Enhanced and
Ethernet PLC-5
Programmable
Controllers
1785-L11B, -L20B, -L30B, -L40B,
-L40L, -L60B, -L60L, -L80B, -L20E,
-L40E, -L80E, -L26B, -L46B, -L86B
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.ab.com/manuals/gi) describes some important differences
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for
solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manua l , in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment,
which may lead to personal injur y or death, property
damage, or economic loss.
Identifies information that is critical for successful
application and understanding of the product.
Identifies information about practices or circumstances
that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may
be present.
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfa ces may be
dangerous temperatures.
Summary of Changes
Summary of Changes
Changes to this Manual
Find the New Information
This user manual contains new and updated information.
The black revision bars, as shown on the left, indicate the changes.
For specific locations of the new information, refer to the table below.
This New and Updated InformationIs on Page
Domain Name Service11-15
User Provided Web Pages11-16
Multihop Messaging over Ethernet11-29
TCP/IP Communications11-32
Additional Ethernet Diagnostics11-35
Memory Card DiagnosticsB-12
Troubleshooting and DiagnosticsF-2
Additional Ethernet PLC-5 Controller Enhan ce ment
Ethernet PLC-5 controllers support use of the 1785-RC Relay Cartridge.
The relay cartridge serves as an interface from the controller to a user-supplied
external device such as an Allen-Bradley 700P relay. When the controller is in
run mode, it monitors online ladder program edits and I/O forcing activity.
When either of these is detected, the controller opens the relay on the relay
cartridge for one second.
The purpose of this manual is to help you design, operate and maintain an
Enhanced and Ethernet PLC-5 programmable controller system. Use this
manual to:
• determine the features of the controllers and how you use them
• design your PLC-5 system
• operate and maintain your PLC-5 system
The following docume nts contain additional i nformation rela ted to the
procedures described in this document..
Publication TitlePublication Number
Industrial Automation Wiring and Grounding Guidelines1770-4.1
PLC-5 Programmable Controller Instruction Set Reference1785-6.1
Configuring Complementary I/O for PLC-5 Controllers 1785-6.8.3
Data Highway Cable Installation Manual1770-6.2.2
SCADA System Selection Guide,AG-SG001
PLC-5 Protected Controllers Product Data1785-2.28
PLC-5 Protected Controller Supplement1785-6.5.13
1771 Remote I/O Adapter Module User Manual1771-UM001
ControlNet PLC-5 Programmable Controllers User Manual1785-UM022
To get this documentation, you can either:
• view or download an electronic version from the internet at
www.rockwellautomation.com/literature
• contact y our local di stri but or or Rockwell Auto mation representative to
place an order
1Publication 1785-UM012D - EN-P - July 2005
Preface 2
Terms Used in This Manual
TermDefinition
Block-transfer data data transferred, in blocks of data up to 64 words, to/from a block-
Discrete-transfer data data (words) transferred to/from a discrete I/O module
Enhanced PLC-5 controllersreferences PLC-5/11, -5/20, -5/26, -5/30, -5/40, -5/46, -5/40L,
Etherneta local area network with a baseband communication rate of 10M
Ethernet PLC-5 controllersreferences PLC-5/20E, -5/40E, and -5/80E controllers
Become familiar with the following terms and definitions which are used
throughout this manual.
transfer I/O module (for example, an analog module)
-5/46L, -5/60, -5/60L, -5/80, and -5/86 controllers
PLC-5/26, -5/46, and -5/86 controllers are protected
controllers. See the PLC-5 Protected Controllers Supplement,
publication 1785-6.5.13
This term also refers to the PLC-5/V30B, -5/V40B, -5/V40L, and
-5/V80B controllers when applicable. See the PLC-5/VME VMEbus
Programmable Controllers User Manual, publication 1785-6.5.9,
for more information
bps designed for the high-speed exchange of information between
computers and related devices
Extended-local I/OI/O connected to a controller across a parallel link to achieve
higher throughput, thus limiting its distance from the controller
Extended local I/O linka parallel link for carrying I/O data between a PLC-5/40L or -5/60L
controller and extended-local I/O adapters
PLC-5 controllerused to generically reference Enhanced PLC-5 and Ethernet PLC-5
controllers in this manual only
Controller-resident local I/O
chassis
Remote I/O link a serial communication link between a PLC-5 controller port in
Remote I/O chassis the hardware enclosure that contains an adapter and I/O modules
the I/O chassis in which the PLC-5 controller is installed
scanner mode and an adapter as well as I/O modules that are
located remotely from the PLC-5 controller
that are located remotely on a serial communication link to a PLC-5
controller in scanner mode
Publication 1785-UM012D-EN-P - July 2005
Preface 3
Manual Overview
This manual has three main sections:
• Design
• Operate
• Maintain
Section:For information about:SeeTitle:
DesignAn overview of the PLC-5 controllers’ capabilities and keyswitchChapter 1Understanding Your Controller
Guidelines for selecting and placing I/O modulesChapter 2Selecting and Placing I/O
The proper environment for your PLC-5 systemChapter 3Placing System Hardware
Choosing addressing mode, assigning rack numbers, and understanding
PLC-5 memory
OperateConfiguring the controller for controller-resident I/O, transferring data, and
monitoring status
Configuring a system for remote I/O communication, designing a remote
I/O link, transferring data, and monitoring status
Configuring a PLC-5 adapter channel, transferring data, and
monitoring status
For PLC-5/40L, -5/46L, and -5/60L Controllers only: Configuring an
extended-local I/O system, transferring data, and monitoring status
Configuring a system for Data Highway Plus™ and monitoring
channel status
Configuring a system for serial communications and monitoring
channel status
Chapter 4Addressing I/O and Controller Memory
Chapter 5Communicating with Controller-Resident I/O
Chapter 6Communicating with Remote I/O
Chapter 7Communicating with a PLC-5
Adapter Channel
Chapter 8Communicating with Extended-Local I/O
Chapter 9Communicating with Devices on a DH+ Link
Chapter 10 Communicating with Devices on a
Serial Link
For PLC-5/20E, -5/40E, and -5/80E Controllers only:
Configuring a system for Ethernet communications and monitoring
channel status
Assigning passwords and privilegesChapter 12 Protecting Your Programs
PLC-5 programming feature overviewChapter 13 Programming Considerations
Defining power-up procedureChapter 14 Preparing Power-Up Routines
Defining, programming, and monitoring fault routinesChapter 15 Preparing Fault Routines
Configuring and monitoring main control programsChapter 16 Using Main Control Programs
Using, defining, and monitoring selectable timed interruptsChapter 17 Using Selectable Timed Interrupts
Using, defining, and monitoring Controller input interruptsChapter 18 Using Controller Input Interrupts
MaintainSystem specificationsAppendix A System Specifications
Listing of the controller status file words and meaningAppendix B Controller Status File
General and specific performance considerationsAppendix C Maximizing System Performance
Guide to ladder instructions and execution timesAppendix D Instruction Set Quick Reference
How to set system switchesAppendix E Switch Setting Reference
Potential problems and recommended solutionsAppendix F Troubleshooting
Guidelines for choosing and making cablesAppendix G Cable Reference
Chapter 11 Communicating with Devices on an
Ethernet Network
Publication 1785-UM012D - EN-P - July 2005
Preface 4
Notes
Publication 1785-UM012D-EN-P - July 2005
Using This Chapter
Chapter
1
Understanding Your Programmable Controller
For Information AboutGo to Page
Lay Out the System1-1
Identifying controller components1-2
Programming features1-10
Using a controller channel as a remote I/O scanner1-11
Using a controller channel as a remote I/O adapter1-12
Using a PLC-5/40L, -5/60L programmable controller as an
extended-local I/O scanner
1-14
Lay Out the System
Lay out the system by determining the network configuration and the
placement of components in each location. Decide at this time whether each
location will have its own controller.
Place each controller’s I/O on an isolated network to maximize the
performance and to more ea sily accommodate future network or system
configuration changes. If you plan to share I/O, make sure the I/O is on a
network that each controller can access.
Assume that Network A and Netw or k B both re quir e a c ontr oller and its I/O.
Both controllers interact with time critical information.
RSView
Network C
Panel C
Network B
Panel B
chassis 1
Panel B
chassis 2
Panel A
chassis 1
Network A
Panel A
chassis 2
Panel A
chassis 3
Panel
View
1Publication 1785-UM012D - EN-P - July 2005
Panel
View
1-2 Understanding Your Programmable Controller
For a PLC-5 controller to control I/O modules, both the contro ller and the
I/O modules must be directly attached to the same network.
Identifying Controller
Components
I/O LocationController in
Panel A, chassis 1
Panel A, chassis 1yesyes
Panel A, chassis 2yesno
Panel A, chassis 3yesno
Panel B, chassis 1yesyes
Panel B, chassis 2noyes
Panel C, chassis 1yesyes
Controller in
Panel B, chassis 1
Evaluate what communications need to occur between controllers. If there is
sporadic information that is not time-critical, use a message-based network
such as an EtherNet/IP (the information portion) or Data Highway Plus
TM
.
To become familiar with the controller’s front panels, use these figures:
For the Front Panels OfPage
PLC-5/11, -5/20 and -5/26 controllers1-3
PLC-5/30 controllers1-4
PLC-5/40, -5/46, -5/60, -5/80 and -5/86 controllers1-5
PLC-5/20E controllers1-6
PLC-5/40E and -5/80E controllers1-7
PLC-5/40L and -5/60L controllers1-8
Publication 1785-UM012D-EN-P - July 2005
Understanding Your Programmable Controller 1-3
PLC-5/11, -5/20, and -5/26 Controll er Front Panels
keyswitch; selects controller mode
channel 0-25-pin D-shell serial port;
supports standard EIA RS-232C and
RS-423 and is RS-422A compatible
1
Use this port with ASCII or DF1
full-duplex, half-duplex master, and
half-duplex slave protocols. The port's
default configuration supports controller
programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
PLC-5/11 Controller
PLC-5/20 or -5/26 Controller
battery indicator (red when
the battery is low)
controller RUN/FAULT
indicator (green when
running; red when faulted)
force indicator (amber when
I/O forces are enabled)
channel 0 communication
status indicator (green when
the channel is communicating)
Install memory module here.
Install battery here
channel 1A status indicator
(lights green and red)
8-pin mini-DIN, DH+ programming
terminal connection parallel to
channel 1A
channel 1A communication port; for
the PLC-5/11 controller, the default
configuration is DH+
2
channel 1A communication port;
this 3-pin port is a dedicated DH+ port
1
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422A
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
Configure these 3-pin ports for:
2
remote I/O scanner
remote I/O adapter,
DH+ communication
unused
channel 1B status indicator
(lights green and red)
channel 1B communication port;
its default configuration is remote
I/O scanner
2
PLC-5 family member designation
Publication 1785-UM012D - EN-P - July 2005
1-4 Understanding Your Programmable Controller
keyswitch; selects controler mode
channel 1A status indicator
(lights green and red)
PLC-5/30 Controller Front Panell
battery indicator (lights red when the
battery is low)
controller RUN/FAULT indicator (green
when running; red when faulted)
force indicator (amber when
I/O forces are enabled)
channel 0 communication status indicator
(green when the channel is communicating)
channel 0-25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible
Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports processor programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
1
8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A
channel 1A communication port;
its default configuration is DH+
channel 1B communication port;
its default configuration is remote I/O scanner
2
2
Install battery here
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422
1
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
2
Configure these 3-pin ports for:
remote I/O scanner,
remote I/O adapter,
DH+ communication
unused
channel 1B status indicator (lights green and red)
Install memory module here
Use these labels to write information about the
channel: communication mode, station addresses, etc.
PLC-5 family member designation
Publication 1785-UM012D-EN-P - July 2005
keyswitch; selects controller mode
channel 2A status indicator
(lights green and red)
Understanding Your Programmable Controller 1-5
PLC-5/40, -5/46, -5/60, -5/80, and -5/86 Controller Front Panel
battery indicator (red when the battery is low)
controler RUN/FAULT indicator (green when
running; red when faulted)
force indicator (amber when I/O forces are enabled)
channel 0 communication status indicator
(green when the channel is communicating)
8-pin mini-DIN, DH+ programming
terminal connection parallel to channel
2A when channel 2A is configured for
DH+ communications
channel 2A communication port;
its default configuration is unused
2
channel 2B communication port;
its default configuration is unused
2
channel 1A status indicator
(lights green and red)
8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A
channel 1A communication port;
its default configuration is DH+
at 57.6 kbps
2
channel 1B communication port;
its default configuration is remote I/O scanner
channel 2B status indicator (lights green and red)
channel 0-25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible
1
Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports processor programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
channel 1B status indicator (lights green and red)
Use these labels to write information about the
channel: communication mode, station addresses etc.
Install memory module here
2
Install battery here
1
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422A
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
2
Configure these 3-pin ports for:
remote I/O scanner,
remote I/O adapter,
DH+ communication
unused
PLC-5 family member designation
Publication 1785-UM012D - EN-P - July 2005
1-6 Understanding Your Programmable Controller
external transceiver fuse
keyswitch; selects controller mode
channel 2 Ethernet status indicator (green when
functioning normally; red when not functioning)
channel 2 communication port;
a 15-pin Ethernet port
channel 0*25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible
Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports controller programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
PLC-5/20E Controller Front Pa ne l
1
battery indicator (red when the battery is low)
controller RUN/FAULT indicator (green when
running; red when faulted)
force indicator (amber when I/O forces
are enabled)
channel 0 communication status indicator
(green when the channel is communicating)
channel 2, Ethernet transmit indicator
(green when the channel is communicating)
Install memory module here
Install battery here
channel 1A status indicator
(lights green and red)
8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A
channel 1A communication port; its default
configuration is DH+ communication
1
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422A
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
2
Configure these 3-pin ports for:
remote I/O scanner
remote I/O adapter
DH+ communication
unused
Configure this 3-pin port for:
3
remote I/O adapter
DH+ communication
3
PLC-5/20E
Programmable
Controller
channel 1B status indicator
(lights green and red)
channel 1B communication port;
its default configuration is remote I/O scanner
PLC-5 family member designation
2
Publication 1785-UM012D-EN-P - July 2005
external transceiver fuse
keyswitch; selects controller mode
channel 2 Ethernet status indicator (green when
functioning normally; red when not functioning)
PLC-5/40E and -5/80E Con troller Front Panels
Understanding Your Programmable Controller 1-7
battery indicator (red when the battery is low)
controller RUN/FAULT indicator (green when
running; red when faulted)
force indicator (amber when I/O forces
are enabled)
channel 0 communication status indicator
(green when the channel is communicating)
channel 2, Ethernet transmit indicator (green when
the channel is communicating)
channel 2 communication port;
a 15-pin Ethernet port
channel 1A status indicator
(lights green and red)
8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A
channel 1A communication port; its default
configuration is DH+ communication
2
channel 1B communication port; its default
configuration is remote I/O scanner
2
Install battery here
PLC-5/40E
Programmable
Controller
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422A
1
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
2
Configure these 3-pin ports for:
remote I/O scanner
remote I/O adapter
DH+ communication
unused
channel 0-25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible
Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports controller programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
channel 1B status indicator (lights green and red)
Install memory module here
Use these labels to write information about the
channel: communication mode, station addresses etc.
PLC-5 family member designation
1
Publication 1785-UM012D - EN-P - July 2005
1-8 Understanding Your Programmable Controller
PLC-5/40L and -5/6 0L Controller Front Panels
battery indicator (red when the battery is low)
controller RUN/FAULT indicator (green when
running; red when faulted)
force indicator (amber when I/O forces
are enabled)
keyswitch; selects controller mode
channel 2 extended-local I/O status indicator
(green when functioning normally; red when
not functioning)
channel 2 communication port; a 50-pin,
dedicated extended-local I/O port
channel 1A status indicator
(lights green and red)
8-pin mini-DIN, DH+ programming terminal
connection parallel to channel 1A
channel 1A communication port; its default
2
configuration is DH+ communication
channel 1B communication port; its default
configuration is remote I/O scanner
2
channel 0 communication status indicator
(green when the channel is communicating)
channel 0*25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible
Use this port with ASCII or DF1 full-duplex, half-duplex
master, and half-duplex slave protocols. The port's
default configuration supports controler programming:
DF1 point-to-point
2400 bps
no parity
one stop-bit
BCC error check
no handshaking
channel 1B status indicator (lights green and red)
Install memory module here
Use these labels to write information about the
channel: communication mode, station addresses etc.
1
Install battery here
1
Channel 0 is optically-coupled (provides high electrical noise immunity) and can be used with most RS-422A
equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply with RS-423 requirements
Configure these 3-pin ports for:
2
remote I/O scanner,
remote I/O adapter,
DH+ communication
unused
Publication 1785-UM012D-EN-P - July 2005
PLC-5 family member designation
Understanding Your Programmable Controller 1-9
Use the keyswitch to change the mode in which a controller is operating.
If You Want toTurn the Keyswitch to
• Run your program.
Outputs are enabled. (Equipment being controlled by the I/O
addressed in the ladder program begins operation.)
• Force I/O.
• Save your programs to a disk drive (during operation).
• Enable outputs.
• Edit data table values.
Notes:
• You cannot create or delete a program file, create or delete
data files, edit online, or change the modes of operation
through the programming software while in run mode.
• You can prevent forcing and data table changes by
usingRSLogix5 programming software to set user control bit
S:26/6.
• Disable outputs (outputs are turned off).
• Create, modify, and delete ladder files, SFC files, or data
files.
• Download to/from a memory module.
• Save/restore programs.
Notes:
• The controller does not scan the program.
• You cannot change the mode of operation through the
programming software while in program mode.
Change between remote program, remote test, and remote run
modes through the programming software.
RUN
PROG
R
E
M
RUN
PROG (program)
PROG
R
E
M
RUN
REM (remote)
Remote run
• Enable outputs.
• Save/restore programs.
• Edit while operating.
Remote program
See the program-mode description above.
Remote test
• Execute ladder programs with outputs disabled.
• Cannot create or delete ladder programs or data files.
• Save/restore programs.
• Edit while operating.
PROG
R
E
M
RUN
Publication 1785-UM012D - EN-P - July 2005
1-10 Understanding Your Programmable Controller
Programming Features
This CapabilityLets You
Ladder logicprogram using a language that is representative of relay logic.
Subroutinesstore recurring sections of program logic that can be accessed from multiple program
Sequential Function Charts
(SFCs)
This table highlights the programming features of a PLC-5 programmable
controller.
Choose this language
• if you are more familiar with ladder logic than with programming languages such
as BASIC
Your plant personnel may be more familiar with ladder logic; consider their needs
as well.
• performing diagnostics
• programming discrete control
files.
A subroutine saves memory because you program repetitive logic only once. The JSR
instruction directs the controller to go to a separate subroutine file within the logic
controller , scan that subroutine file once, and return to the point of departure.
use sequence-control language to control and display the state of a sequential process.
Instead of using one long ladder program for your application, divide the logic into steps
and transitions. A step corresponds to a control task; a transition corresponds to a
condition that must occur before the programmable controller can perform the next
control task. The display of these steps and transitions lets you see what state the
machine process is in at a given time via a flowchart form.
