Rockwell Automation 1336T User Manual

Allen-Bradley
TM
TM
1336 FORCE ControlNet
Firmware Rev 1.02 Compatible with ControlNet Version 1.5
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-1.1) describes some important differences between solid state equipment and hard–wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or
!
Attentions help you:
death, property damage, or economic loss.
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is especially important for
successful application and understanding of the product.
Preface
Table of Contents
Who Should Use this Manual P-1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
What Is the ControlNet Adapter Board P-1. . . . . . . . . . . . . . . . . . . . . .
Purpose of this Manual P-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents of this Manual P-2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Related Documentation P-3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms and Abbreviations P-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Techniques Used in this Manual P-6. . . . . . . . . . . . . . . . . . .
Allen–Bradley Support P-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Product Support P-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Product Assistance P-7. . . . . . . . . . . . . . . . . . . . . . . .
Catalog Number Description P-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Wiring
Starting Up
Chapter 1
Chapter Objectives 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the ControlNet Adapter Board 1-2. . . . . . . . . . . . . . . . . . . . .
Setting Your Input Voltage 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Writing to BRAM 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Block Locations 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete I/O 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete Outputs 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete Inputs 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog I/O Connections 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Outputs 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Determining Y our Communications Configuration 1-8. . . . . . . . . . . . . .
Fiber Optic Cable Installation 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable Types 1-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Associated Hardware 1-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Chapter Objectives 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the DIP Switches 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switch settings for Node Address 2-2. . . . . . . . . . . . . . . . . . . . .
Setting Up the Analog I/O 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . .
Understanding the Scale and Offset Parameters for Input 2-6. . . .
Understanding the Scale and Offset Parameters for Output 2-7. . .
Using the SCANport Capabilities 2-9. . . . . . . . . . . . . . . . . . . . . . . . . .
Pre-Configured Links 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1336 FORCE–5.18 –– March, 1998
Table of Contentsii
Scheduled Data Transfer
Unscheduled Messaging
Chapter 3
Chapter Objectives 3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Understanding ControlNet Communications 3–1. . . . . . . . . . . . . . . . . .
Transferring Data Using Discrete Data Transfer 3–1. . . . . . . . . . . . . . .
Discrete PLC Programming 3–3. . . . . . . . . . . . . . . . . . . . . . . . .
Scaling 3–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete I/O Program Example 3–4. . . . . . . . . . . . . . . . . . . . . . .
Chapter 4
Chapter Objectives 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlNet Features 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Message Instruction 4–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlNet Command Set 4–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emulated Block Transfer 4–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Transfer Status Word 4–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Message Summary 4–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Value Read 4–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Parameter Value Read 4–1 1. . . . . . . . . . . . . . . . . . . . . . . .
Scattered Parameter Value Read 4–13. . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Read Full 4–15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter V alue W rite 4–18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Parameter Value Write 4–19. . . . . . . . . . . . . . . . . . . . . . . .
Scattered Parameter Value Write 4–21. . . . . . . . . . . . . . . . . . . . . . . . .
Fault Clear/Reset 4–23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trip Fault Queue Number 4–25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Entry Read Full 4–26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warning Clear 4–28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warning Queue Read Full 4–30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Save/Recall/Initialize 4–32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Link Parameter Read 4–34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Parameter Link Read 4–35. . . . . . . . . . . . . . . . . . . . . . . . .
Scattered Parameter Link Read 4–37. . . . . . . . . . . . . . . . . . . . . . . . . .
Link Parameter Write 4–39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Parameter Link Write 4–40. . . . . . . . . . . . . . . . . . . . . . . . .
Scattered Parameter Link Write 4–42. . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Link Clear 4–44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Text String Read 4–45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Text String Write 4–47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock Data Read 4–49. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock Data Write 4–51. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run Time Accumulator Data Read 4–53. . . . . . . . . . . . . . . . . . . . . . . .
Clear Run Time Accumulator 4–55. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Time Stamp Data Read 4–56. . . . . . . . . . . . . . . . . . . . . . . .
Reference Time Stamp Data Write 4–58. . . . . . . . . . . . . . . . . . . . . . . .
