Rockwell Automation 21G-750 User Manual

Programming Manual
PowerFlex 750-Series AC Drives
Firmware Versions:1.xxx…10.xxx

Important User Information

IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

New and Updated Information

This table contains the changes made to this revision.
Top ic Pag e
The PowerFlex 753 and PowerFlex 755 flashing yellow STS status description changed. 18
Main DC Bus Volt parameter moved to the Metering Group. 42
The following parameters have new descriptions or default, minimum, and/or maximum values h ave changed.
[Comman ded Trq]
4 35 [Motor Ctrl Mode] 40 [Mtr Options Cfg]
[DI Precharge]
189 312 [SpdTrqPsn Mode D] 326 [Manual Cmd Mask]
[FlyingStart Mode]
356
[Pwr Loss A Level ] and 454 [Pwr Loss B Level]
451 688
[Notch Fltr Atten] [Psn Reg Ki]
838 839 [Psn Reg Kp] 731 [Homing Control]
[DLX Out 01]…14 [DLX Out 14]
1 17 [DLX In 01]…30 [DLX In 14] 82 [Enc Out FD PPR]
Motor control parameter 40 [Mtr Options Cfg] default setting for Jerk Select changed. 56
Motor control parameter 63 [Break Frequency] has the Voltage to Frequency table added. 60
Motor control parameter 80 [PM Cfg] has a table added. 62
Feedback & I/O parameters 181 [Dl SpTqPs Sel 0 and 182 [Dl SpTqPs Sel 1] has a table added. 73
Units for the following parameters were added.
244 [TO0 On Time]
[TO0 Off Time]
245 276 [Anlg Out0 Stpt]
The following parameters have been added.
[CbFan TotalLife]…484 [CbFan RemainLife]
482
[HSFan TotalLife]…491 [HSFan RemainLife]
489 496
[InFan TotalLife]…498 [InFan RemainLife] [CRC Fl t Cfg]
964 1700…1731 1800…1831 [UserData Real 00…UserData Real 31] 1900 1901, 1905…1929 [ScaleBlk Scal 00…07] 1902 1903
Diagnostics parameter 935 [Drive Status 1] table changed. 156
Removed “755” icon from parameters 1153 [Dead Time Comp] and 1154 [DC offset Crtl]. 180
Universal feedback parameter 6 [FBO Device Sel] options changed. 275
Descriptions for the following event numbers have changed.
24 “Decel Inhibit 27 “Torq Pro ve C fl ct” 35 “IPM OverCurrent 211 “Safety Brd Fault 901…927 “Machine CheckCIP Motion Error
The following event numbers were added.
333 “I3 Comm Loss 343 “C3 Comm Loss
[UserData Int 00…UserData Int 31]
, 1904…1928 [ScaleBlk Sel 00…07]
, 1906…1930 [ScaleBlk Int 00…07] , 1907…1931 [ScaleBlk Real 00…07]
,307, 308
52 55 56 73 86 88 92 102 127 147 147 136 243 243 286
79 79 81
105 106 107 212 212 212 212 212 212 213
314 314 314 321 323
323 323
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 3
Summary of Changes
Top ic Pag e
Added Predictive Maintenance with Logix
Remove Table 8 - Integrated Motion on EtherNet/IP Attribute Alphabetical Order from
Appendix E.
Base 10 and Base 16 numbers were added to the attribute mapping tables in Appendix E. 512
information in Appendix B. 475
505
4 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Summary of Changes Table of Contents Preface Overview
Start Up

Table of Contents

Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
New and Updated Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
What Is Not In This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Recommended Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Obtaining Manuals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Allen-Bradley Drives Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Product Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 1
Start-Up Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Start-Up Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Drive Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Establishing A Connection With EtherNet/IP . . . . . . . . . . . . . . . . . . . . . 19
Parameter Organization
Drive Port 0 Parameters
Chapter 2
About Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Parameter Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
How Drive Parameters are Organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
How Option Module Parameters are Organized . . . . . . . . . . . . . . . . . . . . 45
Chapter 3
Drive (Port 0) Monitor File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Drive (Port 0) Motor Control File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Drive (Port 0) Feedback & I/O File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Drive (Port 0) Cfg File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Drive (Port 0) Protection File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Drive (Port 0) Speed Control File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Drive (Port 0) Torque Control File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Drive (Port 0) Position Control File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Drive (Port 0) Communication File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Drive (Port 0) Diagnostics File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Drive (Port 0) Applications File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Drive (Port 0) General Purpose Parameters. . . . . . . . . . . . . . . . . . . . . . . . 212
Port 10 and Port 11 Parameters
Chapter 4
Inverter (Port 10) Common Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Inverter n (Port 10) Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Converter (Port 11) Common Parameters . . . . . . . . . . . . . . . . . . . . . . . . 221
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 5
Table of Contents
Embedded Feature and Option Module Parameters
Troubleshooting
Converter n (Port 11) Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Precharge (Port 11) Common Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 227
Precharge n (Port 11) Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Chapter 5
Embedded EtherNet/IP (Port 13) Parameters . . . . . . . . . . . . . . . . . . . . . 234
Communication Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Embedded DeviceLogix (Port 14) Parameters. . . . . . . . . . . . . . . . . . . . . . 243
11-Series I/O Module Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
22-Series I/O Module Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Single Incremental Encoder Module Parameters . . . . . . . . . . . . . . . . . . . 267
Dual Incremental Encoder Module Parameters . . . . . . . . . . . . . . . . . . . . 269
Universal Feedback Module Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
Safe Speed Monitor Module Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Chapter 6
Faults, Alarms and Configurable Conditions . . . . . . . . . . . . . . . . . . . . . . 306
Drive Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
HIM Indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Manually Clearing Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Power Layer Interface (PLI) Board 7-Segment Display . . . . . . . . . . . . . 310
Setting Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
System Resource Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Hardware Service Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Integrated Motion Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Fault and Alarm Display Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Parameter Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Drive Fault and Alarm Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Inverter (Port 10) Faults and Alarms (Frame 8 and Larger) . . . . . . . . . 328
Converter (Port 11) Faults and Alarms (Frame 8 and Larger) . . . . . . . 333
Precharge (Port 11) Faults and Alarms (Frame 8 and Larger). . . . . . . . 338
N-1 and Re-Rate Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Embedded EtherNet/IP (Port 13) Events . . . . . . . . . . . . . . . . . . . . . . . . . 345
I/O Faults and Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Safe Torque Off Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
ATEX Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
Single Incremental Encoder Faults and Alarms. . . . . . . . . . . . . . . . . . . . . 348
Dual Incremental Encoder Faults and Alarms. . . . . . . . . . . . . . . . . . . . . . 349
Universal Feedback Faults and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Port Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Common Symptoms and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 357
PowerFlex 755 Lifting/Torque Proving . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
External Brake Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Technical Support Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
6 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Appendix A
Table of Contents
PowerFlex 753 Control Block Diagrams PowerFlex 755 Control Block Diagrams
Application Notes
Using DeviceLogix
List of PowerFlex 753 Control Block Diagrams . . . . . . . . . . . . . . . . . . . . 363
Diagram Conventions and Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
List of PowerFlex 755 Control Block Diagrams . . . . . . . . . . . . . . . . . . . . 398
Diagram Conventions and Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Appendix B
Voltage Tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
PowerFlex 755 Lifting/Torque Proving . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Crane Setup with Encoder Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
Crane Setup - Encoderless. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Pump Off Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Predictive Maintenance with Logix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475
Appendix C
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483
Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485
Function Block Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485
Bit and Analog I/O Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 486
Tips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 488
Program Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
Permanent Magnet Motors
Integrated Motion on EtherNet/IP
Index
Appendix D
Compatible Allen-Bradley Servo Motors . . . . . . . . . . . . . . . . . . . . . . . . . . 501
Appendix E
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505
Feedback Configuration Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
Parameter / Instance Attribute Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . 512
Enhanced Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 527
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 7
Table of Contents
8 Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Preface

