Schneider Electric Andover Continuum I/O Modules Catalog

Andover ContinuumTM
The Andover Continuum intelligent building system allows you to mix and match various combinations of DIN rail-mounted modules — flexible I/O, CPU and power supply, and your choice of several user interface modules — in a single controller location to meet your building’s control and monitoring needs.
Andover Continuum I/O Modules Features
With the Andover Continuum system, as your network grows, simply add or replace I/O modules as needed.
The Andover Continuum I/O modules feature a sleek, lightweight casing designed for natural convection cooling, and a 3-position front cover for easy access. Built-in quick-release fasteners at the back of each I/O module are provided for DIN rail mounting — no tools required. These fasteners also snap into a locked position for panel mounting. Input and output connectors are located at the bottom of each I/O module and are removable for easy field access and maintenance. All Andover Continuum modules are designed for mounting in an optional NEMA 1-style Andover Continuum enclosure.
02
PRODUCT AT A GLANCE
Flexible, Modular Design Fits Every Application
User- Config urable I/O Sele ction to Meet
Specific Control Needs
DIN Rail Mo unting Provides Eas y Insta llation
and System Expansion
NEMA 1-Style Enclosure Available
Three-Position Front Cover for Easy Access
Built-in Quick-Release Fasteners—
No Tools Required!
Removable Input/Output Connectors for
Easy Installation
Slid e-Together Power/Co mmunica tions
Connections
Optional Remote Mounting
Push-Button Network Commissioning
Choice of RS-485 or FTT-10A Media
The Andover Continuum I/O modules communicate with the Andover Continuum NetController CPU module using Andover LON communications. Like all Andover Continuum modules, the I/O modules slide together via built-in connectors on either side so network expansion is quick and easy. Both power transmission and communication signals feed through these connectors. For added convenience, in applications such as door control or lighting control, a single module or groups of I/O modules can be remotely located and connected using approved cable, and powered from a local power supply. Each I/O module features its own push-button for quick and easy network commissioning.
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Andover Continuum I/O Modules
03
Features
(continued)
Communication Choices
All Andover Continuum modules are available in either the standard RS-485 or the Free Topology (FTT-10A) media interface. RS-485 is perfect for local mounting applications and is a lower cost media choice. FTT-10A provides increased flexibility and reliability. FTT modules are connected using a twisted-pair cable and can be wired in a bus, star, distributed star, or even a ring topology for added resilience. Note: You cannot mix and match both media types on the same I/O bus.
Dimension Drawings
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Andover Continuum I/O Modules Specifications
I/O Modules
04
N1831
Mechanical
Operating Environment
32–120°F (0 to 49°C),
10–95%RH (non-condensing)
Size*
3.8˝ W (96.5mm) including connectors
7.2˝ H (182.88mm) with mounting
clips extended
6.2˝ H (157.48mm) with mounting
clips closed
2.5˝ D (96.5 x 170.2 x 63.5mm)
*With the exception of the VS-8-4 models –
9.0˝ W x7.2˝ H (6.2˝ H closed) x 2.5˝ D
(228.7 x 182.88mm (157.48 mm closed)
x 63.5mm)
Weight*
.75 lbs (0.34kg)
*With the exception of the VS-8-4 models –
1.32lbs (0.60kg)
Enclosure Type
UL open class,
flammability rating of UL94-5V, IP 10
Mounting
Mount on DIN rail or wall-mount
using attached clips.
