/2020
For further information, refer to:
The connection between the Lexium 62 ILMs is established as follows (refer to Wiring from the Lexium 62 Connection Module in a daisy chain topology
Power cable for power distribution (DC bus voltage/24V/Inverter Enable signals) with an M23
Sercos cable for distribution of the Sercos signals via M12 connector
Reference
Product Reference ILM Daisy Chain Connector Box
Type Code
Item Meaning Product
family Size 62 = Integrated Lexium 62 Type DC = Daisy Chain Connector Box Series A = Power at back, Sercos at bottom (ILM070, ILM100,
Internal 0 = Serial production Customer 00 = Standard Type code
(example)
System Overview
Electrical Connections for the ILM Daisy Chain Connector Box (see page 179) Mechanical and Electrical Data for the ILM Daisy Chain Connector Box (see page 197)
(see page 120)
):
connector
ILM62DCA000ILM62DCB000ILM62DCC000
ILM = Integrated Lexium Servo Module
ILM140) B = Power at bottom, Sercos at left and right (ILM070) C = Power at bottom, Sercos at left and right (ILM100) Z = Protection cap for the last M23 connector
ILM 62 DC A 0 00
EIO0000001351 02/2020 39
System Overview
40
EIO0000001351 02/2020
Lexium 62 ILM Engineering EIO0000001351 02/2020

Engineering

Chapter 3
Engineering
What Is in This Chapter?
This chapter contains the following sections:
Section Topic Page
3.1 Electromagnetic Compatibility, EMC 42
3.2 Control Cabinet Planning 46
3.3 Information about Wiring 51
3.4 Functional Safety 66
3.5 Special Conditions 93
EIO0000001351 02/2020 41
Engineering

Electromagnetic Compatibility, E MC

Section 3.1

Electromagnetic Compatibility, EMC

Electromagnetic Compatibility, EMC
Electromagnetic Disturbances of Signals and Devices
This product meets the EMC requirements according to the standard IEC 61800-3 if the measures described in this manual are implemented during installation.
Signal interference can cause unexpected responses of the drive and of other equipment in the vicinity of the drive.
WARNING
SIGNAL AND EQUIPMENT INTERFERENCE
Only operate the drive with the specified external mains filter.Install the wiring in accordance with the EMC requirements described in the present
document.
Verify compliance with the EMC requirements described in the present document.Verify compliance with all EMC regulations and requirements applicable in the country in
which the product is to be operated and with all EMC regulations and requirements applicable at the installation site.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
42
WARNING
ELECTROMAGNETIC DISTURBANCES OF SIGNALS AND DEVICES Use proper EMC shielding techniques to help prevent unintended device operation in accordance
with the standard IEC 61800-3. Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001351 02/2020
These types of devices are not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference is expected if used in such a network.
RADIO INTERFERENCE Do not use these products in domestic electrical networks. Failure to follow these instructions can result in death, serious injury, or equipment damage.
Layout Control Cabinet (Enclosure)
The prerequisite for compliance with the specified limit values is an EMC compatible layout. Depending on the application, the following measures can improve the EMC-dependent values:
EMC measures Objective Use galvanized or chromium-plated sub plates, bond
metallic parts across large surface areas, remove paint layer from contact surfaces.
Ground control cabinet (enclosure), door, and sub plates by using grounding strips or grounding cables
with a cross-section of 10 mm Supplement switch devices such as contactors,
relays, or magnetic valves with interference suppression combinations or spark suppressor elements (for example, diodes, varistors, RC elements).
Fit power and control components separately. Reduces mutual interference.
2
(AWG 6).
Engineering
WARNING
Good conductivity by surface area contact.
Reduce emission.
Reduces mutual interference.
Shielded Cables
EMC measures Objective Connect large surface areas of cable shields, use
cable clamps and ground straps. Ground shields of digital signal wires at both ends by
connecting them to a large surface area or via conductive connector housings.
Ground shield of analog signal cables directly on the device (signal input), insulate the shield at the other cable end or ground the same through a capacitor, such as 10 nF.
EIO0000001351 02/2020 43
Reduce emission.
Reduce interference action on signal cables, reduce emissions.
Reduce grounding loops by low frequency interferences.
Engineering
Cable Installation
EMC measures Objective Do not route fieldbus cables and signal wires in a
single cable duct together with lines with DC and AC voltages of more than 60 V. (Fieldbus cables, signal lines, and analog lines may be in the same cable duct) Recommendation: Use separate cable ducts at least 20 cm (7.84 in) apart.
Keep cables as short as possible. Do not install unnecessary cable loops, use short cables from the central grounding point in the control cabinet to the external ground connection.
Use equipotential bonding conductors (stranded wire of equal potential at all grounding locations connected to an equipotential grounding plane) in the following cases: wide-area installations, different voltage supplies, and installation across several buildings.
Use stranded wire potential equalization conductor. Discharging of high frequency interference currents. If motor and machine are not connected in a
conducting fashion, for example, due to an insulated flange or a connection not across a full surface, the motor must be grounded via a grounding cable with a
minimum 4 mm grounding strip with a length as short as possible.
Use twisted pair for 24 Vdc signals. Reduce interference action on signal cables, reduce
2
(AWG 11) cross-section or a
Reduces mutual interference.
Reduces capacitive and inductive interference.
Reduces current in the cable shield, reduces emissions.
Reduce emissions, increase interference resistance.
emissions.
Power Supply
EMC measures Objective Operate product on mains with grounded neutral
point. Use surge arrester if there is a risk of overvoltage. Reduces the risk of damage caused by overvoltage.
44
Enables effectiveness of mains filter.
EIO0000001351 02/2020
Additional Measures for Improving the EMC
Depending on the respective application, the following measures may lead to an EMC compatible layout:
EMC measures Objective Upstream connection of mains line reactor (choke) Reduction of the harmonic network oscillations,
Upstream connection of external mains filters Improvement of the EMC limit values. Special EMC-appropriate layout, for example, within
an enclosed control cabinet complete with 15 dB attenuation of the interferences emitted
Engineering
extension of the service life of the product.
Improvement of the EMC limit values.
EIO0000001351 02/2020 45
Engineering

Control Cabinet Planning

Section 3.2
Control Cabinet Planning
What Is in This Section?
This section contains the following topics:
Degree of Protection (IP) 47 Mechanical and Climatic Environmental Conditions in the Control Cabinet 48 Using Cooling Units 49
Topic Page
46
EIO0000001351 02/2020

Degree of Protection (IP)

