Schneider Electric AM-610 Data Sheet

Application

To provide 24 Vac power to components such as actuators and controllers.

Features

Meets NEC Class 2 requirements
120/208/240 Vac multiple primary

AM-610

Transformer
General Instructions
Color coded leads
Cross-Reference Guide, F-23638
Reference Manual, F-12683
Application Manual, F-21335
Printed in U.S.A. 4/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-24859-3
SPECIFICATIONS
Transformer Inputs
Environment
INSTALLATION
Inspection
Voltage and Current Ratings:
Primary, 120/208/240 volts, 50/60Hz.
Secondary, 24 Vac, 40 VA. Leads: 7" (178 mm) long, #18 GA. stranded wire. Rating: NEC Class 2. Mounting: 1/2"-14 standard straight pipe thread conduit nipple.
Ambient Temperature Limits:
Shipping and Storage, -40 to 160°F (-40 to 71°C).
Operating, -40 to 140°F (-40 to 60°C). Location: NEMA Type 1.

Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

Requirements
Tools (not provided):
Volt-ohm Meter (VOM)
Appropriate screwdriver for mounting screws and terminal connections
Training: Installer must be a qualified, experienced technician.
WARNING
Avoid locations where excessive moisture, corrosive fumes or vibration are present.
Make all connections in accordance with the wiring table (Table-1) and in accordance with
national and local electrical codes. Use No. 18 AWG or larger copper conductors only.
CAUTION
Do not exceed ratings of the device.
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-24859-3