Hazardous Location Considerations3
European Union Directive Compliance4
Wiring and Safety Guidelines5
Enclosures5
Required Tools5
Mounting Dimensions6
Cutout Dimensions7
Clearances7
Installing Terminal in a Panel9
Installing the Memory Card11
Connecting AC Power12
Connecting DC Power13
EtherNet/IP Protocol15
ControlNet Protocol15
Battery Removal and Disposal15
For More Information17
Installation Instructions
2 PanelView 550 Terminals
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
available from your local Rockwell Automation sales office or online at
SGI-1.1
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
) describes some important differences between solid state
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment, for example, a drive or motor, to alert
people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert
people that surfaces may reach dangerous temperatures.
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 3
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class II,
Division 2, Groups F and G; Class III Division 2; or non-hazardous locations only.
The following WARNING statement applies to use in hazardous locations.
WARNING
See the nameplate on terminal for hazardous locations certifications.
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I, Class II, Class III
Division 2.
• Do not replace components or disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been switched off
or the area is known to be non-hazardous.
• This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-4(b), 502-4(b), 503-3(b) as
appropriate.
ATTENTION
In Class I, Class II, Class III Division 2 Hazardous locations, the PanelView 550
terminal must be wired per the National Electric Code as it applies to hazardous
locations. Peripheral equipment must also be suitable for the location in which it is
installed.
The following PV550 terminals have an operating temperature code of T2
(maximum operating temperature of 300 °C or 572 °F):
• keypad terminals (series G or earlier)
• keypad and touch screen terminals (series G or earlier)
Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 300 °C (572 °F).
Publication 2711-IN009E-EN-P - February 2009
4 PanelView 550 Terminals
The following PV550 following PV550 terminals have an operating temperature
code of T4 (maximum operating temperature of 135 °C or 275 °F):
• keypad terminals (series H and later)
• keypad and touch screen terminals (series H and later)
Do not install these terminals in environments where atmospheric gases have
ignition temperatures less than 135 °C (275 °F).
European Union Directive Compliance
If a PanelView 550 Operator Terminal is installed within the European Union or
EFTA regions and has a CE mark, the following regulations apply.
EMC and Low Voltage Directives
This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic
Compatibility (EMC) and amending directives 91/263/EEC, 92/31/EEC, 93/68/EEC;
72/23/EEC Low Voltage Directive, and amending directive 93/68/EEC using the
following standards, in whole or in part:
• EN 50081-2:1993 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 61000-6-2:1999 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
• EN 61131-2:1995 EMC - Programmable Controllers - Equipment
Requirements and Tests
• Low Voltage Directive - Safety Sections of EN 61131-2
The product described is intended for use in an industrial environment.
Intended Use of Product
According to these Standards, the factor which determines, for EMC purposes,
whether an apparatus is deemed to be “Industrial” or “Residential, commercial and
light industrial”, is given in Clause 1 of EN50081-2 as follows:
Apparatus covered by this standard is not intended for connection to a
public mains network but is intended to be connected to a power network
supplied from a high- or medium-voltage transformer dedicated for the
supply of an installation feeding a manufacturing or similar plant.
The PanelView 550 terminals are intended for use solely in an industrial
environment as defined above. When installed in Europe, any other application is
in contravention of European Union Directives, and a breach of these laws.
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 5
Wiring and Safety Guidelines
Install the PanelView 550 terminal using publication 70E, Electrical Safety
Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, follow these recommendations:
• Connect the PanelView terminal to its own branch circuit.
• The input power source should be protected by a fuse or circuit breaker
rated at no more than 15 amps.
• Route incoming power to the PanelView 550 terminal by a separate path
from the communications cable.
• Where power and communication lines must cross, they should cross at
right angles. Communications lines can be installed in the same conduit as
low level DC I/O lines (less than 10 Volts).
• Grounding minimizes noise from Electromagnetic Interference (EMI) and is
a safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.
• A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.
Enclosures
Mount the PanelView 550 terminal in a panel or enclosure to protect the internal
circuitry. The terminal meets NEMA Type 12/13 and 4X (indoor use) ratings only
when properly mounted in a panel or enclosure with the equivalent rating.
Allow enough space within the enclosure for adequate ventilation. Consider heat
produced by other devices in the enclosure. The ambient temperature around the
terminal must be between 0…55 °C (32…131 °F).
Make provisions for accessing the back panel of the terminal for wiring,
maintenance, installing a memory card, and troubleshooting.
Required Tools
Other than the tools required to make the panel cutout, the tools required for
installation are:
• 7mm (M4) deep well socket wrench or nut driver.
• small slotted screwdriver.
• torque wrench (N•m, lb•in).
