Rockwell Automation 1336Z User Manual

1336 SPIDER Adjustable FrequencyACDrive for the Fibers Industry
9.9A-60.0A Firmware Version 2.xxx-5.xxx
User Manual
Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-1.1 available from your local Rockwell Automation Sales Office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss.
Attentions help you:
identify a hazard
avoid the hazard
recognize the consequences
Important:Identifies information that is especially important forsuccessful
application and understanding of the product.
Shock Hazard labels may be located on or inside the drive to alert people that dangerous voltage may be present.
Burn Hazard labels located on the front of the drive alerts people about a hazard of burns. Do not touch the heatsink surface during operation of the drive. After disconnecting power allow time for cooling.
SCANport is a trademark of Rockwell Automation, Inc. PLC is a registered trademark of Rockwell Automation, Inc. IBM is a registered trademark of International Business Machines Corporation. Windows 95 is a registered trademark of Microsoft Corporation.
Summary of Changes

Manual Changes The information below summarizes the changes to the 1336 SPIDER

User Manual since the last release. In general, this includes new
information pertaining to Firmware 5.xxx.
Description of Change Page(s)
Step Logic function added (see New and Updated Parameters below).
Updated Parameters:
[Freq Select 1] [Current Limit] [Freq Select 2] [Language] [Flying Start En] [LLoss Restart] [TB5 Term 2x Sel] [CRx Out Select] [Freq Source] [Break Freq]
New Parameters:
[SLx Logic Step] [SLx Logic Jump] [SLx Step Jump] [SLx Step Setting] [SLx Time] [SLx Encoder Cnts]
[Current Step] Parameter Cross References updated Parameter Record updated
7–60
7–8, 7–16 7–9 7–16 7–21 7–21 7–22 7–27 7–28 7–38 7–57
7–61 7–62 7–62 7–62 7–63 7–63 7–63
A–4 A–11
soc–2 Summary of Changes
Notes

Table of Contents

Chapter 1
Information and Precautions Manual Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
Nameplate Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–3
Chapter 2
General Installation for All Drives
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–1
Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–2
AC Supply Source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–3
Input Power Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–3
Input Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–4
Input Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–5
Electrical Interference - EMI/RFI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–5
RFI Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–6
CE Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–6
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–6
Power Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–9
Output Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–12
Cable Termination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–13
Adapter Definitions and Communication Option Installation. . . . . . . . . . 2–14
Chapter 3
Installation/Wiring for Stand­Alone Drives
Control and Signal Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–2
Pulse Input/Output Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
Analog I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
Standard Analog I/O Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
Optional Analog I/O Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–11
Chapter 4
Installation/Wiring for PLC Control Drives
Control and Signal Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
Chapter 5
Human Interface Module HIM Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
HIM Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
Handheld HIM Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–13
Chapter 6
Start-Up Start-Up Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
Initial Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
Assisted Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
Advanced Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
toc–ii Table of Contents
Chapter 7
Programming Function Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
Programming Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
Chapter Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
Chapter 8
Troubleshooting Fault Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–1
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–9
Appendix A
Specifications and Supplemental Information
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–1
Derating Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–3
Parameter Cross Reference - By Number . . . . . . . . . . . . . . . . . . . . . . . . A–4
Parameter Cross Reference - By Name. . . . . . . . . . . . . . . . . . . . . . . . . . A–5
HIM Character Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–6
Communications Data Information Format . . . . . . . . . . . . . . . . . . . . . . . A–7
Typical Programmable Controller Communications Configurations. . . . . A–9
Typical Serial Communications Configurations . . . . . . . . . . . . . . . . . . . A–10
Read/Write Parameter Record. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–11
Initial Parameter Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–12
Dimensions Appendix B
Appendix C
CE Conformity Requirements for Conforming Installation . . . . . . . . . . . . . . . . . . . . . . . . C–2
Electrical Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–2
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–4
Appendix D
Flash Memory What is Flash Memory?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D–1
Firmware Download Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D–1

Chapter 1

Information and Precautions

Chapter 1 provides information on the general intent of this manual, gives an overall description of the 1336 Frequency AC Drive and provides a listing of key drive features.

Manual Objectives This publication provides planning, installation, wiring and

diagnostic information for the Stand-alone (full I/O) and PLC control (limited I/O) 1336 SPIDER Drive. To assure successful installation and operation, the material presented must be thoroughly read and understood before proceeding. Particular attention must be directed to the Attention and Important statements contained within.

Catalog Number Explanation The diagram below describes the SPIDER catalog numbering system.

SPIDER Adjustable
1336Z
First Position
Bulletin Number
1
P
Second Position
Drive Types
Letter Type
P PLC Control S Stand-Alone
Control
This current is only possible with synchronous motors and for spinning applications. For actual motor current rating, refer to Appendix A.