Overview
Install components such that a degree of protection corresponding to the actual operational environment is set up.
For more information on the degree of protection of the component, refer to
(see page 187)
The following ambient conditions may damage the components:
OilMoistureElectromagnetic interferenceAmbient temperatureMetal dust deposits
UNINTENDED EQUIPMENT OPERATION
Observe and conform to ambient temperatures, storage temperatures and transport
temperatures of the individual components as specified in the operating manuals of the components.
Prevent the formation of moisture during the operation, storage and transport of individual
components.
Conform to the vibration and shock requirements specified in the operating manuals for the
components when operating, storing and transporting system components.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
.
Engineering
Ambient Conditions
WARNING
EIO0000001351 02/2020 47
Engineering

Mechanical and Climatic Environmental Conditions in the Control Cabinet

Overview
Step Action
1 Observe the climatic and mechanical ambient conditions.
For more information on the general climatic and mechanical environmental conditions according to IEC 60721, refer to
2 Verify the technical data of the device whether the permitted deviations (for example, higher
shock load or higher temperature) are specified.
Ambient Conditions (see page 187)
.
48
EIO0000001351 02/2020

Using Cooling Units

Installing a Cooling Unit
How to proceed when installing a cooling unit:
Step Action
1 Position the cooling units so that no condensate drips out of the cooling unit onto electronic
components or is sprayed by the cooling air flow. 2 Provide specially designed control cabinets for cooling units on the top of the control cabinet. 3 Design the control cabinet so that the cooling unit fan cannot spray any accumulated condensate
onto the electronic components when it restarts after a pause. 4 When using cooling units, use only well-sealed control cabinets so that warm, humid outside air,
which causes condensation, does not enter the cabinet. 5 When operating control cabinets with open doors during commissioning or maintenance, ensure
that the electronic components are at no time cooler than the air in the control cabinet after the
doors are shut, in order to avoid any condensation. 6 Continue to operate the cooling unit even when the system is switched off, so that the
temperature of the air in the control cabinet and the air in the electronic components remains the
same. 7 Set cooling unit to a fixed temperature of 40 °C or lower (104 °F). 8 For cooling units with temperature monitoring, set the temperature limit to 40 °C (104 °F) so that
the internal temperature of the control cabinet does not fall below the external air temperature.
Engineering
WARNING
UNINTENDED EQUIPMENT OPERATION Follow the installation instructions such that the condensation from the cooling unit can not enter
electrical equipment. Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001351 02/2020 49
Engineering
Installing a cooling unit
50
EIO0000001351 02/2020

Information about Wiring

Section 3.3
Information about Wiring
What Is in This Section?
This section contains the following topics:
General Information about Wiring 52 Cable Characteristics 53 ESD Protection Measures 55 Conditions for UL / CSA Compliant Use 56 Fusing the Mains Connection 58 Mains Contactor 60 Mains Filter 61 Mains Line Reactor (Choke) 62 Connection of the Lexium 62 Power Supply 63 Leakage (Touch) Current 64 Residual Current Operated Protective Device 65
Engineering
Topic Page
EIO0000001351 02/2020 51
Engineering

General Information about Wiring

Overview
Use only Schneider Electric approved devices in your application, and especially Schneider Electric pre-fabricated cables, wherever and whenever possible.
For further information, refer to Use an appropriate torque indication or screwdriver for tightening connections. Observe and implement the following points when wiring:
1. Observe the minimum cross-sections of the cables necessary for the load carrying capacity of the equipment being connected.
2. Verify the integrity of cable shields to ensure continuity to ground.
3. Ensure that there is a proper, equipotential connection to ground for all interconnected equipment.
4. Ensure connection of the motors to the machine ground.
5. Eliminate any ground loops.
6. Do not disconnect cable connection terminals when under power.
7. Ensure that all ground connections have sufficient surface area continuity.
8. Do not interchange motor phases.
9. Do not interchange encoder connections.
10.Connect the hybrid or power cable connections and the Sercos cable connections to the Lexium 62 Connection Module according to the connection diagram of the machine manufacturer. For information on the different cable type refer to
11.Do not interchange the emergency stop circuits. This has to be observed especially when two different safety-related circuits are used for axis A and axis B of the Lexium 62 Double Drive.
If, for example, two parallel conductors are shown as coming from one point, you may not run just one conductor and then branch it off at a later point. If it is wired this way, induction loops (interference emitters and antennas) as well as interfering potential shifts may occur.
Cable Characteristics (see page 53)
Cable Characteristics (see page 53)
.
.
52
DANGER
INCORRECT OR UNAVAILABLE GROUNDING Remove paint across a large surface at the installation points before installing the devices (bare
metal connection). Failure to follow these instructions will result in death or serious injury.
EIO0000001351 02/2020

Cable Characteristics

Overview
Cable characteristics of the hybrid cable:
Property Value Hybrid cable voltage isolation 1000 V Maximum continuous current
Temperature range -40...+80 °C / -40...+176 °F Cable diameter 14.8 ± 0.3 mm (0.58 ± 0.012 in.) Bending radius Five x diameter (fixed routing)
Sheath PUR, oil resistant, halogen-free
The hybrid cable (daisy chain wiring) is drag chain capable. Cable characteristics of the power cable (daisy chain wiring):
Property Value Voltage isolation 1000 V Maximum continuous current
Temperature range -40...+80 °C / -40...+176 °F (fixed routing)
Cable diameter 11.7 ± 0.3 mm (0.45 ± 0.012 in.) Bending radius 5 x diameter (fixed routing)
Sheath PUR, oil resistant, halogen-free, flame-retardant
Engineering
DC Bus: 20 A24 Vdc: 20 A
10 x diameter (mobile, 5 million bending cycles)
DC Bus: 20 A24 Vdc: 20 A
-25...+80 °C / -13...+176 °F (mobile)
10 x diameter (mobile, 5 million bending cycles)
The power cable (daisy chain wiring) is drag chain capable.
EIO0000001351 02/2020 53
Engineering
Cable characteristics of the Sercos cable (daisy chain wiring):
Property Value Voltage isolation 300 V Temperature range -20...+60 °C / -4...+140 °F Cable diameter 6.7 ± 0.2 mm (0.26 ± 0.008 in.) Bending radius 5 x diameter (fixed routing)
Sheath PUR, halogen-free, flame-retardant Cable type and shielding CAT6 with S/FTP (Sercos III)
10 x diameter (mobile, 5 million bending cycles)
54
EIO0000001351 02/2020

ESD Protection Measures

General
Observe the following instructions to help avoid damages due to electrostatic discharge:
ELECTROSTATIC DISCHARGE
Do not touch any of the electrical connections or components.Prevent electrostatic charges, for example, by wearing appropriate clothing.If you must touch circuit boards, do so only on the edges.Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.
Engineering
NOTICE
EIO0000001351 02/2020 55
Engineering