Overview

The purpose of this manual is to provide you with the basic information needed to install, start-up and troubleshoot PowerFlex® 750-Series Adjustable Frequency AC Drives.
For information on … See page...
Who Should Use This Manual 9 What Is Not In This Manual 9 Recommended Documentation 9 Obtaining Manuals 10 Allen-Bradley Drives Technical Support 11 Product Certification 11 Manual Conventions 11 General Precautions 12

Who Should Use This Manual

What Is Not In This Manual

Recommended Documentation

This manual is intended for qualified personnel. You must be able to program and operate Adjustable Frequency AC Drive devices. In addition, you must have an understanding of the parameter settings and functions.
The PowerFlex 750-Series User Manual is designed to provide only basic start-up information.
All the recommended documentation listed in this section is available online at
http://www.rockwellautomation.com/literature
.
The following publications provide general drive information.
Title Publication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives DRIVES-IN001 Safety Guidelines for the Application, Installation and Maintenance of Solid State Control SGI-1.1 A Global Reference Guide for Reading Schematic Diagrams 100-2.10 Guarding Against Electrostatic Damage 8000-4.5.2
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 9
Preface
The following publications provide specific PowerFlex 750-Series information on drive installation, features, specifications, and service:
Title Publication
PowerFlex 750-Series AC Drive Installation Instructions 750-IN001 PowerFlex 750-Series AC Drives Technical Data 750-TD001 Enhanced PowerFlex 7-Class Human Interface Module (HIM) User Manual 20HIM-UM001 PowerFlex 750-Series Safe Torque Off User Manual 750-UM002 Safe Speed Monitor Option Module for PowerFlex 750-Series AC Drives Reference Manual 750-RM001 PowerFlex 750-Series AC Drives Hardware Service Manual (Frame 8 and Larger) 750-TG001 Dynamic Braking Resistor Calculator PFLEX-AT001 DeviceLogix User Manual RA-UM003
The following publications provide specific Network Communications information:
Title Publication
PowerFlex 755 Drive Embedded EtherNet/IP Adapter 750COM-UM001 PowerFlex 750-Series Drive DeviceNet Option Module 750COM-UM002 PowerFlex 20-750-CNETC Coaxial ControlNet Option Module 750COM-UM003

Obtaining Manuals

The following publications provide necessary information when applying the Logix Processors:
Title Publication
Logix5000 Controllers Common Procedures 1756-PM001 Logix5000 Controllers General Instructions 1756-RM003 Logix5000 Controllers Process Control and Drives Instructions 1756-RM006 RSLogix 5000 Getting Results 9399-RLD300GR
The following publications provide information that is useful when planning and installing communication networks:
Title Publication
ContolNet Coax Tap Installation Instructions 1786-5.7 ControlNet Cable System Planning and Installation Manual 1786-6.2.1 ContolNet Fiber Media Planning and Installation Guide CNET-IN001
To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
To find your local Rockwell Automation distributor, visit
www.rockwellautomation.com/locations
10 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Preface

Allen-Bradley Drives Technical Support

Product Certification

Manual Conventions

Online at… By Email at… By Telephone at…
www.ab.com/support/abdrives support@drives.ra.rockwell.com 262-512-8176
For Automation and Control Technical Support:
Title Online at…
Rockwell Automation Technical Support
http://support.rockwellautomation.com/knowledgebase
Product Certifications and Declarations of Conformity are available on the internet at: www.rockwellautomation.com/products/certification
In this manual we refer to PowerFlex 750-Series Adjustable Frequency AC Drives as: drive, PowerFlex 750, PowerFlex 750 drive or PowerFlex 750 AC drive.
Specific drives within the PowerFlex 750-Series may be referred to as:PowerFlex 753, PowerFlex 753 drive or PowerFlex 753 AC drivePowerFlex 755, PowerFlex 755 drive or PowerFlex 755 AC drive
To help differentiate parameter names and LCD display text from other
text, the following conventions will be used: – Parameter Names will appear in [brackets] after the Parameter Number.
For example: parameter 308 [Direction Mode].
Display text will appear in “quotes.” For example: “Enabled.”
The following words are used throughout the manual to describe an
action:
Word Meani ng
Can Possible, able to do something Cannot Not possible, not able to do something May Permitted, allowed Must Unavoidable, you must do this Shall Required and necessary Should Recommended Should Not Not recommended
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 11
Preface

General Precautions

Qualified Personnel

ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and
associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.

Personal Safety

ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and -DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements.
ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input source sensitivity.
ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected together via 1202 cables. Unpredictable behavior can result if two or more devices are connected in this manner.
ATTENTION: The drive start/stop/enable control circuitry includes solid state components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas or solids exists, an additional hardwired stop circuit may be required to remove the AC line to the drive. An auxiliary braking method may be required.
ATTENTION: Hazard of personal injury or equipment damage due to unexpected machine operation exists if the drive is configured to automatically issue a Start or Run command. Do not use these functions without considering applicable local, national and international codes, standards, regulations or industry guidelines.
12 Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Product Safety

ATTENTION: An incorrectly applied or installed drive can result in component damage
or a reduction in product life. Wiring or application errors such as under sizing the motor, incorrect or inadequate AC supply, or excessive surrounding air temperatures may result in malfunction of the system.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference Guarding Against Electrostatic Damage, publication 8000-4.5.2 or any other applicable ESD protection handbook.
ATTENTION: Configuring an analog input for 0-20 mA operation and driving it from a voltage source could cause component damage. Verify proper configuration prior to applying input signals.
ATTENTION: A contactor or other device that routinely disconnects and reapplies the AC line to the drive to start and stop the motor can cause drive hardware damage. The drive is designed to use control input signals that will start and stop the motor. If an input device is used, operation must not exceed one cycle per minute or drive damage will occur.
Preface
ATTENTION: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.

Class 1 LED Product

ATTENTION: Hazard of permanent eye damage exists when using optical transmission
equipment. This product emits intense light and invisible radiation. Do not look into module ports or fiber optic cable connectors.
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 13
Preface
Notes:
14 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 1

Start Up

This chapter provides the information needed to start up the PowerFlex 750-Series drive.
Top ic Pag e
Start-Up Check List 15
Start-Up Menu 17
Drive Status Indicators 18
Establishing A Connection With EtherNet/IP 19

Start-Up Check List

This check list supports the Start-Up menu option.
A Human Interface Module (HIM) is required to run the Start-Up
routine. For detailed information on using the HIM, refer to the Enhanced
PowerFlex 7-Class Human Interface Module (HIM) User Manual, publication 20HIM-UM001.
The Start-Up routine may modify parameter values for Analog and Digital I/O.
ATTENTION: Power must be applied to the drive to perform the following start-up procedure. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning.