Publication 2711-IN009E-EN-P - February 2009
6 PanelView 550 Terminals
Mounting Dimensions
266 mm
(10.47 in.)
Top View
167 mm
(6.57 in.)
86 mm
(3.39 in.)
106 mm
(4.17 in.)
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 7
Cutout Dimensions
Use the full size template shipped with the terminal to mark the cutout dimensions.
The figure below shows a reduced size cutout.
243 mm
(9.55 in.)
4.8 mm dia.
(0.188 in.)
3.3 mm
(0.13 in.)
144 mm
(5.66 in.)
3.3 mm
(0.13 in.)
150 mm
(5.91 in.)
25.9 mm
(1.02 in.)
191 mm
(7.51 in.)
106 mm
(4.19 in.)
85 mm
(3.33 in.)
Recommended Panel
Cutout Dimensions
Clearances
Allow adequate clearances for mounting, air flow, maintenance, and for installing a
memory card and legend inserts.
Publication 2711-IN009E-EN-P - February 2009
8 PanelView 550 Terminals
Leave 25 mm (1 in.) for
Mounting and Air Flow
Side, Top and Bottom Clearances
Leave 25 mm (1 in.)
for Mounting and
Air Flow
Terminal Cutout
Use full size template shipped
with terminal.
Front View
Leave 38 mm (1.5 in.) for
Mounting and Legend Inserts
Leave 25 mm (1 in.) for
Mounting and Air Flow
Back Clearance
Approximately
207 mm (8.15 in.) is
required to insert
and remove a
memory card with
the memory card
retainer.
86 mm
(3.39 in.)
card
Memory Card Retainer
Publication 2711-IN009E-EN-P - February 2009
106 mm
(4.17 in.)
Installing Terminal in a Panel
To install the PV500 terminal in a panel:
PanelView 550 Terminals 9
ATTENTION
• Disconnect all electrical power from the panel before making the cutout.
• Make sure the area around the panel cutout is clear.
• Take precautions so that metal cuttings do not enter any components that may
already be installed in panel.
• Failure to follow this warning may result in personal injury or damage to the
panel components.
1. Cut an opening in the panel using the panel cutout provided with the
terminal. Remove sharp edges or burrs.
2. Make sure the sealing gasket is properly positioned on the terminal (as
shown below). This gasket forms a compression type seal. Do not use
sealing compounds.
Tape
Sealing GasketLegend Strip Adhesive
3. Verify that the ends of the legend strips are secured with the legend strip
adhesive.
4. Place the terminal in the panel cutout.
5. Make sure the ends of the legend inserts are positioned behind the panel
cutout.
6. Install the six self-locking nuts, hand tight.
Publication 2711-IN009E-EN-P - February 2009
10 PanelView 550 Terminals
Mounting Studs
(3 Top/3 Bottom)
Protective Installation Label
Self-locking Nuts
(6 used, 8 provided)
7. Alternately tighten the self-locking nuts until the terminal is held firmly
against the panel. Tighten the nuts to a torque of 1.13 N•m (10 lb•in). Do
not overtighten nuts.
ATTENTION
Mounting nuts must be tightened to a torque of 1.13 N•m (10 lb•in) to
provide a proper seal and to prevent potential damage to the terminal.
Allen-Bradley assumes no responsibility for water or chemical damage to
the terminal or other equipment within the enclosure because of improper
installation.
8. Remove the protective installation label covering the top vents of the
terminal.
ATTENTION
Failure to remove the protective installation label covering the top vents
could result in overheating and damage to the terminal.
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 11
Installing the Memory Card
The memory card retainer is required for UL508 installations where a memory card
is inserted in the card slot. The retainer protects against electrostatic discharge
(ESD) up to 15 KV and prevents accidental removal of a memory card in high
vibration environments.
To attach the memory card retainer:
Retainer Base
Memory Card
Retainer
Base Mounting Screws
1. Secure the base of the retainer over the existing memory card slot using the
two screws provided. Tighten screws to a torque of 0.7…0.9 N•m
(6…8 lb•in).
2. Insert the memory card and install the retainer until it is properly seated.
3. To remove the retainer, press the tabs on each side and pull.
Publication 2711-IN009E-EN-P - February 2009
12 PanelView 550 Terminals
Connecting AC Power
The table below shows the electrical ratings for the AC versions of the terminals.
Terminal TypeSupply VoltagePower Consumption
PV55085…264V AC, 47…63 Hz45VA maximum
ATTENTION
ATTENTION
• The PanelView 550 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
• Do not apply power to the terminal until all wiring connections have been made.
Failure to do so may result in electrical shock.
Explosion Hazard - Do not connect or disconnect equipment while circuit is live
unless area is known to be non-hazardous.