Andover Continuum NEMA 1-style
enclosure available
Battery Backup
Via Andover Continuum
UPS power supply
Communications
Communications Interface:
TAC-LON communications with
Andover Continuum CPU module
Choice of RS-485 or FTT-10A interface
Comm. Error Checking
International Standard CRC 16
RS-485
Communications Speed: 39k baud
Bus Length: 2,000 ft. (610m)
Bus Media: Shielded, twisted pair cable
120v termination required at both ends
of the ACC-LON network (when modules
are mounted remotely)
FTT-10A
Communications Speed: 78k baud
Bus Length: Up to 8858 ft. (2700m) –
bus topology
Up to 1640 ft (500m) – free topology
Repeater required for longer distances
Bus Media: Refer to FTT-10A
documentation in Andover Continuum
I/O System Reference Guide
(P/N: 30-3001-4999--Rev D or higher)
Power/Communications Connections
5-position plug-in connectors on left and
right sides allow Andover Continuum mod-
ules to be directly connected to each other
or remotely connected via approved cable
CPU
3120E2 MCU with internal ROM,
EEPROM, and SRAM
Except VT-1 and AC-1Plus:
3150BFU1 with internal EEPROM
and external FLASH and SRAM
Agency Listings
UL/CUL 916, FCC CFR 47 Part 15,
ICES-003, EN55022,
AS/NZS 3548, and VCCI Class A,
CE UL 864 - (UI-8-10-S, DI-8-S, MI-6-S,
AO-4-8-S, DO-6-TR-S, DO-4-R-S,
DM-20-S, DO-4-R-O-S, UI-8-10-10V-S,
and AO-4-8-0-S only)
UL 294 - (UI-8-10, DI-8, DO-4-R, DM-20,
AC-1, AC-1Plus, AC-1A, UI-8-10-10V,
DO-4-R-O, VS-8-4, and VS-8-4-T only)
UL-1076 - (UI-8-10, UI-8-10-10V, DO-4-R,
DO-4-R-O, AC-1, AC-1a, and AC-1Plus only)
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
UI-8-10
I/O Module
05
The UI-8-10, Andover Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing separate indication of alarm and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, status points, and
Specifications
Input Impedance
UI-8-10 (0–5V): 5 MW w/pullup disabled;
10 KW w/pullup enabled
UI-8-10-10V (0–10V): 4.4 KW
Input Connections
Two-piece, 13-position removable
terminal block
Voltage
UI-8-10 (0–5V)
Range: 0–5 V
Resolution: 5 mV
Accuracy: ±15 mV (±0.3% FSR)
Electrical
Power Consumption
0.7 W @ 10-28VDC max.
Overload Protection
0.5 A resettable fuse with transient
voltage suppressor (TVS) and reverse
polarity protection.
Inputs
Number of Inputs
8 Universal inputs; 10 bit resolution
Input Types
Voltage, Thermistor, Digital, Counter, and
Supervised
Input Protection
24 V AC/DC allowed to any single input
(40V TVS on each input – UI-8-10-10V
model only)
Range: 0–10 V
Resolution: 10 mV
Accuracy: ±15 mV V (±0.4% FSR)
Thermistor
UI-8-10 (0–5V)
Type: 10 KW, Type III Thermistor
Range: -30 to 230°F
Resolution: 40 to 100°F range
Accuracy: 40 to 100°F range
UI-8-10-10V (0–10V)
Type: 10 KW, Type III Thermistor
Range: -30 to 230°F
Resolution: 0.20°F typical
Accuracy: ±1.0°F (±0.55°C)
similar inputs in a control system, with a 0–5 volt input range and 10-bit A/D conversion.
A UI-8-10-10V model is also available for 0–10 volt applications. It provides the identical point type selection, but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0-10 volt range.
Digital & Counter
Input Type: Contact Closure
Frequency: 4 Hz (max.)
Pulse Width: 125 ms ( min.)
(Digital pulse widths are based
on Scan Time.)
Supervised
Input Type: Single or Double Resistor
Supervision, Parallel or Series Circuit
User LEDs/Switches
Status Indicator LEDs
UI-8-10-10V (0–10V)
(-34 to 110°C)
(4 to 38°C)
(4 to 38°C)
(-34 to 110°C)
(0.11°C typical)
Power Power Indicator
Comm TD Indicator
Status Service/Wink Indicator
Push-Button Switches
Commission Reset
Models
UI-8-10
8 Universal inputs; 0-5 Volt input range
UI-8-10-10V
8 Universal inputs; 0-10 Volt input range
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
DI-8
I/O Module
06
The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs—each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP
Specifications
Inputs
Number of Inputs:
8 Digital inputs
Input Types
Digital or Counter, software selectable
Input Protection
24 V AC/DC applied to 4 channels max.
(40V TVS on each input)
Input Impedance
10KW pull-up resistor referenced to +5
VDC
Inputs Connections
Two-piece, 13-position removable
Electrical
Power Consumption
0.8 W @ 10–28 VDC max.
Overload Protection
0.5 A resettable fuse with transient
voltage suppressor (TVS) and reverse
polarity protection
terminal block
Digital
Input Type: Contact closure or 0–5V input
Pulse Width: 50 ms ( min.)