Prepare For Initial Drive Start-Up

1. Confirm that drive has been installed according to the PowerFlex 750-
Series AC Drives Installation Instructions, publication 750-IN001
2. Confirm that all inputs are connected to the correct terminals and are
secure.
.
3. Verify that AC line power at the disconnect device is within the rated value
of the drive.
4. Verify that control power voltage is correct.
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 15
Chapter 1 Start Up
5. The remainder of this procedure requires that a Human Interface Module
(HIM) is connected to DPI Port 1 or 2.
Figure 1 - DPI Ports and
6. Apply AC power and control voltages to the drive.
If any digital inputs are configured to Stop – CF, Run, or Enable, verify that signals are present or the drive will not start. Refer to Chapter
6 for
a list of potential digital input conflicts.
If the STS LED is not flashing green at this point, refer to Drive Status
Indicators on page 18.
7. When prompted, select a display language. The Start-Up Screen will
automatically display for drives that have not been previously configured.
If the Start-Up screen is not displayed press the Enter key.
8. Press the Enter key to display the Start-Up Menu.
9. Use the Up/Down Arrow keys to highlight “2. Basic.”
10. Press the Enter key. Follow the menu using the Enter key which will step
you through the Start-Up routine.
The Start-Up routine asks simple questions and prompts you to input required information.
16 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Start Up Chapter 1
IMPORTANT

Start-Up Menu

Motor Control Motor Data Feedback Limits Tests Reference I/O Done
Motor Ctrl Motor Data Feedback
The Human Interface Module (HIM) displays the General Start-Up menu by default upon initial power up of the drive. To navigate to the Start-Up menu after
the initial power up of the drive, press the (Folders) key.
General Startup
Start-Up Main Menu
Complete these steps in order: Motor Control Motor Data Feedback Limits Tes t s Ref, Ramp, Stop I/O Done
Confi g
Limits Tests Ref, Ramp,
Stop
I/O Return to
Main Menu
Motor Ctrl
Return
Motor Data
Return
Fdbk Cnfg
Return
Limits
Return
Return to
Main Menu
Tes t s
Return
Ref, Ramp,
Stop
Return
I/O
Return
If a start up routine is initiated, but must be terminated before the routine is completed, be sure to press the Abort soft key to completely exit the routine.
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 17
Chapter 1 Start Up

Drive Status Indicators

Table 1 - PowerFlex 753 Status Indicator Descriptions
Name Color State Description
STS (Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running, a start inhibit condition exists and the drive cannot be started.
Steady A t ype 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started until fault
Steady A non-resettable fault has occurred.
Red / Yellow
Yellow / Green
Green / Red
Flashing Alternately
Flashing Alternately
Flashing Alternately
See parameter 933
starting until the alarm condition is cleared. If the drive is running, it continues to run but cannot restart until the alarm condition is cleared.
See parameters 959
condition is cleared. See parameter 951
A minor fault has occurred. When running, the drive continues to run. System is brought to a stop under system control. Fault must be cleared to continue. Use parameter 950
When running, a type 1 alarm exists. See parameters 959
Drive is flash updating.
[Start Inhibits].
[Alarm Status A] and 960 [Alarm Status B].
[Last Fault Code].
[Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
[Alarm Status A] and 960 [Alarm Status B].
Table 2 - PowerFlex 755 Status Indicator Descriptions
Name Color State Description
STS (Status)
ENET Unlit Off Embedded EtherNet/IP is not properly connected to the network or needs an IP
LINK Unlit Off Adapter is not powered or is not transmitting on the network.
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running, a type 2 (non-configurable) alarm condition exists and the
Steady A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started until fault
Steady A non-resettable fault has occurred.
Red / Yellow
Yellow / Green
Green / Red
Red Flashing An EtherNet/IP connection has timed out.
Red / Green
Green Flashing Adapter is properly connected but is not communicating with any devices on the
Green Flashing Adapter is properly connected and transmitting data packets on the network.
Flashing Alternately
Flashing Alternately
Flashing Alternately
Steady Adapter failed the duplicate IP address detection test. Flashing
Alternately
Steady Adapter is properly connected and communicating on the network.
Steady Adapter is properly connected but is not transmitting on the network.
drive cannot be star ted. See parameter 961
starting until the alarm condition is cleared. If the drive is running, it continues to run but cannot restart until the alarm condition is cleared.
See parameters 959 [Alar m Status A] and 960 [Alarm Stat us B].
condition is cleared. See parameter 951
A minor fault has occurred. When running, the drive continues to run. System is brought to a stop under system control. Fault must be cleared to continue. Use parameter 950 [Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
When running, a type 1 alarm exists. See parameters 959
Drive is flash updating.
address.
Adapter is performing a self-test.
network.
[Alarm Stat us A] and 960 [Alarm Status B].
[Type 2 Alarms].
[Last Fault Code].
18 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Start Up Chapter 1
IMPORTANT
IMPORTANT
IMPORTANT
The Status Indicator LEDs on the HIM cradle do not indicate the current status of an installed Communication Adapter option. If an optional Communication Adapter is installed, refer to that option’s user manual for a description of LED location and indication.

Establishing A Connection With EtherNet/IP

There are three methods for configuring the embedded EtherNet/IP adapter’s IP address:
• Adapter Rotary Switches – Use the switches when working on a simple, isolated network (for example, 192.168.1.xxx) that has other products with switches to set their IP addresses, does not need to be accessed from outside the network, and you prefer a simplified node addressing method. The three adapter switches are read when the drive powers up, and represent three decimal digits from top to bottom (see Figure 2
). If set to a valid address (001-254), the adapter will use that value as the lower octet of its IP address (192.168.1.xxx, where xxx = rotary switch settings), along with a subnet mask of 255.255.255.0 and there will be no gateway configured. Also, the setting for adapter P36 [BOOTP] is automatically ignored.
See Figure 2
and its accompanying table for all possible switch settings and
their related descriptions.
When using the adapter rotary switches, set the IP address before power is applied because the adapter uses the IP address it detects when it first receives power.
•BOOTP Server – Use BOOTP if you prefer to control the IP addresses of devices using a server. The IP address, subnet mask, and gateway addresses will then be provided by the BOOTP server.
•Adapter Parameters – Use adapter parameters when you want more flexibility in setting up the IP address, or need to communicate outside the control network using a gateway. The IP address, subnet mask, and gateway addresses will then come from the adapter parameters you set.
Regardless of the method used to set the adapter’s IP address, each node on the EtherNet/IP network must have a unique IP address. To change an IP address, you must set the new value and then remove and reapply power to (or reset) the adapter.
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 19
Chapter 1 Start Up
Ones
Posi tion
Hundreds
Posi tion
Ten s Po si tio n
Figure 2 - Setting the IP Address Switches
5
6
4
7
3
8
2
9
1
0 5
6
4
7
3
8
2
9
1
0 5
6
4
7
3
8
2
9
1
0
Possible Settings Description
000 Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
001…254 Adapter will use the rotary switch settings for the IP address (192.168.1.xxx, where xxx =
255…887 Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
888 Resets the adapter IP address function to factory defaults. Thereafter, the drive must be
889…998 Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
999 (default settings)
settings for the IP address.
rotary switch settings).
settings for the IP address.
powered down, the switches set to a setting other than 888, and then the drive must be powered up again to accept the new address.
settings for the IP address.
Disables the rotary switches. Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter settings for the IP address.
20 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 2