Conditions for UL / CSA Compliant Use

General
If you use the Lexium 62 ILM system in accordance with UL or CSA standards, you must additionally, aside from the installation requirements stated in the present document, meet the following conditions:
Install the “open type equipment” Lexium 62 ILM system at a maximum surrounding air
temperature of 40 °C / 55 °C with derating.
Only connect the power supply to a mains supply with a maximum short circuit current of 22 kA
or, alternatively, take appropriate measures according to UL508A SB4 in the supply circuit of the control cabinet to limit the short circuit current to 22 kA maximum. This does not apply to operation in accordance with CSA 22.2 No. 14. Here, it is only permissible to operate the device for a maximum short circuit current of 5 kA.
Use devices only in connection with a Lexium 62 Power Supply.To protect the power supply, use a class J fuse according to UL248 with a maximum fuse rating
of 60 A / 600 Vac.
Only use hybrid connection cable approved by Schneider Electric and comply with the
requirements of NFPA 79.
Short-Circuit Current Rating (SCCR)
Only connect the Lexium 62 Drive System to a mains supply network not exceeding the non­operational case of SCCR (Short Circuit Current Rating) from following table, or take appropriate measures according to UL 508 A SB4 in the supply (feeder) circuit of the control cabinet to limit the short circuit current to a value below the least SCCR of those devices you are using from the following table.
NOTE: The opening of the branch-circuit protective device (fuses in the case of UL conformance, or any circuit breaker) may be an indication that an invalid condition has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the controller must be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.
56
DANGER
FIRE, ELECTRIC SHOCK OR ARC FLASH Examine and replace if necessary any current-carrying parts or other controller components in
the case of mains- or branch-circuit protection activation. Failure to follow these instructions will result in death or serious injury.
According to CSA 22.2 No.14, only a short circuit current rating of 5 kA is permissible. NOTE: Line reactors according to UL 508 A (SB 4.2.1 Exception No. 1) are not required to have a
short-circuit current rating (SCCR).
EIO0000001351 02/2020
Notes on Wiring
For the wiring of the Lexium 62 Power Supply, use at least 60 °C (140 °F) / 75 °C (167 °F)
copper conductors.
Choose the cross-section according to the load of the system and selected overload protection
in your application. Consider the applicable cross section for the terminal blocks according to following tables: For Lexium 62 Power Supply
Engineering
Connection Torque [Nm] / [lbf in]
CN1 2.5 / 22 N/A CN5 N/A 0.5...16 / 20...6 CN6 N/A 0.75...16 / 18...6 CN7 N/A 0.2...6 / 24...10 CN4 N/A 0.5...1.5 / 20...16 (1) To protect the Lexium 62 Power Supply, use a Class J fuse according to UL 248 with a maximum fuse
rating of 60 A / 600 Vac.
DC Bus Coupling
When using the DC bus connection on CN7 of the Lexium 62 Power Supply, ensure that the current is limited to 35 A via this connection with an appropriate fuse or circuit breaker.
Connection cross section [mm²] / [AWG]
(1)
EIO0000001351 02/2020 57
Engineering

Fusing the Mains Connection

General
This data is only valid for fusing the mains connection of each Lexium 62 Power Supply module:
Protect the power supply against any short-circuit and overload using appropriate measures.Set the overload protection depending on the permanent current of the device:
Lexium 62 Power Supply (LXM62PD84A11000) maximum of 40 A (3-phase),Lexium 62 Power Supply (LXM62PD20A11000) maximum of 10 A (3-phase).
NOTE: The opening of the branch-circuit protective device (fuses in the case of UL conformance, or any circuit breaker) may be an indication that an abnormal condition has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the system should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced. In any and all cases, determine the source of the opening of the branch-circuit protection before re-applying power to the system.
FIRE, ELECTRIC SHOCK OR ARC FLASH Examine and replace if necessary any current-carrying parts or other motor control components
in the case of mains- or branch-circuit protection activation. Failure to follow these instructions will result in death or serious injury.
DANGER
58
EIO0000001351 02/2020
Allowable Combinations
Combine mains contactor and motor protection switch for protection of a Lexium 62 Power Supply as follows:
Engineering
Mains current DC bus
current (with mains lines reactor)
16 A ≤ 8 A 1-phase Circuit breaker iC60N,
20 A ≤10 A 1-phase Circuit breaker iC60N,
9.5 A ≤ 10 A 3-phase TeSys Model U LUB12 with
12 A ≤ 12.5 A 3-phase TeSys Model U LUB12 with
18 A ≤19 A 3-phase TeSys Model U LUB32 with
32 A ≤ 33.5 A 3-phase TeSys Model U LUB32 with
40 A ≤ 42 A 3-phase Mains contactor
Connection type Protection Lexium 62
Power Supply (LXM62PD20A11000)
characteristic C, 16 A
characteristic C, 20 A
LUCA12BL
Protection Lexium 62 Power Supply (LXM62PD84A11000)
LUCA12BL
LUCA18BL
LUCA32BL
LC1D40ABD motor protection switch GV3P40
Limit the external 24 Vdc supply to the Lexium 62 Power Supply module with adequate means to 50 A.
EIO0000001351 02/2020 59
Engineering

Mains Contactor

General
The selection of the mains contactor must be in accordance with the protection requirements of the mains line.
60
EIO0000001351 02/2020

Mains Filter

Overview
The products described in the present document meet the EMC requirements in accordance with the standard IEC/EN 61800-3, if the EMC measures described in this manual are complied with during the installation. The values are based on the reference application specified in the manual. Refer to Electromagnetic Compatibility, EMC
The connected cable length and the number of connected motors has no significant influence on the grid-bound emitted interference. Thus, no external mains filter is required when only the Lexium 62 ILM related components are used.
In the case of a mixed system using the Lexium 62 Servo Drives combined with the Lexium 62 ILM components, the selection of the external mains filter depends on the devices installed in the control cabinet and the motor supply cables. The hybrid cable or power cable (with daisy chain wiring) of the Lexium 62 ILM is not considered as motor supply cables.
NOTE: For additional information on mains filtering, contact your Schneider Electric representative.
(see page 42)
Engineering
.
EIO0000001351 02/2020 61
Engineering

Mains Line Reactor (Choke)

Overview
A mains line reactor (choke) is required for the application. A mains line reactor is necessary to reduce the harmonics of the mains current. The mains line reactor must have at least 4% voltage drop at rated load.
With UL/CSA Certification
Mains line reactor with UL / CSA certification:
Schneider Electric: VPM05D100000 for architectures up to 10 A Schneider Electric: VPM05D250000 for architectures up to 25 ASchneider Electric: VPM05D500000 for architectures up to 50 ASchneider Electric: VW3A4551 for architectures up to 4 A Schneider Electric: VW3A4552 for architectures up to 10 ASchneider Electric: VW3A4553 for architectures up to 16 ASchneider Electric: VW3A4554 for architectures up to 30 ASchneider Electric: VW3A4555 for architectures up to 60 A
A shielded version of the connection cables is not required. NOTE: Verify that the rated current of the mains line reactor is above preset overload protection of
the protective device.
Correlation Between Mains Current and DC Bus Current (3-Phase Operation)
The mains current is approximately the same as the DC bus current and corresponds to the current of the mains line reactor. For the design of the mains line reactor, use a dimensioning of the mains current of 100% to 110% of the DC bus current.
Mains Line Reactor and External Mains Filter
If a mains line reactor and an external mains line reactor are required, the mains line reactor and external mains filter must be arranged according to the following illustrations for EMC reasons.
62
EIO0000001351 02/2020

