Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, RSLinx, RSLogix, Logix5000, FLEX I/O, RSLogix 5000, Stratix 6000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
Top icPag e
Studio 5000™ Logix Designer application is the rebranding of RSLogix™ 5000 software9
Rockwell Automation Publication 1783-UM001D-EN-P - January 20133
Summary of Changes
Notes:
4Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Rockwell Automation Publication 1783-UM001D-EN-P - January 20137
Table of Contents
Notes:
8Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Preface
This manual is intended for users of the switch. We assume you are familiar with
the procedures in the Stratix 6000™ Ethernet Managed Switch Installation
Instructions, publication 1783-IN004
Read and understand this manual before using the products. Consult your
Rockwell Automation representative if you have any questions or comments.
For information about the features supported in your firmware revision, refer to
the firmware release notes, publication 1783-RN003
.
.
Studio 5000 Environment
The Studio 5000™ Engineering and Design Environment combines engineering
and design elements into a common environment. The first element in the
Studio 5000 environment is the Logix Designer application. The Logix Designer
application is the rebranding of RSLogix™ 5000 software and will continue to be
the product to program Logix5000™ controllers for discrete, process, batch,
motion, safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of Rockwell
Automation® engineering design tools and capabilities. It is the one place for
design engineers to develop all of the elements of their control system.
Rockwell Automation Publication 1783-UM001D-EN-P - January 20139
Preface
Terminology
Refer to this table for terms used in this publication.
Table 1 - Managed Switch Terminology
TermDescription
1783-EMSAll references to 1783-EMS in this manual refer to catalog numbers 1783-EMS04T and 1783-EMS08T.
Allows the switch to detect the required cable type (straight-through or crossover) for copper Ethernet connections and configures the interfaces
accordingly.
BOOTPCommonly used with Allen-Bradley Ethernet products, the BOOTP protocol is used by a client machine to locate its IP address and network mask.
DHCPDynamic Host Configuration Protocol.
A network protocol that is used to configure devices, so that they can communicate on an IP network. A client machine uses this protocol to acquire
configuration information, such as an IP address and default gateway, from a server running the protocol. The client then uses this information to
configure itself.
DNSDomain Name Server.
Translates domain names into IP addresses, for example, www.example.com can translate to 192.168.100.100.
DomainA group of computers and devices on a network that are controlled as a unit with common rules and procedures.
IGMPInternet Group Management Protocol.
A protocol that manages how adapters and other components join and leave multicast groups. IGMP snooping is a feature of IGMP that allows Ethernet
switches to look (snoop) inside packets to determine which destinations really need to receive the data.
QoSQuality of service.
A method of managing network resources through the classification of Ethernet traffic into high and low priority queues.
SMSShort Message Service.
A communication service that allows text messaging between mobile phones.
SNMPSimple Network Management Protocol.
A protocol that exchanges messages with devices on a network for the purpose of monitoring the devices.SNMP enables a switch to be remotely
managed through other network management software.
Spanning TreeRefers to Rapid Spanning Tree Protocol (RSTP) or Spanning Tree Protocol (STP).
Used with network topologies that provide more than one physical path between two devices, spanning tree protocol manages path redundancies
while preventing undesirable loops in the network. If a fault should occur on an active port, the switch will begin transmitting out one of the blocked
ports.
TCPTransmission Control Protocol.
TCP enables two hosts to establish a connection and exchange streams of data.
TCP guarantees delivery of data and also guarantees that packets are delivered in the same order in which they were sent.
UDPUser Datagram Protocol.
This protocol offers a minimal transport service. UDP is used by applications that do not require the level of service of TCP or use communication
services (for example, multicast or broadcast delivery) not available from TCP.
An application program running over UDP must deal directly with end-to-end communication anomalies that a connection-oriented protocol wo uld
have handled - for example, retransmission for reliable delivery, packetization and reassembly, flow control, and congestion avoidance, when these are
required .
This is commonly seen with I/O type devices that send out information at an RPI rate.
VLANVirtual local-area network.
A logical segment of network users and resources grouped by function, team, or application. This segmentation is without regard to the physical
location of the users and resources.
10Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com
Internet Engineering Task Force website,
http://www.ietf.org
Provides technical specifications for Stratix Ethernet switches.
Provides detailed specifications and information related to
installation of the switch.