Parameter Organization

This chapter lists and describes the PowerFlex 750-Series Port 0 drive parameters. The parameters can be programmed (viewed/edited) using a Human Interface Module (HIM). Refer to Enhanced PowerFlex 7-Class Human Interface Module (HIM) User Manual, publication 20HIM-UM001 HIM to view and edit parameters. As an alternative, programming can also be performed using DriveTools™ software and a personal computer.
Top ic Pag e
About Parameters 22
Parameter Access Level 23
How Drive Parameters are Organized 24
How Option Module Parameters are Organized 45
, for information on using the
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 21
Chapter 2 Paramete r Organ ization
753
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In 2
Digital In 1
Digital In 0
Default0000000000000000
Bit 1514131211109876543210
0 = Condition False 1 = Condition True

About Parameters

To configure a drive module to operate in a specific way, certain drive parameters may have to be configured appropriately. Three types of parameters exist:
•Numeric Parameters
These parameters have a single numeric value (such as 1750.0 RPM).
•ENUM Parameters
These parameters allow a selection from 2 or more items. The LCD HIM will display a text message for each item.
•Indirect Parameters
These parameters, represented by a maximum value of 159999 or
159999.15, are used to create assignments or to select either a data source or destination. The first two digits are used to select a port. The next four digits select a parameter number. If applicable, the two digits following the decimal point select a bit. For example, to assign an I/O option module in port 4 using a run contact on digital input 0, parameter 163 [DI Run] is set to 040001.00.
•Bit Parameters
These parameters have individual bits associated with features or conditions. If the bit is 0, the feature is off or the condition is false. If the bit is 1, the feature is on or the condition is true.
The following table shows how each parameter type is presented in this manual.
Table 3 - Table Explan ation
➊➋
No. Display Name
Full Na me Description
28 Motor NP RPM
Motor Nameplate Revolutions Per Minute
Motor Data
MOTOR CONTROL
Vector Regulator
Digin Functions
FEEDBACK & I/O
Digital Inputs
Rated RPM shown on the motor nameplate.
107 Trq Adapt En
Tor que Ad apt io n En ab le Enables or disables the adaptive torque calculation. This selec tion is active only in motor
control mode flux vector induction (P35 [Motor Ctrl Mode] = 3 “Induction FV”).
164 DI Run Forward
Digital Input Run Forward Assigns a digital input used to run the drive (2 wire control) and command forward
direction.
220 Digital In Sts
Digital Input Status
Status of the digital inputs resident on the main control board (Port 0).
Values
Units: Default: Min/Max:
Default: Options:
Default: Min/Max:
RPM
1750.0
1.0 / 40000.0
1 = “Enabled” 0 = “Disabled” 1 = “Enabled”
0.00
0.00 / 159999.15
Read-Write
Data Type
RW Real
RW 32-bit
Integer
RW 32-bit
Integer
RO 16-bit
Integer
22 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Param eter Organizat ion Chapter 2
753
755
755 (8+)
No. Name
Description
File and Group organization
No. - Parameter Number
Parameter value cannot be changed until the drive is stopped.
Parameter cannot be set to DataLink In.
Name - Parameter name as it appears in the DriveExecutive software.
Description - Brief description of parameter function. The first line is the full text parameter name.
= Parameter or option is specific to PowerFlex 753 drives only. = Parameter or option is specific to PowerFlex 755 drives only. = Parameter or option is specific to PowerFlex 755 Frame 8 drives and larger only.
Value s - Define the various operating characteristics of the parameter. There are 3 types of Values.
ENUM Default: Lists the value assigned at the factory.
Options: Displays the selections available.
Bit Default: Lists the value assigned at the factory.
Options: Displays the selections available.
Numeric Default Lists the value assigned at the factory.
Min/Max. Displays lowest possible setting/Displays highest possible setting.
Indicates if parameter is read-write or read-only.
RW = Read-Write RO = Read Only
Indicates parameter data type (i.e. integer, floating point, boolean). 32-bit Integer
Read-Write Data Type
RW RO

Parameter Access Level

Three parameter access level options are selectable by P301 [Access Level].
Option 0 “Basic” is the most limited view that only displays commonly utilized parameters and options.
Option 1 “Advanced” is an expanded view that may be required to access more advanced drive features.
Option 2 “Expert” provides a comprehensive view of the drive’s entire parameter set.
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 23
Chapter 2 Paramete r Organ ization

How Drive Parameters are Organized

DriveExecutive programming software displays parameters in “Linear List” or “File Group Parameter” format. Viewing the parameters in “File Group Parameter” format simplifies programming by grouping parameters that are used for similar functions. There are eleven files. Each file is divided into multiple groups of parameters.
Drive (Port 0) parameter descriptions begin on page 51

Basic Parameter View (Port 0)