Connection of the Lexium 62 Power Supply

Overview
Connection of a Lexium 62 Power Supply
Engineering
NOTE: The 24 Vdc supply input current must be limited to 50 A, which can be realized by a 50 A fuse as shown above. In particular, a 50 A fuse is mandatory if a passive 24 Vdc power supply is used.
For further information, refer to
EIO0000001351 02/2020 63
Fusing the Mains Connection (see page 58)
.
Engineering

Leakage (Touch) Current

Overview
Application Per Lexium 62 Connection
Module
Typical (400V, 50Hz) < 9mA < 18mA ≤141mA
Per Lexium 62 Distribution Box
Per Lexium 62 Power Supply
NOTE: If the leakage (touch) current is too high for the respective application, use an isolating transformer on the mains supply.
This product has a leakage (touch) current greater than 3.5 mA. If the protective ground connection is interrupted, a hazardous leakage (touch) current may flow if the housing is touched.
DANGER
INSUFFICIENT GROUNDING
Use a protective ground copper conductor with at least 10 mm
ground copper conductors with the same or larger cross section of the conductors supplying the power terminals.
Verify compliance with all local and national electrical code requirements as well as all other
applicable regulations with respect to grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
2
(AWG 6) or two protective
64
EIO0000001351 02/2020

Residual Current Operated Protective Device

Using Residual Current Protective Devices
When using a residual current protective device in combination with the Lexium 62 Drive System, certain conditions and restrictions must be considered. As a dc current component in the ground conductor may result from insulation damage or direct contact, residual current circuit-breakers of type A or AC may not be triggered and therefore must not be used. Moreover, during system power-up and also in normal operation the Lexium 62 Drive System can generate a significant leakage (touch) current
(see page 64)
protective device. Consequently, observe the following when using residual current protective devices in combination
with the Lexium 62 Drive System:
Only use universal current sensitive residual current circuit-breaker of type B.Use residual current protective devices with a latent time to prevent unintended triggering at
system power-up.
Consider the leakage (touch) current of the Lexium 62 Drive System in normal operation when
selecting the triggering threshold of the residual current protective device.
If no residual current protective device or only a device with a high current threshold can be
installed, appropriate other measures must be applied to provide protection against electrical
shock and fire hazard
which may lead to unintended triggering of a residual current
Engineering
EIO0000001351 02/2020 65
Engineering

Functional Safety

Section 3.4
Functional Safety
What Is in This Section?
This section contains the following topics:
Process Minimizing Risks Associated with the Machine 67 Designated Safety Function 69 Setup, Installation and Maintenance 77 Perform Muting with the Optional Modules DIS1 79 Application Proposals for Hardware-Based Safety Functions 82 Application Proposals for Software-Based Safety Functions 85 Commissioning 86 Best Practices 87 Maintenance 89 Physical Environment 90 Safety Standards 91
Topic Page
66
EIO0000001351 02/2020

Process Minimizing Risks Associated with the Machine

General
The goal of designing machines safely is to protect people. The risk associated with machines with electrically controlled drives comes chiefly from moving machine parts and electricity itself.
Only you, the user, machine builder, or system integrator can be aware of all the conditions and factors realized in the design of your application for the machine. Therefore, only you can determine the automation equipment and the related safeties and interlocks which can be properly used, and validate such usage.
Hazard and Risk Analysis
Based on the system configuration and utilization, a hazard and risk analysis must be carried out for the system (for example, according to ISO 12100 or ISO 13849-1). The results of this analysis must be considered when designing the machine, and subsequently applying safety-related equipment and safety-related functions. The results of your analysis may deviate from any application examples contained in the present or related documentation. For example, additional safety components may be required. In principle, the results from the hazard and risk analysis have priority.
WARNING
NON-CONFORMANCE TO SAFETY FUNCTION REQUIREMENTS
Specify the requirements and/or measures to be implemented in the risk analysis you perform.Verify that your safety-related application complies to applicable safety regulations and
standards.
Make certain that appropriate procedures and measures (according to applicable sector
standards) have been established to help avoid hazardous situations when operating the machine.
Use appropriate safety interlocks where personnel and/or equipment hazards exist.Validate the overall safety-related function and thoroughly test the application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Engineering
EIO0000001351 02/2020 67
Engineering
The ISO 13849-1 Safety of machinery - Safety-related parts of control systems - Part 1: General principle for design describes an iterative process for the selection and design of safety-related parts of controllers to reduce the risk to the machine to a reasonable degree:
To perform risk assessment and risk minimization according to ISO 12100, proceed as follows:
1. Defining the boundary of the machine.
2. Identifying risks associated with the machine.
3. Assessing risks.
4. Evaluating risks.
5. Minimizing risks by:
6. Designing safety-related controller parts (SRP/CS, Safety-Related Parts of the Control System)
To design the safety-related controller parts in an interactive process, proceed as follows:
Step Action 1 Identify necessary safety functions that are executed via SRP/CS (Safety-Related Parts of the
2 Determine required properties for each safety function. 3 Determine the required performance level PL
4 Identify safety-related parts executing the safety function. 5 Determine the performance level PL of the afore-mentioned safety-related parts. 6 Verify the performance level PL for the safety function (PL ≥ PL
7 Verify if all requirements have been met (validation).
Intrinsically safe designProtective devicesUser information (see ISO 12100)
in an interactive process.
Control System).
.
r
).
r
68
Additional information is available on
www.schneider-electric.com
.
EIO0000001351 02/2020