SFCs offer constructs that enable execution of multiple paths of logic, or a single
selected path of logic, as well as the ability to jump forwards and backwards.
Troubleshooting can be reduced to a small routine of logic instead of an entire ladder
file.
SFCs are best for defining the order of events in a sequential process.
Structured textprogram using a language similar to BASIC.
Choose structured text if you are:
• more familiar with programming languages such as BASIC than with ladder logic
• using complex mathematical algorithms
• using program constructs that repeat or “loop”
• creating custom data-table monitoring screens
Main Control Programs
(MCPs)
separate sequential logic from ladder logic and structured text as a way of modularized
your process and making troubleshooting easier.
Use several main control programs (MCPs) to define one main control program for each
particular machine or function of your process. MCPs accommodate independent or
non-sequential activities.
A main control program can be an SFC file numbered 1-999 or a ladder-logic file or
structured-text program numbered 2-999.
One data table is used by all MCPs (i.e., you do not have a separate data table for each
MCP).
Publication 1785-UM012D-EN-P - July 2005
Understanding Your Programmable Controll er 1-11
Using a Controller Channel
Configure a remote I/O channel for scanner mode to read and write I/O
information between a controller and an I/O device remotely located from the
as a Remote I/O Scanner
A controller with a channel configured for scanner mode
acts as a supervisory controller for other controllers that
are in adapter mode as well as remote I/O adapter modules.
The scanner-mode PLC-5 controller can:
gather data from node adapter devices in remote I/O racks
process I/O data from 8-, 16-, or 32-point I/O modules
address I/O in 2-, 1-, or 1/2-slot I/O groups
support a complementary I/O configuration
support block-transfer in any I/O chassis
controller.
PLC-5/40
1771-ASB
Remote I/O
Link Cable:
Belden 9463
PLC-5/20
The scanner-mode PLC-5 controller:
transfers discrete data and block-transfer data
to/from modules in remote I/O racks as well as
to/from controllers in adapter mode.
scans remote I/O buffers asynchronously to the
program scan.
updates the input/output image data table from
the remote I/O buffer(s) synchronously to the
program scan
PLC-5 data table
is updated
synchronously to
program scan
(at housekeeping).
Remote I/O buffers
are updated
asynchronously to
the program scan.
PLC-5
Data Table
Output
Remote I/O
Buffer
OutputInput
Input
Remote I/O
Link
Controller
-resident
I/O
Publication 1785-UM012D - EN-P - July 2005
1-12 Understanding Your Programmable Controller
A controller transfers I/O data and status data using:
Using a Controller Channel
as a Remote I/O Adapter
In this example, a PLC-5/40 controller channel is
the supervisory (scanner-mode) controller of the
1771-ASB module and the PLC-5/20 controller.
• discrete
data transfers of 8 words per rack
transfers
occur automatically on the remote I/O network
• block-transfers special data transfers that require ladder logic
instructions to achieve the transfer
allow a transfer of a maximum of 64 words of data
also used to communicate information between a
scanner channel and an adapter-mode controller
channel
Configure a controller channel for adapter mode when you need predictable,
real-time exchange of data between a distributed control adapter-mode
controller channel and a supervisory controller. The remote I/O adapter
channel exchanges data with a supervisory controller.
PLC-5/40
Connect the controllers via the remote I/O link.
You can monitor status between the
supervisory controller and the adapter-mode
PLC-5 controller channel at a consistent rate
(i.e., the transmission rate of the remote I/O link
is unaffected by programming terminals and
other non-control-related communications).
The adapter-mode PLC-5 controller can monitor
and control its controller-resident local I/O while
communicating with the supervisory controller via
a remote I/O link.
1771-ASB
Remote I/O
Link Cable:
Belden 9463
PLC-5/20
Publication 1785-UM012D-EN-P - July 2005
Loading...
+ 358 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.