Parameter 301 [Access Level] set to option 0 “Basic.”
File Group Parameters
Monitor Metering O utput Frequency 1
Monitor
Drive Data Rated Volts 20 Rated Amps 21 Rated kW 22
Motor Control Motor Data Motor NP Volts 25
Motor Control
Mtr Ctrl Options Motor Ctrl Mode 35 Maximum Voltage 36
Volt s per Hert z VHz Curv e 65
Autotune Autot une 70 Autotun e Torque 71 IPM_Lg_25_pc t 1630
Feedback & I/O Digin Functions Digital In Cfg 150
Feedback and IO
Control Board IO
Digital Inputs
753
Digital Outputs
753
Motor PTC
Analog Inputs
753
Analog Outputs
Commanded SpdRef 2 Mtr Vel Fdbk 3 Commanded Trq 4
Motor NP Amps 26
DI Enable 155 DI Clear Fault 156 DI Aux Fault 157 DI Stop 158 DI Cur Lmt Stop 159 DI Coast Stop 160
755
Digital In Sts 220
Digital In Sts 220 Dig In Filt Mask 222 Dig In Filt 223
753
Dig Out Sts 225 Dig Out Invert 226
PTC Cfg 250 PTC Status 251
Anlg In Type 255 Anlg In0 Value 260 Anlg In0 Hi 261 Anlg In0 Lo 262
753
Anlg Out Type 270 Anlg Out0 Sel 275 Anlg Out0 Data 277
Tor que C ur F dbk 5 Flux Cur Fdbk 6 Output Current 7 Output Voltage 8
Motor NP Hertz 27 Motor NP RPM 28
Maximum Freq 37
DI Start 161 DI Fwd Reverse 162 DI Run 163 DI Run Forward 164 DI Run Reverse 165
RO0 Sel 230 RO0 Level Sel 231 RO0 Level 232 RO0 Level CmpSts 233
.
Output Power 9 DC Bus Volts 11
Mtr NP Pwr Units 29 Motor NP Power 30
PWM Frequency 38 IPM Stc OfsTst K
IPM_Lg_50_pct 1631 IPM_Lg_75_pct 1632 IPM_Lg_100_pct 1633 IPM_Lg_125_pct 1634
DI Jog 1 166 DI Jog 1 Forward 167 DI Jog 1 Reverse 168 DI Jog 2 169 DI Jog 2 Forward 170 DI Jog 2 Reverse 171
TO0 S el 240 TO0 Leve l Sel 241 TO0 Leve l 242 TO0 Level CmpSts 243
Anlg Out0 DataHi 278 Anlg Out0 DataLo 279
Motor Poles 31
(1) Frames 1…7 Only
IPM_Ld_0_pct 1635 IPM_Ld_100_pct 1636
DI Manual Ctrl 172 DI Speed Sel 0 173 DI Speed Sel 1 174 DI Speed Sel 2 175 DI HOA Start 176 DI Accel 2 179 DI Decel 2 180
Anlg Out0 Hi 280 Anlg Out0 Lo 281 Anlg Out0 Val 282
(1)
1660
24 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
File Group Parameters
Drive Cfg Preferences Speed Units 300 Access Level 301 Language 302
Drive Cong
Control Cfg Voltage Class 305
SpdTrqPsn Mode A 309 Duty Rating 306 Direction Mode 308
Auto Manual Ctrl Logic Mask 324
Auto Mask 325 Manual Cmd Mask 326
Alt Man Ref Sel 328
Alt Man Ref AnHi 329
Alt Man Ref AnLo 330
Manual Preload 331
Manual Ref Mask 327
Braking Features Stop Mode A 370
Stop Mode B 371 Bus Reg Mode A 372 Bus Reg Mode B 373
Protection Motor Overload Motor OL Actn 410
Protection
Mtr OL at Pwr Up 411
DB Resistor Type 382
DB Ext Ohms 383
DB Ext Watts 384
DB ExtPulseWatts 385
Mtr OL Factor 413
Mtr OL Hertz 414
Stop Dwell Time 392 Dec Inhibit Actn 409
Mtr OL Reset Lvl 415 MtrOL Reset Time 416
Mtr OL Alarm Lvl 412
Load Limits Current Lmt Sel 421
Current Limit 1 422
Shear Pin Cfg 434 Shear Pin 1 Actn 435 Shear Pin1 Level 436 Shear Pin 1 Time 437
Power Loss Power Loss Actn 449 Pwr Loss Mode A 450
Speed Control Speed Limits Max Fwd Speed 520
Speed Control
Max Rev Speed 521
Speed Ramp Rates Accel Time 1 535
Accel Time 2 536
Speed Reference Spd Ref A Sel 545
Spd Ref A Stpt 546 Spd Ref A AnlgHi 547 Spd Ref A AnlgLo 548
Torque Control Torque Reference Trq Ref A Sel 675
Torq ue Con tro l
Trq Ref A Stpt 676 Trq Ref A AnlgHi 677 Trq Ref A AnlgLo 678 Trq Ref A Mult 679
Min Fwd Speed 522
Min Rev Speed 523
Decel Time 1 537
Decel Time 2 538
Spd Ref B Sel 550
Spd Ref B Stpt 551
Spd Ref B AnlgHi 552
Spd Ref B AnlgLo 553
Trq Ref B Se l 68 0
Trq Ref B Stpt 681
Trq Ref B An lgH i 682
Trq Ref B An lgL o 68 3
Trq Ref B Mult 684
Jog Acc Dec Time 539
Jog Speed 1 556 Jog Speed 2 557 MOP Init Select 566 MOP Init Stpt 567
Selected Trq Ref 685
Param eter Organizat ion Chapter 2
Preset Speed 1 571 Preset Speed 2 572 Preset Speed 3 573 Preset Speed 4 574 Preset Speed 5 575 Preset Speed 6 576 Preset Speed 7 577
Communication Comm Control Port 1 Reference 871
Communication
DPI Datalinks Data In A1 895
Data In A2 896 Data In B1 897 Data In B2 898
Diagnostics Status Speed Ref Source 930
Diagnostics
Last StartSource 931 Last Stop Source 932 Start Inhibits 933 Last StrtInhibit 934
Fault/Alarm Info Minor Flt Cfg 950
Last Fault Code 951 Fault Status A 952 Fault Status B 953
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 25
Data In C1 899
Data In C2 900
Data In D1 901
Data In D2 902
Drive Status 1 935
Drive Status 2 936
Condition Sts 1 937
Data Out A1 905 Data Out A2 906 Data Out B1 907 Data Out B2 908
Data Out C1 909 Data Out C2 910 Data Out D1 911 Data Out D2 912
Chapter 2 Paramete r Organ ization

Advanced Parameter View (Port 0)