Conventions Used in this Manual

General Precautions

A
Third Position
Voltage
Letter Voltages
A 200-240V AC or
310V DC
B 380-480VAC or
513-620V DC
022
Fourth Position
Peak Current Rating
Code Peak Current
022 21.6A 036 36.0A 060 60.0A
010 9.9A 017 16.5A 033 33.0
N
Fifth Position
1
Enclosure Type
Code Type
N IP 20 (Open Type)
with Line Choke
AE IP 20 (Open Type)
with EMC Filter
GM1
Sixth Position
Communication Options
Code Description
GM1 Single Point Remote I/O GM2 RS-232/422/485, DF1 &
DH485 GM5 DeviceNet™ GM6 Enhanced DeviceNet
To help differentiateparameter names and display text from other text the following conventions will be used:
Parameter Names will appear in [brackets]
Display Text will appear in “quotes”
ATTENTION: Only personnel familiar with the 1336
SPIDER Adjustable Frequency AC Drive and associated
!
machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failureto comply may result in personal injury and/or equipment damage.
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life.
!
Wiring or application errors, such as, undersizing the motor, incorrect or inadequate ACsupply, or excessive ambient tem­peratures may result in malfunction of the system.
1–2 Information and Precautions
General Precautions (continued)
ATTENTION:Toavoidahazardof electric shock,verifythat the voltage on the bus capacitors has discharged before
!
performinganyworkon thedrive.MeasuretheDCbusvoltage atthe + &–terminalsof thePowerTerminalBlock(see Figure
2.1 for location). The voltage must be zero. ATTENTION: This drive contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control pre-
!
cautions are required when installing, testing, servicing or repairingthisassembly.Componentdamage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “GuardingAgainst Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: Ground fault detection devices must not be used on this drive as the sole protection measure against unin-
!
tentionalshockhazard. TheDCcomponentin the groundfault current may inhibit the correct function of the fault detector.
ATTENTION:ACdrivescancause disturbancestothesupply network. The basic version of the 1336 SPIDER Drive does
!
not include any harmonic filters and may not fulfill the limits of the national recommendations. The harmonic voltage dis­turbances produced by the drive are dependent on the supply network impedance.
Machinery Directive
ATTENTION: The 1336 SPIDER Drive is a component intended for implementation in machines or systems for the
!
capital goods industry. The start-up of the drive in the European market is not
permitted until it has been confirmed that the machine into which the drives are built is in conformance with the regulations of the Council Directive Machinery 89/392/EWG.
ATTENTION: The built-in Stop function (control input at terminal20-25)mustnotbeusedasanemergencystopcircuit.
!
To inhibit uncontrolled machine operation in case of the mal­function of the drive, the user must provide an external emergency stop circuit, which ensures disconnection of the power source from the motor. This circuit must be hardwired with electro-mechanic components and shall not depend on electronic logic or software. The stopping device (e.g. mushroom head pushbutton with lock) must be accessible to the operator. Failure to observe this precaution could result in bodily injury or loss of life.

Nameplate Location

Information and Precautions 1–3
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
L1 L2 L3
45 (–) 47 (+)
48
U V W
PE
Nameplate Located on
Side Panel
9.9A through 36A Drives
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
Nameplate Located on
33A and 60A Drives
Side Panel
14 Information and Precautions
End of Chapter 1

Chapter 2

General Installation for All Drives

Chapter 2 provides the information you need to properly mount and wire the main power connections of 1336 SPIDER Drives. In addition, installation instructions are provided for the communication options (GM1, GM2, etc.). Detailed control and signal wiring for the Stand-alone or PLC control version is presented in Chapter 3 or 4, respectively. Since most start-up difficulties are the result of incorrect wiring, every precaution must be taken to assure that the wiring is done as instructed. All items must be read and understood before the actual installation begins.
ATTENTION: Thefollowinginformationismerely a guide for proper installation. The Allen-Bradley
!
Company cannot assume responsibility for the complianceorthenoncompliancetoanycode,national, localorotherwisefortheproperinstallationofthisdrive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Mounting Minimum Mounting Requirements for Proper Heat Dissipation

(Dimensions shown are between drives or other devices)
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
101.6 mm (4.0 in.)
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
Normal Spacing
5.1 mm (0.2 in.)
15.2 mm (0.6 in.) Required to
Remove Cover
101.6 mm (4.0 in.)
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
UP
101.6 mm (4.0 in.)
101.6 mm (4.0 in.)
22 General Installation for All Drives

Installation Guidelines

GND
CAT. NO. FREQUENCY POWER RATING PRIMARY VOLTAGE SECONDARY VOLTAGE INSULATION CLASS NO. OF PHASES VENDOR PART NO.
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
AC Supply Source
Harmonics/RFI/EMC
Page 2–3
Page 2–5 & Appendix C
ALLEN-BRADLEY
Input Power Conditioning
Input Fusing & Circuit Breakers
Input Devices
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
Electrical Interference
Grounding
Page 2–3
Page 2–4
Page 2–5
Page 2–5
Page 2–6
PE
Power Cabling
Control & Signal Cabling
Output Devices
Cable Termination
Page 2–9
Chapters 3 & 4
Page 2–12
Page 2–13
Motor
General Installation for All Drives 2–3

AC Supply Source 1336 SPIDER drives are suitable for use on a circuit capable of

delivering up to a maximum of 200,000 rms symmetrical amperes, 600 volts.
ATTENTION: To guard against personal injury and/or equipmentdamage causedby improperfusing, useonly the
!
recommended line fuses specified in Table 2.A.
Unbalanced Distribution Systems
This drive is designed to operate on earthed-neutral, three-phase supply systems whose line voltages are symmetrical. 240V ACdrives may be operated with one phase referenced to ground.
Ungrounded Distribution Systems
1336 SPIDER drives are not designed to operate in ungrounded systems.

