Description of terminal __________________________________________________________________________________ 18
Description of the graphic screen__________________________________________________________________________ 19
First power-up - [5. LANGUAGE] menu _____________________________________________________________________ 22
Subsequent power ups__________________________________________________________________________________ 23
Programming: Example of accessing a parameter_____________________________________________________________ 24
Quick navigation_______________________________________________________________________________________ 25
Functions of the display and the keys_______________________________________________________________________ 28
Accessing menus ______________________________________________________________________________________ 29
Read and understand these instructions bef ore performing any procedure on this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Manual before i nstalling or operating the ATV71 drive. Instal lation, adjustment,
repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT
TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with volta ge present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure
given in the Installation Manual to verify that the DC voltage is less than 45 V. The drive LEDs are not accurate
indicators of the absence of DC bus voltage.
Electric shock will result in death or serious injury.
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
4AAV49426 12/2009
Documentation structure
The following Altivar 71 technical documents are available on the Schneider-Electric website (www.schneider-electric.com) as well as on
the CD-ROM supplied with the drive.
Installation Manual
This describes how to assemble and connect the drive.
Programming manual
This describes the functions, parameters and use of the drive terminal (integrated display terminal and graphic display terminal).
The communication functions are not described in this manual, but in the manual for the bus or network used.
Communication Parameters Manual
This manual describes:
• The drive parameters with specific information for use via a bus or communication network.
• The operating modes specific to communication (state chart).
• The interaction between communication and local control.
Manuals for Modbus, CANopen, Ethernet, Profibus, INTERBUS, Uni-Telway, FIPIO
and Modbus Plus, etc.
These manuals describe the assembly, connection to the bus or network, signaling, diagnostics, and configuration of the communicationspecific parameters via the integrated display terminal or the graphic display terminal.
They also describe the communication services of the protocols.
AAV49426 12/20095
Software enhancements
Since the Altivar ATV 71 was first launched, it has benefited from the addition of several new functions. Software version has now been
updated to V2.8. The new version can be substituted to the previous versions without making any changes.
Although this documentation relates to versi on V2.8, it can st ill be used with previ ous versions, as the update s merely invol ves t he additi on
of new values and parameters. None of the previous versions parameters have been modified or removed.
The software version is indicated on the nameplate attached to the body of the drive.
Enhancements made to version V1.2 in comparison to V1.1
Factory setting
Note 1: In version V1.1, the analog input was 0 ± 10 V. For safety reasons, in the new vers ion this inpu t has been set t o 0 + 10 V.
Note 2: In version V1.1, analog output AO1 was assigned to the motor f requency. In the new version, this output is not assigned
at all.
With the exception of these two parameters, the factory settings of version V1.1 remain the same in the new version. The new functions
are factory-set to disabled.
Motor frequency range
The maximum output frequency has been extended from 1000 to 1600 Hz (depending on the drive rating and control profile).
New parameters and functions
Menu [1.2 MONITORING](SUP-)
Addition of internal states and values relating to the new functions described below.
Menu [1.3 SETTINGS](SEt-)
• [High torque thd.](ttH) page 67.
• [Low torque thd.](ttL) page 67
• [Pulse warning thd.](FqL) page 68
• [Freewheel stop Thd.](FFt) page68
.
.
.
Menu [1.4 MOTOR CONTROL](drC-)
• [rpm increment](InSP) page 76.
• Extension of the following configurations to all drive ratings; previously limited to 45 kW (60 HP) for ATV71
(100 HP) for ATV71
• Input Al1 can now be configured to 0 +10 V or 0 ± 10 V via [AI1 Type] (AI1t) page 107.
• [AI net. channel] (AIC1) page 111
• New methods of assigning relays and logic outputs page 118
rotation, motor in reverse rotation, measured speed threshold reached, load variation detection.
• Analog output AO1 can now be used as a logic output and assigned to relay functions and logic outputs, page 123
• New method of modifying the scale of analog outputs page 125
max](ASHx).
• New methods of assigning logic outputs page 126
• New methods of assigning alarm groups page 130
threshold reached, load variation detection.
.
: rope slack, high torque threshold, low torque threshold, motor in forwa rd
using the parameters [Scaling AOx min](ASLx) and [Scaling AOx
• The summing, subtraction and multiplication reference fu nctions can now be assigned to virtual input [Network AI] (AIU1) page 151.
• New parameter [Freewheel stop Thd.] (FFt) page 156
or fast stop.
• Brake engage at regulated zero speed [Brake engage at 0] (bECd) page 176
• Weight [Weight sensor ass.] (PES) page 183
• New "rope slack" function page 187
• Use of the ramp [Acceleration 2] (AC2) page 195
• The torque limitation [TORQUE LIMITATION] (tOL-) page 202
increment] (IntP) and assigned to virtual input [Network AI] (AIU1).