Parameter 301 [Access Level] set to option 1 “Advanced.”
File Group Parameters
Monitor Metering O utput Frequency 1
Monitor
Drive Data R ated Volts 20 Rated Amps 21 Rated kW 22
Motor Control Motor Data Motor NP Volts 25
Motor Control
Mtr Ctrl Options Motor Ctrl Mode 35 Maximum Voltage 36
Volts per Hertz Start Acc Boost 60
Autotune Au totune 70
Feedback & I/O Digin Functions Digital In Cfg 150
Feedback and IO
Control Board IO
Digital Inputs
753
Digital Outputs
753
Motor PTC
Analog Inputs
753
Analog Outputs
R0 Predict Main
Commanded SpdRef 2 Mtr Vel Fdbk 3 Commanded Trq 4
Motor NP Amps 26
Run Boost 61
Autotune Torque 71 IR Voltage Drop 73 Ixo Voltage Drop 74 Flux Current Ref 75
DI Enable 155 DI Clear Fault 156 DI Aux Fault 157 DI Stop 158 DI Cur Lmt Stop 159 DI Coast Stop 160 DI Start 161 DI Fwd Reverse 162 DI Run 163 DI Run Forward 164 DI Run Reverse 165
755
Digital In Sts 220
Digital In Sts 220 Dig In Filt Mask 222 Dig In Filt 223
753
Dig Out Sts 225 Dig Out Invert 226 Dig Out Setpoint 227
PTC Cfg 250 PTC Status 251
Anlg In Type 255 Anlg In Sqrt 256 Anlg In Loss Sts 257
753
Anlg Out Type 270 Anlg Out Abs 271
753
RO PredMaint Sts 285 RO0 Load Type 286
Torque Cur Fdbk 5
Flux Cur Fdbk 6
Output Current 7
Output Voltage 8
Output Power 9
Output Powr Fctr 10
Motor NP Hertz 27
Motor NP RPM 28
Maximum Freq 37
PWM Frequency 38
Break Voltage 62
Break Frequency 63
Total Inertia 76
Inertia Test Lmt 77
DI Jog 1 166
DI Jog 1 Forward 167
DI Jog 1 Reverse 168
DI Jog 2 169
DI Jog 2 Forward 170
DI Jog 2 Reverse 171
DI Manual Ctrl 172
DI Speed Sel 0 173
DI Speed Sel 1 174
DI Speed Sel 2 175
DI HOA Start 176
DI MOP Inc 177
DI MOP Dec 178
RO0 Sel 230
RO0 Level Sel 231
RO0 Level 232
RO0 Level CmpSts 233
RO0 On Time 234
RO0 Off Time 235
Anlg In0 Value 260
Anlg In0 Hi 261
Anlg In0 Lo 262
Anlg Out0 Sel 275
Anlg Out0 Stpt 276
RO0 Load Amps 287
RO0 TotalLife 288
DC Bus Volts 11 DC Bus Memory 12 Elapsed MWH 13 Elapsed kWH 14 Elapsed Run Time 15
Mtr NP Pwr Units 29 Motor NP Power 30
Mtr Options Cfg 40 Flux Up Enable 43 Flux Up Time 44
VHz Curve 65
IPM_Lg_25_pct 1630 IPM_Lg_50_pct 1631 IPM_Lg_75_pct 1632 IPM_Lg_100_pct 1633 IPM_Lg_125_pct 1634
DI Accel 2 179 DI Decel 2 180 DI SpTqPs Sel 0 181 DI SpTqPs Sel 1 182 DI Stop Mode B 185 DI BusReg Mode B 186 DI PwrLoss ModeB 187 DI Pwr Loss 188 DI Precharge 189 DI Prchrg Seal 190 DI PID Enable 191 DI PID Hold 192
TO0 Sel 240 TO0 Level Sel 241 TO0 Level 242 TO0 Level CmpSts 243 TO0 On Time 244 TO0 Off Time 245
Anlg In0 LssActn 263 Anlg In0 Raw Val 264
Anlg Out0 Data 277 Anlg Out0 DataHi 278 Anlg Out0 DataLo 279
RO0 ElapsedLife 289 RO0 RemainLife 290
Elpsd Mtr MWHrs 16 Elpsd Rgn MWHrs 17 Elpsd Mtr kWHrs 18 Elpsd Rgn kWHrs 19
Motor Poles 31
(1)
IPM Stc OfsTst K
1660
(1) Frames 1…7 Only
IPM_Ld_0_pct 1635 IPM_Ld_100_pct 1636
DI PID Reset 193 DI PID Invert 194 DI Torque StptA 195 DI Fwd End Limit 196 DI Fwd Dec Limit 197 DI Rev End Limit 198 DI Rev Dec Limit 199 DI PHdwr OvrTrvl 200 DI NHdwr OvrTrvl 201
Anlg In0 Filt Gn 265 Anlg In0 Filt BW 266
Anlg Out0 Hi 280 Anlg Out0 Lo 281 Anlg Out0 Val 282
RO0 LifeEvntLvl 291 RO0 LifeEvntActn 292
26 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
File Group Parameters
Drive Cfg Preferences Speed Units 300 Access Level 301 Language 302
Drive Cong
Control Cfg Voltage Class 305
Duty Rating 306 Direction Mode 308
SpdTrqPsn Mode A 309
SpdTrqPsn Mode B 310
SpdTrqPsn Mode C 311
Actv SpTqPs Mode 313 SLAT Err Stpt 314 SLAT Dwell Time 315
SpdTrqPsn Mode D 312
Auto Manual Ctrl Logic Mask 324
Auto Mask 325 Manual Cmd Mask 326
Alt Man Ref Sel 328
Alt Man Ref AnHi 329
Alt Man Ref AnLo 330
Manual Preload 331
Manual Ref Mask 327
Drive Memory Reset Meters 336
Start Features Start At PowerUp 345
PowerUp Delay 346 Auto Retry Fault 347 Auto Rstrt Tries 348 Auto Rstrt Delay 349
Sleep Wake Mode 350
SleepWake RefSel 351
Sleep Level 352
Sleep Time 353
Wake Level 354
FlyingStart Mode 356
Wake Time 355
Braking Features Stop Mode A 370
Stop Mode B 371 Bus Reg Mode A 372 Bus Reg Mode B 373 Bus Reg Lvl Cfg 374 Bus Reg Level 375
Protection Motor Overload Motor OL Actn 410
Protection
Mtr OL at Pwr Up 411
DB Resistor Type 382
DB Ext Ohms 383
DB Ext Watts 384
DB ExtPulseWatts 385
Flux Braking En 388
Flux Braking Lmt 389
Mtr OL Factor 413
Mtr OL Hertz 414
Stop Dwell Time 392 DC Brake Lvl Sel 393 DC Brake Level 394 DC Brake Time 395
Mtr OL Reset Lvl 415 MtrOL Reset Time 416
Mtr OL Alarm Lvl 412
Load Limits Drive OL Mode 420
Current Lmt Sel 421 Current Limit 1 422 Current Limit 2 423 Active Cur Lmt 424 Current Rate Lmt 425 Regen Power Lmt 426
Power Loss Power Loss Actn 449 Pwr Loss Mode A 450
Motor Power Lmt 427 Shear Pin Cfg 434
Shear Pin 1 Actn 435 Shear Pin1 Level 436 Shear Pin 1 Time 437 Shear Pin 2 Actn 438 Shear Pin2 Level 439 Shear Pin 2 Time 440
Pwr Loss Mode B 453 Pwr Loss A Level 451 Pwr Loss A Time 452
Pwr Loss B Leve l 454
Pwr Loss B Time 455
Ground Fault Ground Warn Actn 466
Ground Warn Lvl 467
Predictive Main PredMaint Sts 469
PredMaintAmbTemp 470 PredMaint Rst En 471 PredMaint Reset 472 CbFan Derate
755 (8+)
CbFan TotalLife CbFan ElpsdLife CbFan RemainLife CbFan EventLevel CbFan EventActn
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
