Rockwell Automation 193-ETN E1 User Manual

User Manual
Bulletin 193 E1 Plus EtherNet/IP Side Mount Module
Catalog Number
193-ETN
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Installation and Wiring
Protection Functions
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Network Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Trip Status / Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Trip Resetting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Trip and Warning Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Overload and Phase Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Overload Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Jam Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Jam Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Jam Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Underload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Underload Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Comm Fault Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Communication Idle Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Comm Idle Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Configure an E1 Plus EtherNet/ IP Module To Operate on the Network
Automation Controller and Software Communications
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Determining Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Setting the IP Network Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Assign Network Parameters via the BOOTP/DHCP Utility. . . . . . . . . 20
Assign Network Parameters Via a Web Browser and MAC Scanner
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Other Factors to Consider When Assigning Network Parameters . . . . 24
Duplicate IP Address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Behavior of Modules With Duplicate IP Addresses . . . . . . . . . . . . . . 25
DNS Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Download EDS File Embedded in the Module . . . . . . . . . . . . . . . . . . 26
Download EDS File from Allen-Bradley EDS File Download Site 27
Register the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ControlLogix Configuration with Add-On Profiles . . . . . . . . . . . . . 33
EtherNet/IP Network Configuration with Add-On Profiles . . . . . 35
Accessing Module Data with Add-On Profiles . . . . . . . . . . . . . . . . . . 37
ControlLogix Generic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 38
EtherNet/IP Network Generic Configuration . . . . . . . . . . . . . . . . . . 40
Downloading the Generic Configuration to the PLC . . . . . . . . . . . . 43
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 3
Accessing Generic Module Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Logix Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MicroLogix 1100 and 1400 Explicit Messaging . . . . . . . . . . . . . . . . . . . . . 48
FactoryTalk View with Predefined Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Email Notifications
Device Parameters and Tags
Troubleshooting
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Notification Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Email Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Email Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Configure Device Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Parameter and Tag Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Program Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Resetting to the Factory Default Values. . . . . . . . . . . . . . . . . . . . . . . . . 63
Parameter Group Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Monitor Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Advanced Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Reset/Lock Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
I/O Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Trip History Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
EtherNet/IP Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Power-Up Reset Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Recoverable Error Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Unrecoverable Error Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
EtherNet/IP Troubleshooting Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . 75
Input and Output Troubleshooting Procedures. . . . . . . . . . . . . . . . . . . . . 75
Specifications
EtherNet/IP Information
4 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Electronic Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
EtherNet/IP Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Identity Object — CLASS CODE 0x01. . . . . . . . . . . . . . . . . . . . . . . . 81
Message Router Object — CLASS CODE 0x02. . . . . . . . . . . . . . . . . 82
Assembly Object — CLASS CODE 0x04 . . . . . . . . . . . . . . . . . . . . . . 83
Connection Manager Object — CLASS CODE 0x06 . . . . . . . . . . . 85
Discrete Input Point Object — CLASS CODE 0x08 . . . . . . . . . . . . 85
Discrete Output Point Object — CLASS CODE 0x09 . . . . . . . . . . 86
Parameter Object — CLASS CODE 0x0F. . . . . . . . . . . . . . . . . . . . . . 87
Parameter Group Object — CLASS CODE 0x10 . . . . . . . . . . . . . . . 88
Control Supervisor Object — CLASS CODE 0x29 . . . . . . . . . . . . . 89
Overload Object — CLASS CODE 0x2C . . . . . . . . . . . . . . . . . . . . . . 91
PCP Object — CLASS CODE 0xC2 . . . . . . . . . . . . . . . . . . . . . . . . . . 91
TCP/IP Interface Object — CLASS CODE 0xF5 . . . . . . . . . . . . . . 92
Ethernet Link Object — CLASS CODE 0xF6 . . . . . . . . . . . . . . . . . . 93
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Installation Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
New Product Satisfaction Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 5
6 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Installation and Wiring

Chapter
1

Introduction

The purpose of this chapter is to provide the necessary instructions to successfully install an E1 Plus EtherNet/IP Module to an E1 Plus Overload Relay and properly connect to a EtherNet/IP network.
ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.
ATTENTION: The side mount module contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Rockwell Automation publication 8000-4.5.2, “Guarding Against Electrostatic Damage”, or any other applicable ESD protection handbook.
ATTENTION: The purpose of this document is to serve as a guide for proper installation. The National Electrical Code and any other governing regional or local code will take precedence. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the side mount module or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
ATTENTION: An incorrectly applied or installed side mount module can result in damage to the components or reduction in product life. Wiring or application errors such as supplying incorrect or inadequate supply voltage, or operating/storing in excessive ambient temperatures may result in malfunction of the product.
ATTENTION: Only personnel familiar with the side mount module and associated machinery should plan to install, set up, and maintain the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: This is a Class A product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take adequate measures.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 7
Chapter 1
Network Status LED
Output Status LED
Input Status LED
Power Connector
I/O Connector
Module Status LED
Link/Activity LED
Ethernet Connector
Module Status LED
Input Status LED
Output Status LED
Network Status LED
Link/Activity LED
ATTENTION: To remain compliant with UL/CSA Certifications, the
EtherNet/IP power supply must meet NEC Class 2 requirements.

Features

Figure 1 - Features

8 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 1
#2 Driver
0.7…1.1 N•m (6…10 lb.-in)
0.6 mm X 3.5 mm Blade (0.02 in X 0.14 in Blade
)
0.5…0.6 N•m (4.4…5.3 lb.-in)
7 mm
(0.28 in)

Installation

Figure 2 - Installation [1]

Figure 3 - Installation [2]

Figure 4 - Installation [3]

Rockwell Automation Publication 193-UM012B-EN-P - June 2011 9
Chapter 1
OUTA
(B300)
13
14
1
2
3
A1 (+)
SSV
IN2
IN1
GND
A2 (-)
(20.4…26.4V DC)

Wiring

Table 1 - Wire and Size Torque Specifications

Figure 5 - Wiring Diagram

1X 2X
1X 2X
1X 2X
24…12 AWG 24…16 AWG
5 lb.-in
0.2…2.5 mm
0.25…1 mm
0.56 N•m
0.2…2.5 mm
0.2…1 mm
0.56 N•m
2
2
2
2
10 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 1
A
F
G
B
D
E
K
L
H
C
J

Dimensions

Figure 6 - Dimension Diagram

Table 2 - Dimension Specifications

Contactor Cat. No.
100-C09, -C12,
-C16, -C23
100-C30, -C37
100-C43
100-C60, -C72,
-C85

Network Design

E1 Plus Cat. No.
193*-EE_B
193*EE_D
193*-EE_E
ABC D E FGHJKL
67,3 mm
(2.65 in)
67,3 mm
(2.65 in)
71.8 mm (2.83 in)
94,3 mm
(3.71 in)
148 mm (4.83 in)
148 mm (5.83 in)
148 mm (5.83 in)
191.6 mm (7.54 in)
85.2 mm (3.35 in)
101.2 mm (3.98 in)
101.2 mm (3.98 in)
120.4 mm (4.74 in)
The E1 Plus EtherNet/IP module has one RJ45 port to connect a CAT5 type or better Ethernet cable. Rockwell Automation offers a wide variety of
24.5 mm (0.96 in)
24.5 mm (0.96 in)
24.5 mm (0.96 in)
29 mm
(1.14 in)
13.9 mm (0.55 in)
13.9 mm (0.56 in)
18.4 mm (0.74 in)
23.8 mm (0.94 in)
35 mm
(1.38 in)
35 mm
(0.55 in)
45 mm
(1.77 in)
55 mm
(2.16 in)
60 mm
(2.36 in)
60 mm
(2.36 in)
60 mm
(2.36 in) 100 mm
(3.94 in)
86.5 mm (3.40 in)
104 mm (4.09 in)
104 mm (4.09 in)
126 mm (4.94 in)
2 mm
(0.08 in)
2 mm
(0.08 in)
2 mm
(0.08 in)
2 mm
(0.08 in)
4.5 mm
(0.17 in)
4.5 mm
(0.17 in)
4.5 mm
(0.17 in)
5.4 mm
(0.21 in)
22,3 mm
(0.88 in)
22,3 mm
(0.88 in)
22,3 mm
(0.88 in)
22,3 mm
(0.88 in)
Allen-Bradley Ethernet patch cables with its Bulletin 1585 line of Ethernet cables (http://www.ab.com/sensors/ethernet/incabinet.html).
The E1 Plus supports a Star Ethernet topology in which all Ethernet nodes wire back to a central Ethernet switch, hub, or router as shown below:
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 11
Chapter 1
Rockwell Automation offers a line of Allen-Bradley managed and unmanaged Ethernet Switches with its Stratix family of Ethernet Switches (http:// www.ab.com/networks/switches/).
12 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Protection Functions

IMPORTANT
Chapter
2

Introduction

Trip Status / Identification

Trip Resetting

The purpose of this chapter is to provide detailed information regarding the protective trip and warning functions that the E1 Plus EtherNet/IP Module adds to the E1 Plus Overload Relay. In this chapter, you will find considerable mention given to parameters as they relate to these functions. For complete descriptions of the programming parameters, refer to Chapter 6- Device Parameters and Tags.
The E1 Plus EtherNet/IP Module determines trip status and identification through monitoring of reference signals inside the E1 Plus Overload Relay. On power-up, it assumes that the E1 Plus Overload Relay is in a non-tripped condition. For definitive feedback on trip status of the E1 Plus Overload Relay, one of the E1 Plus EtherNet/IP module inputs may be wired to the N.O. auxiliary contact (terminals 97 and 98) of the E1 Plus Overload Relay. Parameters 40 and 41 are used to configure the assignment of the inputs. For this function, use the “OL Contact” configuration.
The following options are available for resetting a tripped E1 Plus Overload Relay with an E1 Plus EtherNet/IP module:
Blue mechanical reset button located on the front of the E1 Plus Overload Relay
Setting Parameter 14, Tri p Re set , to “Reset trip”
Setting the trip reset bit in an output assembly from a logic controller
Using a push button (N.O. contact configuration) wired to one of the
EtherNet/IP module inputs, programming the corresponding input assignment parameter (40 or 41) to “Trip Reset”
Setting the CIP Tag, Trip_Reset, to 1

Trip and Warning Enable

Setting parameter 16, Reset Mode, to “Automatic” does not result in other reset commands being ignored.
Parameter 12, Trip E na bl e, allows the installer to enable or disable the jam trip protective function.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 13
Chapter 2
IMPORTANT
IMPORTANT
Parameter 13, War n in g En a bl e , allows the installer to enable or disable the overload, jam, underload, and communication warning protective functions.
ATTENTION: The Trip Enable settings should not be altered during machine operation, as unexpected behavior could occur. This may result in an unintended actuation of controlled industrial equipment, with the potential for machine damage or serious injury to personnel.