Input Power Conditioning In general, the 1336 SPIDER is suitable for direct connection to an

AC line of the correct voltage. Certain conditions can exist, however, that prompt consideration of a line reactor or isolation transformer ahead of the drive.
The basic rules to aid in determining whether a line reactor or isolation transformer should be considered are as follows:
1. If the AC source experiences frequent power outages or
significant voltage transients, users should calculate the source transformer VA. If thesource transformer VA exceeds the VAmax (1MVA) and the drive is installed close to the source, it is an indication that there may be enough energy behind these voltage transients to cause nuisance input fuse blowing, overvoltage faults or drive power structure damage. In these cases, a line reactor or isolation transformer should be considered.
2. If the AC source does not have a neutral or one phase referenced
to ground (see Unbalanced Distribution Systems), an isolation transformer with the neutral of the secondary grounded is required. If the line-to-ground voltages on any phase can exceed 125% of the nominal line-to-line voltage, an isolation transformer with the neutral of the secondary grounded, is
3. If the AC line supplying the drive has power factor correction
capacitors that are switched in and out, an isolation transformer or 5% line reactor is recommended between the drive and capacitors. If the capacitors are permanently connected and not switched, the general rules above apply.
highly recommended.
2–4 General Installation for All Drives

Input Fuses The 1336 SPIDER should be installed with input fuses. However,

local/national electrical codes may determine additional requirements for these installations.
Installations per U.S. NEC/UL/CSA
In general, the specified fuses are suitable for branch short circuit protection and provide excellent short circuit protection for the drive. The fuses offer a high interrupting capacity and are fast acting. Refer to the North American selections in Table 2.A.
IEC Installations
For those installations that are not required to meet the U.S. NEC/
UL/CSA, the specified fuses are suitable for branch short circuit protection and provide excellent short circuit protection for the drive. The fuses offer a high interrupting capacity and are fast acting. Refer to the selections in Tables 2.A and 2.B.
ATTENTION: The 1336 SPIDER does not provide input powershort circuit protection.Specifications forthe recom-
!
mendedfusetoprovidedriveinputpowerprotectionagainst short circuits is provided.
Table 2.A Maximum Recommended AC InputLine Fuse Ratings (fuses are user supplied)
European Installations
The recom­mended fuse is Class gG, general industrial applica­tions.
NorthAmerican Installations
The recom­mended fuse is UL Class CC, T or J.
Drive Catalog Number
1336Z- _ A022 3.0 1.8 30A 1336Z- _ A036 5.0 3.0 30A 1336Z- _ A060 8.3 5.0 50A 1336Z- _ B010 2.7 1.6 20A 1336Z- _ B017 4.6 2.7 20A 1336Z- _ B033 9.1 5.5 40A
Drive Output kVA Rating
Drive Output kW Rating
Table 2.B Recommended Fuses for Shared DC Bus Applications
(Fuses must be mounted between the drive and the shared DC bus)
AC Line Rating Description Fuse Type
240V AC with Earthed Transformer
Star Point
with B Phase Grounded AJT (Gould or equivalent),
480V AC with Earthed Transformer
Star Point
LP-CC (Bussmann or equivalent), 300V DC rating
AJT (Gould or equivalent), 500V DC rating
500V DC rating AJT (Gould or equivalent),
500V DC rating
Maximum Fuse Rating
Maximum Fuse Rating
See Table
2.A
General Installation for All Drives 2–5

Input Devices Starting and Stopping the Motor

ATTENTION: The drive start/stop control circuitry in­cludes solid-statecomponents. If hazards due to accidental
!
contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop cir­cuit may be required to remove ACline power to thedrive. WhenAC power isremoved, there will be a lossof inherent regenerativebrakingeffect &the motor will coast toa stop. An auxiliary braking method may be required.
Repeated Application/Removal of Input Power
ATTENTION: The drive is intended to be controlled by control input signals that will start and stop the motor. A
!
device that routinely disconnects then reapplies line power to the drive for the purpose of starting and stopping the motor is not recommended.

Electrical Interference - EMI/RFI Immunity

The immunity of 1336 SPIDER drives to externally generated interference is good. Usually, no special precautions are required beyond the installation practices provided in this publication.
Since coils can generate severe electrical transients, it is recommended that the coils of DC energized contactors associated with drives be suppressed with a diode or similar device. AC supplied coils should utilize an R-C suppressor.
Emission
Careful attention must be given to the arrangement of power and ground connections to the drive to avoid interference with nearby sensitive equipment. The cable to the motor carries switched voltages and should be routed well away from sensitive equipment.
The ground conductor of the motor cable must be connected to the drive ground (PE) terminal directly. Connecting this ground conductor to a cabinet ground point or ground bus bar may cause high frequency current to circulate in the ground system of the enclosure. The motor end of this ground conductor must be solidly connected to the motor case ground.
Shielded cable must be used to guard against radiated emissions from the motor cable. The shield must be connected to the drive ground (PE) terminal and the motor ground as outlined above. Armored cable can be used if radiation is not a concern.
2–6 General Installation for All Drives
The drive has a smallcommon mode choke in the power output (U, V & W). On installations that do not use shielded cable, additional common mode chokes can help reduce common mode noise at the drive output. Common mode chokes can also be used on analog or communication cables. Refer to page 2–13 for further information.
An RFI filter can be used and in most situations provides an effective reduction of RFI emissions that may be conducted into the main supply lines.
If the installation combines a drive with sensitive devices or circuits, it is recommended that the lowest possible drive PWM carrier frequency be programmed.

RFI Filtering 1336 SPIDER drives can be ordered with an integral RFI filter, which

controls radio-frequency conducted emissions into the main supply lines and ground wiring.
If the cabling and installation recommendation precautions described in this manual are adhered to, it is unlikely that interference problems will occur when the drive is used with conventional industrial electronic circuits and systems. However, a filter may be required if there is a likelihood of sensitive devices or circuits being installed on the same AC supply.
Where it is essential that very lowemission levelsmust be achievedor if conformity with standards is required the optional RFI filter must be used. Refer to Appendix C for installation and grounding information.