481 482 483 484 485 486
HSFan Derate 488 HSFan TotalLife 489 HSFan ElpsdLife 490 HSFan RemainLife 491 HSFan EventLevel 492 HSFan EventActn 493 HSFan ResetLog
(1)
InFan Derate 495 InFan TotalLife 496 InFan ElpsdLife 497
MtrBrngTotalLife 502
MtrBrngElpsdLife 503
MtrBrngRemainLif 504
MtrBrngEventLvl 505
MtrBrngEventActn 506
MtrBrng ResetLog 507
494
MtrLubeElpsdHrs 508
MtrLubeEventLvl 509
MtrLubeEventActn 510
InFan RemainLife 498 InFan EventLevel 499 InFan EventActn 500 InFan ResetLog 501 (1) 755 Frames 1…7 only.
Param eter Organizat ion Chapter 2
Prchrg Control 321 Prchrg Delay 322 Prchrg Err Cfg 323
Brake Off Adj 1 402 Brake Off Adj 2 403 Dec Inhibit Actn 409
Mtr OL Counts 418 Mtr OL Trip Time 419
Load Loss Action 441 Load Loss Level 442 Load Loss Time 443 OutPhaseLossActn 444 Out PhaseLossLvl 445
UnderVltg Action 460 UnderVltg Level 461 InPhase LossActn 462 InPhase Loss Lvl 463 DC Bus Mem Reset 464
MchBrngTotalLife 511 MchBrngElpsdLife 512 MchBrngRemainLif 513 MchBrngEventLvl 514 MchBrngEventActn 515 MchBrngResetLog 516 MchLubeElpsdHrs 517 MchLube EventLvl 518 MchLubeEventActn 519
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 27
Chapter 2 Paramete r Organ ization
File Group Parameters
Speed Control Speed Limits Max Fwd Speed 520
Speed Control
Max Rev Speed 521
Speed Ramp Rates Accel Time 1 535
Accel Time 2 536
Speed Reference Spd Ref A Sel 545
Spd Ref A Stpt 546 Spd Ref A AnlgHi 547 Spd Ref A AnlgLo 548 Spd Ref A Mult 549 Spd Ref B Sel 550 Spd Ref B Stpt 551 Spd Ref B AnlgHi 552 Spd Ref B AnlgLo 553 Spd Ref B Mult 554
Sp eed Trim Tr im R ef A Sel 6 00
Trim Ref A Stpt 601 Trim RefA AnlgHi 602 Trim RefA AnlgLo 603
Slip/Droop Comp Droop RPM at FLA 620
Slip RPM at FLA 621 Slip Comp BW 622
Speed Regulator Spd Options Ctrl 635
Speed Reg BW 636 Filtered SpdFdbk 640 Speed Error 641
Speed Comp Speed Comp Sel 665
Speed Comp Gain 666 Speed Comp Out 667
Torque Control Torq ue Li mit s Pos Torqu e Lim it 670
Torq ue Con tro l
Neg Torque Limit 671
Torque Reference Trq Ref A Sel 675
Trq Ref A Stpt 676 Trq Ref A AnlgHi 677 Trq Ref A AnlgLo 678 Trq Ref A Mult 679
Inertia Comp
755
Inertia Adaption
Inertia CompMode 695 Inertia Acc Gain 696
755
InAdp LdObs Mode 704 Inertia Adapt BW 705 InertiaAdaptGain 706
Frictio n Comp
755
FrctnComp Mode 1560 FrctnComp Trig 1561
Min Fwd Speed 522 Min Rev Speed 523
Decel Time 1 537 Decel Time 2 538
Spd Ref Scale 555 Jog Speed 1 556 Jog Speed 2 557 MOP Reference 558 Save MOP Ref 559 MOP Rate 560 MOP High Limit 561 MOP Low Limit 562 MOP Init Select 566 MOP Init Stpt 567
Trim Ref B Sel 604 Trim Ref B Stpt 605 Trim RefB AnlgHi 606 Trim RefB AnlgLo 607
Speed Reg Kp 645 Speed Reg Max Kp 646 Speed Reg Ki 647
Trq Ref B Sel 680 Trq Ref B Stpt 681 Trq Ref B AnlgHi 682 Trq Ref B AnlgLo 683 Trq Ref B Mult 684
Inertia Dec Gain 697
Load Estimate 707 InertiaTrqAdd 708
FrctnComp Hyst 1562 FrctnComp Time 1563
Overspeed Limit 524
Zero Speed Limit 525
Skip Speed 1 526 Skip Speed 2 527 Skip Speed 3 528 Skip Speed Band 529
Jog Acc Dec Time 539 S Curve Accel 540
S Curve Decel 541
DI ManRef Sel 563
DI ManRef AnlgHi 564
DI ManRef AnlgLo 565
Preset Speed 1 571 Preset Speed 2 572 Preset Speed 3 573 Preset Speed 4 574 Preset Speed 5 575 Preset Speed 6 576 Preset Speed 7 577
TrmPct RefA Sel 608
TrmPct RefA Stpt 609
TrmPct RefA AnHi 610
TrmPct RefA AnLo 611
Spd Loop Damping 653
Spd Reg Int Out 654
TrmPct RefB Sel 612 TrmPct RefB Stpt 613 TrmPct RefB AnHi 614 TrmPct RefB AnLo 615
VHzSV Spd Reg Kp 663
VHzSV Spd Reg Ki 664 Spd Reg Pos Lmt 655 Spd Reg Neg Lmt 656 SReg Output 660
Selected Trq Ref 685 Torque Step 686
Filtered Trq Ref 689
Limited Trq Ref 690
Inert Comp LPFBW 698
Ext Ramped Ref 700 Inertia Comp Out 699
IA LdObs Delay 709
Load Observer BW 711 InertAdptFltrBW 710
FrctnComp Stick 1564 FrctnComp Slip 1565
FrctnComp Rated 1566
FrctnComp Out 1567
28 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
File Group Parameters
Posit ion Cont rol Position Cfg/Sts PTP PsnRefStatus 720
Position Control
Position Control 721
Position Homing Homing Status 730
Homing Control 731
755
Position Watch
PsnWatch1 Select 745 PsnWatch1 DtctIn 746 PsnWatch1 Stpt 747
Interpolator
755
Interp Control 755 Interp Psn Input 756
Direct Psn Ref Select 765 Psn Direct Stpt 766
Point to Point PTP Control 770
PTP Mode 771 DI Indx Step 772 DI Indx StepRev 773 DI Indx StepPrst 774
755
Phase Lock Loop
PLL Control 795 PLL Ext Spd Sel 796 PLL Ext Spd Stpt 797 PLL Ext SpdScale 798
Electronic Gear Psn Ref EGR Out 815 Psn EGR Mult 816
Position Offset Psn Offset 1 Sel 820
Psn Offset 1 821
Ld Psn Fdbk Scal
755
LdPsn Fdbk Mult 825 LdPsn Fdbk Div 826
Position Reg Psn Error 835
Communication Comm Control Port 1 Reference 871
Communication
Port 2 Reference 872 Port 3 Reference 873
Security Port Mask Act 885
Logic Mask Act 886
DPI Datalinks Data In A1 895
Data In A2 896 Data In B1 897 Data In B2 898
Owners Stop Owner 919
Start Owner 920
Psn Selected Ref 722 Psn Command 723
DI Find Home 732 DI Redefine Psn 733 DI OL Home Limit 734
PsnWatch2 Select 748 PsnWatch2 DtctIn 749 PsnWatch2 Stpt 750
Interp Vel Input 757 Interp Trq Input 758
Psn Direct Ref 767
PTP Ref Sel 775 PTP Reference 776 PTP Feedback 777 PTP Ref Scale 778 PTP Index Preset 779