Designated Safety Function

Functional Description
With the Inverter Enable function (IE), you can bring drives to a defined safe stop. This Inverter Enable function relates to the components
Lexium 62 Connection ModuleLexium 62 Distribution BoxLexium 62 ILM Integrated Servo Drive
In the sense of the relevant standards, the requirements of the stop category 0 (Safe Torque Off, STO) and stop category 1 (Safe Stop 1, SS1) can be met. Both categories lead to a torque-free motor while SS1 takes this state after a predefined time. As a result of the hazard and risk analysis, it may be necessary to choose an additional brake as a safety-related option (for example, for hanging loads).
With the optionally available Lexium 62 ILM Safety Module it is also possible to realize the extended safety functions such as Safety Limited Speed (SLS) in connection with the SLC100/200 FS and the associated software EcoStruxure Machine Expert - Safety.
UNINTENDED EQUIPMENT OPERATION
Make certain that no hazards can arise for persons or material during the coast down period
of the axis/machine.
Do not enter the zone of operation during the coast down period.Ensure that no other persons can access the zone of operation during the coast down period.Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Engineering
WARNING
EIO0000001351 02/2020 69
Engineering
Designated Safety Function Safe Torque Off (STO)
The Inverter Enable function relates to Lexium 62 Connection Module, Lexium 62 Distribution Box and Lexium 62 ILM, hereinafter referred to as Lexium 62 Drive System.
The function is selected via a signal (pair) at the input of the Lexium 62 Connection Module (2), which is forwarded to all drives (7) of the Lexium 62 Connection Module network. The supply voltage (AC) does not need to be interrupted
The graphic shows the Lexium 62 Drive System with emergency stop:
1 Control cabinet 2 Contactor 3 Lexium 62 Connection Module 4 Emergency stop switch 5 Safety switching device (for example Preventa XPS AV) 6 Lexium 62 ILM Integrated Servo Drive 7 Lexium 62 Distribution Box 8 Logic Motion Controller
Operating Principle
The Inverter Enable function switches off the motor torque. It is sufficient to set a logical zero at the function input. There is no need to interrupt the power supply. Standstill, however, is not monitored.
Defined Safe State
Inverter Enable is synonymous with "Safe Torque Off (STO)" according to IEC 61800-5-2:2007. This torque-free state is automatically entered when errors are detected and is therefore the defined safe state of the drive.
70
EIO0000001351 02/2020
Mode of Operation
The safety-related circuit with Inverter Enable was developed to minimize wear on the mains contactor. When the stop or the emergency stop button is activated, the mains contactor is not switched off. The defined safe stop is achieved by removing the “InverterEnable” for the optocouple in the power stage. Thus, the PWM signals cannot control the power stage so that a startup of the drives is prevented (pulse pattern lock).
You can use the Inverter Enable function to implement the control function “Stopping in case of emergency” (IEC 60204-1) for stop categories 0 and 1. Use an appropriate external safety-related circuit to prevent the unintended restart of the drive after a stop, as required in the machine directive.
Stop Category 0
In stop category 0 (Safe Torque Off, STO), the drive coasts to a stop (provided there are no external forces operating to the contrary). The STO safety-related function is intended to help prevent an unintended start-up, not stop a motor, and therefore corresponds to an unassisted stop in accordance with IEC 60204-1.
In circumstances where external influences are present, the coast down time depends on physical properties of the components used (such as weight, torque, friction, and so on), and additional measures such as mechanical brakes may be necessary to help prevent any hazard from materializing. That is to say, if this means a hazard to your personnel or equipment, you must take appropriate measures (refer to
Hazard and Risk Analysis (see page 67)
Engineering
).
WARNING
UNINTENDED EQUIPMENT OPERATION
Make certain that no hazards can arise for persons or material during the coast down period
of the axis/machine.
Do not enter the zone of operation during the coast down period.Ensure that no other persons can access the zone of operation during the coast down period.Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001351 02/2020 71
Engineering
Stop Category 1
For stops of category 1 (Safe Stop 1, SS1) you can request a controlled stop via the Logic Motion Controller (LMC). The controlled stop by the LMC is not safety-relevant, nor monitored, and does not perform as defined in the case of a power outage or if an error is detected. The final switch off in the defined safe state is accomplished by switching off the "Inverter Enable" input. This has to be implemented by using an external safety-related switching device with safety-related delay (see
Application Proposal (see page 85)
Independent of the safety function, the detectable errors not affecting the safety function are recognized by the controller, thus avoiding the drive from starting by switching off the mains contactor. Contactor K2 prevents the mains contactor from being switched on.
Execute Muting
To execute muting, determine the muting reaction time for switching off, that is, without the Inverter Enable function, within the application.
Should a response time be required because of the risk assessment of the machine, the total response time of the machine has to be taken into account. That is to say, the components related to the safety functions from the sensor to the drive shaft or the driven mechanics have to be considered. The determined reaction time must correspond to the results of the hazard and risk analysis.
UNINTENDED EQUIPMENT OPERATION
Verify that the maximum response time corresponds to your risk analysis.Be sure that your risk analysis includes an evaluation for the maximum response time.Validate the overall function with regard to the maximum response time and thoroughly test
the application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
).
WARNING
72
Proceed as follows to disable the Inverter Enable function:
Step Action
1 You can deactivate the Inverter Enable function by using the optional module DIS1
2 In order to use the optional module DIS1, you must define the configuration with the parameter
(see page 79)
Result:The defined safe state can only be achieved if the power is removed from the power supply.
InverterEnableConfig of the Lexium 62 ILM in the motion controller configuration.
.
EIO0000001351 02/2020
Engineering
If the software configuration does not match the physical configuration of the Lexium 62 ILM, then the diagnostic message 8978 InverterEnableConfig invalid with Ext. diagnostic = x(HW)!=y(Cfg) is triggered. The drive is disabled as long as the configuration is incorrect. The detected error can only be acknowledged if the set InverterEnableConfig corresponds to the physical
configuration. The deactivation of the Inverter Enable function can be used to divide the drives on a Lexium 62 Connection Module in two groups if it is technically not possible to use two Lexium 62 Connection Module for the two groups in the existing machine.
The axes without Inverter Enable function become torque-free via the mains contactor and come to a stop.
If only some of the drives attached to a Lexium 62 Connection Module are to be put in the defined safe state, this can be achieved by the configuration of the drives. This can be of interest, for example, for maintenance procedures. If an optional module DIS1 is set, then the Inverter Enable signal is ignored.
To implement the emergency stop, the supply voltage on the Lexium 62 Power Supply must be interrupted:
1 Control cabinet 2 Emergency stop switch 3 Safety switching device (for example Preventa XPS AV) 4 Contactor 5 Switch: Operating mode (normal/maintenance) 6 Lexium 62 Connection Module 7 Lexium 62 ILM Integrated Servo Drive 8 Lexium 62 Distribution Box 9 Logic Motion Controller
EIO0000001351 02/2020 73
Engineering
Extended Safety-Related Functions - Operating Principle
The safety concept is based upon the general consideration that the required safety-related travel movement is performed by the controller and the drive. The safety system monitors the correct execution of the motion, and if it is not respected the safety system initiates the required fall-back level (for example the defined safe state).
An example for Safe Limited Speed (SLS) is as follows: A light curtain is connected to a safety-related digital input. As soon as a person enters the
protected zone passing the light curtain, a corresponding information is transmitted to the Safety Logic Controller (SLC) and the LMC via the Sercos bus. After that the LMC initiates an adequate travel movement, for example by using decelerating and then moving slowly. After an adjustable delay time this slow movement is monitored by Lexium 62 ILM Safety Module. Upon exceeding an adjustable threshold value (for example, high velocity), the required fall-back level is entered, for example, the defined safe state.
Application of safety-related function SLS:
74
EIO0000001351 02/2020
Extended Safety-Related Functions - Inverter Enable via Hardware Input
The Lexium 62 ILM Safety Module has been primarily developed to realize the extended safety functions, however, it still can be accessed using the usual hardware input for the Inverter Enable of the Lexium 62 Drive System. If only this is to be used, the device still needs to be configured and parameterized by using the software. If it is hardwired, the Safe Torque Off (STO) function can be triggered via this input or the Sercos bus. The Lexium 62 ILM Safety Module can be configured to ignore the hardware input. In this case, the Safe Torque Off (STO) function can only be activated upon a request over the Sercos bus. Otherwise, if the hardware input is not ignored then both requests (hardware input and Sercos bus) are verified and the Safe Torque Off (STO) function is triggered if one or both requests are active. The default configuration is not to ignore the hardware input.
Extended Safety-Related Functions - Defined Safe State
The defined safe state of the device is characterized by the following features:
The drive is torque-free, which is equivalent to Safe Torque Off (STO) according to IEC 61800-
5-2.
There is no safety-related communication from the drive via the Sercos bus.
This state is automatically entered when errors are detected.
Validity of the Safety Case
The safety case for the Inverter Enable function of the Lexium 62 ILM is identified and defined by the standards listed in
Safety Standards (seepage91)
. The safety case for the designated safety function of the Lexium 62 ILM system applies to the following hardware codes, which can be found examining the appropriate software object in EcoStruxure Machine Expert
Machine Expert, Programming Guide)
:
Engineering
(see EcoStruxure
Unicode Hardware code ILM 070/xx xxxxxxxxx1xx, xxxxxxxxx2xx ILM 100/xx xxxxxxxxx1xx, xxxxxxxxx2xx ILM140/xx xxxxxxxxx1xx, xxxxxxxxx2xx DIS1 1 ILM62CM xxxxxx1xx, xxxxxx2xx ILM62DB xxxxxx1xx
Device Hardware code VW3E702200000 011A1110
For questions on this, contact your Schneider Electric representative.
EIO0000001351 02/2020 75
Engineering
Interface and Control
The Inverter Enable function is operated via the switching thresholds of the InverterEnable-input (IE_p1/IE_p2 at Pin1/Pin2, IE_n1/IE_n2 at Pin3/Pin4) of the Lexium 62 Connection Module.
Maximum downtime: 500 µs at UMaximum test pulse ratio: 1 Hz
STO active: -3 V ≤ UPower stage active: 15 V ≤ U
For information on the technical data and electrical connections, refer to the chapter
Data (see page 185)
> 20 V with dynamic control
IEX
≤ 5 V
IE
≤ 30 V
IE
Technical
.
76
EIO0000001351 02/2020