• New "stop at distance calculated after deceleratio n limit swi tch" funct ion page 211
linear speed] (nLS) and [Stop corrector] (SFd).
• Positioning by sensors or limit switch [POSITIONING BY SENSORS] (LPO-) page 212
negative logic using [Stop limit config. (SAL) and [Slowdown limit cfg.] (dAL).
• Parameter set switching [PARAM. SET SWITCHING] (MLP-) page 215
[Freq. Th. att.] (FtA) and [Freq. Th. 2 at ta in . ] (F2A).
• New half-floor: [HALF FLOOR] (HFF-) menu page 229
, with the parameters [Rope slack config.] (rSd) and [Rope slack trq level] (rStL).
can now be assigned to virtual input [Network AI] (AIU1).
Menu [1.8 FAULT MANAGEMENT](FLt)
• Possibility of reinitializing the drive without turning it off, via [Product reset] (rP) page 237.
• Possibility of reinitializing the drive via a logic input without turning it off, using [Product reset assig.] (rPA) page 237
• The possibility of configuring the "output phase loss" fault [Output Phase Loss] (OPL) page 242
extended to all drive ratings (previously limited to45 kW (60 HP) for ATV71
• The external fault [EXTERNAL FAULT] (EtF-) page 245
(LEt).
• New monitoring function based on speed measurement via "Pulse input" page 252
• New function for detecting load variation page 254
• Short-circuit faults on the braking unit can now be configured via [Brake res. fault Mgt] (bUb) page 256
used to set a threshold for switching to freewheel at the end of a stop on ramp
.
when starting and "waking up" the PID function.
can now be configured in whole % or in 0.1% increments using [Torque
, with the parameters [Stop distance] (Std),[Rated
can now be configured in positive logic or
can now be assigned to the frequency thresholds attained
.
.
to [Output cut] (OAC) has been
pppM3X and 75 kW (100HP) for ATV71pppN4).
can now be configured in positive or negat ive logic via [External fault config.]
, via the [FREQUENCY METER] (FqF-) menu.
, via the [DYNAMIC LOAD DETECT] (dLd-) menu.
.
Menu [7 DISPLAY CONFIG.]
In [7.4 KEYPAD PARAMETERS]page 284, the [KEYPAD CONTRAST] and [KEYPAD STAND-BY] parameters to adjust the contrast and
stand-by mode of the graphic display unit.
Enhancements made to version V1.3 (S383) in comparison to V1.2
New parameters and functions
Menu [1.4 MOTOR CONTROL](drC-)
New option of operating with Closed-loop synchronous motor page 83
• [Angle auto-test] (ASA) page 84
• [Angle offset value] (ASU)page 85
• [Sync.CL](FSY) assignment page 71 of parameter [Motor control type] (Ctt)
Menu [1.5 INPUTS / OUTPUTS CFG](I-O-)
• [Resolver Exct. Freq.] (FrES) and [Resolver poles nbr](rPPn) page 115
Menu [1.7 APPLICATION FUNCT.](Fun-)
• New "Inspection" function, page 227, with [Inspection](ISP) and [Inspection speed] (ISrF) parameters.
AAV49426 12/20097
Software enhancements
Enhancements made to version V1.7 (S383) in comparison to V1.3 (S383)
New parameters and functions
Menu [1.1 SIMPLY START](SIM-)
• Addition of a [Lift](LIFt) macro configuration to the [Macro configuration](CFG) parameter page 41
Menu [1.3 SETTINGS](SEt-)
New parameters:
• [Fr.Loop.Stab](StA) page 56
• [FreqLoopGain](FLG) page 56
Menu [1.4 MOTOR CONTROL](drC-)
This menu has been reorganized with parameters now appearing in a different order and some grouped under submenusto simplify
configuration.