PLL Psn Ref Sel 799 PLL Psn Stpt 800 PLL BW 801 PLL LPFilter BW 802 PLL Virt Enc RPM 803
Psn EGR Div 817
Psn Offset 2 Sel 822 Psn Offset 2 823
Psn Actual 836 Psn Load Actual
755
837 Psn Reg Ki 838 Psn Reg Kp 839
Port 4 Reference 874 Port 5 Reference 875 Port 6 Reference 876
Write Mask Act 887 Write Mask Cfg 888
Data In C1 899 Data In C2 900 Data In D1 901 Data In D2 902
Jog Owner 921 Dir Owner 922
Param eter Organizat ion Chapter 2
Psn Reg Status 724 Zero Position 725
Find Home Speed 735 Find Home Ramp 736
Interp Psn Out 759 Interp Vel Out 760 Interp Trq Out 761
PTP Setpoint 780 PTP Accel Time 781 PTP Decel Time 782 PTP Speed FwdRef 783 PTP Command 784
PLL EPR Input 804 PLL Rvls Input 805 PLL Psn Out Fltr 806 PLL Speed Out 807 PLL Speed OutAdv 808
Psn Offset Vel 824
PReg Pos Int Lmt 840 PReg Neg Int Lmt 841 PsnReg IntgrlOut 842 PsnReg Spd Out 843
Port13 Reference
755
877
Port14 Reference 878
Data Out A1 905 Data Out A2 906 Data Out B1 907 Data Out B2 908
Clear Flt Owner 923 Manual Owner 924
In Pos Psn Band 726 In Pos Psn Dwell 727
Actual Home Psn 737 User Home Psn 738
PTP Fwd Vel Lmt 785 PTP Rev Vel Lmt 786 PTP S Curve 787 PTP Vel Override 788 PTP EGR Mult 789 PTP EGR Div 790
PLL Enc Out 809 PLL Enc Out Adv 810 PLL EPR Output 811 PLL Rvls Output 812
PReg Pos Spd Lmt 844 PReg Neg Spd Lmt 845 Psn Reg Droop 846 Psn Fdbk 847 Psn Gear Ratio 848
Drive Logic Rslt 879 DPI Ref Rslt 880 DPI Ramp Rslt 881 DPI Logic Rslt 882 Drive Ref Rslt 883 Drive Ramp Rslt 884
Data Out C1 909 Data Out C2 910 Data Out D1 911 Data Out D2 912
Ref Select Owner 925
Rockwell Automation Publication 750-PM001J-EN-P - October 2014 29
Chapter 2 Paramete r Organ ization
File Group Parameters
Diagnostics Status Speed Ref Source 930
Diagnostics
Last StartSource 931 Last Stop Source 932 Start Inhibits 933 Last StrtInhibit 934
Fault/Alarm Info Minor Flt Cfg 950
Last Fault Code 951 Fault Status A 952 Fault Status B 953
755
Peak Detection
PkDtct Stpt Real 1035 PkDtct Stpt DInt 1036 PkDtct1 In Sel 1037
Applications Process PID PID Cfg 1065
Applications
PID Control 1066 PID Ref Sel 1067 PID Ref AnlgHi 1068 PID Ref AnlgLo 1069 PID Setpoint 1070 PID Ref Mult 1071
Tor que Pro ve
755
Trq Prove Cfg 1100 Trq Prove Setup 1101 DI FloatMicroPsn 1102 Trq Prove Status 1103
Fibers Function Fiber Control 1120
Fiber Status 1121 Sync Time 1122
Adjustable Vltg Adj Vltg Config 1131
Adj Vltg Selec t 1133 Adj Vltg Ref Hi 1134 Adj Vltg Ref Lo 1135
Pump Jack Rod Speed 1165
Rod Torque 1166 Rod Speed Cmd 1167
Pump Off Pump Off Config 1187
Pump Off Setup 1188 Pump Off Action 1189 Pump Off Control 1190 Pump Off Status 1191
Drive Status 1 935 Drive Status 2 936 Condition Sts 1 937 Drive OL Count 940
Status1 at Fault 954 Status2 at Fault 955 Fault Frequency 956 Fault Amps 957 Fault Bus Volts 958
PkDtct1PresetSel 1038 Peak1 Cfg 1039 Peak 1 Change 1040
PID Fdbk Sel 1072 PID Fdbk AnlgHi 1073 PID Fdbk AnlgLo 1074 PID FBLoss SpSel 1075 PID FBLoss TqSel 1076 PID Fdbk 1077 PID Fdbk Mult 1078
Trq Lmt SlewRate 1104 Speed Dev Band 1105 SpdBand Intgrtr 1106
Traverse Inc 1123 Traverse Dec 1124 Max Traverse 1125
Adj Vltg TrimSel 1136 Adj Vltg Trim Hi 1137 Adj Vltg Trim Lo 1138 Adj Vltg Command 1139 Adj Vltg AccTime 1140 Adj Vltg DecTime 1141
TorqAlarm Action 1168 TorqAlarm Config 1169 TorqAlarm Dwell 1170 TorqAlarm Level 1171 TorqAlm Timeout 1172 TorqAlarm TOActn 1173
Pump Cycle Store 1192 Set Top ofStroke 1193 Torque Setpoint 1194 Pump Off Level 1195 Pump Off Speed 1196 Pump Off Time 1197
IGBT Temp Pct 941 IGBT Temp C 942
At Limit Status 945
Safety Port Sts 946 Drive Temp Pct 943 Drive Temp C 944
Alarm Status A 959 Alarm Status B 960
AlarmA at Fault 962
AlarmB at Fault 963 Type 2 Alarms 961
PeakDetect1 Out 1041 PkDtct2 In Sel 1042 PkDtct2PresetSel 1043
PID Output Sel 1079 PID Output Mult 1080 PID Upper Limit 1081 PID Lower Limit 1082 PID Deadband 1083 PID LP Filter BW 1084 PID Preload 1085
Peak2 Cfg 1044
Peak 2 Change 1045
PeakDetect2 Out 1046
PID Prop Gain 1086
PID Int Time 1087
PID Deriv Time 1088
PID Status 1089
PID Ref Meter 1090
PID Fdbk Meter 1091
PID Error Meter 1092
PID Output Meter 1093
Brk Release Time 1107 Brk Set Time 1108 Brk Alarm Travel 1109 Brk Slip Count 1110
Float Tolerance 1111
MicroPsnScalePct 1112
ZeroSpdFloatTime 1113
755
Br ake Test To rq
1114
P Jump 1126 DI Fiber SyncEna 1129
DI Fiber TravDis 1130
Adj Vltg Preset1 1142 Adj Vltg Preset2 1143 Adj Vltg Preset3 1144 Adj Vltg Preset4 1145 Adj Vltg Preset5 1146 Adj Vltg Preset6 1147
Adj Vltg RefMult 1149
Adj Vltg Scurve 1150
Adj Vltg TrimPct 1151
Min Adj Voltage 1152
Dead Time Comp 1153
DC Offset Ctrl 1154 Adj Vltg Preset7 1148
Total Gear Ratio 1174 Max Rod Speed 1175 Max Rod Torque 1176 Min Rod Speed 1177 Motor Sheave 1178
PCP Pump Sheave 1180
Gearbox Limit 1181
Gearbox Rating 1182
Gearbox Ratio 1183
Gearbox Sheave 1184 OilWell Pump Cfg 1179
Pct Cycle Torque 1198 Pct Lift Torque 1199 Pct Drop Torque 1200 Stroke Pos Count 1201 Stroke Per Min 1202
Pump Off Count 1203
PumpOff SleepCnt 1204
Day Stroke Count 1205
DI PumpOff Disbl 1206
Pump OffSleepLvl 1207
30 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Loading...
+ 514 hidden pages