CE Conformity Refer to Appendix C.

Grounding Refer to the grounding diagram on page 2–8. The drive must be

connected to system ground at the power ground (PE) terminal. Ground impedance must conform to the requirements of national and local industrial safety regulations (NEC, VDE 0160, BSI, etc.) and should be inspected and tested at appropriate and regular intervals.
In any cabinet, a single, low-impedance ground point or ground bus bar should be used. All circuits should be grounded independently and directly. The AC supply ground conductor should also be connected directly to this ground point or bus bar.
Sensitive Circuits
It is essential to define the paths through which the high frequency ground currents flow. This will assure that sensitive circuits do not share a path with such current. Control and signal conductors should not be run near or parallel to power conductors.
General Installation for All Drives 2–7
Motor Cable
The ground conductor of the motor cable (drive end) must be connected directly to the drive ground (PE) terminal (see General Grounding on page 2–8), not to the enclosure bus bar. Grounding directly to the drive (and filter, if installed) can provide a direct route for high frequency current returning from the motor frame and ground conductor. At the motor end, the ground conductor should also be connected to the motor case ground.
If shielded or armored cables are used, the shield/armor should also be grounded at both ends as described above.
Discrete Control and Signal Wiring
The control and signal wiring must be grounded at the drive (see General Grounding on page 2–8). If shielded control and signal wires are used, the shield must also be grounded at the drive end only.
If the control and signal wires are short, and contained within a cabinet which hasno sensitive circuits, the use of shielded control and signal wiring may not be necessary, but is always recommended.
Safety Ground - PE (Potential Earth)
This is the safety ground required by code. This point must be connected to adjacent building steel (girder, joist) or a floor ground rod, provided grounding points comply with national or local electric code regulations. The line input PE wire must be connected to the bottom PE terminal (see General Grounding on page 2–8). If a cabinet ground bus is used, refer to Grounding on page 2–6.
RFI Filter
Important: Using the integral RFI filter may result in relatively high
ground leakage currents. Surge suppression devices are incorporated in the drive. The filter must be solidly grounded. Grounding must not rely on flexiblecables and should not include any form of plug or socket that would permit inadvertent disconnection. The integrity of this connection should be periodically checked.
2–8 General Installation for All Drives
General Grounding
Conduit/4-Wire Cable
to Motor & Signal PE Ground
Nearest
Building Structure Steel
(for further grounding info, see "
PWR RUN STOP FAULT
PE
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
L1 (R)
L2 (S)
L3 (T)
Do Not Use
PE
RIO/DH+
Common
or Analog
Mode Core*
To Computer/Position Controller
Control and Signal Wiring" in Chapter 3 or 4
Single-Point Grounding/Panel Layout
L1 (R)
U (T1) V (T2) W (T3) PE/Gnd.
Common
Mode Core*
Shield*
Shield
Motor
Terminator*
)
Motor Frame
PE
Ground per
Local Codes
* Options that can be
installed as needed.
Nearest
Building Structure Steel
L2 (S)
L3 (T)
Zero Volt Potential Bus
(Isolated from Panel)
PE Ground Bus
(Grounded to Panel)
For Programmable Controller grounding recommendations, refer to publication 1770-4.1
1336 SPIDER 1336 SPIDER
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
PE PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
To Nearest Building
Structure Steel
Nearest Building
Structure Steel
Important:Grounding requirementswillvarywith the drivesbeingused. Other driveswithTrueEarth (TE)terminalsmusthave azeropotentialbus, separate frompotential earth(PE) ground bus. Notethat busescanbe tied together atonepoint in the control cabinetorbrought back separately tothebuilding ground grid (tied within3meters (10 feet)).
General Installation for All Drives 2–9