Setup, Installation and Maintenance

Prevent Possible Unintended Operation and Avoid Overvoltage
The following measures avoid overvoltages and help prevent possible unintended equipment operation through conductive pollution or parts falling into the device:
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Install Lexium 62 Connection Module in a control cabinet or housing with a minimum IP 54
rating.
Comply with the clearances and creepage distances according to EN 50178.Lexium 62 ILM Integrated Servo Drive must only be operated with 24 Vdc power supplies
certified according to EN 60950 or EN 50178.
Failure to follow these instructions will result in death or serious injury.
NOTE: These power supply units do not deliver an overvoltage over 120 Vdc for more than 120 ms or no permanent overvoltage over 60 Vdc.
Only operate the drive system with approved, specified cables, accessories and replacement equipment by Schneider Electric.
Engineering
DANGER
ELECTRIC SHOCK OR ARC FLASH Do not use non-Schneider Electric approved cables, accessories or any type of replacement
equipment. Failure to follow these instructions will result in death or serious injury.
Avoid Unintentional Restart
The unintentional restart of the equipment must be avoided by appropriate means, depending on your particular application.
DANGER
UNINTENTIONAL RESTART OF THE MOTOR
Ensure that a restart of the motor is not possible after a return of power or the tripping of a
functional safety device unless preceded by a deliberate enable signal from the system.
Ensure that the enable signal meets the specified safety criteria.
Failure to follow these instructions will result in death or serious injury.
EIO0000001351 02/2020 77
Engineering
Encoder Connection When Using Extended Safety-Related Functions
Lexium 62 ILM Safety Module enables the use of extended, position-dependent and/or velocity­dependent safety-related functions.
DANGER
INOPERABLE SAFETY FUNCTION
Observe the specified maximum configuration (number of devices, network structure and
cable length), or else a voltage drop of the Inverter Enable signal will occur over the cable length and therefore the system will be in the defined safe state continuously.
Connect per Lexium 62 Connection Module a maximum of 45 Lexium 62 ILMs.
Failure to follow these instructions will result in death or serious injury.
For more information on the dimensions of the maximum system extension for
structure or tree structure or daisy chain structure (see page 120)
.
Wiring in line
78
EIO0000001351 02/2020

Perform Muting with the Optional Modules DIS1

Overview
Implementation of Emergency stops combining hardwired control of supply power with the Inverter Enable function:
Lexium 62 ILM Maintenance Emergency stop Parameter InverterEnableConfig
Lexium 62 ILM without DIS1
Lexium 62 ILM with DIS1
How to Install the Optional Modules DIS1
You cannot use the option modules DIS1 and Lexium 62 ILM Safety Module together.
Step Action
1 Remove power to the Lexium 62 Power Supply during the installation of the optional module
2 Remove the transparent cover plate on the motor. 3 Remove plugged in jumpers J1 and J2:
Torque-free motor Torque-free motor Standard/1
Torque-free motor Off/0
DIS1.
Engineering
EIO0000001351 02/2020 79
Engineering
Step Action
4 Connect the optional module DIS1 by inserting it into the contact pin, as shown in the following
graphic:
5 Replace the transparent cover plate on the motor and secure it.
How to Disassemble the Optional Module DIS1
Step Action
1 Remove power to the Lexium 62 Power Supply during the installation of the optional module
DIS1. 2 Remove the transparent cover plate on the motor. 3 Remove the optional module DIS1.
80
EIO0000001351 02/2020
Step Action
4 Reconnect the jumpers J1 and J2.
5 Replace the transparent cover plate on the motor and secure it.
Engineering
EIO0000001351 02/2020 81
Engineering