Load Clock Info Reference Stamp 4–60. . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1336 FORCE–5.18 –– March, 1998
Table of Contents iii
Number of Trends Available 4-61. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum Trend Size Available 4-62. . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend Command 4-63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend Status 4-65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Data Full 4-67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
All Info 4-70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trigger Time 4-73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run File Data 4-75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stored File Data 4-78. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend Parameter Definition 4-80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend T riggered Setup Parameter Values 4-82. . . . . . . . . . . . . . . . . . .
Drive Resources
Parameters
Chapter 5
Chapter Objectives 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the SCANport Capabilities 5-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Understanding the Logic Command Parameter 5-1. . . . . . . . . . .
Configuring the SCANport Controls 5-5. . . . . . . . . . . . . . . . . . . .
Determining Function Ownership 5-6. . . . . . . . . . . . . . . . . . . . .
Masking Control Functions 5-7. . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Loss of Communications Fault 5-8. . . . . . . . . . . . . . .
Viewing the SCANport Fault Status 5-9. . . . . . . . . . . . . . . . . . . .
Using the SCANport Image 5-9. . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Up the Analog I/O Parameters 5-10. . . . . . . . . . . . . . . . . .
Understanding Function Blocks 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Using System Resources 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6
Chapter Objectives 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BRAM Functions 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Listing 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Files and Groups 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
File 1 – Startup 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
File 2 – Communications I/O 6-6. . . . . . . . . . . . . . . . . . . . . . . . .
File 3 – Velocity Torque 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
File 4 – Diagnostics 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Conventions 6-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Descriptions 6-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting
Chapter 7
Chapter Objectives 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault and Status LEDs 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Processor (AP) Status D1 and D2 7-2. . . . . . . . . . . .
Domino Processor (DP) Status D3 and D6 7-3. . . . . . . . . . . . . . .
ControlNet Adapter Status D4, D5, D7, D9, and D11 7-3. . . . . . . .
Publication 1336 FORCE–5.18 –– March, 1998
Table of Contentsiv
Primary Channel Status D8, D10, and D12
Redundant Channel Status D13, D14, and D15 7-5. . . . . . . . . . .
Fault Queues 7-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Faults 7-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Fault Reporting and Handling 7-6. . . . . . . . . . . . . . . .
Fault Code Descriptions 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Displays 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Trend Features
Specifications
Chapter 8
Setting Up Trending 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting the Parameter to Sample 8-1. . . . . . . . . . . . . . . . . . . . . . . .
Setting the Trigger Condition 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Sample Rate 8-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Number of Post Samples 8-5. . . . . . . . . . . . . . . . . . . . . . .
Setting the Trend Mode and Selection 8-6. . . . . . . . . . . . . . . . . . . . . .
Trending Status 8-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Looking at the Output 8-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 9
Chapter Objectives 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software Block Diagram 9-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1336 FORCE–5.18 –– March, 1998
This Page Intentionally Blank
Table of Contents v
Publication 1336 FORCE–5.18 –– March, 1998


Read this preface to familiarize yourself with this manual. This preface covers the following topics:
who should use this manual
an overview of the ControlNet Adapter Board
the purpose of this manual
terms and abbreviations
conventions used in this manual
Allen-Bradley support
Who Should Use this Manual
Communication Channels 2 independently configurable 1 channel with redundancy
What Is the ControlNet Adapter Board
Use this manual if you are responsible for installing, wiring, starting up, programming, or troubleshooting control systems that use the ControlNet Adapter Board.
To use this product, you should be able to program and operate an Allen-Bradley PLC and/or DriveTools. In particular, you need to be familiar with ControlNet concepts and configurations, and be able to program messaging instructions.
The ControlNet board contains primarily the same functionality of the PLC Comm Board except as shown in the following matrix:
Function: PLC Comm Board: ControlNet Adapter Board:
Messaging Via Data Highway Plus Via ControlNet
Discrete Data Transfer
You can add a ControlNet Adapter Board to your 1336 FORCE system to expand the communications capabilities. The following are the major features of the CNA Board:
1
/4, 1/2, full rack via RIO Full rack via ControlNet
Direct Connection to ControlNet V 1.5 Network providing
Discrete I/O transfer and message blocks.
support for up to five SCANport devices that allow you to
connect to a wide range of Allen-Bradley devices
four analog inputs and four analog outputs
function block programming to help you customize the way your
drive operates
Publication 1336 FORCE–5.18 –– March, 1999
PrefaceP–2
trending capabilities as a diagnostic tool to allow you to capture
data values for a parameter
a 32-event fault and warning queue
Purpose of this Manual
Chapter: Title: Contents:
This manual:
provides planning, installation, and wiring information for the
ControlNet Adapter Board
explains the procedures you need to mount and configure your
CNA Board
describes the available parameters and block messaging
instructions
provides information to help you troubleshoot your CNA Board
Contents of this Manual
This manual contains the following information:
Preface
Installing and
1
Wiring Your ControlNet Adapter Board
Describes the purpose, background, and scope of this manual as well as an overview of this product.