Power Cabling Input and output power connections are performed through the power

terminal blocks (see Figure 2.1 for location). Important: For maintenance and setup procedures, the drive may be
operated without a motor connected.
ATTENTION: The National Codes and standards (NEC, VDE,BSI etc.) andlocalcodes outlineprovisionsfor safely
!
installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection anddisconnect devices.Failure to do so may result in personal injury and/or equipment dam­age.
Figure 2.1 Power Terminal Block Locations
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTA GE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
45 (–) 47 (+)
PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
Power Terminal Blocks
L1 L2 L3
48
U V
W
Cover Removed to
Show Terminal
Blocks
L1 L2 L3 45
M4
(–)47(+)
48 U V W
PE
M4
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTA GE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
Table 2.C Power Terminal Block Signals
Terminal Description
PE Potential Earth Ground L1 (R), L2 (S), L3 (T) AC Line Input Terminals (+) 47 & (–) 45 DC Bus Terminals (+) 47 & 48 Braking Resistor U (T1), V (T2), W (T3) Motor Connection
2–10 General Installation for All Drives
Table 2.D Power Terminal Block Specifications
Drive Catalog Number
1336Z-_ A022 1336Z-_ A036 1336Z-_ B010 1336Z-_ B017
1336Z-_ A060 1336Z-_ B033
1
Motor Cables
A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, long parallel runs mustbe avoided. Usecable with the appropriate insulation class.
Max./Min. Wire Size
mm2 (AWG)
0.2/4 (24/10) M3 0.5-0.6 (4.4-5.3) 7 (0.28)
0.5/10 (20/6) M4 1.2-1.5 (10.6-13.3) 10 (0.39)
Wire sizes given are maximum/minimum sizes that terminal block will accept - these are not recommendations. Use Copper wire only. Wire gauge requirements and recommendations are based on 75 degree C. Do not reduce wire gauge when using higher temperature wire.
1
Screw Size
Torque Range
N-m (lb.-in.)
Remove Insulation
mm (in.)
The cable should be 4-conductor with the ground lead being connected directly to the drive ground terminal (PE) and the motor frame ground terminal.
Shielded Cable
Shielded cable is recommended if sensitive circuits or devices are connected or mounted to the machinery driven by the motor. The shield must be connected to both the drive ground (drive end) and motor frame ground (motor end). The connection must be made at both ends to minimize interference.
If cable trays or large conduits are to be used to distribute the motor leads for multiple drives, shielded cable is recommended to reduce or capture the noise from the motor leads and minimize “cross coupling” of noise between the leads of different drives. The shield should be connected to the ground connections at both the motor and drive end.
Armored cable also provides effective shielding. Ideally it should be grounded only at the drive (PE) and motor frame. Some armored cable has a PVC coating over the armor to prevent incidental contact with grounded structure. If, due to the type of connector, the armor is grounded at the cabinet entrance, shielded cable should be used within the cabinet if power leads will be run close to control signals.
In some hazardous environments it is not permissible to ground both ends of the cable armor because of the possibility of high current circulating at the input frequency if the ground loop is cut by a strong magnetic field. This only applies in the proximity of powerful electrical machines. In such cases, consult factory for specific guidelines.
General Installation for All Drives 2–11
Conduit
If metal conduit is preferred for cable distribution, the following guidelines should be followed.
Drives are normally mounted in cabinets and ground connections
are made at a common ground point in the cabinet. Normal installation of conduit provides grounded connections to both the motor frame ground (junction box) and drive cabinet ground. These ground connections help minimize interference. This is a noise reduction recommendation only, and does not affect the requirements for safety grounding (refer to pages 2–6 and 2–7).
No more than three sets of motor leads can be routed through a
single conduit. This will minimize “cross talk” that could reduce the effectiveness of the noise reduction methods described. If more than threedrive/motor connections per conduit are required, shielded cable as described above must be used. If practical, each conduit should contain only one set of motor leads.
ATTENTION: Toavoidapossible shockhazardcaused by induced voltages, unused wires in the conduit must be
!
grounded at both ends. For the same reason, if a drive shar­ing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will eliminate the pos­sible shock hazard from “cross coupled” drive motor leads.
Motor Lead Lengths
Installations with long cables to the motor may require the addition of output reactors or cable terminators to limit voltage reflections at the motor. Excessive cable charging current can also reduce the amount of current available to produce rated motor torque. Refer to Table 2.E for the maximum cable length allowed for various installation techniques. Shaded distances are restricted by cable capacitance charging current. The figure on the next page illustrates how total cable length iscalculated. Failure to followthese guidelines can result in poor motor performance and nuisance drive overcurrent or overload tripping. For installations that exceed the recommended maximum lengths listed, contact the factory.
Please note that the cable lengths shown are guidelines. Your application may be restricted to a shorter cable length due to wire type, wire placement, line reactor and type of motor.
Dynamic Brake Resistor Wiring
All brake resistor wiring must be twisted wire run in conduit separate from control wiring. Maximum cable length is 2.5 meters (8.2 feet). Size wire according to the “Brake Current” provided on page A–3. Brake resistor dimensions and specifications can be found in Appendix B.
2–12 General Installation for All Drives
How to Measure Motor Cable Lengths Limited by Capacitance
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
PE
15 (50)
90 (295)
90 (295)
165 (540)
180 (590)
150 (490)
15 (50) 15 (50)
All examples represent motor cable length of 180 meters (590 feet).
Table 2.E Maximum Motor Cable Length Restrictions in meters (feet) - 380V-480V Drives
No External Devices 1321-3R55-A Reactor at Drive 1321-3R25-A Reactor at Drive Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
Drive Catalog Number
Peak Current Rating
1
Cable Diameter
mm2 (AWG)
220-240V AC 800V 1000V 1200V 800V 1000V 1200V
1336Z- _ A022 21.6A 2.5 (12) 120 (394) 120 (394) 120 (394) 180 (590) 180 (590) 180 (590) 1336Z- _ A036 36.0A 2.5 (12) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590) 1336Z- _ A060 60.0A 6.0 (8) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590) 180 (590)
380-400V AC 1000V 1200V 1400V 1000V 1200V 1400V 1000V 1200V 1400V
1336Z- _ B010 9.9A 2.5 (12) 15 (50) 105 (344) 105 (344) 30 (98) 180 (590) 180 (590) 60 (197) 1336Z- _ B017 16.5A 2.5 (12) 15 (50) 115 (377) 115 (377) 30 (98) 180 (590) 180 (590) 60 (197) 1336Z- _ B033 33.0A 6.0 (8) 15 (50) 155 (509) 180 (590) 30 (98) 180 (590) 180 (590) 60 (197)
460-480V AC 1200V 1400V 1600V 1200V 1400V 1600V 1200V 1400V 1600V
1336Z- _ B010 9.9A 2.5 (12) 15 (50) 105 (344) 105 (344) 30 (98) 180 (590) 180 (590) 60 (197) 1336Z- _ B017 16.5A 2.5 (12) 15 (50) 115 (377) 115 (377) 30 (98) 180 (590) 180 (590) 60 (197) 1336Z- _ B033 33.0A 6.0 (8) 15 (50) 120 (394) 180 (590) 30 (98) 180 (590) 180 (590) 60 (197)
1
This current is only possible with synchronous motors and for spinning applications. For actual motor current rating, refer to Appendix A.

