Aperio® Hub AH20/AH30 Installation Instructions
Covers AAWL-260 3 May 2011
ASSA ABLOY, the global leader in door opening solutions
1
Page 2
AH20/AH30 - Table of Contents
AH20/AH30 - FCC and Industry Canada Statements 3
AH20/AH30 - Placement of Communication Hub 4
AH20 (J100) - Connections 5-6
AH20 (J103) - Connections 7
AH20 - DIP Switch Configuration Table 8
AH30 (J100) - Connections 9
AH30 - DIP Switch Configuration Table 10
AH30 - RS485 Bus Connection 11
AH30 - RS485 Addressing 12-13
AH20/AH30 - Communication Hub LED Indication 14
AH20/AH30 - Technical Data 15
ETL marking
Recognized component
N
16329
Z
1217
4002570
Conforms to ANSI/UL standard 294, ANSI/UL 60950-1 Certified to CAN/CSA standard C22.2 No. 60950-1
2
Page 3
AH20/AH30 - FCC and Industry Canada Statements
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC Rules and with RSS-210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence.L’exploitation est autorisée aux deux conditions suivantes:
1. l’appareil ne doit pas produire de brouillage, et
2. l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le fonctionnement.
The term “IC:” before the equipment certification number only signifies that the Industry Canada technical specifications were met.
Le terme “IC” devant le numéro de certification signifie seulement que les spécifications techniques Industrie Canada ont été respectées.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
IEEE 802.15.4 operation of this product in U.S.A. and Canada is limited to channels 11-25 by Aperio Canada another version of the Aperio programming application allow use of channels 11-26.
®
Programming Application. Outside of U.S.A. and
3
Page 4
AH20/AH30 - Placement of Communication Hub
< 25 m / ~ 80 ft
AH20 (Wiegand Hub) - Placement of the Hub, 1 door
Note: AH20 can be installed with an Aperio bottom cover or Americas adaptor plate.
< 25 m / ~ 80 ft
AH30 (RS485 Hub) - Placement of the Hub, 1-8 doors
Note: Note: AH20/AH30 must be installed into a junction box ex European 2-Gang, Aperio bottom cover or with Americas adaptor plate to junction box. AH20/AH30 must be installed by qualified
4
and trained personal. Indoor installation only!
Page 5
AH20 (J100) - Connections
S100
K500 K501 K502 K503
J103
NCL1
COM1
NOP1
NCL2
COM2
NOP2
NCL3
COM3
NOP3
NCL4
COM4
NOP4
J100
A
B
D1
D0
RED
GREEN
GND
8-24V
ON
S101
1 2 3 4 5 6 7 8 9 10
AH20 Connectors (J100)
Note: The installation must comply with national wiring regulations.
5
Page 6
Hub ConneCtor
DesCription
AH20 (J100) - Connections
Communication Hub hardware version AH20 has four Wiegand signals plus power supply. The purpose and connection of these signals are described in the table below.
Wiegand Data 1 signal. Output from Communication Hub.
DATA 1
Used to transmit credentials.
Wiegand Data 0 signal. Output from Communication Hub.
DATA 0
Used to transmit credentials.
Wiegand Red LED signal. Input to Communication Hub. Used
RED
for access decision. Leave unconnected if DIP switch 1 is selected “OFF”. Signal is active low.
Wiegand Green LED signal. Input to Communication Hub.
GREEN
Used for access decision. Signal is active low. See DIP 1 for alternate instructions.
GND = Signal ground. Should be connected to EAC system
GND
GND and power supply GND.
8-24 VDC Power supply input, 8-24 VDC, 2 W.
AH20 Connectors (J100)
6
Page 7
AH20 (J103) - Connections
relays DesCription
relay ContaCts DesCription
S100
K500 K501 K502 K503
J103
NCL1
COM1
NOP1
NCL2
COM2
NOP2
NCL3
COM3
NOP3
NCL4
COM4
NOP4
J100
A
B
D1
D0
RED
GREEN
GND
8-24V
AH20 Connectors (J103)
Relay 1/K500 DPS (Door Position)
Relay 2/K501 RX (Request to exit)
Relay 3/K502 Battery Alarm Output
Relay 4/K503
NCL Normally Closed
COM Common
NOP Normally Open
Tamper Alarm Output/ Lock Jammed
ON
1 2 3 4 5 6 7 8 9 10
S101
Relay max voltage: 30 VDC Relay max current: 1 A
resistive load
On the AH20 four form C relays are available.The purpose of the four relays is to provide door status information to the EAC system.
7
Page 8
switCH number
label DesCription
AH20 - DIP Switch Configuration Table (S101)
Dip
Controls use of Red LED signal for access decision.
1 A0
2 A1 Set to OFF by default. Reserved for future use.
3 A2
4 A3
5 A4
6-8 Not applicable (only used for AH30).
9 Not used.
10
ON => Red LED is used.
OFF => Red LED is ignored.
Controls addition of parity bits if required.
ON => Addition of parity bits is enabled.
OFF => Addition of parity bits is disabled. Credentials are transmitted as received.
Controls byte order of transmitted credentials.
ON => The byte order is reversed on the Wiegand interface compared to what is received from the
®
lock.
Aperio
OFF => The byte order is left as is.
Used in “Pairing Mode”.
ON => Starts in pairing mode.
OFF => Normal use.
