Schneider Electric i2887 Data Sheet

Andover Continuum Infinet II
i2887 Terminal Controllers
The Andover Continuum Infinet II (i2) 887 is a fully programmable, low cost, general purpose terminal controller. It has all the power of an Andover Continuum Infinet II controller, but with a small form factor.
With its unique mix of three universal inputs, one Smart Sensor/room sensor input, four triac outputs and one relay output, the i2887 can be easily configured to control Heat Pumps, Fan Coils, or AC units. Use the i2887 for direct control of fans, staged heating and cooling and monitoring of room temperature, outside air temperature, return air temperature or occupancy status.
02
PRODUCT AT A GLANCE
Compact Terminal Controller Provides
Low-cost Fan Coil and Heat Pump Control
Three Universal Inputs and One Smart Sensor/
Room Sensor Input
Four For m A Triac Output s, One Fo rm A Re lay,
277 VAC @3A
Non-Vola tile Fl ash Mem ory Prov ides U tmost
Reli ability — Stor es Both Applic ation P rogram
and Operating S ystem
Flash Memory Allows Easy On-Line
Software Updates
R emovable Te rminal Blocks for Easy
Serviceability
View and Mo dify In formatio n with Optional
Andover Continuum Smart Sensor Display
Local On-Board Service Port
Typical Applications:
- Fan Coil Unit
- Heat Pump
- Chilled Beams
The i2887 is compact so it can be installed in tight locations with three mounting screws; and its removable terminal connectors allow for easy servicing.
While the standard i2887 version uses 24 VAC input power, the i2887-L model accepts incoming line voltage at 115 or 230 VAC, has an onboard transformer, and the same versatile I/O configuration.
Similar to all i2 controllers, the i2887 features Flash memory and a fast (32-bit) processor for faster scan times, with plenty of additional memory available for data logging of your critical data.
The i2887 communicates with the entire Andover Continuum Infinet™ RS-485 field bus; i.e., both Andover Continuum Infinet and Andover Continuum Infinet II controllers, and is compatible with Andover Continuum CyberStation 254 Andover Continuum Infinet devices can be networked to any Andover Continuum network controller.
TM
Version 1.6x or greater. Up to
TM
TM
Schneider Electric
SDS-I2887-A4.BU.N.EN.1.2006.0.00.CC
03
Features
(continued)
Increased Reliability with Flash Memory
The i2887’s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application will be restored when power is returned. In addition, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out proms.
Inputs
The input configuration on the i2887 consists of three full range Universal inputs that accept voltage (0-5VDC), digital (on/off), counter signals (up to 4Hz), or temperature signals. The i2887 also offers a fourth input to support the Andover Continuum Smart Sensor, or any standard room temperature sensor.
Dimensional Drawings
2
Outputs
The i2887 contains five digital outputs — four Form A
Triac-based outputs plus one Form A Relay
output, capable of switching line voltage.
These outputs can be used separately for on/off or pulsed control of lighting, heat, and fan units or can be configured into Form K Tri-state outputs (2-max) for bi-directional control of dampers and valves. (Note: Any two consecutive Triac outputs can be configured as a Form K output.) All Triac outputs are ground referenced and rated for AC loads only.
Software Capabilities
The dynamic memory of the i2887 can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Plain English Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the i2887 using the Andover Continuum CyberStation. Programs are then stored in, and executed by, the i2887.
TM
programming language.
3
1
i2887 Dim ensional Drawing
2
4
4
S
chneider Electric
SDS-I2887-A4.BU.N.EN.1.2006.0.00.CC
3 4
1
i2887-L-xxx Dime nsional Drawing
04
Features
Programming multiple i2887s is inherently easy with Plain English. A complete copy of one i2887’s programs can be loaded directly into other i2887s without changing any point names or programs. In addition, channel assignments for the i2887 are similar to other Andover Infinet devices such as the i2851 for easy program conversion.
(continued)
Smart Sensor Interface
The i2887 provides a built-in connection for Andover Continuum Smart Sensor. The Smart Sensor provides a 2-character LED display and a 6-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a 4-digit custom LCD that provides the following icons: PM, %, °, Setpoint, Cool, Heat, CFM, Fan, OA, and SP.