Provides procedures for installing and wiring your CNA Board.
2 Starting Up Provides information for starting up your system.
Using Scheduled
3
4
5
6 Parameters
7 Troubleshooting
8
9
Discrete Data Transfer
Using Unscheduled Messaging
Understanding the Resources of Your Drive.
Using the Trending Features
Specifications and Supplemental Information
Provides information about using ControlNet communications to transfer scheduled discrete data.
Provides information on emulated block transfer messaging.
Provides an overview of the function block software and the available system resources.
Provides information about the parameters that are specific to the ControlNet Adapter Board.
Explains how to interpret and correct problems with your ControlNet Adapter Board.
Provides step–by–step instructions for using trending for diagnostic purposes.
Provides specifications and supplemental information including a parameter cross reference by number.
Publication 1336 FORCE–5.18 –– March, 1999
Preface P–3
ATTENTION: This board contains ESD (electrostatic
!
discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if you do not follow ESD control precautions. If you are not familiar with static control procedures, refer to Guarding Against Electrostatic Damage, Allen-Bradley Publication 8000-4.5.2, or any other applicable ESD protection handbook.
ATTENTION: Only personnel familiar with SCANport devices and associated machinery should plan or implement the installation, start-up, or subsequent troubleshooting of this board. Failure to comply may result in personnel injury and/or equipment damage.
Related Documentation
The following documents contain additional information concerning related Allen–Bradley products. To obtain a copy, contact your local Allen–Bradley office or distributor.
For: Read this document: Document number:
A description of function blocks and function block programming
Information to help you install, program, start up, and maintain the 1336 FORCE digital AC drive
In-depth information on grounding and wiring Allen-Bradley programmable controllers
A description on how to install a PLC-5 system
A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices
An article on wire sizes and types for grounding electrical equipment
A complete listing of current Allen–Bradley documentation, including ordering instructions. Also indicates whether the documents are available on CD-ROM or in multi–languages.
A glossary of industrial automation terms and abbreviations
A glossary of ControlNet terms and abbreviations PLC–5 Programmable Controllers ControlNet PLC–5 User Manual 1.5 1785–6.5.22
1336 FORCE PLC Communications Adapter Function Block Programming Manual
1336 FORCE Field Oriented Control User Manual
Allen-Bradley Programmable Controller Grounding and Wiring Guidelines
PLC-5 Family Programmable Controllers Hardware Installation Manual
Application Considerations for Solid-State Controls
National Electrical Code
Allen-Bradley Publication Index SD499
Allen-Bradley Industrial Automation Glossary
ControlNet Network System Overview
1336 FORCE-5.9
1336 FORCE-5.12
1770-4.1*
1785-6.6.1*
SGI-1.1
Published by the National Fire Protection Association
AG-7.1
1786-2.9*
Publication 1336 FORCE–5.18 –– March, 1999
PrefaceP–4
Terms and Abbreviations
This term: Has the following definition:
CNA Board ControlNet Adapter Board BRAM See Non-volatile memory.
Configuration parameter
Drive units
Emulated Block Transfer
Engineering units
The following terms and abbreviations are specific to this product. For a complete listing of Allen-Bradley terminology, refer to the Allen-Bradley Industrial Automation Glossary.
A configuration parameter is a sink parameter whose value may be changed while the drive is in operation. Configuration parameters are used to input reference and feedback information to the drive and to provide monitoring points for control signals. Refer to the 1336 FORCE user manual for a description of source and sink parameters.
Drive units are the actual values of the parameters as stored within the drive parameter table. The drive units may be converted to engineering units or to hexadecimal for display, or may be displayed directly in drive units. All internal values in the drive are in terms of per unit numbering.
The ControlNet network emulates the “block transfer” functions of the 1336 FORCE drive via messaging. The 1336 FORCE drive does not support CI/O (the newest method of ControlNet block transfer).
Engineering units is a label given to parameter data that specifies what units are to be used to display the parameter value.