Output Devices Drive Output Disconnection

ATTENTION: Toguard againstdrive damage, always dis­ablethedrivebefore disconnecting themotorfrom the drive
!
output terminals. Any disconnecting means wired to the drive output terminals U, V and W must be capable of dis­abling the driveif opened duringdrive operation.If opened (motor disconnected) during drive operation, the drive will continue to produce output voltage between U, V, & W (drive damage could occur). An auxiliary contact must be used to simultaneously disable the drive.
General Installation for All Drives 2–13
Common Mode Cores
The 1336 SPIDER includes an integral output common mode core. This will help reduce the common mode noise at the drive output and guard against interference with other electrical equipment (program­mable controllers, sensors, analog circuits, etc.). In addition, reducing the PWM carrier frequency will reduce the effects and lower the risk of common mode noise interference. Refer to the table below for additional information.
Table 2.F 1336 SPIDER Common Mode Chokes
Catalog Number Used with . . . Description
1321-M001 Communications Cables, Analog
Signal Cables, etc.

Cable Termination Optional Cable Terminator

Voltage doubling at motor terminals, known as reflected wave phe­nomenon, standing wave or transmission line effect, can occur when using drives with long motor cables.
Open Style - Signal Level
Inverter duty motors with phase-to-phase insulation ratings of 1200 volts or higher should be used to minimize effects of reflected wave on motor insulation life.
Applications with non-inverter duty motors or any motor with excep­tionally long leads may require an output filter or cable terminator. A filter or terminator will help limit reflection to the motor, to levels which are less than the motor insulation rating.
Table 2.D lists the maximum recommended cable length for untermi­nated cables, since the voltage doubling phenomenon occurs at differ­ent lengths for different drive ratings. If your installation requires longer motor cable lengths, a reactor or cable terminator is recom­mended.
Optional Input/Output Reactor Specifications
Bulletin 1321 Reactors listed in the 1336 PLUS-3.0 Price Sheet can be used for drive input and output. These reactors are specifically constructed to accommodate IGBT inverter applications with switch­ing frequencies up to 20 kHz. They have a UL approved dielectric strength of 4000 volts, opposed to a normal rating of 2500 volts. The first two and last two turns of each coil are triple insulated to guard against insulation breakdown resulting from high dv/dt. When using motor line reactors, it is recommended that the drive PWM frequency be set to its lowest value to minimize losses in the reactors.
Important: By usingan outputreactor theeffectivemotor voltage will
be lower because of the voltage drop across the reactor ­this may also mean a reduction of motor torque.
2–14 General Installation for All Drives
Adapter Definitions and Communication Option Installation
Serial communication devices such as the Human Interface Module that are connected to the drive are identified by SCANport as Adapters. Depending on the drive and options ordered, different adapters are available. The communication options available for the 1336 SPIDER can be mounted as shown in Figure 2.2. Access to the communication ports and LEDs is gained by removing the knockouts shown. Figure 2.3 shows the maximum distance allowed between external devices.
Figure 2.2 Adapter Locations
Remote I/O
Adapter 2
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
45 (–) 47 (+)
PE
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
(Remove Shaded Areas)(Installed)
DeviceNet
Adapter 1
L1 L2 L3
48
U V
W
J1
J3
TB1
Slot A
Slot B
(Communication Board Installed)
J11
J8
J13
J2
(Remove Shaded Areas)
(Installed)
Figure 2.3 Remote Device Distances
RIO
PWR RUN STOP FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO 180SEC AFTER REMOVING MAINS VOLTAGE. GERÄT FÜHRT BIS 180SEK NACH DEM AUSSCHALTEN SPANNUNG. L'APPAREIL RESTE SOUS TENSION JUSQU'A 180 S APRES LA MISE HORS SERVICE.
L1 L2 L3
45 (–) 47 (+)
48 U V W
PE
Total cable distance between
each device and drive must
Length = X Meters
ESC SEL
JOG
Cable Length in Meters = 10 – X
Maximum Cable
Length = 10 Meters
HIM or Other
Remote Device
Port Expansion
Option
(1203-SG2)
or
ESC SEL
JOG
be 10 meters (33 feet) or less.
1
Communications Port for remote HIM/communication options (Adapter 2) or Expansion Options (Adapters 2, 3, 4, 5) is located at TB1.
SCANport
Comm Status
120/240V AC
Input
Communication Module
Cable Length in Meters = 10 – X
HIM or Other
Remote Device
23
1203-SG2
2345
1203-SG4
Expansion Options
1

Installation/Wiring for Stand-Alone Drives

Chapter 3 provides the information you need to perform the control and signal wiring for Stand-alone 1336 SPIDER Drives. In addition, installation information is provided for the Analog Option Boards. Refer to Chapter 2 for general installation and wiring.

Control and Signal Wiring General Wiring Information

General requirements for analog and digital signal wire include: stranded copper 0.750-0.283 mm shield, 300V minimum insulation rating and a temperature rating suitable for the application (not less than 60 degrees C.). Refer to Table 3.A for terminal block specifications and Figure 3.1 for locations.