Application Proposals for Hardware-Based Safety Functions

How to Implement the Safe Stop Category 1 (SS1)
Refer to the schematic EL-1122-05-xx: Inverter Enable circuit Lexium 62 Connection Module / Lexium 62 ILM using the Logic Motion Controller LMC•00C with safety switch device for an emergency stop circuit.
NOTE:
All application proposals provide for a protected Inverter Enable-wiring (control cabinet IP54)
from the safety-related switch device to the Lexium 62 Connection Module, as wiring issues need to be ruled out.
Protection against automatic restart must be provided by the external safety-related switch
device.
NOTE: The mains contactor in the circuit suggestion EL-1122-05-xx is not necessary for functional safety purposes. It is, however, used in the application proposal for the device protection of the Lexium 62 Power Supply or the components connected to it.
82
EIO0000001351 02/2020
EL-1122-05-xx Sheet 1:
Engineering
EIO0000001351 02/2020 83
Engineering
EL-1122-05-xx Sheet 2:
84
EIO0000001351 02/2020

Application Proposals for Software-Based Safety Functions

How to Use the Inverter Enable via Hardware or Extended Safety Functions
Proceed as follows to use the Inverter Enable via hardware or extended safety functions using the Lexium 62 ILM Safety Module:
Step Action
1 Perform the assembly for Lexium 62 ILM Safety Module. 2 Configure the safety-related network. 3 Adjust the parameters, in particular the prioritization of Inverter Enable via hardware and STO
via the bus.
4 Program the EcoStruxure Machine Expert - Safety application.
NOTE: Observe the information on the parameters and the EcoStruxure Machine Expert - Safety in the EcoStruxure Machine Expert online help.
Further information on the parameters and the EcoStruxure Machine Expert - Safety Software can be found in the EcoStruxure Machine Expert online help.
Engineering
EIO0000001351 02/2020 85
Engineering

Commissioning

General
Step Action
1 Carry out a functional test of the STO function for all drives that need the safety function. 2 Especially verify the correct application of the axes without Inverter Enable function. 3 Complete installation in accordance with the EMC regulations and further specifications in the
4 Afterwards, commission the drive systems.
NOTE: When using the extended safety functions, the Lexium 62 ILM Safety Module must be configured, parameterized, and programmed according to the EcoStruxure Machine Expert online help and the EcoStruxure Machine Expert - Safety online help.
device operating manuals.
86
EIO0000001351 02/2020

Best Practices

General
At machine start-up, the connected drives are usually hidden from sight of the machine operator and cannot be monitored directly.
UNSUPERVISED MACHINE START-UP Only start the machine if there are no persons within the zone of operation of moving machine
components. Failure to follow these instructions can result in death, serious injury, or equipment damage.
Verify Connections
Step Action
1 Verify all terminals, connectors, and other connections on all system components for correct
2 Only use robust connectors and secure fixings. 3 Verify the protective earth ground (24 Vdc PELV (Protective Extra Low Voltage) supply. 4 Verify the wiring of the safety function to the axes to avoid an interchange of the ie_sig and
5 Use coded connectors (refer to chapter
6 Use only appropriate transport packaging to forward or return individual devices.
WARNING
and firm fit.
ie_ref inputs as well as the 24 V supply.
commissioning test (refer to chapter
Information about Wiring (see page 51)
Commissioning (see page 86)
Engineering
) and perform a
).
DANGER
ELECTRIC SHOCK DUE TO INADEQUATE PROTECTIVE SEPARATION Only connect devices, electrical components, or lines to the signal voltage connectors of these
products that feature a sufficient, protective separation from the connected circuits in accordance with the standards (IEC 61800-5-1: Adjustable speed electrical power drive systems - safety requirements).
Failure to follow these instructions will result in death or serious injury.
EIO0000001351 02/2020 87
Engineering
External Forces
The defined safe state of the motor is the torque-free output shaft. If external forces act upon the output shaft, it will not necessarily maintain its position. In any case, the motor will coast to an unassisted stop. This coast down time depends on physical properties of the components used (such as weight, torque, friction, and so on), and additional measures such as mechanical brakes may be necessary to help prevent any hazard from materializing. If the torque-free defined safe state is inappropriate for your application where external forces may move the output shaft as determined by your risk assessment, implement other external safety-related measures.
UNINTENDED EQUIPMENT OPERATION
Make certain that no hazards can arise for persons or material during the coast down period
of the axis/machine.
Do not enter the zone of operation during the coast down period.Ensure that no other persons can access the zone of operation during the coast down period.Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Hanging and Pulling Loads
UNINTENDED AXIS MOVEMENT
Do not use the internal holding brake as a safety-related measure.Only use certified external brakes as safety-related measures.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
WARNING
88
If the suspension of hanging / pulling loads is a safety objective for the machine, then you can only achieve this objective by using an appropriate external brake as a safety-related measure.
NOTE: The drive does not provide its own safety-related output to connect an external brake to use as a safety-related measure.
EIO0000001351 02/2020

Maintenance

General
The Inverter Enable function has been designed for a defined lifetime that does not require to verify the safety-related function, nor any specific maintenance requirements. After this lifetime
(see page 91)
the aging of the component. If you want to ensure the functional safety after this period, you need to replace the device that includes the safety function.
NOTE: Subject the product to a complete function test after replacement. The following applies for Lexium 62 ILM Safety Module. In addition to the LED state, data of the Safety Logger is also available in the EcoStruxure Machine
Expert Logic Builder. These are provided for information only and must not be used for safety­related diagnostics.
For information about initial start-up and maintenance, refer to the chapter
Maintenance (see page 97)
Engineering
has elapsed, a statement about the Inverter Enable function cannot be made due to
Installation and
.
EIO0000001351 02/2020 89
Engineering

Physical Environment

General
The system is not protected against physical or chemical sources of damage by any design features, such as:
toxic, explosive,corrosive,highly reactive, orinflammable types.
This equipment has been designed to operate outside of any hazardous location. Only install this equipment in zones known to be free of a hazardous atmosphere.
POTENTIAL FOR EXPLOSION Install and use this equipment in non-hazardous locations only. Failure to follow these instructions will result in death or serious injury.
UNINTENDED EQUIPMENT OPERATION
Observe and conform to ambient temperatures, storage temperatures and transport
temperatures of the individual components as specified in the operating manuals of the components.
Prevent the formation of moisture during the operation, storage and transport of individual
components.
Conform to the vibration and shock requirements specified in the operating manuals for the
components when operating, storing and transporting system components.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DANGER
WARNING
90
The Lexium 62 Power Supply and the Lexium 62 Connection Module must only be installed in an electrical equipment enclosure (for example, in a control cabinet). The electrical equipment enclosure must be lockable by using a key or tool
The Lexium 62 ILM and the Lexium 62 Distribution Box are intended for installation in a machine.
EIO0000001351 02/2020