Provides general guidelines for installin g a Rockwell Automation
industrial system.
Provides declarations of conformity, certificates, and other
certification details.
Provides access to documents such as the RFC (request for
comment), public documents on networking topics and
protocols, Internet standards documents, best current-practices
information, and related informational documents.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201311
Preface
Notes:
12Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Chapter 1
IMPORTANT
Basic Configuration
This chapter covers how to access the switch’s web interface home page. It also
includes information about how to set an IP address and security, work with
miscellaneous options, and understand status indicators.
Access the Home Page
Use these steps to access the web interface home page for the switch.
Before connecting to the network, set the IP address of the switch as
described in Set the IP Address
1. Connect the switch to your computer’s LAN card.
This connection is required before you can access the home page. For
information about how to establish this connection, see the Stratix 6000
Ethernet Managed Switch Installation Instructions, publication
1783-IN004
2. Open your web browser once the connection is established.
3. In the address bar of your web browser, type your switch's IP address.
For example, to use the default IP address, type http://192.168.1.1.
4. From the user name and password dialog box, leave the user name empty
and type the following case-sensitive password: PASSWORD
If the web browser does not open, verify this information:
• The IP address of the switch. The default IP address is 192.168.1.1.
• Your connection setup. Refer to the Stratix 6000 Ethernet Managed
• Whether the switch has power. The green power-status indicator
should be on.
• Whether the cable is connected. A green or yellow status indicator
should be lit on the Ethernet port.
• A proxy server is not preventing you from accessing the switch.
.
.
.
5. When the home page appears, refer to Ta b l e 2
items on the page.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201313
for information about the
Chapter 1Basic Configuration
Table 2 - Items on the Home Page
ValueDescription
Device NameYou provide this entry to identify the switch. See page 18 for instructions on entering the switch’s name.
Spanning TreeIndicates the current Rapid Spanning Tree Protocol (RSTP) mode of the switch. Possible values are Enabled (RSTP), Enabled (STP
VLAN 802.1QIndicates whether the virtual local-area network (VLAN) feature is enabled on the switch, as described on page 57. Note that the VLAN
IGMP SnoopingFiltering mechanism for multicast traffic should be used when I/O is running on the Ethernet network. For more about IGMP snooping,
Port MirroringAllows traffic on one port to be copied and sent (mirrored) to another port so that an Ethernet protocol analyzer can capture it. For more
QoSWhen enabled, the switch can prioritize packet delivery to a certain port or MAC address. For more about QoS, see page 65.
MAC ID ManagementDetermines if a MAC ID is authorized on the network by checking the allowed MAC IDs and notifies the switch’s controller when an
Product TypeShows the part number of the switch.
Serial NumberUnique to every switch.
MAC AddressIndicates the Ethernet address of the switch.
Firmware RevisionCheck our website to make sure you are up to date.
Web RevisionCheck our website to make sure you are up to date.
UptimeThis setting indicates the switch’s running time. This timer is reset when the switch is powered up.
Link (Port Status)Possible values are ON and OFF.
Compatibility), or Disabled. For more about setting the RSTP mode, see page 55
.
feature used in earlier firmware revisions has been renamed port segmenting. As of firmware revisions 0.11 and 0.53, a new VLAN
feature is provided for only the 1783-EMS08T switch.
see page 25.
about port mirroring, see page 61
unauthorized node appears on the network. For more about MAC ID management, see page 63
.
.
This file updates product firmware. The web interface must be updated separately.
This file updates your web interface. For related information, see Appendix A
.
ON is if a device is connected to the port and has power. ON corresponds to the Link State Status indicator on the switch port being either
solid or flashing green.
14Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Basic ConfigurationChapter 1
Table 2 - Items on the Home Page (continued)
ValueDescription
VLAN (Port Status)If virtual local-area network (VLAN) is enabled on the switch, the VLAN column indicates the VLAN ID assigned to each port. If the port is
Speed (Port Status)Possible values are 10 or 100 signifying a 10 Mbps or 100 Mbps connection.
Duplex (Port Status)Possible values are Full and Half.
Gigabit Port InformationThis is offered as an option to the 1783-EMS08T switch and requires a pluggable SFP MSA-compliant transceiver that you must purchase
ResourcesProvides links to our website and th is manual (you have to be connected to the Interne t to reach our website).
ContactsDisplays contact information entered on the Miscellaneous tab, as described on page 18.
assigned the role of a switch or router, the VLAN column displays the word ‘trunk’.
For more about VLAN configuration, see page 57.
This corresponds to the Data Rate status indicator on the switch port being off (10 Mbps) or solid amber (100 Mbps).
separately.
A fiber optic transceiver can be used to connect to a fiber optic network.
Information about the transceiver used and the connection speed are found on the home page.
The manual link in this section does not require an Internet connection because it is embedded in the product.
For convenience, we have also embedded the EDS file for this device under the EDS file link in this section. Download and install it with
the EDS hardware installation tool (one of the RSLinx® tools).
This lets you enter a name or phone number and email address of the appropriate contact person.
Access Basic Configuration
Options
Set the IP Address
From the home page, click the Basic Configuration folder to expand the menu
bar in the left pane to show these tabs:
• Network Configuration
• Set Security
• Miscellaneous
You normally need to change your IP address to install the switch into your
Ethernet network.
Use these steps to change the IP address.
1. Find an available IP address on your subnet.
2. Connect the switch to your computer’s LAN card.
For additional information, refer to the Stratix 6000 Ethernet Managed
Switch Installation Instructions, publication 1783-IN004
.
3. From the navigation pane, expand the Basic Configuration folder and
select Network Configuration to display the Network Configuration tab.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201315
Chapter 1Basic Configuration
IMPORTANT
4. Type your new IP address.
5. Change the subnet mask and default gateway, if needed.
6. Turn off BOOTP Client to prevent dynamic IP address assignment.
If using host names on the network, Name Resolution must be turned on
and the DNS server addresses must be configured (usually required if using
the email function).
7. Click Apply Changes to change the IP and subnet.
The switch does not load the new IP and subnet address until
power is cycled.
8. Cycle power.
Once the IP and subnet are changed, you must cycle power to load the new
address. Power can be cycled remotely through the management interface
by expanding the Diagnostics folder and clicking Controller Restart. This
restarts the 1783-EMS switch and does not restart the controller. All
communication through the switch is interrupted.
16Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Basic ConfigurationChapter 1
IMPORTANT
Set the IP Address with
BOOTP
Set Security
The 1783-EMS switch ships with the BOOTP client enabled by default. To
assign an address, use this procedure.
1. Put the switch on a network with a BOOTP server.
2. Cycle power to the switch.
The 1783-EMS switch attempts to obtain an IP address several times from
the server before timing out and defaulting to the factory preset address of
192.168.1.1.
The MAC address of the switch is on the home page.
192.168.1.1 could interfere with another device on the network.
We recommend changing the administrator and read-only password before you
place the switch in service.
The administrator password is used for the management interface (HTTP
session), Telnet, and the FTP interface (used to upgrade the firmware). The user
name is verified for the FTP session only. The user name for the HTTP session is
not checked (therefore can be anything). The read-only password is used for
read-only access to the management interface (HTTP session).
Use these steps to change your administrative or read-only user name and
password.
1. From the navigation pane, expand the Basic Configuration folder and
select Set Security to display the Set Security tab.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201317
Chapter 1Basic Configuration
IMPORTANT
2. Change the user name and password.
Work with Miscellaneous
Settings
See Appendix B
3. Click Apply Changes.
4. Cycle power to the switch to load the new user name and password.
The administrative password applies to Telnet, FTP, and the web browser
interface.
Use these steps to configure miscellaneous switch settings.
1. From the navigation pane, expand the Basic Configuration folder and
select Miscellaneous to display the Miscellaneous tab.
for recommendations.
The 1783-EMS switch does not load the new settings until power is
cycled.
2. Use the information in Ta b l e 3
3. Click Apply Changes.
18Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
to configure the settings.
Basic ConfigurationChapter 1
Table 3 - Miscellaneous Switch Settings
SettingDescription
Box NameLets you give your 1783-EMS switch a name that describes its location or connected devices. This feature is useful when multiple 1783-EMS
Minutes of User Inac tivityLets you change the length of time the management inter face (HTTP session) remains open while inactive. Choose from 0…99 min. Select
Seconds Between RefreshControls the refresh rate of the management interface.
Contact Info, Contact EmailUse to identify the responsible service personnel.
switches are installed. The switch reports this name on the home page. To change this setting, complete this procedure.
1. Click Basic Configuration.
2. Click Miscellaneous.
3. Type the new name in the text box and click Apply Changes.
The new name does not show in the home page until you click Refresh on the browser.
0 = Feature Disabled for the interface to remain open until it is closed. The default is 3 min.
• Valid values are 0…99 seconds
• 0 = Feature disabled for no refresh
• Default value is 5 seconds
Rockwell Automation Publication 1783-UM001D-EN-P - January 201319
Chapter 1Basic Configuration
1783-EMS08T
1783-EMS04T
1
2
3
4
1
2
3
4
5
Status Indicators
The figures and table show the status indicators.
ItemIndicatorStateDescription
1Link state
2Data rate
3PWRSolid greenPower to the switch is present.
4STAFlashing greenThis heartbeat indicator normally flashes at a slow rate.
5UPLSolid greenFiber transceiver present.
(1)
(1)
Solid greenEthernet link exists.
Flashing greenValid link is present and transmitting data.
Solid amber100 Mbit link is present.
Off10 Mbit link is present.
It flashes at a faster rate when the switch is being upgraded
or set back to factory default settings by using the button
on the back of the switch.
Flashing greenFlashing indicates data is being transmitted over the
gigabit link on the 1783-EMS08T switch that has a gigabit
fiber transceiver on the bottom of the switch.
(1) Appears on all copper Ethernet por ts.
20Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Chapter 2
Network Services Setup
This chapter covers information related to network services setup using the
switch’s web interface, including how to configure these protocols:
• Simple Network Management Protocol (SNMP)
• Internet Group Management Protocol (IGMP)
• Dynamic Host Configuration Protocol (DHCP)
For information about how to access the web interface for the switch, refer to
Chapter 1
.
SNMP
Simple Network Management Protocol (SNMP) specifies the diagnostic data
that a host computer must maintain for network management software. Hosts
typically keep statistics on the status of their network interfaces, incoming and
outgoing traffic, dropped datagrams, and error messages generated. Network
management protocols let network management software access these statistics.
SNMP is based on three concepts:
• SNMP managers, also known as client software or SNMP browsers
• SNMP agents, also known as network devices or SNMP servers
• Management Information Base (MIB)
The SNMP manager runs SNMP management software. Network devices to be
managed, such as bridges, routers, servers, and workstations, have an agent
software module. The agent provides access to a local MIB of objects that reflects
the resources and activity of the device. The agent also responds to manager
commands to retrieve values from the MIB. The agent and the MIB are on the
switch. To configure SNMP on the switch, you define the relationship between
the manager and the agent.
The Stratix 6000 switchsupports SNMP versions 1 and 2.
• SNMP versions 1 and 2 are generally used for network monitoring
without network control.
• The supported versions use a community-based form of security. SNMP
managers can access the agent MIB through passwords referred to as
community names.
• The Stratix 6000 switch automatically recognizes the SNMP version from
an incoming request, but you must manually set the version for SNMP
trap destinations, as described on page 24
.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201321
Chapter 2Network Services Setup
Supported MIBs
The Stratix 6000 switch supports the MIBs listed below.
• MIB-II—The published definition of MIB-II has been modified for the
Stratix 6000 switch, as described in MIB-II Modifications
detailed definition of MIB-II, refer to RFC 1213 at http://www.ietf.org/
rfc/rfc1213.txt.
• ETHERLIKE-MIB—For a detailed definition, refer to RFC 1643 at
http://tools.ietf.org/html/rfc1643
• RMON-MIB—The Stratix 6000 supports only the Ethernet Statistics
Group in the RMON-MIB. For a detailed definition, refer to RFC 2819 at
http://tools.ietf.org/html/rfc2819
.
.
MIB-II Modifications
Standard read-write access has been changed to read-only access for the MIB-II
variables listed below.
22Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Network Services SetupChapter 2
ip.ipNetToMediaTable.ipNetToMediaEntry.ipNetToMediaIf Index
ip.ipNetToMediaTable.ipNetToMediaEntry.ipNetToMediaPhysAddress
ip.ipNetToMediaTable.ipNetToMediaEntry.ipNetToMediaIpAddress
ip.ipNetToMediaTable.ipNetToMediaEntry.ipNetToMediaType
(A static entry cannot be added into the ARP cache table)
tcp.tcpConnTable.tcpConnEntry.tcpConnState
(An established or pending TCP connection cannot be reset)
SNMP Configuration
Enable SNMP if you want to run SNMP on your network. SNMP is disabled by
default.
Before configuring SNMP settings, understand these concepts:
• Community names—Community names are passwords to the switch
Management Information Base (MIB) that allow a remote manager readonly or read-write access to the switch. The Stratix 6000 switch supports
one read-only community name and one read-write community name.
You can change the default names.
• SNMP traps—SNMP traps are unsoliticited messages sent to a remote
manager from an agent. Traps are an efficient way to inform managers that
are connected to a large number of devices with many objects. By
providing unsolicited messaging, traps can reduce SNMP polling by a
manager. The Stratix 6000 switch supports two destination traps that can
be enabled or disabled. By default, both traps are disabled.
Use these steps to configure SNMP.
1. From the navigation pane, expand the Network Services Setup folder and
select SNMP Configuration.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201323
Chapter 2Network Services Setup
2. From the SNMP Enabled pull-down menu, choose Enabled to use SNMP.
3. Change the deault case-sensitive community names if desired.
• The read-only community enables the switch to validate Get (read-
only) requests from a network management station. If you set the
SNMP read community, users can access MIB objects, but cannot
change them.
• The read-write community enables the switch to validate Set (readwrite) requests from a network management station.
4. In the System Info area, provide optional information about the switch for
informational purposes only.
a. In the Location field, type the physical location of the switch, such as
the building where the switch is locatd.
b. In the Contact field, type the switch name or network administrator.
5. Identify up to two trap destinations by completing the fields below.
Trap Destination FieldDescription
EnabledCheck to enable trap messages to be sent.
IP AddressType the IP address of the SNMP trap recipient.
PortType the UDP port number to which traps will be sent.
The default port number is 162.
CommunityType the read-only or read-write SNMP community name to be used in
SNMP VersionChoose the SNMP version to use.
traps sent to the destination.
Community names are case-sensitive.
6. Click Apply Changes.
The changes will take effect immediately without requiring you to cycle
power to the switch.
24Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Network Services SetupChapter 2
IGMP
Internet Group Management Protocol (IGMP) snooping sorts multicasting
devices into groups. This limits the multicast packets received by hosts that do
not need the information and makes the network more efficient and
deterministic.
OptionDescription
BroadcastWithout IGMP snooping, an I/O module acts like a broadcasting device and all
devices on the subnet are flooded with I/O traffic.
MulticastIGMP snooping filters the I/O traffic from devices that are not in the intended
multicast group.
UnicastA message instruction from one Logix controller to another is an example of
unicast; it contains one source and one destination address.
By default, IGMP is disabled. Enable IGMP snooping when I/O is running on
your network. IGMP helps to isolate this UDP traffic to ports that need to
receive it. When it is not used, other devices may be slowed down by the
continuous flow of UDP packets.
IGMP Product Support
Rockwell Automation products support IGMP, version 2.
When using the Logix Designer application to configure your switch, consider
the following:
• Settings on the IGMP page in the Add-on Profile overwrite settings made
on the web management interface.
• If you are scanning the 1783-EMS switch with the Logix Designer
application, use the IGMP page in the Add-on Profile to configure IGMP
to avoid confusion. See Appendix E
The switch manages a report of IGMP information, including multicast groups,
querier information, and IGMP states per virtual local-area network (VLAN).
The report is available through the web interface. For more information about
this report, refer to IGMP Report
on page 45.
for more information.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201325
Chapter 2Network Services Setup
IGMP Querier
The IGMP querier function can be enabled to query your network for group
information at a specified time interval. The configuration options available for
IGMP querier depend on whether VLANs are enabled on your network.
• If you plan to use VLANs on your network, the IGMP querier function
can be enabled for only one VLAN per switch. The IP address of the
querier may be different on each VLAN.
You can choose to assign the querier to the management VLAN or a
custom VLAN. The querier is assigned to the management VLAN by
default.
– If the querier is assigned to the management VLAN, the querier IP
address is the IP address defined on the Network Configuration tab, as
described in Set the IP Address
– If you want to assign the querier to a custom VLAN, you must first set
up the custom VLAN on the VLAN Configuration tab, as described in
VLAN Configuration
on page 57. Assigning the querier to a custom
VLAN requires you to know which IP address you want to assign to the
querier.
• If you do not plan to use VLANs on your network, you can enable or
disable a single querier instance on the network. The querier function is
enabled by default. If more than one querier instance is detected on the
network, only the querier with the lowest IP address is active. All other
queriers are silent.
on page 15.
26Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Network Services SetupChapter 2
IGMP Configuration
Use these steps to configure IGMP.
1. From the navigation pane, expand the Network Services Setup folder and
select IGMP Configuration.
2. From the IGMP Snooping pull-down menu, choose Enabled to use IGMP
snooping.
When you enable IGMP snooping, additional configuration options
appear on the screen.
3. From the IGMP Version menu, choose version 1 or 2.
Version 2 is the default when IGMP snooping is enabled and is the
recommended setting. Per the IGMP definition, hosts and routers
implementing differing IGMP versions will interoperate correctly on the
network.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201327
Chapter 2Network Services Setup
IMPORTANT
Additional fields appear when you
choose the Enabled on Custom
VLAN querier mode.
4. If VLAN is not enabled on the switch, choose to enable or disable the
IGMP querier function from the Querier Mode pull-down menu.
or
If VLAN is enabled on the switch, choose one of these options from the
Querier Mode pull-down menu:
• Disabled—The IGMP querier function is disabled on all VLANs.
• Enabled on Management VLAN—The IGMP querier function is
enabled and assigned to the management VLAN only. This is the
default setting. For more information about setting up the management
VLAN, refer to VLAN Configuration
on page 57.
• Enabled on Custom VLAN—The IGMP querier function is enabled
and assigned to a custom VLAN. If you choose this option, you must
also specify the querier VLAN and IP address as described in step 6
5. In the Querier Period field, specify a time interval in minutes, 1…60, to
determine how often your network is queried for group information.
The default querier period is 2 minutes.
.
Specify the same number of minutes on all switches in the network.
The querier period must be specified even if the querier function is
disabled.
6. If you chose the Enabled on Custom VLAN querier mode, complete the
fields described below.
• Querier VLAN—Choose the custom VLAN to which to assign the
querier.
• Querier IP Address—Type the IP address of the querier running on the
custom VLAN.
28Rockwell Automation Publication 1783-UM001D-EN-P - January 2013
Network Services SetupChapter 2
TIP
7. In the Router Ports Configuration area, choose the methods to use for
detecting when a multicast router is connected to a switch port.
When a multicast router, including IGMP querier, is connected to a switch
port, all multicast packets and IGMP reports are forwarded on that port.
This behavior is important for the proper functioning of IGMP snooping.
You can enable one or both of the following options:
• Autodetect—Accept the default setting of Enabled if you want the
switch to automatically determine whether an end station or multicast
router is connected to its ports. To determine which type of device is
connected to a port, the switch uses Cisco Discovery Protocol (CDP)
or Multicast Router Discovery (MRD).
• Manual—Enable this setting if you need to connect a switch from a
different vendor that does not support CDP or MRD protocols. When
you enable the Manual setting, a series of checkboxes appears, so you
can specify which ports will be connected to a router that does not
support CDP or MRD protocols.
8. From the Multicast Packets Forwarding pull-down menu, choose where to
forward multicast packets.
• To Listeners Only—The switch forwards multicast packets to ports in
the Listening state only.
• To Listeners and Uplink Port—The switch forwards multicast packets
to ports in the Listening state and the uplink port. This is the default
setting.
This setting is useful if you need to route multicast packets between
two networks.
• To Listeners and All Snooper Ports (Standard)—The switch forwards
multicast packets to ports in the Listening state and to all multicast
routers, or snoopers. Use this setting if you want multicast traffic to be
filtered only on ports where end stations are connected and not
between switches.
9. From the Uplink Port pull-down menu, choose Autodetect (Querier) if
you want the Stratix 6000 switch to automatically determine the uplink
port. Otherwise, set the uplink port manually by choosing a specific port.
10. Click Apply Changes.
The changes will take effect immediately without requiring you to cycle
power to the switch.
Rockwell Automation Publication 1783-UM001D-EN-P - January 201329
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.