The new submenus are as follows:
• [ENCODER FEEDBACK](EnS-) page 75
• [ASYNC. MOTOR](ASY-) page 76
• [SYNCHRONOUS MOTOR](SYn-) page 81
• [ANGLE TEST SETTING](ASA-) page 84
• [FLUXING BY LI](FLI-) page 86
• [AUTOMATIC TUNE](tUn-) page 88
• [SPEED LOOP](SSL-) page 89
New parameters:
• [Boost](bOO) page 95
• [Action Boost](FAb) page 95
• [Increment EMF](IPHS) page 81
• [Read motor param.](rEqP) page 82
• [Status motor param](rEtP) page 82
• [Angle setting type](ASt) pages 84 and 87
• [Angle auto test](ASL) page 84
• [Angle setting activ.] (AtA) page 85
• [Angle setting status](AStS) page 85
• [Speed loop type] (SSL) page 89
• [Inertia Mult. Coef.](JMUL) page 89
• [Estim. app. inertia](JESt) page 89
• [Application Inertia](JAPL) page 90
• [Fr.Loop.Stab](StA) page 90
• [FreqLoopGain](FLG) page 90
• [Feed forward](FFP) page 91
• [Bandwidth feedfor.](FFU) page 91
Parameters moved from menu [1.7 APPLICATION FUNCT.](Fun-):
• [Motor fluxing](FLU) page 86
• [Fluxing assignment](FLI) page 86
• [Auto-tune assign.](tUL) page 88
Menu [1.5 INPUTS / OUTPUTS CFG](I-O-)
New encoder parameters:
• [Encoder protocol] (UECP) page 116
• [Encoder supply volt.] (UECU) page 116
• [Sincos lines count] (UELC) page 116
• [SSI pari t y] (SSCP) page 116
• [SSI frame size] (SSFS) page 116
• [Nbr of revolution] (EnMr) page 116
• [Turn bit resolution] (Entr) page 116
• [SSI code type] (SSCd) page 117
• [Encoder filter activ.] (FFA) page 117
• [Encoder filter value] (FFr) page 117
Menu [1.7 APPLICATION FUNCT.](Fun-)
Removal of the following parameters (now located in the [1.4 MOTOR CONTROL](drC-) menu):
• [Motor fluxing](FLU)
• [Fluxing assignment](FLI)
• [Auto-tune assign.](tUL)
8AAV49426 12/2009
Software enhancements
Enhancements made to version V1.9 (S383) in comparison to V1.7 (S383)
New parameters and functions
Menu [1.4 MOTOR CONTROL](drC-)
• New method of assigning [Angle setting type](ASt) page 87 : optimised measurement (without motion with memorization).
New parameter :
• [App. Inertia Coef.](JACO) page 89
Removal from the sub-menu [ASYNC. MOTOR](ASY-) of the following parameters (now located directly in the
[1.4 MOTOR CONTROL] (drC-) menu):
• [Boost](bOO) page 95
• [Action Boost](FAb) page 95
.
Menu [1.5 INPUTS / OUTPUTS CFG](I-O-)
New encoder parameters:
• [Coder rotation inv.] (EnrI) page 114
• [Clock frequency] (EnSP) page 117
Menu [1.7 APPLICATION FUNCT.](Fun-)
• New method of assigning for the parameters set switching [2 Parameter sets](CHA1) page 215 and [3 Parameter sets](CHA2)
page 215
starting of the ramp (useful for lift application).
: switching during braking sequence. This new assignment allo ws to put higher gain when the brak e is open and before the
.
.
.
.
New sub-menu:
• [TOP Z MANAGEMENT](tOP-) page 231
and if [Encoder type] (EnS) = [AABB] (AAbb).
New encoder parameter:
• [Stop on top Z] (tOSt) page 231
.
(the parameter can be accessed only if an encoder card VW 3A 411 has been inserted
Enhancements made to version V2.4 (S383) in comparison to V1.9 (S383)
New parameters and function
Menu [1.7 APPLICATION FUNCT.](Fun-)
New sub-menu:
• [ROLLBACK MGT](rbM-) page 181
- only for ATV71
-if [Motor control type] (Ctt) page 70
-if [Brake assignment] (bLC) page 175
New parameter of [ROLLBACK MGT] function:
• [Rollback MGT] (rbM) page 181
• [Rbk Compensation] (rbC) page 181
• [Rbk Damping] (rbd) page 181
pppM3X drives up to 45 kW and for ATV71pppN4 drives up to 75 kW,
. Menu can be accessed:
= [Sync.CL] (FSY) or [FVC] (FUC),
is assigned.
.
.
.
Enhancements made to version V2.8 (S383) in comparison to V2.4 (S383)
Menu [1.7 APPLICATION FUNCT.](FUn-)
• The adjustment range [Time to restart](ttr) page 177 can now be configured to 0 to 15.00 s.
Menu [7 DISPLAY CONFIG.]
•Addition in [7.4 KEYPAD PARAMETERS]page 284 parameter [Power up menu] to choose the menu displayed on the drive on
power up
.
