Schneider Electric AFS–222–112 Data Sheet

Cleveland Controls
Model
Division of UniControl Inc.
AFS–222–112
AIR PRESSURE SENSING SWITCH WITH ADJUSTABLE SET POINT RANGE
APPLICATION
Model AFS-222-1 12 Air Pressure Sens­ing Switch is a general purpose proving
switch designed for HVAC and Energy Management applications. It may be used to sense positive, negative, or differen­tial air pressure. The AFS-222-112 is equipped with convenient barbed sample line connectors that accept flexible tub­ing.
GENERAL DESCRIPTION & OPERATION
The plated housing contains a diaphragm, a calibration spring and a snap-acting SPDT switch.The barbed sample line con­nections located on each side of the dia­phragm accept flexible tubing.
An enclosure cover guards against acci­dental contact with the live switch termi­nal screws and the set point adjusting screw. The enclosure cover will accept a ½" conduit connection.
MOUNTING (SEE FIGURE 1)
AIR SAMPLING CONNECTION (SEE FIGURE 2)
Select a mounting location which is free from vibration. The AFS-222-112 must be mounted with the diaphragm in any verti­cal plane in order to obtain the lowest specified operating set point. Avoid mounting with the sample line connec­tions in the "up" position. Surface mount via the two 3/16" diameter holes in the
(Figure 1)
Cleveland Controls
DIV
ISION OF UNICONTROL INC.
integral mounting bracket. The mounting holes are 3-7/8" apart.
The AFS-222-112 is designed to accept flexible tubing by means of barbed 1/4" slip-on connections. For sample lines of up to 10 feet, ¼” OD tubing is acceptable. For lines up to 20 feet, use ¼” ID tubing. For lines up to 60 feet, use ½” ID tubing. Locate the sampling probe a minimum of
1.5 duct diameters downstream from the air source. Install the sampling probe as close to the center of the airstream as possible. Refer to Figure 2 to identify the high pressure inlet (H) and the low pres­sure inlet (L). Connect the sample lines as follows:
POSITIVE PRESSURE ONLY: Connect the sample line to inlet H; inlet L remains open to the atmosphere.
NEGATIVE PRESSURE ONLY: Connect the sample line to inlet L; inlet H remains open to the atmosphere.
TWO NEGA TIVE SAMPLES: Connect the higher negative sample to inlet L. Con­nect the lower negative sample to inlet H.
TWO POSITIVE SAMPLES: Connect the higher positive sample to inlet H. Connect the lower positive sample to inlet L.
ONE POSITIVE AND ONE NEGATIVE SAMPLE: Connect the positive sample to
inlet H. Connect the negative sample to inlet L.
Bulletin AFS222-112.01
(Figure 2)
(Figure 3)
(Figure 4)
ELECTRICAL CONNECTIONS (SEE FIGURE 3)
Before pressure is applied to the dia­phragm, the switch contacts will be in the normally closed (NC) position. The snap switch has screw top terminals with cup washers. Wire alarm and control appli­cations as shown in Figure 4.
FIELD ADJUSTMENT
The adjustment range of an AFS-222-112 Air Switch is 0.05 ±.02" w.c. to 12.0" w .c. To adjust the set point, t urn the adjust­ing screw counterclockwise until motion has stopped. Next, turn the adjusting screw 4 complete turns in a clockwise direction to engage the spring. From this point, the next ten turns will be used for the actual calibration. Each full turn rep-
resents approximately 1.2" w.c. Please note: T o properly calibrate an air
switch, a digital manometer or other mea­suring device should be used to confirm the actual set point.
SPECIFICATIONS
MODEL AFS-222-1 12 AIR
PRESSURE SENSING
SWITCH WITH
ADJUSTABLE SET POINT
RANGE
Mounting Position: Mount with the diaphragm in any vertical plane.
Set Point Range: 0.05 ± 0.02" w.c. to
12.0"w.c. Field Adjustable “Operate Range”:
0.07"w.c. to 12.0" w.c. Field Adjustable “Release Range”:
0.04"w.c. to 11.2" w.c.
Approximate Switching Differential:
Progressive, increasing from 0.02 ±
0.01"w.c. at minimum set point to approximately 0.8 " w.c. at maximum set point.
Measured Media: Air, or combustion by-products that will not degrade silicone.
Maximum Pressure: ½ psi (0.03 bar). Operating Temperature Range:
-40F to 180F (-40 to 82C).
Life: 100,000 cycles minimum at 1/2 psi maximum pressure each cycle and at maximum rated electrical load.
Electrical Rating:
300 VA pilot duty at 115 to 277 VAC, 15 amps noninductive to 277 VAC, 60
Hz.
Contact Arrangement: SPDT. Electrical Connections: Screw-type
terminals with cup washers. Conduit Opening: 7/8" diameter
opening accepts ½" conduit. Sample Line Connectors: Two
barbed ¼" connectors will accept flexible tubing.
Sample Line Connections: Two barbed ¼" connectors will accept flexible tubing.
Approval: UL, FM, CSA, CE Shipping Weight: 1.2 lbs. Accessories:
• Sample line probes.
• Orifice plugs (pulsation dampers).
Nominal Dimensions in Inches (Millimeters)
Loading...