Overload and Phase Loss Protection

Thermal overload and phase loss trip protection is provided exclusively by the E1 Plus Overload Relay. The E1 Plus Overload Relay provides uninterrupted protection to the motor, even in the event of an E1 Plus EtherNet/IP Module failure. Settings for FLA and trip class are found directly on the E1 Plus Overload Relay.
The reset mode DIP switch adjustment is overridden by the E1 Plus EtherNet/IP module parameter 16, OL Reset Mode, while the E1 Plus EtherNet/IP module is powered.

Overload Warning

The E1 Plus EtherNet/IP Module continuously monitors the E1 Plus Overload Relay's percentage of thermal utilization signal. Parameter 2,%Therm Utilized, provides this value.
Parameter 17, OL Warn Level, is used to adjust the setpoint to alert for an impending overload trip and is adjustable from 0…100% TCU.
The E1 Plus EtherNet/IP Module will indicate an overload warning if all the following conditions are met:
No warning currently exists
Overload warning is enabled
%Therm Utilized is equal to or greater than OL Warn Level
When the overload warning conditions are satisfied, the following will occur:
Bit 0 in Parameter 4, Wa r n in g S t at us , will go to “1”
Bit 1 of Parameter 10, Device Status, will go to “1”
%Therm Utilized will stabilize at a value of approximately 88% with the motor operating continuously at rated current.
14 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 2
IMPORTANT
IMPORTANT

Jam Protection

Motor current greater than the motor's nameplate rating can indicate a high overload or stall condition, such as an overloaded conveyor or jammed gear. These conditions can result in overheating of the motor, and equipment damage. Rapid jam fault detection helps to minimize damage and loss of production.
By continuously monitoring the motor current level signal as a percentage of the E1 Plus Overload Relay's dial FLA setting, the E1 Plus EtherNet/IP module allows jam trip and warning capability.

Jam Trip

The following parameters are available for configuring the E1 Plus EtherNet/IP Module's jam trip performance:
Parameter 18, Jam Inhibit Time, allows the installer to inhibit a jam trip from occurring during the motor starting sequence. It is adjustable from 0…250 seconds.
Parameter 19, Jam Trip Delay, allows the installer to define the time period a jam condition must be present before a trip occurs. It is adjustable from 5…250 seconds.
Parameter 20, Jam Trip Level, allows the installer to define the current at which the E1 Plus Overload Relay will trip on a jam. It is user-adjustable from 150…600% of the FLA dial setting.
The E1 Plus EtherNet/IP Module will command the E1 Plus Overload Relay to trip if all the following conditions are met:
No trip currently exists
Jam Protection is enabled
Jam Inhibit Time has expired
The motor current is greater than the Jam Trip Level for a time period
greater than the Jam Trip Delay
When the conditions for a jam trip are satisfied, the following will occur:
Bit 2 in Parameter 3, Trip Sta tus , will go to “1”
Bit 0 in Parameter 10, Device Status, will go to “1”
The E1 Plus Overload Relay's trip relay contacts (95 and 96) will open
Out A will be placed in their Protection Fault State (if so programmed)
The Protection Fault State of OUT A is defined by parameter 34 (OUTA Pr FltState) and parameter 35 (OUTA Pr FltValue).
The jam inhibit timer starts after the load current transitions from 0 A to 30% FLA. The E1 Plus EtherNet/IP Module does not begin monitoring for a jam condition until the Jam Inhibit Time expires.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 15
Chapter 2
IMPORTANT

Jam Warning

Parameter 21, Jam Warn Level, allows the installer to define the current at which the EtherNet Module will indicate a warning. It is user-adjustable from 100…600% FLA.
The E1 Plus EtherNet/IP Module will indicate a Jam warning if:
No warning currently exists
Jam Warning is enabled
Jam Inhibit Time has expired
The motor current is equal to or greater than the Jam Warn Level
When the Jam Warning conditions are satisfied, the following will occur:
Bit 2 in Parameter 4, Warning Status, will go to “1”
Bit 1 in Parameter 10, Device Status, will go to “1”
The Jam Warning function does not include a time delay feature. Once the Jam Inhibit Time has expired, the Jam Warning indication is instantaneous.

Underload Protection

Motor current less than a specific level may indicate a mechanical malfunction in the installation, such as a torn conveyor belt, damaged fan blade, broken shaft, or worn tool. Such conditions may not harm the motor, however, rapid detection may help to minimize equipment damage and loss of production.

Underload Warning

The following parameters are available for configuring the E1 Plus EtherNet/IP Module's underload warning performance:
Parameter 22, UL Inhibit Time, allows the installer to inhibit an underload indication from occurring during the motor starting sequence. It is adjustable from 0…250 seconds.
Parameter 23, UL Warn Level, allows the installer to define the current at which the E1 Plus EtherNet/IP Module will indicate a warning. It is user­adjustable from 30…100% of the FLA dial setting.
The E1 Plus EtherNet/IP Module will immediately indicate an Underload warning if:
No warning currently exists
Underload Warning is enabled
UL Inhibit Time has expired
The motor current is less than the UL Warn Level
16 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 2
IMPORTANT
IMPORTANT
When the Underload Warning conditions are satisfied, the following will occur:
Bit 3 in Parameter 4, War n in g S ta tu s , will go to “1”
Bit 1 of Parameter 10, Device Status, will go to “1”
The Underload Warning function does not include a time delay feature. Once the UL Inhibit Time has expired, the Underload warning indication is instantaneous.

Communication Fault Protection

A disruption of the communication link between the E1 Plus EtherNet/IP Module and a EtherNet/IP network can result in the loss of application control and/or critical process diagnostic data. Rapid communication fault detection helps minimize potential damage due to uncontrolled or unmonitored applications.

Comm Fault Warning

The E1 Plus EtherNet/IP Module will indicate a Comm Fault warning if:
No warning currently exists
Comm Fault Warning is enabled
The EtherNet/IP Module experiences a loss of communication
When the Comm Fault warning conditions are satisfied, the following will occur:
The Network Status LED will blink red or become solid red
Bit 5 in Parameter 4, War n in g S ta tu s , will go to “1”
Bit 1 of Parameter 10, Device Status, will go to “1”
The Comm Fault State of OUT A is defined by Parameter 36 (OUTA En FltState) and parameter 37 (OUTA En FltValue).

Communication Idle Protection

When a programmable controller is placed into the program mode, the execution of its ladder program is suspended, and any connected networks go to an idle state. If inadvertent, this can result in the loss of application control and/or critical process diagnostic data. Rapid communication idle detection helps minimize the potential damage due to uncontrolled or unmonitored applications.

Comm Idle Warning

The E1 Plus EtherNet/IP Module will indicate a Comm Idle warning if:
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 17
Chapter 2
IMPORTANT
No warning currently exists
Comm Idle Warning is enabled
The network controller that is communicating to the E1 Plus EtherNet/IP
Module is placed in idle mode
When the Comm Idle warning conditions are satisfied, the following will occur:
Bit 6 in Parameter 4, Wa r n in g S t at us , will go to “1”
Bit 1 in Parameter 10, Device Status, will go to “1”
The Comm Idle State of OUT A is defined by Parameter 38 (OUTA En IdlState) and parameter 39 (OUTA En IdlValue).
18 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter
3

Configure an E1 Plus EtherNet/IP Module To Operate on the Network

Introduction

Determining Network
This chapter describes how to configure an E1 Plus EtherNet/IP module to operate on an EtherNet/IP network.
When you first install an E1 Plus EtherNet/IP module, the module is Dynamic Host Configuration Protocol (DHCP) enabled.
To operate an EtherNet/IP network, you must define these parameters.
Parameters

Table 3 - EtherNet/IP Network Parameters

EtherNet/IP Network Parameter Description
IP address The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where
Subnet mask Subnet addressing is an extension of the IP address scheme that allows a site to use a single
Gateway A gateway connects individual physical networks into a system of networks. When a node needs to
each xxx is a number from 0...255. These are reserved values you cannot use:
0.0.0.1...0.255.255.255
127.0.0.0...127.255.255.255
224.255.255.255...255.255.255.255
network ID for multiple physical networks. Routing outside of the site continues by dividing the IP address into a net ID and a host ID via the class. Inside a site, the subnet mask is used to redivide the IP address into a custom network ID portion and host ID portion.
If you change the subnet mask of an already-configured module, you must cycle power to the module for the change to take effect.
communicate with a node on another network, a gateway transfers the data between the two networks.
If you use DNS addressing, or reference the module via a host name in an MSG instruction, then define these parameters.

Table 4 - EtherNet/IP Network Parameters for DNS Addressing

EtherNet/IP Network Parameter Description
Host name A host name is part of a text address that identifies the module. The full text address of a module is
Domain name A domain name is part of a text address that identifies the domain in which the module resides. The
Primary DNS server address This identifies any DNS servers used in the network. You must have a DNS server configured if you Secondary DNS server address
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 19
host_name.domain_name.
full text address of a module is host_name.domain_name. The domain name has a 48-character limit.
specify an SMTP server with a name. The DNS server converts the domain name or host name to an IP address that can be used by the network.
For more information on DNS addressing, see page 26.
Chapter 3
IMPORTANT
Check with your Ethernet network administrator to determine if you need to specify these parameters.

Setting the IP Network Address

Assign Network Parameters via the BOOTP/ DHCP Utility

E1 Plus EtherNet/IP modules ship with DHCP enabled. You can set the network Internet Protocol (IP) address by:
Using a Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol (DHCP) server, such as the Rockwell Automation BOOTP­DHCP Server Utility, which is included with Rockwell Software’s RSLinx™ Classic software
Using a web browser and MAC Scanner software
By default, the E1 Plus EtherNet/IP module is DHCP enabled. The BOOTP/ DHCP utility is a standalone program that is located in the:
BOOTP-DHCP Server folder accessed from the Start menu.
Before you start the BOOTP/DHCP utility, make sure you have the hardware MAC ID of the module, which is printed on the side of the E1 Plus EtherNet/IP module. The MAC ID has a format similar to: 00­0b-db-14-55-35.
This utility recognizes DHCP-enabled devices and provides an interface to configure a static IP address for each device.
To assign network parameters via the BOOTP/DHCP utility, perform this procedure.

1. Start the BOOTP/DHCP software.

2. Select Tool Network Settings.
3. If appropriate for the network, enter the subnet mask, gateway address,
primary/secondary server addresses, and domain name.

4. Click OK.

The Request History panel displays the hardware addresses of modules issuing BOOTP or DHCP requests.
20 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

5. Double-click the MAC address of the module to be configured.

The MAC address is printed on the side of the E1 Plus EtherNet/IP module. The format of the hardware address resembles 00-0b-db-14-55-35.
The New Entry window appears with the module’s Ethernet Address (MAC).
Chapter 3

6. Enter the IP address, host name, and a module description.

7. Click OK.

8. Re-cycle power to the module. To recycle power, remove and reapply the
control power terminals A1 and A2.

9. To permanently assign this configuration to the module, highlight the module in the Relation List panel and click the Disable BOOTP/DHCP button.

When module power is recycled, it uses the assigned configuration and does not issue a DHCP request.
If you do not select the Disable BOOTP/DHCP button, on a power cycle, the module clears the current IP configuration and will again begin sending DHCP requests.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 21
Chapter 3

Assign Network Parameters Via a Web Browser and MAC Scanner Software

In the event that a user does not have access to a DHCP software utility, a user can assign network parameters via a web browser, such as Microsoft’s Internet Explorer, and Media Access Control (MAC) scanner software, such as MAC Scanner from Colasoft - http://www.colasoft.com/ configure the module using this method.
. Follow these steps to

1. Locate and identify the MAC ID printed on the label of the E1 Plus EtherNet/IP Side Mount Module. This address has a format that is similar to: 00-0b-db-14-55-35

2. Connect the E1 Plus EtherNet/IP Side Mount Module to the same Wide Area Network (WAN) as your personal computer.

3. Start the MAC scanner software

4. Select the appropriate subnet to scan for available MAC addresses.

5. Scan the Subnet for all available MAC addresses.

6. Identify the IP address assigned to the MAC ID of the E1 Plus EtherNet/
IP Side Mount Module. The IP address will have a format that is similar to
192.168.0.100.
22 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 3

7. Open a web browser and type the IP address on the address line to view the internal web server of the E1 Plus EtherNet/IP Side Mount Module.

8. Select Administration Settings->Network Configuration to change the IP address of the E1 Plus EtherNet/IP Side Mount Module to a static IP address.

9. The module will prompt the user for a User Name and Password. Use “Administrator” for the user name, leave the password field blank, and select OK.

Rockwell Automation Publication 193-UM012B-EN-P - June 2011 23
Chapter 3

10. Assign the appropriate network settings per the recommendation of the network administrator for the network that this module will be communicating on and select Apply.

Other Factors to Consider When Assigning Network Parameters

11. Recycle the power on the E1 Plus EtherNet/IP module for the communications changes to take affect. To recycle power, remove and reapply the control power terminals A1 and A2.

There are other factors to consider when assigning networks parameters, which include:
Network isolation from or integration into the plant/enterprise network
Network size
For large networks, even isolated networks, it might be more convenient and safer to use a BOOTP/DHCP server rather than RSLinx software. The BOOTP/DHCP server also limits the possibility of assigning duplicate IP addresses.
Company policies and procedures dealing with plant floor network installation and maintenance
Level of involvement by IT personnel in plant floor network installation and maintenance
Type of training offered to control engineers and maintenance personnel
If you use the Rockwell Automation BOOTP or DHCP server in an uplinked subnet where an enterprise DHCP server exists, a module may get an address from the enterprise server before the Rockwell Automation utility even sees the
24 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 3
module. You might have to disconnect from the uplink to set the address and configure the module to retain its static address before reconnecting to the uplink. This is not a problem if you have node names configured in the module and leave DHCP enabled.
ATTENTION: The E1 Plus EtherNet/IP module must be assigned a fixed network address. The IP address of this module must not be dynamically provided.
Failure to observe this precaution may result in unintended machine motion or loss of process control.

Duplicate IP Address Detection

When you change the IP address or connect the module to an EtherNet/IP network, the module checks to make sure that the IP address assigned to this module does not match the address of any other network device. If the module determines that another device on the network with a matching IP address, the EtherNet/IP port of the module goes into conflict mode.
NETWORK STATUS LED indicator is solid red.
To resolve this conflict, use the instructions in this chapter to change the IP address of the module. Then cycle power to the module or reset the modules by disconnecting and then reconnecting the EtherNet cable.
Two modules could possibly detect a conflict simultaneously. If this occurs, perform this procedure.

1. Remove the module with the incorrect IP address and correct its conflict.

2. Cycle power or disconnect the EtherNet cable from the second module
and reconnect it.

Behavior of Modules With Duplicate IP Addresses

Devices in conflict over an IP address behave differently depending on whether connections have been established to either of the modules and whether both modules support duplicate IP address detection.
Table 5 - Device Conflict Over Duplicate IP Addresses
If Then
Both modules support duplicate IP address detection The first started module uses and retains its IP address.
The other module will detect a conflict, give up the IP address and enter conflict mode.
Both modules support duplicate IP address detection and are started at roughly the same time
One module supports duplicate IP address detection and a second module does not
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 25
One of them surrenders the IP address and enters conflict mode.
The second module generally keeps its IP address, regardless of which module first obtains the IP address.
The module that supports duplicate IP address detection will detect the conflict and give up the IP address.
Chapter 3

DNS Addressing

Install EDS File

To further qualify a module’s address, use DNS addressing to specify a host name for a module, which also includes specifying a domain name and DNS servers. DNS addressing makes it possible to set up similar network structures and IP address sequences under different domains.
DNS addressing is only necessary if you refer to the module by host name, such as in path descriptions in MSG instructions.
To use DNS addressing, perform this procedure.

1. Assign a host name to the module.

A network administrator should be able to assign a host name. Valid host names should be IEC-1131-3 compliant.

2. Configure the module's parameters.

3. In addition to the IP address, subnet mask, and gateway address, configure
a host name for the module, domain name, and primary/secondary DNS server addresses.
Before the E1 Plus EtherNet/IP Side Mount Module is configured to communicate on an EtherNet/IP network, it must be registered to the software that configures the network such as Rockwell Software’s RSLinx Classic and RSNetWorx for EtherNet/IP software. A user registers the module by installing an Electronic Data Sheet (EDS file). The EDS file for the E1 Plus EtherNet/IP Side Mount Module can be obtained from one of two locations:
Embedded in the module
Allen-Bradley EDS file download website

Download EDS File Embedded in the Module

The EDS file for the E1 Plus EtherNet/IP Side Mount Module is embedded within the module. After the IP address for the module has been configured, connect the module to same Ethernet network as a personal computer. Using a web browser on the personal computer, a user can download the EDS file using a web browser by following these steps:
26 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 3
1. Type the IP address of the E1 Plus EtherNet/IP Side Mount Module on
the address line of the web browser.
2. Right click on the EDS File link
3. Select Save to save the EDS file to the personal computer.

Download EDS File from Allen-Bradley EDS File Download Site

The EDS file for the E1 Plus EtherNet/IP Side Mount Module can also be downloaded from the Allen-Bradley EDS File download site. Using a web browser on the personal computer that is connected to the Internet, a user can download the EDS file by following these steps:
1. Type http://www.ab.com/networks/eds
on the address line of the web
browser.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 27
Chapter 3
2. Select the network type as EtherNet/IP and select Search.
3. Locate the EDS file for the E1 Plus EtherNet/IP Side Mount Module and
download it to the personal computer.

Register the EDS File

After the EDS file has been downloaded, a user will need to register the EDS file with the software that configures the EtherNet/IP network. The following example lists the steps needed to register an EDS file with Rockwell Software’s RSLinx Classic software.
1. Start the EDS Hardware Installation Tool, located at Start->Programs­>Rockwell Software->RSLinx Tools.
2. Select Add to register a new device.
28 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 3
3. Register a single file, browse to the location where the EDS file is located, and select Next.
4. Select Next to accept the installation test results.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 29
Chapter 3
5. Accept the Graphic Image by selecting Next.
6. Select Next to register the device.
30 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
7. Select Finish to successfully register the module.
Chapter 3
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 31
Chapter 3
32 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter

Automation Controller and Software Communications

4

Introduction

I/O Messaging

The E1 Plus EtherNet/IP Side Mount Module supports three types of EtherNet/ IP messaging:
I/O Messaging — Used for deterministic Ethernet communications with ControlLogix™, CompactLogix™, SoftLogix™, and EtherNet/IP scanners. Its primary use is to read and write I/O data for control purposes.
Explicit Messaging — Used for non-deterministic communications in which the data is not critical for control. Explicit messages have a lower priority compared to I/O messages, and they are used to read and write non-critical data. Logix controllers, MicroLogix 1100 and 1400 controllers support Explicit Messaging using a MSG instruction.
ControlLogix Style Tags — Used for non-deterministic communications in which the data will is used in an HMI, SCADA, or historical data logging software system. Software packages can read and write data directly from the device.
This chapter describes and shows examples of how each type of messaging is used.
RSLogix 5000™ software is used to configure I/O messaging between an automation controller and an E1 Plus EtherNet/IP Side Mount Module on an EtherNet/IP Network. This example will show the steps necessary to configure a ControlLogix controller for this type of messaging.
Note: If you are not using Add-on profiles, please turn to page 38
.

ControlLogix Configuration with Add-On Profiles

If you have RSLogix 5000 v. 20.0, the E1 Plus add-on profile (AOP) is included. Proceed with the following instructions. If you do have v. 19 or earlier, download the AOP before proceeding.
An existing project can be used or a new project can be created to configure EtherNet/IP I/O messaging. To create a new configuration in RSLogix 5000, select File New.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 33
Chapter 4
1. Select the controller type, chassis type, slot number, and project path. Enter a name for the controller and click OK.
2. Right-click on I/O Configuration and select New Module to open the Select Module Type window.
34 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
3. Select the desired EtherNet/IP scanner module and click OK.
4. Enter the desired communication settings and click Finish.
Chapter 4
EtherNet/IP Network Configuration with Add-On Profiles
After the controller configuration, the E1 Plus EtherNet/IP Side Mount Module has to be added to the I/O configuration.
1. Place the program in Offline mode.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 35
Chapter 4
2. Right-click on the Ethernet/IP scanner in I/O Configuration and select New Module to open the Select Module Type window.
3. Select E1 Plus Ethernet Module and click OK.
4. Enter a name for the E1 Plus EtherNet/IP Side Mount Module. The name
will create a tag in RSLogix 5000 that can be used to read and write data from the E1 Plus EtherNet/IP Side Mount Module.
36 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
5. Enter the IP address of the E1 Plus EtherNet/IP Side Mount Module.
6. Click Next.
7. The E1 Plus EtherNet/IP Side Mount Module is now shown as a module
in the I/O configuration.
Accessing Module Data with Add-On Profiles
With both the controller and EtherNet/IP network configured, the ControlLogix controller can exchange data with the E1 Plus EtherNet/IP Side Mount Module.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 37
Chapter 4
1. Open the Controller Tags window.
2. Select the Monitor Tags tab.
Three tags, "E1Plus:C", "E1Plus:I" and "E1Plus:O", have been added to represent the three I/O Instances: Configuration, input and output. The Configuration Instance was created even though its size was configured as zero. The E1Plus:I tag represents input data, which is data coming from the E1Plus into the controller (%FLA, %TCU, Trip Status, Warning Status, etc.). The E1 Plus:O tag represents output data, which is data going from the controller out to the E1 Plus (Enable Output A, Trip Reset, etc.).
ControlLogix Generic Configuration
An existing project can be used or a new project can be created to configure EtherNet/IP I/O messaging. To create a new configuration in RSLogix 5000, select File New.
38 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
1. Select the controller type, chassis type, slot number, and project path. Enter a name for the controller and click OK.
2. Right-click on I/O Configuration and select New Module to open the Select Module Type window.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 39
Chapter 4
3. Select the desired EtherNet/IP scanner module and click OK.
4. Enter the desired communication settings and click Finish.
EtherNet/IP Network Generic Configuration
After the controller configuration, the E1 Plus EtherNet/IP Side Mount Module has to be added to the I/O configuration.
1. Place the program in Offline mode.
40 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
2. Right-click on the Ethernet/IP scanner in I/O Configuration and select New Module to open the Select Module Type window.
3. Select Generic Ethernet Module and click OK.
4. Enter a name for the E1 Plus EtherNet/IP Side Mount Module. The name
will create a tag in RSLogix 5000 that can be used to read and write data from the E1 Plus EtherNet/IP Side Mount Module.
5. Select Data-SINT for the Comm Format. The Comm Format tells RSLogix 5000 the format of the data. The Data-SINT format will represent the data from the E1 Plus EtherNet/IP Side Mount Module as a field of 8-bit values.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 41
Chapter 4
6. Set the Connection Parameters. I/O data is accessed using Input Instances 50, 51, 106, 110 or 111 and Output Instances 2, 101 or 103. The size of the input connection and the output connection shall correspond to the size of the chosen instance. The E1 Plus configuration assembly instance is
120. In this example configuration data is not used, so the data size is set to
0.
7. Enter the IP address of the E1 Plus EtherNet/IP Side Mount Module.
8. Click Next.
9. Enter a value for the time between each scan of the module. Make sure
Inhibit Module is not checked.
10. Click Finish to add the E1 Plus to the I/O Configuration in RSLogix 5000.
42 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
Downloading the Generic Configuration to the PLC
1. In the RSLogix 5000 program, select Communications Who Active.
2. Select the desired communication path and click Set Project Path.
3. Select Communications Go Online.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 43
Chapter 4
4. In the Connected To Go Online window, click Download.
5. In the Download confirmation window, click Download to download the
configuration to the PLC.
If there are any errors, a warning triangle will be present on the E1 Plus in the I/O configuration listing. Double-click the module to view any error that is reported.
Accessing Generic Module Data
With both the controller and EtherNet/IP network configured, the ControlLogix controller can exchange data with the E1 Plus EtherNet/IP Side Mount Module.
1. Go online and switch the controller to Remote Run mode.
44 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
2. Open the Controller Tags window.
3. Select the Monitor Tags tab.
Chapter 4

Logix Explicit Messaging

Rockwell Automation Publication 193-UM012B-EN-P - June 2011 45
Three tags, "E1Plus:C", "E1Plus:I" and "E1Plus:O", have been added to represent the three I/O Instances: Configuration, input and output. The Configuration Instance was created even though its size was configured as zero. The E1Plus:I tag represents input data, which is data coming from the E1Plus into the controller (%FLA, %TCU, Trip Status, Warning Status, etc.). The E1 Plus:O tag represents output data, which is data going from the controller out to the E1 Plus (Enable Output A, Trip Reset, etc.).
CompactLogix, ControlLogix, and SoftLogix controllers can read and write specific information to and from the E1 Plus EtherNet/IP Side Mount Module using Explicit Messaging and the Parameter Object. An example of configuring a ControlLogix explicit message using the MSG instruction to read the Device Status parameter data from the E1 Plus EtherNet/IP Side Mount Module is shown below.
Chapter 4

1. Configure the configuration tab for the message instruction with the follow settings:

Message type: CIP Generic
Service type: Parameter Read
Instance: 10: The parameter you want to read back (e.g., 10 represents
device status)
Destination: The controller tag to write the data to.

2. Configure the path field in the communications tab to point to the E1 Plus EtherNet/IP Side Mount Module.

Path: 1, 2, 2, 192.168.0.100
For this example, 1 represents the processor slot, 2 represents the EtherNet/IP scanner slot, 2 represents the EtherNet/IP port, and
192.168.0.100 represents the IP address of the E1 Plus EtherNet/IP Side Mount Module.
46 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
Users can read all of the motor diagnostic data back in one MSG instruction by using Assembly Instance 111. An example of configuring a ControlLogix explicit message using the MSG instruction to read all of the motor diagnostic data from the E1 Plus EtherNet/IP Side Mount Module is shown below.

1. Configure the configuration tab for the message instruction with the follow settings:

Message type: CIP Generic
Service type: Get Attribute Single
Class: 4 – the Assembly Object
Instance: 111 - the Complete Motor Starter assembly
Destination: The controller tag to write the data to.
Attribute: 3 – get/set data instance attribute

2. Configure the path field in the communications tab to point to the E1 Plus EtherNet/IP Side Mount Module.

Path: 1, 2, 2, 192.168.0.100
For this example, 1 represents the processor slot, 2 represents the EtherNet/IP scanner slot, 2 represents the EtherNet/IP port, and
192.168.0.100 represents the IP address of the E1 Plus EtherNet/IP Side Mount Module.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 47
Chapter 4

MicroLogix 1100 and 1400 Explicit Messaging

MicroLogix 1100 and 1400 controllers can read and write information to and from the E1 Plus EtherNet/IP Side Mount Module using Explicit Messaging and the Assembly Object. RSLogix 500 Version 8.10 or higher is required to configure EtherNet/IP explicit messaging with these controllers.
An example of a MicroLogix 1100 using the MSG instruction to read all of the motor diagnostic data from the E1 Plus EtherNet/IP Side Mount Module is shown below.

1. Write the appropriate ladder logic to periodically execute a MSG instruction for the MicroLogix controller.

2. Configure General tab in the MSG instruction with the following parameters:

Channel: 1 (Integral) - the Ethernet port on the processor
Communication Command: CIP Generic
Data Table Address: the location to store the information
Size in Bytes: 22 – assembly 111 consists of 22 bytes of information
MultiHop: Yes
Service: Read Assembly – to read an input assembly
48 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Class: 4 – the Assembly Object
Instance: 111 – the Complete Motor Starter assembly
Attribute: 3 – get/set data instance attribute
Chapter 4

3. Configure MultiHop tab in the MSG instruction with the following parameters:

To Address: the IP address of the E1 Plus EtherNet/IP Side Mount Module.
An example of a MicroLogix 1100 using the MSG instruction to write data to energize an output relay on the E1 Plus EtherNet/IP Side Mount Module is shown below.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 49
Chapter 4

1. Write the appropriate ladder logic to execute a MSG instruction for the MicroLogix controller (an EEM instruction for the SLC-5/05) to control the E1 Plus EtherNet/IP Side Mount Module.

2. Configure General tab in the MSG instruction with the following parameters:

Channel: 1 (Integral) - the Ethernet port on the processor
Communication Command: CIP Generic
Data Table Address: the location to write the information from
Size in Bytes: 1 – assembly 101 consists of 1 byte of information
MultiHop: Yes
Service: Write Assembly – to write an output assembly
Class: 4 – the Assembly Object
Instance: 101 – the Basic Contact output assembly
Attribute: 3 – get/set data instance attribute
50 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4

3. Configure the MultiHop tab in the MSG instruction with the following parameters:

To Address: the IP address of the E1 Plus EtherNet/IP Side Mount Module.

FactoryTalk View with Predefined Tags

The E1 Plus EtherNet/IP Side Mount Module embedded predefined CIP tags within the module. This allows software packages, such as FactoryTalk View Supervisory Edition (SE), to read and write data directly from the E1 Plus EtherNet/IP Side Mount Module. An example of using RSLinx Classic as an OPC (OLE for Process Control) server to serve data to FactoryTalk View SE is show below. Follow these steps to read data directly from the E1 Plus EtherNet/ IP Side Mount Module using its predefined tags.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 51
Chapter 4

1. Configure an OPC topic within RSLinx Classic to communicate to the E1 Plus EtherNet/IP Side Mount Module. In the Data Source tab, select New to create a new OPC topic name, high light the device to establish communications with, and press Apply.

2. In the Data Collection tab, select the process type Logix5000 and select Apply

52 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4

3. Start FactoryTalk View Studio and create a new application. Draw a numeric display. Right click on the display and select Connections.

4. Select the Tag selector tool to select a tag from the E1 Plus EtherNet/IP Side Mount Module.

5. Right click on the project name and select Refresh All Folders to get an updated list of topics to read data from.

Rockwell Automation Publication 193-UM012B-EN-P - June 2011 53
Chapter 4
6. Expand the OPC topic name that you created in RSLinx Classic, select the
Online folder, choose the tag you would like to display in the numeric display, and press OK.

7. Select OK to select the tag to display in the numeric display.

54 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4

8. Test the display by pressing the Test Run button to view data directly from the E1 Plus EtherNet/IP Side Mount Module on the display.

Rockwell Automation Publication 193-UM012B-EN-P - June 2011 55
Chapter 4
56 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Email Notifications

IMPORTANT
Chapter
5

Introduction

Notification Events

This chapter describes email notifications and how to configure an E1 Plus EtherNet/IP module to send email notifications for different events.
There are several events that can trigger an email notification; the events are listed below.
Overload trip
Phase loss trip
Jam trip
Tri p c le ar
Overload warning
Jam warning
Underload warning
Communication fault warning
Communication idle warning
EEPROM fault warning
Warning clear
If an event has been disabled within the Control Supervisor Attribute 108 or 109 (see page 90 emails generated.
), it is not possible to override this and have

Email Contents

The subject and body contents in the email message will be created from the type of trip or warning that is detected, the Device Name, Device Description, Device Location and Contact Info. Sample email messages are shown here:
Email Subject
E1Plus module has detected a trip
Email Body
Trip status: Overload Device Name: E1 Plus EtherNet/IP Side Mount Module Device Description: Module under development Device Location: The Location Contact Info: Contact Person
contact.person@thecontact.com
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 57
Chapter 5
The first word in the subject is the Device Name. If a Device Name is not configured, then the product name attribute from the identity object will be used.

Email Configuration

To be able to send an email, the IP address or the hostname of a Simple Mail Transfer Protocol (SMTP) server must be configured and notifications must be selected. Follow these steps to configure an email notification.

1. In a web browser, enter the IP address of the E1 Plus EtherNet/IP module in the address bar and press Enter.

2. Select Administrative Settings email Configuration, and a login window will appear.

3. Log in with the username "Administrator" and no password. If desired, a password can be set within the Administrative Settings tab Password Configuration.

58 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 5
Email Recipient The email address of the person who will receive the notifications. Email Sender The email address from which the notification will be sent. SMTP Server The SMTP server address. Ask your network administration what address
to use.
SMTP Username The username for the SMTP server. Ask your network administration what
username to use.
SMTP Password The password for the SMTP server. Ask your network administration what
password to use.
SMTP Port The SMTP Server Port. Ask your network administration what port number
to use (Port 25 is a common SMTP port).

4. Enter the information into the email notification fields as described below.

5. Select the specific fault and warning notifications to send to the email
recipient. These can be changed after the initial configuration.

6. Click "Apply Changes" to save the configuration.

Configure Device Identity

The Device Identity properties populate the notification email subject and body. To configure the Device Identity, perform these steps:
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 59
Chapter 5
1. In a web browser, enter the IP address of the E1 Plus EtherNet/IP module in the address bar and press Enter.
2. Select Administrative Settings Device Identity and a login window will appear.
3. Log in with the username "Administrator" and no password. If desired, a password can be set within the Administrative Settings tab Password Configuration.
60 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 5
Device Name The name of the E1 Plus EtherNet/IP module. Device Description The description of the E1 Plus EtherNet/IP module. Device Location The location of the E1 Plus EtherNet/IP module. Contact Info Contact information for the E1 Plus EtherNet/IP module.
4. Enter the Device Identity information into the fields as described below.

Limitations

5. Click "Apply Changes" to save the configuration.
Based on the functionality of the E1 Plus EtherNet/IP module there are some limitations on when emails can be triggered.
If two events occur at the same time, an email will only be sent for the most significant event.
If the module has been configured to send an email for a lower prioritized event and this event occurs at the same time as a higher prioritized event for which the module has not been programmed to send an email, no email will be sent for either event.
The Clear email will only be sent when all events have been cleared and an event email has previously been sent. For example: if the module is configured to send an email when a jam trip is detected and it detects an overload trip for which no email notification is configured , no email will be sent when the overload event is cleared.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 61
Chapter 5
62 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Device Parameters and Tags

IMPORTANT
IMPORTANT
Chapter
6

Introduction

Parameter and Tag Programming

The E1 Plus EtherNet/IP Side Mount Module allows the Parameter Object to respond to explicit messages using the MSG instruction from Logix Controllers and SLC-500/MicroLogix controllers. The module also supports the Symbolic Object, which allows software packages such FactoryTalk View to communicate directly to the E1 Plus EtherNet/IP Side Mount Module as if it were a Logix Controller with predefined tags. This chapter describes each parameter and tag.
Refer to Chapter 3, Configure an E1 Plus EtherNet/IP Module To Operate on the Network, for instructions to modify EtherNet/IP parameter settings.
Parameter setting changes to the E1 Plus EtherNet/IP Module take effect immediately even during a “running” status.

Program Lock

Parameter 24, Program Lock, provides a degree of security from having parameter settings unintentionally altered when programmed to the “locked” setting.

Resetting to the Factory Default Values

Parameter 25, Set to Default, allows the installer to reset all parameter settings (including trip logs) to the factory default values.
Resetting to factory default values also resets the E1 Plus EtherNet/IP Module’s IP and DHCP settings.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 63
Chapter 6

Parameter Group Listing

The E1 Plus EtherNet/IP Module contains five parameter groups
Table 6 - Parameter Groups
Monitor parameters Advanced Setup Reset/Lock I/O Setup Trip History 1 Average %FLA 12 Trip Enable 14 Trip Reset 34 OutA Pr FltState 5 Trip Log 0 2%Therm Utilized 13 Warning Enable 24 Program Lock 35 OutA Pr FltValue 6 Trip Log 1 3 Trip Status 15 Single/Three Ph 25 Set to Default 36 OutA En FltState 7 Trip Log 2 4 Warning Status 16 OL Reset Mode 37 OutA En FltValue 8 Trip Log 3 10 Device Status 17 OL Warning Level 38 OutA En IdlState 9 Trip Log 4
18 Jam Inhibit Time 39 OutA En IdlValue 19 Jam Trip Delay 40 IN1 Assignment 20 Jam Trip Level 41 IN2 Assignment 21 Jam Warn Level 22 UL Inhibit Time 23 UL Warn Level

Monitor Group

Average %FLA Parameter No. 1
This parameter reports the average motor current. The value is reported as a percentage of motor rated current (dial setting on the E1 Plus Overload Relay), and is reported in increments of 5.
% Therm Utilized Parameter No. 2
This parameter reports the percent thermal utilization of the connected motor.
Access Rule Get Data Type UINT Units % Min. Value 0 Max. Value 1275 Default Value 0 Tag Name Average_%FLA
Access Rule Get Data Type USINT Units % Min. Value 0 Max. Value 100 Default Value None Tag Name %_Therm_Utilized
64 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Trip Status Parameter No. 3
This parameter provides trip identification. 1 = Trip
0 = No Trip
Bit 0: Overload — Tag Name: Trip_Status: Overload Bit 1: Phase Loss — Tag Name: Trip_Status: Phase_Loss Bit 2: Jam — Tag Name: Trip_Status: Jam
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000
Chapter 6
Warning Status Parameter
This parameter provides warning identification 1 = Warning
0 = No Warning
Bit 0: Overload — Tag Name: Warning_Status: Overload Bit 2: Jam — Tag Name: Warning_Status: Jam Bit 3: Underload — Tag Name: Warning_Status: Underload Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle Bit 7: Non Vol Mem Fault — Tag Name: NV_Mem_Fault
Device Status Parameter
This parameter provides status information related to the E1 Plus Overload Relay and the SMM.
1 = On or Present 0 = Off or Not Present
Bit 0: Trip — Tag Name: Device_Status: Trip Bit 1: Warning — Tag Name: Device_Status: Warning Bit 2: Output A — Tag Name: Device_Status: Out_A Bit 3: Input #1 — Tag Name: Device_Status: In_1 Bit 4: Input #2 — Tag Name: Device_Status: In_2 Bit 5: Motor Current — Tag Name: Device_Status: Motor_Current
No.
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x00FF Default Value 0x0000
No.
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x003F Default
Value

Advanced Setup Group

4
10
0x0000
Trip Enable Parameter No. 12
This parameter allows the installer to enable or disable the Jam Trip function
1 = Enabled 0 = Disabled
Bit 2: Jam— Tag Name: Trip_Enable: Jam
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 65
Access Rule Get/Set Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000
Chapter 6
Warning Enable Parameter
This parameter allows the installer to enable or disable the warning functions separately. All warning functions are disabled from the factory.
1 = Enabled 0 = Disabled
Bit 0: Overload — Tag Name: Warning_Status: Overload Bit 2: Jam — Tag Name: Warning_Status: Jam Bit 3: Underload — Tag Name: Warning_Status: Underload Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Single/Three Ph Parameter No. 15
This parameter configures the EtherNet/IP Module for single- or three-phase application. This parameter should be set to “Single Phase" when Bulletin 193S or 592S devices are employed.
0 = Single Phase 1 = Three Phase
OL Reset Mode Parameter No. 16
This parameter defines whether a trip can be automatically or manually reset. This setting overrides the E1 Plus DIP switch adjustment while the SMM is powered. Note, however, that the E1 Plus manual reset button, accessible at the front, is always active.
0 = Manual 1 = Automatic
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 1 Tag Name Single_Three_Ph
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OL_Reset_Mode
No.
Access Rule Get/Set Data Type WORD Units — Min. Value 0x0000 Max. Value 0x007F Default Value 0x0000
13
OL Warning Level Parameter No. 17
This parameter sets the overload warning level. Access Rule Get/Set
Data Type USINT Units % TCU Min. Value 0 Max. Value 100 Default Value 90 Tag Name OL_Warning_Level
66 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Jam Inhibit Time Parameter No. 18
This parameter defines the amount of time for which jam detection is inhibited during a motor starting sequence.
Jam Trip Delay Parameter No. 19
This parameter allows the installer to program a time duration for which a jam condition must exist at the programmed level prior to the device tripping.
Access Rule Get/Set Data Type USINT Units Seconds Min. Value 0 Max. Value 250 Default Value 10 Tag Name Jam_Inhibit_Time
Access Rule Get/Set Data Type USINT Units Seconds Min. Value 5 Max. Value 250 Default Value 50 Tag Name Jam_Trip_Delay
Chapter 6
Jam Trip Level Parameter No. 20
This parameter sets the jam trip level. Access Rule Get/Set
Data Type UINT Units % FLA Min. Value 150 Max. Value 600 Default Value 250 Tag Name Jam_Trip_Level
Jam Warn Level Parameter No. 21
This parameter sets the jam warning level. Access Rule Get/Set
Data Type UINT Units % FLA Min. Value 100 Max. Value 600 Default Value 150 Tag Name Jam_Warn_Level
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 67
Chapter 6
UL Inhibit Time Parameter No. 22
This parameter defines the amount of time for which underload detection is inhibited during a motor starting sequence.
UL Warn Level Parameter No. 23
This parameter sets the underload warning level. Access Rule Get/Set
Access Rule Get/Set Data Type USINT Units Seconds Min. Value 0 Max. Value 250 Default Value 10 Tag Name UL_Inhibit_Time
Data Type USINT Units % FLA Min. Value 30 Max. Value 100 Default Value 70 Tag Name UL_Warn_Level

Reset/Lock Group

Trip Reset Parameter No. 14
This parameter provides the user with the capability of resetting a trip over the EtherNet/IP network. After a trip is reset, the parameter automatically returns to a “Ready” state.
0 = Ready 1 = Reset Trip
Note: A transition from 0 to 1 is necessary to trigger a trip reset when mapped on the cyclic data.
Program Lock Parameter No. 24
This parameter prohibits the device parameters from being altered when set to “Locked”. It must be set to “Unlocked” to allow parameter modification.
It doesn’t affect parameters when they’re accessed through the assembly object.
0 = Unlocked 1 = Locked
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name Trip_Reset
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name Program_Lock
68 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Set To Defaults Parameter No. 25
This parameter allows the user to reset the parameter settings to the factory default values. After parameter values have been reset to the factory default settings, the parameter automatically returns to a “Ready” state.
0 = Ready 1 = Reset Defaults
Note: A transition from 0 to 1 is necessary to trigger a set to default when mapped on the cyclic data.
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name Set_To_Default

I/O Setup Group

OutA Pr FltState Parameter No. 34
This parameter, in conjunction with the Pr FltValue, defines how Output A will respond when a trip occurs. When set to “1”, Output A will continue to operate as commanded via the network. When set to “0”, Output A will open or close as determined by the setting of the Pr FltValue.
0 = Go to FltValue 1 = Ignore Fault
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_Pr_FLTState
Chapter 6
OutA Pr FltValue Parameter No. 35
This parameter determines the state that Output A assumes when a trip occurs and the Pr FltState is set to “0”.
0 = Open 1 = Closed
OutA En FltState Parameter No. 36
This parameter, in conjunction with the FltValue, defines how Output A will respond when a EtherNet/IP network fault occurs. When set to “1”, Output A will hold the state prior to trip occurrence. When set to “0”, Output A will open or close as determined by the setting of the FltValue.
0 = Go to FltValue 1 = Hold Last State
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_Pr_FLTValue
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_En_FLTState
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 69
Chapter 6
OutA En FltValue Parameter No. 37
This parameter determines the state that Output A assumes when a EtherNet/IP network fault occurs and the FltState is set to “0”.
0 = Open 1 = Closed
OutA En IdlState Parameter No. 38
This parameter, in conjunction with the IdlState, defines how Output A will respond when the EtherNet/IP network is idle (clear mode). When set to “1”, Output A will hold the state prior to trip occurrence. When set to “0”, Output A will open or close. The En Flt parameters supersede the En Idl parameters.
0 = Go to IdlValue 1 = Hold Last State
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_En_FLTValue
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_En_IdlState
OutA En IdlValue Parameter No. 39
This parameter determines the state that Output A assumes when the network is idle and instructed by the IdlState parameter.
0 = Open 1 = Closed
IN1 Assignment Parameter No. 40
This parameter allows the user to assign a specific function to the discrete IN1 input.
0 = Normal 1 = Trip Reset 2 = OL Contact
Access Rule Get/Set Data Type BOOL Units — Min. Value 0 Max. Value 1 Default Value 0 Tag Name OutA_En_IdlValue
Access Rule Get/Set Data Type USINT Units — Min. Value 0 Max. Value 2 Default Value 0 Tag Name IN1_Assignment
70 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
IN2 Assignment Parameter No. 41
This parameter allows the user to assign a specific function to the discrete IN2 input.
0 = Normal 1 = Trip Reset 2 = OL Contact
Access Rule Get/Set Data Type USINT Units — Min. Value 0 Max. Value 2 Default Value 0 Tag Name IN2_Assignment

Trip History Group

Trip Log 0 Parameter No. 5
This parameter records the latest trip. Access Rule Get
Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000 Tag Name Trip_Log_0
Chapter 6
Trip Log 1 Parameter No. 6
This parameter records the trip previous to Trip Log 0.
Trip Log 2 Parameter No. 7
This parameter records the trip previous to Trip Log 1.
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000 Tag Name Trip_Log_1
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000 Tag Name Trip_Log_2
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 71
Chapter 6
Trip Log 3 Parameter No. 8
This parameter records the trip previous to Trip Log 2.
Trip Log 4 Parameter No. 9
This parameter records the trip previous to Trip Log 3.
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000 Tag Name Trip_Log_3
Access Rule Get Data Type WORD Units — Min. Value 0x0000 Max. Value 0x0007 Default Value 0x0000 Tag Name Trip_Log_4
72 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Troubleshooting

Chapter
7

Introduction

The purpose of this chapter is to assist in troubleshooting the E1 Plus EtherNet/ IP module.
ATTENTION: Servicing energized industrial control equipment can be hazardous. Electrical shock, burns, or unintentional actuation of controlled industrial equipment may cause death or serious injury. For safety of maintenance personnel, as well as other who may be exposed to electrical hazards associated with the maintenance activities, follow the local safety-related work practices (for example, the NFPS 70W, Part II, Electrical Safety for Employee Workplaces, in the United States) when working on or near energized equipment. maintenance personnel must be trained in the safety practices, procedures, and requirements that pertain to their respective job assignments. Do not work alone on energized equipment.
ATTENTION: Do not attempt to defeat or override fault circuits. The cause of a fault indication must be determined and corrected before attempting operation. Failure to correct a control system or mechanical malfunction may result in personal injury and/or equipment damage due to uncontrolled machine system operation.

EtherNet/IP Modes of Operation

The E1 Plus EtherNet/IP Module has four EtherNet/IP modes of operation: Power-Up Reset Mode, Run Mode, Recoverable Error Mode, and Unrecoverable Error Mode.

Power-Up Reset Mode

During Power-Up Reset Mode, the following occurs:
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 73
Chapter 7
IMPORTANT
1. The MODULE STATUS LED should flash green for approximately 1/4 second, then red for 1/4 second. The MODULE STATUS LED will then stay lit green and the NETWORK STATUS LED should flash green for approximately 1/4 second, then red for 1/4 second before turning off. The NETWORK STATUS LED and the MODULE STATUS LED will now return to their standard indication.
The E1 Plus EtherNet/IP Module protection functions are still operational even without an established network connection.
2. The E1 Plus EtherNet/IP Module performs a duplicate IP address check to verify another module is not assigned to the same IP address. If a duplicate IP address is detected on the network, the NETWORK STATUS LED turns solid red, the MODULE STATUS LED turns flashing red, and the E1 Plus EtherNet/IP Module enters the Recoverable Error Mode.
If the power-up or reset is successful, the overload relay will enter Run Mode.

Run Mode

In Run Mode, the E1 Plus EtherNet/IP Module will operate as a slave device to a master device. The NETWORK STATUS LED will blink green if there are no network connections established with a network master. When one or more connections are in the “established” state, the NETWORK STATUS LED will turn solid green. When one or more connections are in the “timed-out” state, the NETWORK STATUS LED will blink red. In the Run Mode, the E1 Plus EtherNet/IP Module will:
Accept messages from a master on the EtherNet/IP network.
Send response messages, COS messages, or CYCLIC messages to a master.
If a communication error is detected, the E1 Plus EtherNet/IP Module will either enter the Recoverable Error or Unrecoverable Error Mode.

Recoverable Error Mode

In Recoverable Error Mode, the E1 Plus EtherNet/IP Module’s MODULE STATUS LED turns flashing red. The overload relays will respond to messages
that are specified in offline node recovery message protocol.
Error Type Description LED State
Recoverable Duplicate IP address detected Flashing Red
74 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 7

Unrecoverable Error Mode

In Unrecoverable Error Mode, the E1 Plus EtherNet/IP Module’s MODULE STATUS LED turns solid red. The overload relay continues in this state as long as
the device is powered.
Error Type Description LED State
Unrecoverable Power-up initialization failure Solid Red
Fatal communication error
EtherNet/IP Troubleshooting
The following table identifies possible causes and corrective actions when troubleshooting EtherNet/IP-related failures using the NETWORK STATUS LED.
Procedures

Table 7 - EtherNet/IP Troubleshooting Procedures

Color State Possible Cause Corrective Action
None The E1 Plus EtherNet/IP Module is not receiving power
Green Red Off
Green Flashing E1 Plus EtherNet/IP Module is online but with no
Green Solid Normal operating state, and the E1 Plus EtherNet/IP
Red Flashing One or more connections timed-out. Reset EtherNet/IP master device. Red Solid 1. Diagnostics test failed on power-up/reset. Internal
Flashing (once) Normal The Network Status LED flashes green, red, and off once
at the EtherNet/IP connector.
connections established.
Module is allocated to a master.
fault exists.
2. Duplicate EtherNet/IP module address exists (two EtherNet/IP modules cannot have the same address).
3. A fatal communication error occurred.
Check EtherNet/IP power and cable connections and the power connection on the EtherNet/IP connector.
during a normal power-up sequence.
Check EtherNet/IP master and its scan list for correct scanner configuration.
No action required.
1. Cycle power to the unit and network. If the fault still exists, replace unit.
2. Change the IP address to a valid setting and reset the device.
3. Check EtherNet/IP media for proper installation.

Input and Output Troubleshooting Procedures

ATTENTION: If the outputs are to be commanded via an explicit
message, ensure that there can never be an established I/O connection that can actively control them, and that the explicit message connection has a non-zero expected packet rate (EPR) setting.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 75
Chapter 7

Table 8 - Input and Output Troubleshooting Procedures

Failure Type Failure Description Corrective Action
Input 1, 2 Input 1 or 2 does not appear
to recognize a contact closure
1. Check the supply voltage on the power connector.
2. If the applicable contact closed but the E1 Plus EtherNet/IP Module Input does not recognize the closure, check the continuity and wiring to the connected contact.
3. Check the IN 1 and 2 status LEDs. If the appropriate LED does not illuminate, measure the voltage across and current through the applicable input. Verify they are within the ratings of the E1 Plus
EtherNet/IP Module (See Appendix A).
4. If the appropriate Input LED does illuminate, but the input status is not reported properly over the EtherNet/IP network, check the programmable controller ladder logic and I/O mapping.
Input 1, 2 Trip reset operation Check the programming of Parameter 40, IN1 Assignment or Parameter 41, IN2 Assignment. OUT A Output A does not appear to
turn on (close) when commanded to do so.
OUT A Output A does not appear to
turn off (open) when commanded to do so.
OUT A The contactor connected to
Output A appears to “chatter”
1. Check the supply voltage on the
2. Check the OUTA status LED. If the appropriate LED does not illuminate, check the programmable controller ladder logic and I/O mapping.
3. If the appropriate Output LED is illuminated, remove the control circuit power and check for continuity across the appropriate output terminals (13/14). If the continuity test indicates the output is open, replace the E1 Plus EtherNet/IP Module. Check the supply voltage against the ratings of the contactor and the relay output before installing a new unit.
4. Remove control circuit power and check the control circuit fuse and the control wiring to the E1 Plus EtherNet/IP Module output terminals.
5. Check the control circuit power supply. Verify the voltage is within the contactor and overload relay ratings.
6. Check the DEVICE STATUS and TRIP STATUS parameters. If a Protection Fault exists, refer to the TRIP STATUS parameters. If a EtherNet/IP-related fault exists, refer to the EtherNet/IP troubleshooting procedure.
7. Check the OUTA Pr FltState, Pr FltValue, En FltState, En FltValue, En IdlState, and En IdlValue programmable parameters. The Pr FltState and Pr FltValue parameter supersede the En Flt or En Idle parameters.
1. Check the OUTA status LED. If the appropriate LED remains illuminated, check the programmable controller ladder logic and I/O mapping.
2. If the appropriate Output LED is not illuminated, remove the control circuit power and check for continuity across the appropriate output terminals (13/14). If the continuity test indicates the output is closed, replace the E1 Plus EtherNet/IP Module. Check the supply voltage against ratings of the contactor and the relay output before installing a new unit.
3. Remove control circuit power and check the control circuit fuse and the control wiring to the E1 Plus EtherNet/IP Module output terminals.
4. Check the OUTA Pr FltState, Pr FltValue, En FltState, En FltValue, En IdlState, and En IdlValue programmable parameters. Then check the DEVICE STATUS and TRIP STATUS parameters. If a Protection Fault exists, refer to the TRIP STATUS parameters. If a exists, refer to the EtherNet troubleshooting procedure.
1. Verify the OUT A LED remains in the appropriate On or Off state. If the LED is flickering, check the programmable controller’s ladder logic program.
2. Check the control circuit supply voltage. Verify it is within the ratings of the contactor coil and the overload relay’s outputs.
3. Remove the control circuit power. Verify all control wiring is properly secured.
power connector.
EtherNet/IP-related fault
76 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Specifications

Appendix

Specifications

Terminal Ratings:
Terminal Screw M3 Wire Cross Section See wiring diagram section Torque 0.56…0.79 N•m (5…7 lb.-in) Degree of Protection IP20
Power Supply Ratings:
Rated Supply Voltage U Rated Operating Range U Rated Supply Current I Maximum Surge Current at Power-Up 2.5 A Maximum Power Consumption 2.7 W
Output Relay Ratings:
Te rm in al s OUT A: 13/14
Type of Contacts Form A
Rated Thermal Current I Rated Insulation Voltage U Rated Operating Voltage U Rated Operating Current I
Minimum Operating Current 10 mA at 5V DC Rating Designation B300 Utilization Category AC-15 Resistive Load Rating
(p.f.=1.0) Inductive Load Rating
(p.f.=0.4), (L/R=7 ms) Short Circuit Current Rating 1,000 A Recommended Control Circuit Fuse KTK-R-6
Rated Number of Operations Out A: W/100-C-09…100-C43 W/100-C-60…100-C85 W/NEMA Size 0…2 W/NEMA Size 3
Input Ratings:
s
e
e
the
i
e
e
24V DC 24V -15%, +10% DC 110 mA at 24V DC
SPST - NO 5 A 300V AC 240V AC 3 A (at 120V AC), 1.5 A (at 240V AC)
0.25 A (at 110V DC), 0.1 A (at 220V DC)
5 A, 250V DC 5 A, 30V DC
2 A, 250V AC 2 A, 30V DC
(6 A, 600V)
5,000,000 2,500,000 1,000,000 300,000
A
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 77
Appendix A
Te rm in al s IN 1: IN 2: SSV (Sensor Supply Voltage)
1 2
3 Supply Voltage (provided by module) 24V DC±10% Type of Inputs Current Sinking ON-State Voltage 15V DC On-State Current (turn-on) 2 mA Steady State Current 5 mA Off-State Voltage 5V DC Off-State Current 0.5 mA Transition Voltage 5…15V DC Transition Current 0.5…2.0 mA
Environmental Ratings:
Ambient Temperature T Storage
amb
-40…+85°C (-40…+185°F) Operating (Open) (Enclosed)
-20…+60°C (-4…+140°F)
-20…+40°C (-4…+104°F) Humidity
Operating Damp Heat - Steady State Damp Heat - Cyclic
5…95% non-condensing per IEC 68-2-3
per IEC 68-2-30 Cooling Method Natural Convection Vibration (per IEC 68-2-6) 3 G Shock (per IEC 68-2-27) 30 G Maximum Altitude 2000 m Pollution Environment Pollution Degree 2 Terminal Marking EN 50012 Degree of Protection IP20
Electromagnetic Compatibility
Electrostatic Discharge Immunity Test Level Performance Criteria
8 kV Air Discharge; 4 kV Contact Discharge
1➊➋ RF Immunity
Test Level Performance Criteria
10V/m
1➊➋ Electrical Fast Transient/Burst Immunity
Test Level Performance Criteria
2 kV (Power); 1 kV (control)
1➊➋ Surge Immunity
Test Level Performance Criteria
2 kV L-E; 1 kV L-L
1➊➋ Radiated Emissions Class A Conducted Emissions Not tested
Performance Criteria 1 requires the DUT (device under test) not to experience degradation or loss of
performance.
Environment 2 - Heavy Industrial.
78 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix A
WARNING: This is a class A product. In domestic environment, this product may cause radio interference, in which case the user may be required to take adequate measures.
EtherNet/IP Communications:
Connections TCP CIP
CIP Unconnected Messages 128 Packet Rates (packets/second)
I/O HIM/MSG
Media Support Twisted Pair Fiber
Speed Duplex (Half/Full) 10/100 Duplicate IP Detection Yes
Jam Protection:
Trip Level 150…600% FLA Trip Delay 0.1…25.0 sec. Inhibit 0…250 sec.
Standards and Certifications
UL 508 CSA 22.2, No. 14 EN 60947-4-1
150 48
500 500
Yes No
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 79
Appendix A
80 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

EtherNet/IP Information

Appendix
B

Electronic Data Sheets

EtherNet/IP Objects

Electronic Data Sheet (EDS) files are specially formatted ASCII files that provide all of the information necessary for a configuration tool (e.g., RSNetWorx for EtherNet/IP) to access and alter the parameters of a device. The EDS file contains all the parameter information of a device: number of parameters, groupings, parameter name, min., max, and default values, units, data format and scaling. The EDS file for the E1 Plus EtherNet/IP Module is available from the Internet at www.ab.com/networks/eds/index/html automatically by some configuration tools since all of the information necessary for an EDS file may be extracted from the E1 Plus EtherNet/IP Module.
The following object classes are supported.

Table 9 - EtherNet object Classes

Class Object
0x01 Identity 0x02 Message Router 0x04 Assembly 0x06 Connection Manager 0x08 Discrete Input Point 0x09 Discrete Output Point 0x0F Parameter 0x10 Parameter Group 0x29 Control Supervisor 0x2C Overload 0xC2 PCP 0xF5 TCP/IP Interface 0xF6 Ethernet Link
. It can also be built

Identity Object — CLASS CODE 0x01

The following class attributes are supported for the Identity Object:
Table 10 - Identity Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 81
Appendix B
Identity Object instances contain the following instance attributes:
Table 11 - Identity Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Vendor ID UINT Programmable via test object 2 Get Device Type UINT 0x0003 3 Get Product Code UINT 300 4 Get Revision Structure of:
Major Revision USINT 1 Minor Revision USINT N/A
5 Get Status WORD Bit 0: Owned, shall be set when at least one connection i
6 Get Serial Number UDINT Unique number assigned for each device 7 Get Product Name SHORT_STRING Product name 8 Get State USINT 3=Operational
configured Bit 1: Reserved, set to 0 Bit 2: Configured Bit 3: Reserved, set to 0 Bit 4-7: See extended device status Bit 8: Minor Recoverable fault BIt 9: Minor Unrecoverable fault Bit 10: Major Recoverable fault Bit 11: Major Unrecoverable fault Bit 12-15: Reserved, set to 0
Extended device status (Bit 4-7) 0000=Unknown 0001=Firmware updated in progress 0010=Faulted I/O connection 0011=No I/O connection established 0100=Non volatile configuration bad 0101=Major fault 0110=Connection in run mode 0111=Connection in idle mode
The following common services are implemented for the Identity Object:
Table 12 - Identity Object Common Services
Service Code Implemented for: Service Name
Class Instance
0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x05 No Yes Reset

Message Router Object — CLASS CODE 0x02

No class or instance attributes are supported. The message router object exists only to rout explicit messages to other objects.
82 Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Assembly Object — CLASS CODE 0x04

The following class attributes are supported for the Assembly Object:
Table 13 - Assembly Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0002 2 Get Max Instance UINT 120
Instance Attributes
Instances/Connection points implements the following data attributes:
Table 14 - Instance Attributes
# Access Name Type Value Description
1 Get Number of members in
list 2 Get Member list Array of N/A Array of CIP paths 3 Get/Set Data Array of UINT Data produced/consumed by the module 4 Get Size UINT N/A No. of USINTs in attribute #3 100 Get Name SHORT_STRING N/A Name of the assembly instance
UINT N/A No. of members to follow in the list in attribute #2
Appendix B
Output Assemblies
The following output assembly instances are implemented:
Table 15 - Instance 2 — Basic Overload Output Assembly from ODVA Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Trip Reset
Table 16 - Instance 101 — Similar to Basic Contact Output Assembly from ODVA Contact Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Output A
Table 17 - Instance 103 — Similar to Basic Starter Output Assembly from ODVA Starter Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Trip Reset Output A
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 83
Appendix B
Input Assemblies
Table 18 - Instance 50 — Trip Status Input Assembly from ODVA Overload Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Tripped
Table 19 - Instance 51 —Basic Status Input Assembly from ODVA Overload Profile
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Warning Tripped
Table 20 - Instance 106 —Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current
Table 21 - Instance 110 —Extended Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current 1Unused 2 Average % FLA (low byte) 3 Average % FLA (high byte) 4 %Therm Utilized (low byte) 5 %Therm Utilized (high byte)
Table 22 - Instance 111 —Complete Motor Starter Input Assembly
Input 2 Input 1 Out A Stat Warning Tripped
Input 2 Input 1 Out A Stat Warning Tripped
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Motor
Current 1Unused 2 Average % FLA (low byte) 3 Average % FLA (high byte) 4 %Therm Utilized (low byte) 5 %Therm Utilized (high byte) 6 Trip Status (low byte) 7 Trip Status (high byte) 8 Warning Status (low byte) 9 Warning Status (high byte) 10 Device Status (low byte) 11 Device Status (high byte) 12 Trip Log 0 (low byte) 13 Trip Log 0 (high byte) 14 Trip Log 1 (low byte) 15 Trip Log 1 (high byte)
Input 2 Input 1 Out A Stat Warning Tripped
84 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
Table 22 - Instance 111 —Complete Motor Starter Input Assembly
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
16 Trip Log 2 (low byte) 17 Trip Log 2 (high byte) 18 Trip Log 3 (low byte) 19 Trip Log 3 (high byte) 20 Trip Log 4 (low byte) 21 Trip Log 4 (high byte)
The following services are implemented for the Assembly Object:
Table 23 - EtherNet Object Common Services
Service Code
0x0E Yes Yes Yes Get Attribute Single 0x10 No Yes No Set Attribute Single
Implemented for: Service Name Class Instance
Consuming
Instance Producing

Connection Manager Object — CLASS CODE 0x06

No class or instance attributes are supported.
The following common service are implemented for the Connection Manager
Object:
Table 24 - Connection Manager Object Common Services
Service Code Implemented for: Service Name
Class Instance
0x54 No Yes Forward Open 0x4E No Yes Forward Close

Discrete Input Point Object — CLASS CODE 0x08

The following class attributes are supported for the Discrete Input Point Object:
Table 25 - Discrete Input Point Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0002 2 Get Max Instance UINT 0x0002
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 85
Appendix B
Two instances of the Discrete Input Point Object are supported as follows:
Table 26 - Discrete Input Point Object Instances
Attribute ID Access Rule Name Data Type Value
3 Get Value BOOL 0=OFF
1=ON
The following common services are implemented for the Discrete Input Point Object:
Table 27 - Discrete Input Object Common Services
Service Code
0x0E Yes Yes Get Attribute Single
Implemented for: Service Name Class Instance

Discrete Output Point Object — CLASS CODE 0x09

The following class attributes are supported for the Discrete Output point Object:
Table 28 - Discrete Output Point Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001 2 Get Max Instance UINT 0x0001
A single instance is implemented and contains the following attributes:
Table 29 - Discrete Output Point Object Instance 1 - Output A
Attribute ID Access Rule Name Data Type Value
3 Get Value BOOL 0=OFF
5 Get/Set Fault Action BOOL 0=Fault Value
6 Get/Set Fault Value BOOL 0=OFF
7 Get/Set Idle Action BOOL 0=Fault Value
8 Get/Set Idle Value BOOL 0=OFF
113 Get/Set Pr Fault Action BOOL 0=Pr Fault Value
114 Get/Set Pr Fault Value BOOL 0=OFF
1=ON
Attribute 1=Hold Last State
1=ON
Attribute 1=Hold Last State
1=ON
Attribute 1=Ignore
1=ON
86 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
The following common services are implemented for the Discrete Output Point Object:
Table 30 - Discrete Output Object Common Services
Service Code
0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single
Implemented for: Service Name Class Instance