Enhancements made to version V3.4 (S383) in comparison to V2.8 (S383)
[1.7 APPLICATION FUNCT.](Fun-) menu
New parameters and functions
• New parameter [REGEN CONNECTION] (AFE) page 232, used to connect an active front end
AAV49426 12/20099
Steps for setting up
INSTALLATION
v 1 Consult the Installation Manual
PROGRAMMING
Procedure applicable if the factory configuration, page 11, and use of the
[SIMPLY START](SIM-) menu only are sufficient for the application.
b 2 Power up without run command
v If you are using a separate power
supply for the control section, follow
the instructions on page 16.
b 3 Select the language, if the drive
has a graphic display terminal
b 4 Configure the [SIMPLY START]
(SIM-) menu
v 2-wire or 3-wire control
v Macro configuration
v Motor parameters
) Perform an auto-tuning
operation
v Motor thermal current
v Acceleration and deceleration
ramps
v Speed variation range
Tips:
• Before you start programming, complete
the user setting tables, page 293
.
• Perform an auto-tuning operation to
optimize performance, page 43
.
• If you get lost, return to the factory
settings, page 269
.
Note: Check that the wiring of the
drive is compatible with its configuration.
b 5 Start
10AAV49426 12/2009
Factory configuration
Drive factory settings
The Altivar 71 is factory-set for the most common operating conditions:
• Macro configuration: Start/Stop
• Motor frequency: 50 Hz
• Constant torque application with asynchronous motor and sensorless flux vector control
• Normal stop mode on deceleration ramp
• Stop mode in the event of a fault: freewheel
• Linear, acceleration and deceleration ramps: 3 seconds
• Low speed: 0 Hz
• High speed: 50 Hz
• Motor thermal current = rated drive current
• Standstill injection braking current = 0.7 x rated drive current, for 0.5 seconds
• No automatic starts after a fault
• Switching frequency 2.5 kHz or 4 kHz depending on drive rating
• Logic inputs:
- LI1: forward, LI2: Forward (2 operating direction), 2-wire control on transition
- L13, L14, LI5, LI6: inactive (not assigned)
• Analog inputs:
- AI1: speed reference 0 +10 V
- AI2: 0-20 mA, inactive (not assigned)
• Relay R1: The contact opens in the event of a fault (or drive off).
• Relay R2: Inactive (not assigned)
• Analog output AO1: 0-20 mA, inactive (not assigned)
If the above values are compatible with the application, the drive can be used without changing the settings.
Option card factory settings
The option card inputs/outputs are not factory-set.
AAV49426 12/200911
Application functions
The tables on the following pages show the most common combinations of functions and applications, in order to guide your selection.
The applications in these tables relate to the foll owing machines in particular:
• High inertia: centrifuges, mixers, unbalanced machines (beam pumps, presses)
• Process
Each machine has its own special features, and the combinations listed here are neither mandatory nor exhaustive.
Some functions are designed specifically for a particular application. In this case, the application is identified by a tab in the
margin on the relevant programming pages.
Motor control functions
Applications
FunctionsPage
V/f ratio
Sensorless flux vector control
Flux vector control with sensor
2-point vector control
Open-loop synchronous motor
Closed-loop synchronous motor
Output frequency of up to 1600 Hz
Motor overvoltage limiting
DC bus connection (see User's Manual)
Motor fluxing using a logic input
Switching frequency of up to 16 kHz
Auto-tuning
70
70
70
70
71
71
76
96
-
86
72
88
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
Process
bbb
bbbbbbbb
bbbbbbbb
bb
b
bbb
bb
bb
bb
bbb
bbb
bbbbbbbb
12AAV49426 12/2009
Application functions
Functions on speed references
FunctionsPage
Applications
Differential bipolar reference104
Reference delinearization (magnifying glass effect)106
Frequency control input140
- 150
Reference switching
Reference summing149
Reference subtraction149
Reference multiplication149
S ramps152
Jog operation160
Preset speeds161
+ speed/- speed using single action pushbuttons
(1 step)
+ speed/- speed using double action pushbuttons
(2 steps)
+/- speed around a reference166
Save reference168
Inspection227
141
164
164
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
bbb
bb
bb
b
b
b
b
bbb
bbb
bbbbb
b
bb
b
Process
b
b
AAV49426 12/200913
Application functions
Application-specific functions
FunctionsPage
Applications
Fast stop156
Limit switch management169
Brake control171
Load measurement182
High-speed hoisting184
Rope slack187
PID regulator189
Torque monitoring198
Motor/generator torque limit201
Load sharing98
Line contactor control205
Output contactor control207
Positioning by limit switches or sensors209
Stop at distance calculated after deceleration limit switch211
ENA system (mechanical with unbalanced load)93
Parameter switching214
Motor or configuration switching217
Traverse control220
Stop configuration156
Evacuation229
Half floor229
Rollback management 181
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
Process
bb
bbb
bbb
bb
b
b
b
bbb
bbbb
bb
bbb
b
bb
bb
b
bbbbbbbb
bbb
b
bbbb
b
b
b
14AAV49426 12/2009
Application functions
Safety functions/fault management
FunctionsPage
Applications
Power Removal (safety function, see User's Manual)
Deferred stop on thermal alarm244
Alarm handling130
Fault management235 to 258
IGBT tests247
Catch a spinning load239
Braking resistor thermal protection256
Motor protection with PTC probes235
Undervoltage management246
4-20mA loss248
Uncontrolled output cut (output phase loss)242
Automatic restart238
Use of the "Pulse input" input to measure the speed of
rotation of the motor
Load variation detection254
-
252
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
Process
bbbbbbbb
b
bbbbbbbb
bbbbbbbb
bbbbbbbb
bbb
bbbb
bbbbbbbb
bbb
bbbbbb
b
b
bbb
b
AAV49426 12/200915
Setup - Preliminary recommendations
DANGER
UNINTENDED EQUIPMENT OPERATION
• Before turning on and configuring the Altivar 71, check that the PWR (POWER REMOVAL) i nput is deact ivated (at
state 0) in order to prevent unintended operation.