Function blocks
NUI (Network Update Interval)
NUT (Network Update Time)
PCCC
Scheduled transfers
Unscheduled transfers
Class 1 Data Connection
Class 3 Data Connection
A function block is a firmware subroutine that is stored in memory within the ControlNet Adapter Board. The ControlNet Adapter Board provides 28 different function block types. By combining function blocks, you can customize the way your drive operates. Refer to the 1336 FORCE function block programming manual for more information about function blocks.
Actual update time, which is a user specified interval which is a power of two multiple of the NUT (Network Update Time).
Repetitive time interval in which data can be sent on the ControlNet network.
Programmable Controller Communications Commands. An application-level command set that Allen–Bradley programmable controllers use to communicate across networks.
Deterministic and repeatable transfers that are continuous and asynchronous to the ladder-logic program scan.
Non-deterministic data transfers through ladder–initiated communication or programming devices.
See “Scheduled transfers”.
See “Unscheduled transfers”.
Publication 1336 FORCE–5.18 –– March, 1999
This term: Has the following definition:
A link is a software connection between a linkable sink parameter and a source parameter . You can use links to transfer data from the source parameter to a linkable sink parameter. Your 1336 FORCE user manual provides a list of linkable sink parameters.
The ControlNet Adapter Board allows up to 50 links in addition to 4 analog output links. You can only program links when the drive is not running. Links are stored in BRAM and established at power up, BRAM recall, and/or system reset.
There are two types of links:
Links
User Link –– A user link is a software connection that you establish.
You can change these links as needed.
Default Link –– A default link is a software connection between two
parameters that is made when the drive is initialized.
Default Links
Sink
CntlNet Out 0 351 CntlNet Out 1 352
ChA Logic Cmd 367 Vel Ref 1 Hi 101
To
To To
To To
Preface P–5
Source
56 Logic Sts Lo 269 Filtered Vel Fdbk
322 CntlNet In 0 323 CntlNet In 1
Mask parameters
Non–volatile memory
Owner parameters
Parameter entry
Through the SCANport interface, up to five different SCANport adapters can control the 1336 FORCE. With this flexibility, conflicts are inherent. The ControlNet Adapter Board allows you to make functional masks. At each port, you can selectively lock out functions such as start, jog, and drive direction as well as many fault interlocks by using mask parameters to select the allowable functions for each port.
Non-volatile memory is data memory in the drive that retains the values of all data even when power is disconnected from the drive. BRAM (Battery backed Random Access Memory) chips are used for the non-volatile memory to store some of the drive parameters, links, and user text.
The ControlNet Adapter Board allows one or more control devices or adapters to own start, jog, direction, and other control functions. T o avoid conflict, some owners are exclusive. For example, only one device can issue a forward direction speed command. Others have multiple control. For example, all devices can jog the drive in the forward direction, but only at a set speed. Devices can, for example, jog the drive in the forward direction only if the jog mask parameter allows for it.
A parameter entry refers to the information stored in the drive that contains the parameter number, parameter data, and all other information related to the specific parameter.
Parameter table
A parameter table is a table of parameter entries for all configuration sink and source parameters in the drive.
Publication 1336 FORCE–5.18 –– March, 1999
PrefaceP–6
This term: Has the following definition:
Per-unit numbering is a numbering system that defines a specific Per–unit numbering
Sink parameters (Read and Write parameters)
numeric value as representing 100% of a particular quantity being
measured. The number 4096 is used in many places in the drive to
represent one per unit.
Sink parameters accept data from other parameters. The drive then uses
this data to perform the desired functions. An example of a sink
parameter is the external velocity reference parameter that accepts a
speed reference from a device such as a PLC. Throughout this manual,
the following symbol indicates a sink parameter: Source
parameters (Read–only parameters)
Trending
Common Techniques Used in this Manual
Source parameters provide real-time information that is available for
other devices to use. These devices can include PLC controllers,
operator interface devices, programming terminals, etc. Throughout this
manual, the following symbol indicates a source parameter:
Trending is a diagnostic tool used to capture and retain an input
parameter data value (such as velocity feedback) until a trigger
condition (drive fault or malfunction condition) halts or suspends
sampling.
The following conventions are used throughout this manual:
Bulleted lists provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical
information.
Publication 1336 FORCE–5.18 –– March, 1999
Preface P–7
Allen-Bradley Support
Allen-Bradley offers support services worldwide, with over 75 Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Allen-Bradley representatives in every major country in the world.