Current: 0.5mA (max.)
switch) on Channels 1 and 2 for high-speed metering and industrial applications.
40 V bipolar transorbs on all eight inputs protect against high voltage short duration transient events. The DI-8 is designed to accept dry contact inputs or 0-5 volts, but can withstand up to 24 VAC/VDC continuous voltage on four channels.
Counter:
Input Type: Contact closure
or 0–5 VDC input
Channels 1 and 2 in HI-speed mode
(selectable via dip switch):
Frequency: 10kHz (max.)
Pulse Width: 50 µS (min.)
Current: 0.5 mA
Channels 3 through 8; and Channel
1 and 2 in LO-speed mode:
Frequency: 10 Hz (max.)
Pulse Width: 50 mS (min.)
Currrent: 0.5 mA
User leads/Switches
Status Indicator LEDs
Power Power Indicator
Comm TD Indicator
Status Service/Wink
Indicator
Input Status 1–8 Input Status Indicator
(Closed circuit=ON)
Switches
Commission
Reset
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
DI-6-AC
I/O Module
07
The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC inputs for cost­effective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6­AC monitors the absence or presence of AC or DC voltage levels directly, with no interposing relays
Specifications
Input Connections
Two-piece, 13-position removable
terminal block
DI-6-AC
AC Inputs
AC Input Range: 20–132 Vrms
AC Input Current: 5 mA (max.)
AC Voltage “ON” Threshold: 16 Vrms
(Above this voltage is considered “ON”)
AC Voltage “OFF” Threshold: 8 Vrms
(Below this voltage is considered “OFF”)
Input Resistance (±5%): 30KW
Maximum Turn ON Time: 20 ms
Electrical
Power Consumption
0.7 W @ 24 VDC (max).; when provided by
Andover Continuum power supply module
Overload Protection
0.5 A re-settable fuse with transient
voltage suppressor (TVS) and reverse
polarity protection
Inputs
Number of Inputs
6 Digital AC or DC voltage inputs
Input Protection
2500 V isolation on each input.
Each input has a 270 V metal
oxide varistor (MOV.)
Maximum Turn OFF Time: 60 ms
DC Input Voltage Range: 20–132 V
DC Input Current: 5 mA (max.)
DC Voltage “ON” Threshold: 20 V
(Above this voltage is considered “ON”)
DC Voltage “OFF” Threshold: 12 V
(Below this voltage is considered “OFF”)
DI-6-AC-HV
AC Inputs:
AC Input Range: 90–250 Vrms
AC Input Current: 2 mA (max.)
AC Voltage “ON” Threshold: 75 Vrms
(Above this voltage is considered “ON”)
AC Voltage “OFF” Threshold: 30 Vrms
(Below this voltage is considered “OFF”)
Input Resistance (±5%): 200KW
Maximum Turn ON Time: 20 ms
Maximum Turn OFF Time: 60 ms
needed. The DI-6-AC can monitor voltages from 24–120V.
A DI-6-AC-HV model is also available for sensing higher voltages—120–240V. Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.
DC Input Voltage Range: 90–250 V
DC Input Current: 2 mA (max.)
DC Voltage “ON” Threshold: 90 V
(Above this voltage is considered “ON”)
DC Voltage “OFF” Threshold: 45 V
(Below this voltage is considered “OFF”)
User leads/Switches
Status Indicator LEDs
Power Power Indicator
Comm TD Indicator
Status Service/Wink
Indicator
Input Status 1–:6 Input Status Indicator
(Above voltage
threshold = ON)
Switches
Commission
Reset
Models
DI-6-AC
6 Digital AC Inputs, 24–120 V input signal
DI-6-AC-HV
6 Digital AC Inputs, 120–240 V input signal
Schneider Electric
SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC