Rockwell Automation 1785-TR10B2 User Manual

Page 1

Installation Instructions

Coax Transceiver for 10BASE2

1785-TR10B2
The mini coax transceive r enables a devi ce with an AUI int erface to connec t to a 10 Mbit/s CSMA/CD LAN (ISO/IEC 8802-3, IEEE 802.3, 10BASE2) via a coaxial cable.
powercollision/jabb er controldata
SQE test can be disabled externally
Can be plugged directly to the device interface
Low current consumption
Compact construction

To the Installer

Topic Pa ge
Description 2 Installation 2 Compliance to European Union Directives 4 Technical Data 7
1785-5.18 - January 1999
Page 2
2 Coax Transceiver for 10BASE2

Description

The 1785-TR10B2 mini coax transceiver can be connected to the AUI interface of a device either directly or via an AUI cable. It is connected to the coaxial cable by a BNC socket. The mini coax transceiver offers these functions according to IEEE 802.3 10BASE2:
indication via a LED of data transmission and reception through the coaxial cable
detection of data collisions in the network and reporting them to the terminal equipment as well as indicating them by a LED
Jabber control and di splay: p rotecti ng the ne twork from dat a packets that are too long (> 25 ms)
ability to enable/disable the SQE test: at the end of every transmit
operation, a short collis ion signal ( heart beat) app rox. 1 µs long is sent to monitor the electronics
Tx
Tx-Packet Detect
ENABLE/ DISABLE
DO

Installation

Jabber Protect
BNC interface
(to 10BASE2)
Collision Detector
Rx
SQE-Test GeneratorGenerator
Collision Oscillator
Rx-Data
CI
AUI interface
(15-pole SUB-D connector)
DI

Coaxial Cable Connection

1. Cut off the coax cable (10BASE2) at the connection point.
2. Apply BNC connectors to both ends of the cable.
3. Put the two ends tog ether vi a a BNC-T-adapter , which you co nnect to the
BNC socket of the transceivers.
4. When connecting to the end of a coax cable, apply a BNC terminator
(50
) to the unused socket of the T-adapter.
1785-5.18 - January 1999
Important:The minimum distance between two transceivers along a coax
cable is 0.5 m.
Page 3
Coax Transceiver for 10BASE2 3

Power Supply

The operating voltage (+12 V) is taken from the connected device via the 15-pin sub-D socket of the AUI interface.

SQE Test Setting

The slide switch loca ted on the top of the tr ansceiver case is use d to acti vate and deactivate the SQE t est. Before pl acing the tr ansceiver in operation, you should check to see whether the connected device requires the SQE test to be on or off. As delivered from the factory, the SQE test is on.

Connecting Devices

Connecting two devices
Connecting more than two devices
Ter mi na tor
PC
1785-TR10B2
PC
* The maximum length is valid between the PC and the terminator.
For Additional Information
Terminator
10BASE2 (max. 185 m *)
BNC-T-Adapter
* The maximum length is valid between the PC and the terminator.
Terminator
10BASE2 (max. 185 m *)
1785-TR10B2
min. 0.5 m
BNC-T-Adapter
PLC5E
PLC5E
PLC5E
For standards information, go to copy of this publication, go to
http://www.theautomationbookstore.com/.
http://www.ieee.org/. To download a .PDF
1785-5.18 - January 1999
Page 4
4 Coax Transceiver for 10BASE2

Compliance to European Union Directives

If this product has the marking, it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet
the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standard s, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment
EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safe ty req uir ements of EN 609 50 - In form ation Technology Equipment.
For specific informat ion requi red by EN 60950 , see the ap propriat e section s in this publication, as well as the following Allen-Bradley publicati ons:
Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1
Automation Systems Catalog, publication B111
1785-5.18 - January 1999
Page 5
Coax Transceiver for 10BASE2 5
Hazardous Location Approval
This product may be certified for general use as well as for use in hazardous locations. Actual agency certification is indicated by the product label as shown below, and not by statements in any user
documentation.
Example of the certification product label:
CL I, DIV 2
GP A,B,C,D
TEMP
To comply with certification for use in hazardous locations, the following information becomes a part of the product literature for this certified industrial control product.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
The products having the appropriate markings (that is, Class I, Division 2, Groups A, B, C, D) are certified for
use in other equipment where the suitability of combination (that is, application or use) is determined by the local authority having jurisdiction.
Important: Due to the modular nature of a programmable control system, the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I, Division 2, location. The temperature code rating is marked on the product label as shown.
Temperature code rating:
CL I, DIV 2
GP A,B,C,D
TEMP
/RRNIRUWHPSHUDWXUH FRGHUDWLQJKHUH
The following warnings apply to products having certification for use in hazardous locations.
ATTENTION: Explosion hazard -
Substitution of components may impair suitability for Class I, Division 2.
!
Do not replace components unless power has been switched off or the area is known to be
non-hazardous.
Do not disconnect equipment unless power has been switched off or the area is known to be
non-hazardous.
Do not disconnect connectors unless power has been switched off or the area is known to be
non-hazardous. Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
1785-5.18 - January 1999
Page 6
6 Coax Transceiver for 10BASE2
Approbation d’utilisation en environnements dangereux
Ce produit est certifié pour une utilisation générale aussi bien que pour une utilisation en environnements dangereux. La certification en vigueur est indiquée par l'étiquette produit et non par des indications dans la
documentation utilisateur.
Exemple d'étiquette de certification d'un produit :
Pour satisfaire à la certification en environnements dangereux, les informations suivantes font partie intégrante de la documentation des produits de commande industrielle certifiés.
Cet équipement ne convient qu’à une utilisation en environnements de Classe 1, Division 2, Groupes A, B, C, D,
ou non dangereux.
Les produits portant le marquage approprié (c'est-à-dire, Classe 1, Division 2, Groupes A, B, C, D) sont
certifiés pour une utilisation avec d'autres équipements, les combinaisons d’applications et d’utilisation étant déterminées par le bureau local d'inspection qualifié.
CL I, DIV 2
GP A,B,C,D
TEMP
Important : De par la nature modulaire des systèmes de commande programmables, le produit ayant le code de température le plus élevé détermine le code de température global du système dans un environnement de Classe 1, Division 2. Le code de température est indiqué sur l'étiquette produit.
Code de température
:
CL I, DIV 2
GP A,B,C,D
TEMP
Le code de température est indiqué ici
Les avertissements suivants s'appliquent aux produits certifiés pour une utilisation en environnements dangereux.
DANGER : Risque d’explosion
La substitution de composants peut rendre cet équipement inadapté à une utilisation en
!
environnement de Classe 1, Division 2.
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de
remplacer des composants.
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de
débrancher l’équipement.
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de
débrancher les connecteurs. Fixer tous les connecteurs fournis par l’utilisateur pour se brancher aux circuits externes de cet équipement à l’aide de vis, loquets coulissants, connecteurs filetés ou autres, de sorte que les connexions résistent à une force de séparation de 15 newtons (1,5 kg - 3,4 lb) appliquée pendant au moins une minute.
1785-5.18 - January 1999
Page 7
Coax Transceiver for 10BASE2 7

Technical Data

Operating voltage +12 V Current consumption (no signal) 2 50 mA Bit rate (Manchester Code) 10 Mbit/s
Coaxial cable interface: Transmitter
AC DC Rise/fall time Harmonic components: 1st harmonic 2nd harmonic 3rd harmonic 4th harmonic 5th harmonic 6th harmonic 7th harmonic and higher
Preamble loss transmit ≤ 2 bit Stady State Delay 15 ns Jabber protect time out 25 ms Jabber reset 500 ms
Coaxial cable interface: Receiver
Coaxial cable Input current 5 µA Capacitive load 2 pF Input resistance > 100 k Noise suppression –250 mV Preamble loss receive 1 bit (max. 3 bit) Steady State Delay 10 ns Collision Detect threshold –1.6 V
Transceiver interface (AUI)
Input: Terminating resistance Sensitivity Maximum DC component
Output: Output voltage (data and CD signal) CD signal frequency SQE Test (heart beat)
delay time length
AUI cable length Connections with pin assignments
Transceiver interface (15-pin sub-D plug)
Coaxial cable interface
1.9 V +0.35 V, –0.5 V –1.025 V ±0.1 V 25 ns ±20%
–34 dB –23 dB –40 dB –39 dB –40 dB –47 dB –55 dB
78 ±1% 500 mVPP ± 50 V
1.6 VPP 10 MHz ± 10% can be disabled 1100 ns 1000 ns 0 to 50 m max.
Input: DO-A: Pin 3; DO-B: Pin 10 Output: DI-A: Pin 5; DI-B: Pin 12 Collision detect:CI-A: Pin 2; CI-B: Pin 9 Power: GND: Pin 6; +12 V: Pin 13 Shielding: Pin 1, 4, 8, 11, 14 1 BNC socket
1785-5.18 - January 1999
Page 8
Connection capabilities Transceiver interface
plugged directly onto the AUI interface of connected device or connected by an AUI cable (50 m max. length)
Coaxial cable interface
with BNC-T-adapter (please order separately) onto coax segment 10BASE2
Displays
* yellow LED: DA (Data)
on – data being transmitted or received
* red LED: CD (Collision Detect)
brief flash – data collision continuously on – jabber control active
* green LED: P (power)
on – supply voltage present Dimensions W x H x D 44 mm x 22 mm x 100 mm (1.8 in. x .83 in. x 3.9 in.) Weight 130 g Ambient temperature 0° C to +50° C Storage temperature –20° C to +80° C Relative humidity 10 % to 90 % (non-condensing) Conductors/Wire Size/Category
Agency Certification (when product is marked)
Category 2
CUS
1
Information Technology Equipment
Industrial Control Equipment
Class I, Div. 2, Groups A, B. C, D
Hazardous Location
EN 50082-1, 2
EN 55022, Radiated Emission Class B
EN 60950
FCC Part 15, SubPart B
1
Refer to the Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1.
Publication 1785-5.18 - January 1999 PN 955134-72
Copyright 1999 of Rockwell International Corporation. Printed in the U.S.A.