• Before turning on the drive, or when exiting the configuration menus, check that the inputs assigned to the run
command are deactivated (at state 0) since they can cause the motor to start immediately.
Failure to follow these instructions will result in death or serious injury.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the li ne voltage is compatible with the sup ply voltage range shown
on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow this instruction can result in equipment damage.
CAUTION
• Avoid operating the contactor frequently (premature ageing of the filter capacitors).
• Cycle times < 60 s may result in damage to the pre-charge resistor.
Failure to follow this instruction can result in equipment damage.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that changes made to the settings during operation do not present any danger.
• We recommend stopping the drive before making any changes.
Failure to follow these instructions will result in death or serious injury.
Turning on and configuring the drive
Separate control section power supply
When the drive control section is powered independently of the power section (P24 and 0V terminals), whenever an option card is added
or replaced, only the power section must be supplied with power next time the drive is powered up.
By default the new card would not be recogniz ed and it wo uld be impossi ble to confi gure it, th ereby causing the dri ve to lock in fau lt mode.
Power switching via line contactor
User adjustment and extension of functions
• The display unit and buttons can be used to modify the settings and to extend the functions described in the following pages.
• Return to factory settings is made easy by the [1.12 FACTORY SETTINGS](FCS-) menu, see page 267
• There are three types of parameter:
- Display: Values displayed by the drive
- Adjustment: Can be changed during operation or when stopped
- Configuration: Can only be modified when stopped and no braking is taking place. Can be displayed during operation.
.
16AAV49426 12/2009
Setup - Preliminary recommendations
CAUTION
• Motor thermal protection will not be provided by the drive if th e motor current is less t han 0.2 times the rate d drive
current. Provide an alternative means of thermal protection.
Failure to follow this instruction can result in equipment damage.
CAUTION
• Motor thermal protection is no longer provided b y the drive. Provide an alternative means of thermal protection on
every motor.
Failure to follow this instruction can result in equipment damage.
Starting
Important:
• In factory settings mode, the motor can only be supplied wit h power once the “forward”, “reverse” an d “DC injection st op” commands
have been reset:
- On power-up or a manual fault reset or after a stop command
If they have not been reset, the drive will display "nSt" but will not start.
• If the automatic restart function has been configured ([Automatic restart](Atr) parameter in the [1.8-FAULT MANAGEMENT](FLt-)
menu, see page 238
Test on a low power motor or without a motor
• In factory settings mode, [Output Phase Loss] (OPL) detectionpage 242 is active (OPL = YES). To check the drive in a test or
maintenance environment without having to switch to a moto r with the same rating as the drive (part icularly useful in the case of high
power drives), deactivate [Output Phase Loss] (OPL = no).
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 70
), these commands are taken into account without a reset being necessary.
)
Using motors in parallel
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 70)
AAV49426 12/200917
Graphic display terminal
1 Graphic display
2 Function keys
F1, F2, F3, F4,
see page 19
.
3 STOP/RESET
button
4 RUN button
5 Navigation button:
• Press (ENT):- To save the current value
- To enter the selected menu or parameter
• Turn CW/
CCW:
- To increment or decrement a value
- To go to the next or previous line
- To increase or decrease the reference if control via
the terminal is activated
7 ESC key: Aborts a value, a
parameter or a menu to return
to the previous selection
6 Button for reversing the directi on
of rotation of the motor
HMI Modbus
Green LED:
DC bus ON
Red LED:
Fault
Although the graphic display terminal is optional for low-power drives, it is a standard component on high-power drives (see catalog). The
graphic display terminal can be disconnected and connected remotely (on the door of an enclosure for example) using the cables and
accessories available as options (see catalog).
Description of terminal
Note: Buttons 3, 4, 5 and 6 can be used to control the drive directly, if control via the terminal i s ac tivated.