Dimensional Drawings
2
1
3
4
i2887-L Clo sed Class
i2887-L-xxxi2887
1
i2887
4
Outputs D rawing
Inputs D rawing
Power Drawing Communi cations Drawing
2
i2887-L-xxx
Schneider Electric
SDS-I2887-A4.BU.N.EN.1.2006.0.00.CC
i2887 Terminal Controllers
05
Electrical
Power
i2887: 24 VAC, +10% -15%,
50/60 Hz or i2887-L-xxx: 115/230 VAC,
+10% -15%, 50/60 Hz
Power Consumption
i2887: 10 VA
i2887-L-xxx: 32 VA
i2887-L-xxx-C 32 VA
Overload Protection
Fused with 1 amp fuse. MOV protected
Software Real-Time Clock
Synchronized through Andover Continuum
Infinet by network controller
Mechanical
Operating Environment
32°–120°F (0–49°C),
10–95% RH (non-condensing)
Size
i2887: 4.40˝ H x 5.13˝ W x 1.15˝ D
(111H x 130W x 30D) mm
i2887-L-xxx: 4.40”H x 7.32”
W x 2.31”D (111H x 186W x 59D) mm
Weight
i2887: 0.5 lbs. (0.23 kg)
i2887-L-xxx: 1.9 lbs. (0.86 kg)
i2887-L-xxx-C: 2.63 lbs. (1.19 kg)
Enclosure Type
UL Open class, IP 10.
Flammability rating of UL94-5V
i2887-L-xxx-C
UL Close class, IP20
Flammability rating of UL-94-5V
Mounting
Panel mount
Communications
Communications Interface
Through Andover Continuum Infinet
RS-485 field bus to network controller
Communications Speed
1200 to 19.2K baud
Bus Length
4,000 ft. (1,220m) standard for
Andover Continuum Infinet, i2 Infilink
module allows extension to longer
distances and is required after every
group of 32 units on the network.
Bus Media
Andover Continuum Infinet: twisted,
shielded pair, low capacitance cable
Comm. Error Checking
International Standard CRC 16
Compatibility: Andover Continuum
CyberStation 1.6x or greater
Compatibility
Andover Continuum CyberStation
1.6x or greater
Inputs
3 Universal inputs: Voltage (0-5.115 VDC);
Temperature -30°F to 230°F (-34°C to
110°C), Digital (on/off), Counter (up to 4Hz
at 50% duty cycle, 125 ms min. pulse
width). Current input (0 - 20 mA) using
external 250 ohm resistor
1 Smart Sensor Temperature Input
(32°F to 105°F) (0°C to 41°C)
Input Voltage Range
0-5.115 volts DC
Input Impedance
10K ohm to 5.120V
Input Protection
24 VAC or 24 VDC temporarily on
any single channel, ±1000V transients
(Tested according to EN61000-4-4)
Input Resolution
5.0 mV
Input Accuracy
±15mV (±0.56°C from -23°C to +66°C or
±1°F from -10°F to +150°F)
Outputs
4 single pole single throw (SPST) Form A
Triacs (any two consecutive outputs can be
configured as one Tri-state Form K)
1 Form A Relay, 277 VAC @3A
Triac Output Rating
Maximum 0.3A, 24VAC,
±2000V transients
(Tested according to EN61000-4-4)
Minimum: 30 mA AC
Each Triac is ground referenced,
DC loads not permitted
Output Accuracy
0.1 sec. for pulse width modulation
Schneider Electric
SDS-I2887-A4.BU.N.EN.1.2006.0.00.CC
06
Specifications
(continued)
i2887 Terminal Controllers
Connections
Power
2-position fixed screw terminal connector
(i2887-L: 3-position fixed)
Communications
3-position removable screw
terminal connector
Inputs/Smart Sensor
7-position removable screw
terminal connector
Outputs
6-position removable screw terminal
connector (i2887-L: 8-position)
Relay
2-position fixed screw
Service Port
4-position connector
User LEDs/Switches
Status Indicator LEDs
CPU CPU Active
General
Memory
512K SRAM, 1MB FLASH
Processor
Motorola 32-bit Coldfire
User LEDs/Switches
i2887: Power: 24 VAC
i2887-L-115: Power: 115 VAC
i2887-L-230: Power: 230 VAC
i2887-L-115-C: Power: 115
VAC-Closed Class
i2887-L-230-C: Power: 230
VAC-Closed Class
Note: i2887-L models provide onboard
24 VAC @750 mA for external loads.
Agency Listings
UL/CUL 916, FCC CFR 47 Part 15,
ICES-003, EN55022, AS/NZS 3548,
and VCCI Class A, CE
All brand names, trademarks and registered trademarks are the proper ty of their respective owners. Information contained within this document is subject to change without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document refle cts the visual identit y of Schneider Electric, however there remains refere nces to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.
Schneider Electric
SDS-I2887-A4.BU.N.EN.1.2006.0.00.CC
January 2 006 pdw
© 200 6-2 009 Schneider Electric. All rights reserved.