To connect AC power to the PanelView 550 terminals:
1. Secure the AC power wires to the L1 and L2N terminal block screws.
2. Secure the Earth Ground/Protective Earth wire to the GND screw on the
terminal block.
ATTENTION
Improper wiring of the power terminals may result in voltage at the
communication connector shells. Refer to the following figure when wiring.
3. Apply power to the terminal.
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 13
Power Terminal Block (fixed)
120/240V AC, 3 Wire,
U.S. Color Code
L1
GNDGND
L2
Black (line)
White
(neutral)
Green (earth
ground)
To Power Source
120/240V AC, 3 Wire,
European Harmonized Color
Code
L1
L2
Brown (line)
Blue
(neutral)
Green/Yellow
(protective earth)
To Power Source
Connecting DC Power
The L1 and L3 versions (Catalog Number 2711-K5A1L1 or 2711-K5A1L3) of the
PV550 terminals connect to a 24V dc power source.
The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions.
Terminal TypeSupply VoltagePower Consumption
PV55018…30V DC, (24V DC nominal)12 Watts maximum
(0.5 Amps @ 24V DC)
ATTENTION
• Do not connect the PanelView terminal to an AC power source. Connecting to an
AC power source may damage the terminal.
• The PanelView 550 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
Publication 2711-IN009E-EN-P - February 2009
14 PanelView 550 Terminals
To connect DC power to the PV550 terminal:
1. Secure the DC power wires to the terminal block screws.
2. Secure the Earth Ground wire to the correct terminal block screw.
ATTENTION
ATTENTION
Explosion Hazard - Do not connect or disconnect equipment while circuit is
live unless area is known to be non-hazardous.
Do not apply power to the terminal until all wiring connections have been
made. Failure to do so may result in electrical shock.
3. Apply 24V DC power to the terminal.
Power Terminal Block (fixed)
+
Earth Ground
DC Negative
DC Positive
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 15
EtherNet/IP Protocol
The PanelView terminal is initially set to DHCP with BootP support (Dynamic Host
Configuration Protocol) enabled. If your network has a DHCP/BootP server, you
can connect the PanelView terminal to the EtherNet/IP network and the
DHCP/BootP server will automatically establish an IP address. If your network does
not have a DHCP/BootP server, you need to program an IP address. This is done by
accessing Configuration Mode on the PanelView terminal and selecting
Communication Setup. For details, refer to the PanelView Standard Operator
Terminals Manual, publication 2711-UM014
.
IMPORTANT
If a PanelView is connected to an EtherNet/IP network and has the same IP address as
another device on the network, both devices will drop off the network.
ControlNet Protocol
IMPORTANT
When making ControlNet connections, only use the PanelView Channel B for redundant
communications. Connecting Channel B to a Channel A only ControlNet network will
result in:
• the PanelView not being able to communicate over the network.
• a PanelView communications fault after several minutes.
Battery Removal and Disposal
The terminal contains a lithium battery, which is intended to be replaced during the
life of the product.
ATTENTION
The clock module contains lithium. Do not dispose of the battery in a fire or incinerator, or
the clock module may explode. Follow disposal regulations in your area for lithium
battery disposal.
At the end of its life, the battery contained in this product should be collected separately
from any unsorted municipal waste.
Publication 2711-IN009E-EN-P - February 2009
16 PanelView 550 Terminals
Follow these steps to remove or replace the battery (older version).
12
345
678
Publication 2711-IN009E-EN-P - February 2009
PanelView 550 Terminals 17
Follow these steps to remove or replace the battery. (newer version)
12
35
4
5
6
7
8
For More Information
ForRefer toRefer to
More detailed information on the 550 and the other
Standard PanelView terminals.
Standard PanelView
Terminals User Manual
2711-UM014
If you would like a publication, you can:
• download a free electronic version from the PanelBuilder32 installation CD.
• download free from the internet: http://literature.rockwellautomation.com
Publication 2711-IN009E-EN-P - February 2009
.
18 PanelView 550 Terminals
Notes:
Publication 2711-IN009E-EN-P - February 2009
Notes:
PanelView 550 Terminals 19
Publication 2711-IN009E-EN-P - February 2009
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in
using its products. At http://support.rockwellautomation.com
technical manuals, a knowledge base of FAQs, technical and application notes,
sample code and links to software service packs, and a MySupport feature that you
can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review
the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your product up and running.
, you can find
United States1.440.646.3434
Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully
operational when shipped from the manufacturing facility. However, if your
product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United
States
PanelView, PanelView 550, PanelBuilder, Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(call the phone number above to obtain one) to your distributor in order to
complete the return process.
Please contact your local Rockwell Automation representative for the return
procedure.