Chapter 3

2
(18-22 AWG), twisted-pair, 100%
Table 3.A Control and Signal Terminal Block Specifications
Drive Catalog Number
All 0.14-1.5 (28-16) M2 0.22-0.25 (1.9-2.2) 9 (0.35)
1
Wire sizes given are maximum/minimum sizes that terminal block will accept - these are not recommendations. Use Copper wire only. Wire gauge requirements and recommendations are based on 75 degree C. Do not reduce wire gauge when using higher temperature wire.
Max./Min. Wire Size
mm2 (AWG)
1
Screw Size
Torque Range
N-m (lb.-in.)
Remove Insulation
mm (in.)
Signal Connections
If the drive control connections are to be linked to an electronic circuit or device, the common or 0V line should, if possible, be grounded at the device (source) end only.
Important: The signal common (0V) of the drive is internally
connected to PE. User speed reference signals are terminated to logiccommon at TB2, terminal 5. This puts the negative (or common) side of these signals at earth ground potential. Control schemes must be examined for possible conflicts with this type of grounding scheme.
Cable Routing
If unshielded cable is used, signal circuits should not run parallel to motor cables or unfiltered supply cables with a spacing less than 0.3 meters (1 foot). Cable tray metal dividers or separate conduit should be used.
Important: When user installed control and signal wiring with an
insulationratingofless than 600Vis used,thiswiringmust be routed inside the drive enclosure and separated from any other wiring and/or uninsulated live parts.
3–2 Installation/Wiring for Stand-Alone Drives
Figure 3.1 Control and Signal Terminal Blocks
PWR RUN STOP FAULT
TB1
1 2 3
TB2
4 5 6 7
8 9 10 11 12
TB3
13 14 15 16
17
TB4
18 19
20 21 22
TB5
23 24 25
26 27
TB6
28 29 30
24VC
TB7
24V
TB1
TB2
TB3
TB4
TB5
TB6
TB7
PWR RUN STOP FAULT
1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 16
17 18 19
20 21 22 23 24 25
26 27 28 29 30
24VC 24V

Digital Inputs Digital inputs are connected at TB4-TB6.