Safety Standards

Overview
The designated safety functions have been designed and tested for functional safety according to the following standards
IEC 61508:2010IEC 61800-5-2:2007EN ISO 13849-1:2008IEC 62061:2005
An independent assessment was performed by TÜV Nord. According to the above listed standards, the figures for the devices for using the Inverter Enable
function are as follows:
Engineering
Standard characteristics Lexium 62 Connection
Module
SFF (IEC 61508)
99% 99.9% 99%
Lexium 62 ILM Lexium 62 ILM with installed
Lexium 62 ILM Safety Module
1
Safe failure fraction HFT (IEC 61508)
111
Hardware Fault Tolerance Type (IEC 61508) A A B SIL (IEC 61508)
333 Safety Integrity Level SILCL (IEC 62061) Safety Integrity Level claim limit
PFH (IEC 61508)
-9
1.3*10
/h 0.08*10-9/h 1.6*10-9/h
Probability of Dangerous Failures per Hour
PL (cat) (EN ISO 13849-1)
e (4) e (4) e(4) Performance Level (Category)
MTTFd (EN ISO 13849-1)
881 years 14487 years 320 years Mean Time to Dangerous Failure
1
Lexium 62 Distribution Box: The elimination from consideration of certain errors within the safety-related parts of the control system, known as Fault Exclusion within various IEC, ISO, NFPA and ANSI standards, has been applied because clearances and creepage standards have been respected in the product. The plug-in connectors have been included in the PFH figures of Lexium 62 Connection Module and Lexium 62 ILM.
NOTE: The values specified are rounded individually and are therefore not a result of a conversion by for
example, PFH in MTTFd or the comparative tables from EN ISO 13849-1:2008.
EIO0000001351 02/2020 91
Engineering
Standard characteristics Lexium 62 Connection
Module
DC (EN ISO 13849-1)
99% 99% 99%
Lexium 62 ILM Lexium 62 ILM with installed
Lexium 62 ILM Safety Module
1
Diagnostic Coverage Lifetime 20 years 20 years 20 years Maximum reaction time
5 ms 5 ms 10 ms between the request and execution of the designated safety function
Maximum reaction time
5 ms 5 ms 10 ms before the detection of safety-related errors
Maximum reaction time
Not applicable Not applicable 10 ms between exceeding the threshold values of extended safety functions and the initiation of substitute reactions
1
Lexium 62 Distribution Box: The elimination from consideration of certain errors within the safety-related parts of the control system, known as Fault Exclusion within various IEC, ISO, NFPA and ANSI standards, has been applied because clearances and creepage standards have been respected in the product. The plug-in connectors have been included in the PFH figures of Lexium 62 Connection Module and Lexium 62 ILM.
NOTE: The values specified are rounded individually and are therefore not a result of a conversion by for
example, PFH in MTTFd or the comparative tables from EN ISO 13849-1:2008.
92
Standard characteristics - Lexium 62 ILM Safety Module
Standard characteristics Lexium 62 ILM Safety Module
MTTFd (EN ISO 13849-1)
Mean Time to Dangerous Failure [years] Use of SLS (Safely Limited Speed (SLS)) etc. – ... with Sick Stegmann encoder SKM36 250 ... with Sick Stegmann encoder SKS36 250
EIO0000001351 02/2020

Special Conditions

Section 3.5
Special Conditions

Low Air Pressure

Description
If the installation altitude exceeds the specified rated installation altitude, the performance of the entire system is reduced.
Low Air Pressure - Lexium 62 Power Supply
Power reduction at increased installation altitude (Lexium 62 Power Supply):
Engineering
EIO0000001351 02/2020 93
Engineering
Low Air Pressure - Lexium 62 Connection Module
Power reduction at increased installation altitude (Lexium 62 Connection Module):
94
EIO0000001351 02/2020
Low Air Pressure - Lexium 62 ILM
Power reduction at increased installation altitude (Lexium 62 ILM at 8 kHz clock frequency of power stage):
NOTE: Multiply the values with the nominal current at 40 °C / 104 °F in order to calculate the maximum current value, depending on the required installation altitude.
Engineering
EIO0000001351 02/2020 95
Engineering
96
EIO0000001351 02/2020
5 Lexium 62 ILM Installation and Maintenance EIO0000001351 02/2020

Installation and Maintenance

Chapter 4
Installation and Maintenance
What Is in This Chapter?
This chapter contains the following sections:
Section Topic Page
4.1 Prerequisites for Installation and Maintenance 98
4.2 Commissioning 99
4.3 Maintenance, Repair, Cleaning, Replacement Equipment Inventory 124
4.4 Replacing Components and Cables 134
EIO0000001351 02/2020 97
Installation and Maintenance

Prerequisites for Installation and Maintenance

Section 4.1
Prerequisites for Installation and Maintenance

Prerequisites for Maintenance and Installation

General Information
Proceed with care during the following steps in order to help to avoid the following points:
Injuries and material damageIncorrect installation and programming of components Incorrect operation of componentsUse of non-authorized cables or modified components
WARNING
INCORRECT INSTALLATION Ensure a correct installation and maintenance of the system according to this manual. Failure to follow these instructions can result in death, serious injury, or equipment damage.
The Lexium 62 ILMs (drive/motor combination) have been derived from the Schneider Electric SH3 family of motors, and therefore share many characteristics. However, when it comes to mounting the motor, the Lexium 62 ILMs are equivalent to the SH3 motors. Refer to the
Servo motor, User Guide (see SH3 Servo Motor, User Guide)
Lexium 62 ILMs. The correspondence between the Lexium 62 ILMs and the SH3 motors are as follows:
SH3 -
for details of installing the
98
Lexium 62 ILM SH3 motor ILM070 SH3070 ILM100 SH3100 ILM140 SH3140
EIO0000001351 02/2020

Commissioning

Section 4.2
Commissioning
What Is in This Section?
This section contains the following topics:
Prerequisites for Commissioning 100 Preparing Commissioning 101 Grinding the Holding Brake 103 Preparing the Control Cabinet 104 Mounting 108 Wiring the Lexium 62 Connection Module in Linear or Tree Topologies 114 Wiring from the Lexium 62 Connection Module in a Daisy Chain Topology 120
Installation and Maintenance
Topic Page
EIO0000001351 02/2020 99
Installation and Maintenance

Prerequisites for Commissioning

Prerequisites
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.Measure the voltage on the DC bus with a properly rated voltage sensing device and verify
that the voltage is less than 42.4 Vdc.
Do not assume that the DC bus is voltage-free when the DC bus LED is off.Block the motor shaft to prevent rotation prior to performing any type of work on the drive
system.
Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
DANGER
100
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operate electrical components only with a connected protective ground (earth) cable.After the installation, verify the secure connection of the protective ground (earth) cable to all
electrical devices to ensure that connection complies with the connection diagram.
Before enabling the device, safely cover the live components to prevent contact.Do not touch the electrical connection points of the components when the module is
energized.
Provide protection against indirect contact.Connect and disconnect cables and terminals only after you have verified that the power has
been removed from the system.
Failure to follow these instructions will result in death or serious injury.
EIO0000001351 02/2020
Loading...