Parameter Object — CLASS CODE 0x0F

The following class attributes are supported for the Parameter Object:
Table 31 - Parameter Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001 2 Get Max Instance UINT 0x0029 8 Get Parameter Class Descriptor WORD 0x000B 9 Get Configuration Assembly Instance UINT 0x0078 10 Get Native Language UINT 0x01=English
The following instance attributes are implemented for all parameter attributes:
Table 32 - Parameter Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get/Set Value Specified in Descriptor N/A 2 Get Link Path Size USINT N/A 3 Get Link Path Packed EPATH: Path to specified object attribute 4 Get Descriptor WORD Parameter Dependent 5 Get Data Type EPATH Parameter Dependent 6 Get Data Size USINT Parameter Dependent 7 Get Parameter Name String SHORT_STRING Parameter Dependent 8 Get Units String SHORT_STRING Parameter Dependent 9 Get Help String SHORT_STRING Parameter Dependent 10 Get Minimum Value Specified in Descriptor Parameter Dependent 11 Get Maximum Value Specified in Descriptor Parameter Dependent 12 Get Default Value Specified in Descriptor Parameter Dependent 13 Get Scaling Multiplier UINT 1 14 Get Scaling Divisor UINT 1 15 Get Scaling Base UINT 1 16 Get Scaling Offset INT 0
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 87
Appendix B
Table 32 - Parameter Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
17 Get Multiplier Link UINT 0 18 Get Divisor Link UINT 0 19 Get Base Link UINT 0 20 Get Offset Link UINT 0 21 Get Decimal Precision USINT Parameter Dependent
The following commons services are implemented for the Parameter Object:
Table 33 - Parameter Object Common Services
Service Code
0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single 0x4B No Yes Get Enum String
Implemented for: Service Name Class Instance

Parameter Group Object — CLASS CODE 0x10

The following class attributes are supported for the Parameter Group Object:
Table 34 - Parameter Group Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 0x0001 2 Get Max Instance UINT 0x0005 8 Get Native Language USINT 0x01=English
The following parameter group objects are supported:
Instance 1 = Monitor Parameters
Instance 2 = Trip History
Instance 3 = Reset/Lock
Instance 4 = Advanced Setup
Instance 5 = I/O Setup
88 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
The following instance attributes are supported for all parameter group instances:
Table 35 - Parameter Group Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Group Name String SHORT_STRING N/A 2 Get Number of Members UINT N/A 3 Get 1st Parameter UINT N/A 4 Get 2nd parameter UINT N/A n Get Nth Parameter UINT N/A
The following common services are implemented for the Parameter Group Object:
Table 36 - Parameter Group Object Common Services
Service Code
0x0E Yes Yes Get Attribute Single
Implemented for: Service Name Class Instance

Control Supervisor Object — CLASS CODE 0x29

No class attributes are supported for the Control Supervisor Object. A single instance (instance 1) of the Control Supervisor Object is supported. The following instance attributes are supported.
Table 37 - Control Supervisor Object Instance 1 Attributes
Attribute ID Access Rule Name Data Type Value
10 Get Faulted BOOL 0=No Fault present
11 Get Warning BOOL 0=No Warnings present
12 Get/Set Fault Rst BOOL 0=No action
13 Get FaultCode UINT If in Faulted state, FaultCode indicates the fault that caused the transition to
14 Get Warning Code UINT Code word indicating warning present. If multiple warnings are present, the
100 Get Trip Status WORD Bit 0=Overload
1= Fault Latched
1=Warning present (not latched)
0->1=Fault reset
Faulted state. If not in Faulted state, FaultCode indicates the fault that caused the last transition to the Faulted state.
lowest code value is displayed.
Bit 1=Phase Loss Bit 2=Jam Bit 3-Bit 15=Not used
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 89
Appendix B
Table 37 - Control Supervisor Object Instance 1 Attributes
Attribute ID Access Rule Name Data Type Value
101 Get Warning Status WORD Bit 0=Overload
102 Get Trip Log 0 WORD Last trip condition. Bit definitions of the value are the same as attribute 101 103 Get Trip Log 1 WORD Last trip condition. Bit definitions of the value are the same as attribute 101 104 Get Trip Log 2 WORD Last trip condition. Bit definitions of the value are the same as attribute 101 105 Get Trip Log 3 WORD Last trip condition. Bit definitions of the value are the same as attribute 101 106 Get Trip Log 4 WORD Last trip condition. Bit definitions of the value are the same as attribute 101 107 Get Device Status WORD Bit 0=Trip
108 Get/Set Trip Enable WORD Bit 0=Not Used
109 Get/Set Warning Enable WORD Bit 0=Overload
110 Get/Set OL Reset Mode BOOL 0=Manual
111 Get/Set IN1 Assignment USINT 0=Normal
112 Get/Set IN2 Assignment USINT 0=Normal
Bit 1=Not Used Bit 2=Jam Bit 3=Underload Bit 4=Not Used BIt 5=Comm Fault Bit 6=Comm Idle Bit 7=Non Vol Mem Fault Bit 8-Bit 15=Not used
Bit 1=Warning Bit 2=OutputA Bit 3=Input 1 Bit 4=Input 2 Bit 5=Motor Current Bit 6-Bit 15=Not used
Bit 1=Not Used Bit 2=Jam Bit 3-Bit 15=Not Used
Bit 1=Not Used Bit 2=Jam Bit 3=Underload Bit 4=Not Used BIt 5=Comm Fault Bit 6=Comm Idle Bit 7-Bit 15=Not Used
1=Automatic
1=Trip Reset 2=OL Contact
1=Trip Reset 2=OL Contact
The following common services are implemented for the Control Supervisor Object:
Table 38 - Control Supervisor Object Common Services
Service Code
0x0E No Yes Get Attribute Single 0x10 No Yes Set Attribute Single 0x05 No Yes Reset
90 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Implemented for: Service Name Class Instance
Appendix B

Overload Object — CLASS CODE 0x2C

No class attributes are supported for the Overload Object. A single instance (instance 1) of the Overload Object is supported:
Table 39 - Overload Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
7 Get % Thermal Utilized USINT xxx% FLA 108 Get Average % FLA UINT 0…1000%FLA 109 Get % Thermal Utilized USINT 0…100% 127 Get/Set Single/Three Phase BOOL 0=Single Phase
132 Get/Set OL Warn Level USINT 0…100% TCU 141 Get/Set Jam Inhibit Time USINT 0…250 s 142 Get/Set Jam Trip Delay USINT 0.5…25.0 s 143 Get/Set Jam Trip Level UINT 150…600%FLA 144 Get/Set Jam Warn Level UINT 100…600%FLA 145 Get/Set UL Inhibit Time USINT 0…250 s 148 Get/Set UL Warn Level USINT 30…100%FLA
1=Three Phase
The following common services are implemented for the Overload Object:
Table 40 - Overload Object Common Services
Service Code
0x0E No Yes Get Attribute Single 0x10 No Yes Set Attribute Single
Implemented for: Service Name Class Instance

PCP Object — CLASS CODE 0xC2

The following class attributes are supported for the PCP Object:
Table B.1 PCP Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 91
Appendix B
The following instance attributes are implemented for all parameter attributes:
Table 41 - PCP Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get/Set MCC Number USINT 0-255 2 Get/Set Vertical Section Number USINT 0-255 3 Get/Set Starting Section Letter USINT 0-255 4 Get/Set Space Factors USINT 0-0x3F 5 Get/Set Cabinet Width USINT 0-255 6 Get/Set Controlled Device USINT 0-255 7 Get Number of Device Inputs USINT 2 8 Get/Set Devices Connected at Inputs Array of USINT 9 Get Number of Device Outputs USINT 1 10 Get/Set Devices Connected at Outputs Array of USINT
The following common services are implemented for the PCP Object:
Table 42 - PCP Object Common Services
Service Code
0x01 No Yes Get Attribute All 0x02 No Yes Set Attribute All 0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single

TCP/IP Interface Object — CLASS CODE 0xF5

The following class attributes are supported for the TCP/IP Interface Object:
Table 43 - TCP/IP Interface Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
The following instance attributes are implemented for all parameter attributes:
Table 44 - TCP/IP Interface Object Instance Attributes
Implemented for: Service Name Class Instance
Attribute ID Access Rule Name Data Type Value
1 Get Status DWORD N/A 2 Get Configuration capability DWORD 0x00000014 3 Get/Set Configuration control DWORD N/A
92 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Table 44 - TCP/IP Interface Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
4 Get Physical Link Object Struct of:
Path size UINT 0x0002 Path Padded EPATH 20 F6 24 01
5 Get/Set Interface configuration Structure of:
IP Address UDINT Network Mask UDINT Gateway Address UDINT Name Server UDINT Name Server 2 UDINT
Domain Name STRING 6 Get/Set Host Name STRING 8 Get/Set TTL Value USINT 1 9 Get/Set Mcast Config Structure of:
Alloc Control USINT 0
Reserved USINT
Num Mcast UINT 4
Mcast Start Addr UDINT
Appendix B
The following common services are implemented for the TCP/IP Interface Object:
Table 45 - TCP/IP Interface Common Services
Service Code
0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute Single
Implemented for: Service Name Class Instance

Ethernet Link Object — CLASS CODE 0xF6

The following class attributes are supported for the Ethernet Link Object:
Table 46 - Ethernet Link Object Class Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 3
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 93
Appendix B
The following instance attributes are implemented for all parameter attributes:
Table 47 - Ethernet Link Object Instance Attributes
Attribute ID Access Rule Name Data Type Value
1 Get Interface Speed UDINT 10 or 100 2 Get Interface Flags DWORD 3 Get Physical Address ARRAY of 6 USINTs MAC Address 4 Get Interface Counters Structure of:
In Octets UDINT N/A In Ucast Packets UDINT N/A In NUcast Packets UDINT N/A In Discards UDINT N/A In Errors UDINT N/A In Unknown Protos UDINT N/A Out Octets UDINT N/A Out Ucast Packets UDINT N/A Out NUcast Packets UDINT N/A Out Discards UDINT N/A Out Errors UDINT N/A
5 Get Media Counters Structure of:
Alignment Errors UDINT N/A FCS Errors UDINT N/A Single Collisions UDINT N/A Multiple Collisions UDINT N/A SQE Test Errors UDINT 0 Deferred Transmission UDINT N/A Late Collisions UDINT N/A Excessive Collisions UDINT N/A MAC Transmit Errors UDINT N/A Carrier Sense Errors UDINT N/A Frame Too Long UDINT N/A MAC Receive Errors UDINT N/A
6 Get/Set Interface Control Structure of:
Control Bits WORD N/A Forces Interface Speed UINT N/A
94 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
The following common services are implemented for the Ethernet Link Object:
Table 48 - Ethernet Link Common Services

Rockwell Automation Support

Service Code
0x01 Yes Yes Get Attribute All 0x0E No Yes Get Attribute Single 0x10 No Yes Set Attribute Single 0x4C No Yes Get And Clear
Implemented for: Service Name Class Instance
Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States 1.440.646.3223
Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return

Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case number
Outside United States
(see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 95
Appendix B
96 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Rockwell Automation Publication 193-UM012B-EN-P - June 2011 98
Supersedes Publication 193-UM012A-EN-P - March 2009 Copyright © 2011 Rockwell Automation, In c. All rights reserved. Printed in the U.S.A.
Loading...