INT/
Internal/External Antenna Use, ON = Internal
EXT
8
Page 9
AH30 (J100) - Connections
Hub ConneCtor
DesCription
S100
K500 K501 K502 K503
J103
NCL1
COM1
NOP1
NCL2
COM2
NOP2
NCL3
COM3
NOP3
NCL4
COM4
NOP4
J100
A
B
D1
D0
RED
GREEN
GND
8-24V
ON
S101
1 2 3 4 5 6 7 8 9 10
AH30 (J100) Connectors
A RS485 Data A.
B RS485 Data B.
GND
GND = Signal ground. Should be connected to EAC system GND and power supply GND.
8-24 VDC Power supply input, 8-24 VDC, 1.1 W.
Note: The installation must comply with national wiring regulations.
9
Page 10
switCH number
label DesCription
AH30 - DIP Switch Configuration Table (S101)
Dip
Controls RS485 addressing BIT 0-BIT 4.
ON => Address bit set.
A0-A4
1-5
6 DOWN
7 UP
8 TERM
9 Not used.
10 INT/EXT
OFF => Address bit NOT set.
See AH30 - RS485 Addressing Reference on page 13.
Controls use of RS485 pull down resistor.
ON => 620 Ohm pull down connected/enabled.
OFF => 620 Ohm pull down disconnected/disabled.
Controls use of RS485 and pull up resistor.
ON =>620 Ohm pull up connected/enabled.
OFF => 620 Ohm pull up disconnected/disabled.
Controls use of termination resistor between RS485 A and RS485 B.
ON =>100 Ohm termination resistor connected/ enabled.
OFF => 100 Ohm termination resistor disconnected/ disabled.
Controls use of external antenna if required.
ON =>Selects use of internal antenna.
OFF => Selects use of external antenna.
10
Page 11
AH30 - RS485 Bus Connection
Examples of connection of multiple Communication Hubs to a single RS-485 bus of an EAC system:
A
EAC system
A
Hub 1
DIP 6 ON DIP 7 ON DIP 8 ON
EAC system
B
Termination enabled
B
A
B
Termination enabled
A
Hub 1
DIP 6 OFF DIP 7 OFF DIP 8 OFF
Hub 2
DIP 6 OFF DIP 7 OFF DIP 8 ON
B
A
B
Hub 2
DIP 6 OFF DIP 7 OFF DIP 8 OFF
A
B
Communication Hub Connections, examples
Note: The RS485 bus cable should be of type twisted pair. The maximum cable length of 1000 meters should not be exceeded.
A
Hub N End of Bus
DIP 6 ON DIP 7 ON DIP 8 ON
B
11
Page 12
aDDress
AH30 - RS485 Addressing
0 Pairing Active
1 ON
2 ON
3 ON ON
4 ON
5 ON ON
6 ON ON
7 ON ON ON
8 ON
9 ON ON
10 ON ON
11 ON ON ON
12 ON ON
13 ON ON ON
14 ON ON ON
15 ON ON ON ON
a0 a1 a2 a3 a4*
Address examples
12
Page 13
AH30 - RS485 Addressing
aDDress
16 ON
17 ON ON
18 ON ON
19 ON ON ON
20 ON ON
21 ON ON ON
22 ON ON ON
23 ON ON ON ON
24 ON ON
25 ON ON ON
26 ON ON ON
27 ON ON ON ON
28 ON ON ON
29 ON ON ON ON
30 ON ON ON ON
31 ON ON ON ON ON
a0 a1 a2 a3 a4*
Address examples
* = A4 is only supported on AH30 in 1 - 1 mode.
13
Page 14
AH20/AH30 - Communication Hub LED Indication
The Communication Hub has a single LED that supports an optical scheme with red, green and yellow. The indication scheme is described by the two figures below:
GreenOnline
®
Lock
Aperio
Offline
EAC Offline
®
Lock and
Aperio
EAC Offline
UHF
Communication
Note: With the software tool Aperio® Programming Application and a USB radio dongle, further system installation parameters can be set.
Green + One Red Flash
Green + Two Red Flashes
Green + Three Red Flashes
Yellow + Off, Fast Flash
YellowPairing Active
14
Page 15
AH20/AH30 - Technical Data
Physical Dimensions 82 mm x 82 mm x 37 mm (H x W x T)
Power Supply 8-24 VDC
Power Rating
Radio Standard
Receiver Sensitivity -100 dBm 20%PER
Wireless Transmit Power
Wireless Operating Range
Internal Antenna Two cross polarized dipoles.
External Antenna
Operating Temperature
Humidity < 95 % non-condensing.
IP Classification IP20
Safety and Emissions
2 W (AH20)
1.1 W (AH30)
IEEE 802.15.4 (2400 – 2483,5MHz) 16 channels (11-26) 15 channels in USA and Canada (11-25) AES 128 bit encryption
10 dBm/MHz. Peak value from average detector according to EN ETSI 300 328 Maximum spectral density.
Indoors 15-25 m depending upon installed environment.
One reverse polarity SMA external antenna connector. AH20/30 is certified to be used with Assa Abloy external antenna AH-ANTENNA-1. If other external antenna is used it must be of same type (dipole) and not have larger antenna gain than 3,9dBi.
5 °C to 35 °C.
FCC 47CFR Part 15 subpart B and subpart C IC RSS-210 EN ETSI 301 489-17 v2.1.1 EN ETSI 300 328 v1.7.1 EN 60950-1 ed.2 2007 UL 294-2010 C22.2
15