Disconnected terminal
When the terminal is disconnected, 2 LEDs become visible:
18AAV49426 12/2009
Graphic display terminal
F1F2F3F4
RDYTerm+0.00 Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1
2
3
4
6
5
• Code F1
•HELP F1
• << F2
• >> F3
• Quick F4
Description of the graphic screen
1. Display line. Its content can be configured; the factory settings show:
• The drive state (see page 20
• The active control channel:
- Term: Terminals
- HMI: Graphic display terminal
- MDB: Integrated Modbus
- CAN: Integrated CANopen
- NET: Communication card
- APP: Controller Inside card
• Frequency reference
• Current in the motor
)
2. Menu line. Indicates the name of the current menu or submenu.
3. Menus, submenus, parameters, values, bar charts, etc., are displayed in drop-down window format on a maximum of 5 lines.
The line or value selected by the navigation button is displayed in reverse video.
4. Section displaying the functions assigned to the F1 to F4 keys and aligned with them, for example :
The function keys are dynamic and contextual.
Other functions (application functions) can be assigned to these keys via the [1.6 COMMAND] menu.
If a preset speed is assigned to a function key and i f the f unction he y is pres sed, the mo tor will run at this preset speed u ntil anothe r preset
speed or JOG is pressed, speed reference is changed, or Stop key is pressed.
5. Indicates that there are no more levels below this display window.
Indicates that there are more levels below this display window.
6. Indicates that this display window does not scroll further up.
Indicates that there are more levels above this display window.
: Displays the code of the selected parameter, i.e., the code corresponding to the 7-segment display.
: Contextual help
: Navigate horizontally to the left, or go to previous menu/submenu or, for a val ue, go to the ne xt di git up, di spl ayed
in reverse video (see the example on page 21
: Navigate horizontally to the right or go to next menu/submenu (going to the [2 ACCESS LEVEL] menu in this
example) or, for a value, go to the next digit down, displayed in reverse video (see the example on page 21
: Quick navigation, see page 25.
).
).
AAV49426 12/200919
Graphic display terminal
Drive state codes:
- ACC: Acceleration
- CLI: Current limit
- CTL: Controlled stop on input phase loss
- DCB: DC injection braking in progress
-DEC: Deceleration
- FLU: Motor fluxing in progress
-FST: Fast stop
- NLP: No line power (no line supply on L1, L2, L3)
- NST: Freewheel stop
- OBR: Auto-adapted deceleration
- PRA: Power Removal function active (drive locked)
- RDY: Drive ready
- RUN: Drive running
- SOC: Controlled output cut in progress
- TUN: Auto-tuning in progress
- USA: Undervoltage alarm
- ASA: Measurement of the phase-shift angle in progress
When only one selection is possible, the selection made is indicated by
Example: Only one language can be chosen.
When multiple selection is possible, the selections made are indi cated by
Example: A number of parameters can be chosen to form the [USER MENU].
Example configuration window for one value:
The << and >> arrows (keys F2 and F3) are used to select the digit to be modified, and the navigation button is rotated to increase or
decrease this number.
AAV49426 12/200921
Graphic display terminal
ATV31HU22N4383
2.2kW/3HP 380/480V
Config. n°1
5 LANGUAGE
English
Français
Deutsch
Español
Italiano
Chinese
RDY Term +0.00Hz 0.0A
2 ACCESS LEVEL
Basic
Standard
Advanced
Expert
RDY Term +0.00Hz 0.0A
1 DRIVE MENU
1.1 SIMPLY START
1.2. MONITORING
1.3. SETTINGS
1.4. MOTOR CONTROL
1.5. INPUTS / OUTPUTS CFG
Code<<>>Quick
RDY Term +0.00Hz 0.0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
First power-up - [5. LANGUAGE] menu
The first time the drive is powered up, the user will automatically be guided through the menus as far as [1. DRIVE MENU].
The parameters in the [1.1 SIMPLY START] submenu must be configured and auto-tuning performed before the motor is started up.
Display for 3 seconds following power-up
3 seconds
Automatically switches to [5 LANGUAGE]
menu 3 seconds later.
Select the language and press ENT.
ESC
Switches to [2 ACCESS LEVEL] menu
(see page 31
)
Select the access level and press ENT.
Switches to [1 DRIVE MENU]
(see page 27
)
Press ESC to return to [MAIN MENU]
22AAV49426 12/2009
Graphic display terminal
3 seconds later, switches to
[1. DRIVE MENU] or to
[1.14 PROGRAMMABLE CARD].
If no operator inputs are made,
switches to "Display" automatically
10 seconds later (the display will
vary depending on the selected
configuration).
Users can return to [MAIN MENU]
by pressing ENT or ESC.
