Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
at http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you
identify a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
ATTENTION: This equipment is intended for use in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft)
without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require
additional system enclosure when used in locations consistent with the
enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information
regarding specific enclosure type ratings, beyond what this product provides,
that are required to comply with certain product safety certifications.
The DeviceNet 1732D ArmorBlock I/O family consists of standalone 24V DC I/O
modules that communicate via the DeviceNet network. The sealed IP67 housing of these
modules requires no enclosure. Note that environmental requirements other than IP67
may require an additional appropriate enclosure. I/O connectors are sealed M12-style.
The 1732D-IBDPM12MND module is shown here.
The DeviceNet network uses advanced network technolog y, producer/consumer
communication, to increase network functionality and throughput. Visit our web site
atwww.ab.com/networks
for producer/consumer technology information and updates.
Catalog Number Explanation
The catalog number 1732D-IBDPM12MND refers to a DeviceNet 24V DC 8-port,
16-input mini-style network connector module.
Install the Module
To install the module:
• Set the node address.
•Mount the module.
• Connect the cordsets.
Set the Node Address
Valid node addresses are 00…63.
Set the node address using either the rotary switches, RSNetWorx for DeviceNet,
DeviceNetManager, or another software configuration tool. Setting the switches at 64…99
lets the software have address control.
Each module is shipped with their node address set at 63. Remove the caps on the front of
the module to access the switches. The two switches are:
• X10 (most significant digit) – left side of module
• X1 (least significant digit) – right side of module
To reset the node address:
1. Rotate the switches using a small-bladed screwdriver.
2. Line up the small black dot on the switch with the number setting you wish
to use.
This example shows
the default node
address set at 63.
Node Address Default Setting
The rotary switches are read periodically. If the switches have been changed since the last
time they were read and no longer match the online address, a minor fault occurs, which is
indicated by the module indicator flashing red.
Settings of 64…99 cause the module to use the last valid node ad dress stored internally. For
example, if the last setting internally was 40 and the setting is changed to 68, when you
power up, the address defaults back to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the module read the
settings already in use on your DeviceNet network and automatically adjusts to
those settings.
Mount the Module
Use the two sets of mounting holes to mount the module directly to a panel or machine.
Mounting holes accommodate #6 (M3) pan-head screws. The torque specification is
0.64 Nm (6 lb-in.).
Refer to the mounting dimensions diagram to help you mount the module.
If you mount the module in an area that is subject to shock or vibration, we recommend
you use a flat and a lock washer to mount the module. Mount the flat and the lock washer
as shown in the mounting diagram. Torque the mounting screws to 0.64 Nm (6 lb-in.).
The ArmorBlock DeviceNet family has 5-pin micro-style connectors. We provide caps to
cover the unused connectors on your module. Connect the quick-disconnect cordsets you
selected for your module to the appropriate ports.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected
I/O must be powered from a source compliant with the following: Safety Extra
Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Network Connector
Refer to the pinout diagram for the network connector.
Mini-style Input Male Connector
1
2
5
4
3
I/O Connectors
Refer to the pinout diagram for the I/O connector.
Refer to Cordsets and Field Attachables, publication M117-CA502A, or visit the
Connection Devices website, http://www.ab.com/connectionsystems
ATTENTION: Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP enclosure
type requirements.
.
Communicate with the Module
This module’s I/O is exchanged with the master through a cyclic, polled, or
change-of-state connection.
• Cyclic: Allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.
• Polled: A master initiates communication by sending its polled I/O message to
the module. The module consumes the message, updates outputs, and produces a
response. The response has input data.
• Change-of-state: Productions occur when an input changes or a fault condition
occurs. If no input or fault condition change occurs within the expected packet
rate, a heartbeat production occurs. This heartbeat production tells the scanner
module that the I/O module is alive and ready to communicate. Consumption
occurs when data changes and the master produces new output data to the
I/O block.
Refer to the Module Data Definitions table for more information.
1732D-IBDPM12MND Data Definitions
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Produce 0 I7I6I5I4I3I2I1I0
Produce 1I15I14I13I12I11I10I9I8
Produce 2In short
Where:I = Input data; 0 = Off, 1 = On
In short 0 = Working, 1 = Sensor source voltage fault
GreenDevice is online and has one or more I/O connections in
Flashing greenDevice needs commissioning due to missing, incomplete, or
RedCritical fault – device timed out or has an unrecoverable fault.
Flashing redRecoverable fault – input or output short circuit.
Network status OffDevice is not online:
GreenDevice operating normally. As a Group 2 module, it means that the
Flashing greenDevice is online with no connections in the established state.
RedCritical link failure – failed communications module.
Flashing redRecoverable fault – an I/O connection has timed out.
I/O statusOffI/O is not energized or is not valid.
YellowI/O is energized and valid.
established state.
incorrect configuration.
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Number of inputs16
Input type61131-2 Type 3 compatible
Off-state input voltage, max 5V DC
On-state input voltage, min 11V DC
On-state input voltage, nom 24V DC
On-state input voltage, max 25V DC
Sensor source voltage, min 11V DC
Sensor source voltage, max 25V DC
Off-state input current, max 1.5 mA @ 5V DC
On-state input current, max 5 mA @ 25V DC
(1)
(2)(3)
0…16,000 s
11…25V DC
500 mA
1 green/red – network status
16 yellow – input status
No isolation between individual inputs
Type tested @ 707V DC for 60 s
250 Kbps @ 200 m (600 ft) for thick cable, flat media length 150 m (492 ft)
500 Kbps @ 100 m (330 ft) for thick cable, flat media length 75 m (246 ft)
179 x 65 x 43.25 mm
(7.05 x 2.56 x 1.70 in)
dust caps or cable termination
1 – on signal ports
2 – on communication ports
Input delay time
Off to On
On to Off
DeviceNet power
voltage range
Sensor source current
per module, max
DeviceNet current75 mA plus sum of sensor currents
Indicators1 green/red – module status
Isolation voltage50V (continuous), Basic Insulation Type, inputs to network
Communication rate125 Kbps @ 500 m (1640 ft) for thick cable, flat media length 375 m (1230 ft)
Dimensions (HxWxD),
approx.
Enclosure type ratingMeets IP65/66/67/69K (when marked), and NEMA 4X/6P with receptacle
Input Off-to-On or On-to-Off delay is time from a valid input signal to recognition by the module.
(2)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
(3)
Refer to Connection Systems, publication C116-CA508.
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±3 kV @ 5 kHz on signal ports
±2 kV @ 5 kHz on communication ports
ODVAODVA conformance tested to DeviceNet specifications
(1)
See the Product Certification lin k at http://www.ab.com for Declaration of Conformity, Certificates, and other
certification details.
Valu e
(1)
UL File E322657.
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United StatesPlease contact your local Rockwell Automation representative for the return
(call the phone number above to obtain one) to your distributor to complete
the return process.
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
.
, available at
Allen-Bradley, Rockwell Automation, ArmorBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1732D-IN007B-EN-E - November 2011PN-126462