Input Mode Select
A number of combinations are available by first programming [Input Mode] to the desired control scheme (i.e. 2 wire, 3 wire or Status). The remaining inputs can then be configured by programming parameters 242-247 ([TB5 Term 22 Sel] - [TB6 Term 28 Sel]). Refer to the table on page 3–5 and the Digital I/O parameter group in Chapter 7 for programming information.
Input 1
Input 2
TB4
19
TB5
20
Installation/Wiring for Stand-Alone Drives 3–3
Figure 3.2 Digital I/O Default Settings
Input Mode (Start/Stop Functions Only)
2
Status
(Factory Default)
Status Run Forward Start
Stop/Fault Reset
2-Wire Control
Single-Source Control
3
Stop/Fault Reset3Stop/Fault Reset
3-Wire Control
Single-Source Reversing
3
Common
Input 3
Input 4
Input 5
Common
Input 6
Input 7
Input 8
Common
Input 9
24V Common
21
22
23
24
25
TB6
26
27
28
29
30
TB7
24V
Common
Rev/For4 (Programmable)
Status Only
Default Mode shown at right
is not active
when
[Input Mode]
is set to "Status"
3
Enable
1
See
Speed Select
2
If this mode is selected, the status of all inputs can be read at the [Input Status] parameter. However, only Stop/Fault Reset and Enable will have control function.
3
These inputs must be present (reprogram if necessary) before drive will start.
4
Bit 0 of [Direction Mask] must = 1 to allow TB5 direction change/bipolar operation.
Jog (Programmable)
Auxiliary3 (Programmable)
Common
1
Speed Select 3
Speed Select 21 (Programmable)
Speed Select 11 (Programmable)
Common
Enable
Table.
(Programmable)
3
(Not Programmable)
Factory
Default Inputs
ATTENTION: A hazard of personal injury from automatic restart exists with 2-wire control. 2-wire
!
control uses maintained Run contacts that act as both Run(closed)andStop (open) devices.OpeningtheStop contact (terminal 20) will stop the drive.If this contact is reclosed, any fault will be reset. If a valid Start commandisstill present,thedrivewillrestart.Only use 2-wire control for applications outlined in NFPA79, “Under Voltage Protection.”
If a 3-wire device (i.e. HIM) is also used, pressing the HIM Stop key will also stop the drive. Releasing the Stop key will clear any faults that are present, but the drive will not restart without cycling the Start contact.
3–4 Installation/Wiring for Stand-Alone Drives
Circuits must be capable of operating with high = true logic. DC external circuits in the low state must generate a voltage of no
more than 8V DC. Leakage current must be less than 1.5 mA into a
2.5k ohm load. DC external circuits in the high state must generate a voltage of +20
to +26 volts and source a current of approximately 10 mA for each input. The stand-alone version is compatible with these Allen-Bradley PLC modules:
• 1771-OB • 1771-OQ16 • 1771-OB16
• 1771-OBD • 1771-OYL
• 1771-OBN • 1771-OZL
• 1771-OQ • 1771-OBB The 24 volt power supply is capable of supplying a total of 16 digital
inputs.
510 510
20k
Typical
0.22µf
510
1k
2019 21 22 23 24 25
TB4 TB5 TB6 TB7
Contacts shown are general, refer to Input Mode Select and information presented above.
26 27 28 29 30
24V Common
24V
Installation/Wiring for Stand-Alone Drives 3–5
Available Functions for Inputs 3 through 8
A variety of combinations made up of the following inputs are a v ailable.
Input Description
“2 Acc/1 Acc” “2 Dec/1 Dec”
“1st Accel” “2nd Accel” “1st Decel” “2nd Decel”
“Aux Fault” Faultsthe drivevia externaldevices (i.e. motor thermoswitch,O.L. relays, etc.).Opening this
“Clear Fault” If drive has faulted, closing this input will clear the fault. “Dig Pot Up”
“Dig Pot Dn” “Forward” Closing these inputs (Forward or Reverse) commands the corresponding direction. If both “Rev/For” Available only with three-wire control - Closing this input commands reverse direction and “Jog” Closingthis inputstarts thedrive and causesit torun at programmedjog frequency.Opening “Local Ctrl” Closing this input gives exclusive control of drive logic to the inputs at terminals 19-30. No “Reverse” See “Forward” above.
“PI Enable” Enables the output of the process PI loop. “PI Reset” Opening this input clamps the process PI integrator value at zero. Closing this input allows
“Run Reverse” Available Only with two-wire control - Closing this input issues both a start command and a “Speed Sel 1”
“Speed Sel 2” “Speed Sel 3”
“Stop Type” Closing thisinput selectsthe stopmode in [Stop Select 2] as the method ofstopping whena
“Sync” Normally wired to multiple drives – When the Sync input is low, the drive operates normally.
“Traverse” Settingthis inputlow disablesthe traverse function. When the input is high,the traversefunc-
Closing these inputs will command the corresponding accel or decel rate. If both inputs are open or both are closed, the current rate is maintained.
Input 1st2
No Command 0 0 Accel/Decel 1 0 1 Accel/Decel 2 1 0
Allows selection of the accel or decel time used by the drive. 1=2nd, 0=1st
contact will fault(F02 -Aux Fault) thedrive andshut theoutput off,ignoring theprogrammed stop mode.
These inputs increase (up) or decrease (down) the drive commanded frequency when MOP (Motor Operated Potentiometer) is chosen as the frequency command source. The rate of increase/decrease is programmable.
inputs are open or both are closed, the current direction is maintained. opening this input commands forward direction. this input stops the drive using the programmed stop mode. other devices may issue logic commands (excluding Stop) to the drive.
the integrator to continue to operate. reverse command to the drive. Opening the input issues a stop command to the drive.
These inputs choose the frequency command source for the drive. See following pages for details.
stop command is issued. Opening this input selects the stop mode in [Stop Select 1] as the method of stopping.
When the input ishigh, the speed of the drive willbe held constant and the speed command willhave no effect.During thisperiod thespeed input ofthe drivewill normally be changedto a different source and/or value. Allows synchronizedchange of frequency command tomulti­ple drives.
tion will be active. [Speed Control] must also be set to “P Jump” for the function to be active.
nd
Important: The [Input Mode] parameter can be changed at any time,
but the change will not affect drive operation until power tothe drivehas beenremovedand busvoltagehas decayed completely. When changing thisparameter,it is important to note that the functions of the Start and Stop inputs will change when power is reapplied to the drive.
The programming options allowyou to select an input combination to meet the needs of a specific installation. The firmware will verify programming, to assure selection of an appropriate combination.
3–6 Installation/Wiring for Stand-Alone Drives
Speed Select/Frequency Reference
The drivespeed command can be obtained from a number of different sources. The source is determined by drive programming and the condition of the Speed Select Inputs on TB6 (or reference select bits of command word if PLC controlled - see Appendix A).
The default source for a command reference (all speed select inputs open) is the selection programmed in [Freq Select 1]. If any of the speed select inputs are closed, the drive will use other parameters as the speed command source. See Table 3.B and the examples that follow.
Table 3.B Speed Select Input State vs. Frequency Source
Speed Select 3 Speed Select 2 Speed Select 1 Frequency Source
Open Open Open [Freq Select 1] Open Open Closed [Freq Select 2] Accessed through [Freq Select 2] parameter [Preset Freq 1] Open Closed Open [Preset Freq 2] Open Closed Closed [Preset Freq 3] Closed Open Open [Preset Freq 4] Closed Open Closed [Preset Freq 5] Closed Closed Open [Preset Freq 6] Closed Closed Closed [Preset Freq 7]
Important: The final speed command may be affected by the type of
modulation selected with [Speed Control], parameter 77. See [Speed Control] in Chapter 7 for further information.
Important: If a bi-polar input option (LA6 or LA7) is installed, the
signal is designated “AnalogInput 0.”Note thefollowing:
3 Wire Control – If [Input Mode] is set to “3 Wire” and the bi-polar input is selected as the active frequency reference [Freq Select 1 or 2], it is assumed that direction control is desired via analog polarity. If another source has control of direction, a “Bipolar Direction” fault (F16) will occur. If direction control via polarity is not required, bit 7 of [Direction Mask] should be set to “0.” This causes the input to be treated as a 0-10V frequency reference only. Negative analog signals are treated as zero and direction control must come from another source.
2 Wire Control – If [Input Mode] is set to “2 Wire,” it is assumed that direction control is provided via the 2 wire inputs (Run Forward and Run Reverse). Bit 7 of [Direction Mask] must be set to “0.” This causes the input to be treated as a 0-10V frequency reference only. Negative analog signals are treated as zero. Failure to set the Mask will generate a “Bipolar Direction” (F16) fault.
Loading...
+ 146 hidden pages