3 seconds
10 seconds
ESC or ESC
ATV71HU22N4383
2.2kW/3HP 380/480V
Config. n°1
RDY Term+38Hz0A
1. DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
RDY Term+38Hz0A
Frequency ref.
Min=0Max=60
Quick
RDY Term+38Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
38 Hz
RDY Term +0.00Hz0A
1.14 PROGRAMMABLE CARD
Modbus add Prg C. :17
DATE/TIME SETTINGS
<<>>Quick
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
Menu selected in
[Power up menu]
page 284
ENT
or, if the Controller Inside card is present
Subsequent power ups
AAV49426 12/200923
Graphic display terminal
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
ENT
ESC
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
ENT
ENT or
ESC
RDY Term +0.00Hz0A
Acceleration
9.51 s
Min = 0.01 Max = 99.99
<<>>Quick
Programming: Example of accessing a parameter
Accessing the acceleration ramp
Note:
• To select a parameter:
- Turn the navigation button to scroll vertically.
• To modify a parameter:
- Use the << and >> keys (F2 and F3) to scroll horizontally and select the digit to be modified (the selected di git chan ges to white
on a black background).
- Turn the navigation button to modify the digit.
• To cancel the modification:
-Press ESC.
• To save the modification:
- Press the navigation button (ENT).
24AAV49426 12/2009
Graphic display terminal
RDY Term +0.00Hz0A
1.4 MOTOR CONTROL
Standard mot. freq: 5 0Hz IEC
Rated motor power: 0.37 kW (0.5 HP)
Rated motor volt.: 206 V
Rated mot. current: 1.0 A
Rated motor freq.: 50.0 Hz
Code<<>>Quick
ENT
RDY Term +0.00Hz0A
QUICK NAVIGATION
RETURN TO MAIN MENU
DIRECT ACCESS TO...
10 LAST MODIFICATIONS
GOTO MULTIPOINT SCREEN
Code
See page 285
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
RDY Term +0.00Hz0A
DIRECT ACCESS TO...
1.3
SETTINGS
<<>>
ENT
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
RDY Term +0.00Hz0A
10 LAST MODIFICATIONS
Acceleration: 10 s
ENA prop.gain: 1.2
Rated mot. current: 15 A
Preset speed 4: 20 Hz
Preset speed 5: 30 Hz
Code
ESC
ENT
RDY Term +0.00Hz0A
Rated mot. current
15.0 A
<<>>
Quick navigation
If the "Quick" function is displayed above the F4 key, you can gain quick access to a parameter from any screen.
Example:
Press F4 to access the Quick screen, which contains
4 selection options.
• [HOME]: Return to [MAIN MENU].
• [DIRECT ACCESS TO...]: Opens the direct access window, which
will contain the text "1". The function keys << and >> (F2 and F3)
can be used to select each of the numbers and the navigation
button to increment or decrement the numbers: 1.3 in the example
below.
• [10 LAST MODIFICATIONS]: Opens a window in which the l ast 10
parameters modified can be accessed directly.
AAV49426 12/200925
Graphic display terminal
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
[MAIN MENU] - Menu mapping
Content of [MAIN MENU] menus
[1 DRIVE MENU]See next page
[2 ACCESS LEVEL]Defines which menus can be accessed (level of complexity)
[3 OPEN / SAVE AS]Can be used to save and recover drive configuration files
[4 PASSWORD]Provides password protection for the configuration
[5 LANGUAGE]Language selection
[6 MONITORING CONFIG.]Customization of information displayed on the graphic display terminal during operation
[7 DISPLAY CONFIG.] • Customization of parameters
• Creation of a customized user menu
• Customization of the visibility and protection mechanisms for menus and parameters
26AAV49426 12/2009
Graphic display terminal
[1 DRIVE MENU]
RDY Term +0.00Hz0A
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
1 DRIVE MENU
Code<<>>Quick
Content of [1. DRIVE MENU] menus:
[1.1 SIMPLY START]:Simplified menu for a quick start
[1.2 MONITORING]:Visualization of current, motor and input/output values
[1.3 SETTINGS]:Accesses the adjustment parameters, which can be modified during operation
[1.4 MOTOR CONTROL]:Moto r parameters (motor nameplate, auto-tuning, switching frequency, control algorithms, etc.)
[1.5 INPUTS / OUTPUTS CFG]:I/O configuration (scaling, filtering, 2-wire control, 3-wire control, etc.)
[1.6 COMMAND]:Configuration of command and reference channels (graphic displ ay t erminal , t erminals , bu s, e tc.)
[1.7 APPLICATION FUNCT.]:Configuration of application functions (e.g., preset speeds, PID, brake logic con trol, etc.)
[1.8 FAULT MANAGEMENT]:Configuration of fault management
[1.9 COMMUNICATION]:Communication parameters (fieldbus)
[1.10 DIAGNOSTICS]:Motor/drive diagnostics
[1.11 IDENTIFICATION]:Identifies the drive and the internal options
[1.12 FACTORY SETTINGS]:Access to configuration files and return to factory settings
[1.13 USER MENU]:Specific menu set up by t he user in the [7. DISPLAY CONFIG.] menu
[1.14 PROGRAMMABLE CARD]:Configuration of optional Controller Inside card
AAV49426 12/200927
Integrated display terminal
• Four 7-segment
displays
• Enters a menu or
parameter, or saves the
displayed parameter or
value
• Returns to the previous
menu or parameter, or
increases the
displayed value
• Exits a menu or parameter,
or aborts the displayed
value to return to the
previous value in the
memory
• Goes to the next menu
or parameter, or
decreases the
displayed value
• 2 CANopen status LEDs
• 2 Modbus status LEDs
Note:
Low-power Altivar 71 drives (see catalog) feature an integrated display terminal with a 7-segment 4-digit display. The graphic display
terminal described on the previous pages can also be connected to these drives as an option.
Functions of the display and the keys
• Pressing or does not store the selection.
• Press and hold down (>2 s) or to scroll through the data quickly.
Save and store the selection: ENT
The display flashes when a value is stored.
Normal display, with no fault present and no startup:
- 43.0: Display of the parameter selected in the SUP menu (default selection: motor frequency)
- CLI: Current limit
- CtL: Controlled st op on in pu t phase loss
- dCb: DC injection braking in progress
- FLU: Motor fluxing in progress
- FSt: Fast stop.
- nLP: No line power (no line supply on L1, L2, L3)
- nSt: Freewheel stop
- Obr: Auto-adapted deceleration
- PrA: Power Removal function active (drive locked)
- rdY = Drive ready
- SOC: Controlled output cut in progress
- tUn: Auto-tuning in progress
- USA: Undervoltage alarm
- ASA: Measurement of the phase-shift angle in progress
The display flashes to indicate the presence of a fault.
28AAV49426 12/2009
Integrated display terminal
XXX
CtL-
FUn-
SIM-
I-O-
SEt-
SUP-
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
FCS-
LAC-
CON-
FLt-
ESC
ESC
ESC
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
SPL-
ESC
ENT
ESC
drC-
COd-
USr-
ESC
ENT
ESC
Displays the state of the drive
SETTINGS
APPLICATION FUNCT.
INPUTS / OUTPUTS CFG
FAULT MANAGEMENT
SIMPLY START
Menus
MONITORING
MOTOR CONTROL
COMMAND
Power-up
FACTORY SETTINGS
PASSWORD
ACCESS LEVEL
COMMUNICATION
(page 54) Adjustment parameters, can be modified during
operation
(page 144
)Configuration of application functions (e.g., preset
) Visualization of current, motor and i nput/output values
(page 71
) Motor parameters (motor nameplate, auto-tuning,
switching frequency, control algorithms, etc.)
(page 131
) Configuration of command and reference channels
(graphic display terminal, terminals, bus, etc.)
(page 267
) Access to configuration files and return to factory
settings
(page 274
)
(page 31
)
(page 259
) Communication parameters (fieldbus)
(page 270
) Specific menu, set up by the user using the graphic
display terminal.
USER MENU
PROGRAMMABLE CARD
(page 271
) Menu for the Controller Inside card, if present.
Accessing menus
A dash appears after menu and submenu codes to differentiate them from parameter codes.
Examples: FUn- menu, ACC parameter.
AAV49426 12/200929
The grayed-out menus may not be accessible depending on the control access (LAC) configuration.
Integrated display terminal
ENT
ACC15.0
ENT
ESC
ENT
ESC
26.026.0
ESC
dEC
ENT
SEt-
Menu
Value or assignment
1 flash
(save)
Parameter
(Next parameter)
ENT
ESC
1
st
n
th
last
Menu
ENT
ESC
I-O-
Alarm not selected
Alarm selected
Accessing menu parameters
Save and store the displayed selection :
The display flashes when a value is stored.
All the menus are "drop-down" type menus, which means that after the last pa rameter, if
you continue to press, you will return to the first parameter and, conver sely, you can
switch from the first parameter to the last parameter by pressing.
Selection of multiple assignments for one parameter
Example: List of group 1 alarms in [INPUTS / OUTPUTS CFG]
(I-O-) menu
A number of alarms can be selected by "checking" them as
follows.
The digit on the right indicates: selected
not selected.
The same principle is used for all multiple select ions.
30AAV49426 12/2009
Loading...
+ 285 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.