Local Product Support
Contact your local Allen-Bradley representative for:
sales and order support
product technical training
warranty support
support service agreements
Technical Product Assistance
If you need to contact Allen-Bradley for technical assistance, please review the information in the Troubleshooting chapter first. If you are still having problems, then call your local Allen-Bradley representative.
Catalog Number Description
A language module is located on each ControlNet Adapter Board. Catalog numbers identifying the language modules are as follows:
1336T GT3EN
1336T = Field Installed GT3EN = English Version (Blank) = Factory Installed GT3EN = English Version
Publication 1336 FORCE–5.18 –– March, 1999
PrefaceP–8
This Page Intentionally Blank
Publication 1336 FORCE–5.18 –– March, 1999
Chapter
Installing and Wiring Your ControlNet Adapter Board
1
Chapter Objectives
Language Module
Keyed Mounting Slot
AP Status –– D1 AP Status –– D2
Fault Out –– D4
Ext Fault –– D5
Norm Stop –– D7 Motor Thermo –– D9 Drive Enable –– D11
Primary Channel
Chapter 1 provides information so that you can:
mount the ControlNet Adapter Board
configure and connect the communications
configure and set up the discrete inputs and analog I/O
Important: The installation and wiring information in this manual
The following illustration shows the ControlNet Adapter Board.
J1 Control Board Interface
Plug Board
is specific to the ControlNet Adapter Board. For information about mounting the drive, connecting the motor leads, or connecting the power, refer to the 1336 FORCE user manual.
BRAM Jumper J3
Configuration DIP Switches
Not
Node
Used
Address
U2 U3 U4 U5
Not Used In This Application
DP Status –– D3 DP Status –– D6 Primary Status –– D8 Primary Status –– D10 Primary Status –– D12 Redundant Status –– D13 Redundant Status –– D14 Redundant Status –– D15
Redundant Channel
Network Access Port
Voltage Selection
Inputs
J11
J10
J9 J8
1
T erminal Block TB20: Discrete I/O Connections
10 1 19
T erminal Block TB21: Analog I/O Connections
D3 – Red
Solid = Soft Fault
Port 1
Port 2
Publication 1336 FORCE–5.18 ––March, 1999
Blinking = Hard Fault
D6 – Green
Solid = No Fault Blinking = Warning
D8 – Red
Mimics Primary Plug Channel LED
D10 – Yellow
Blinking 1Hz = Operational
D12 – Green
Mimics Primary Plug Channel LED
D13 – Red
Mimics Redundant Channel LED
D14 – Yellow
Blinking 1 Hz = Operational
D15 – Green
Mimics Redundant Channel LED
Keyed Mounting Slot
1–2 Installing and Wiring Your ControlNet Adapter Board
Mounting the ControlNet Adapter Board
To mount your ControlNet Adapter Board on to your 1336 FORCE, you need to:
ATTENTION: To avoid a shock hazard, assure that all power to the drive has been removed before
!
1. Place the CNA Board over the keyed mounting slots.
2. Slide the board up into the main control board connector J1.
3. Secure the board to the 1336 FORCE mounting plate using the
two Phillips-head screws that are provided with the kit.
4. Connect primary and redundant ControlNet channels at the fiber
optic connector. You must maintain a minimum bend radius on the fiber optic cable of 1 inch at all times. If you cannot maintain this bend radius, remove the plastic strain relief following the instructions for Frame D drives detailed on page 1-8. Using the ControlNet Adapter Board on a Frame D drive, always requires the removal of the cable strain relief. See page 1-8 for special cable instructions for D Frame drives.
proceeding.
Publication 1336 FORCE–5.18 ––March, 1999
1–3Installing and Wiring Your ControlNet Adapter Board
Setting Your Input Voltage
24V
120V
Writing to BRAM
To select your input voltage, you need to set the discrete I/O jumpers.
ATTENTION: To avoid damaging the CNA Board, you must set all discrete I/O jumpers to the same input
!
Set this discrete
I/O jumper:
DR EN Drive Enable 24V dc or 120V ac M THERM Motor Thermoguard 24V dc or 120V ac N STOP Normal Stop 24V dc or 120V ac X FLT External Fault 24V dc or 120V ac
You can use jumper J3 on the ControlNet Adapter Board to either allow (enable) or not allow (disable) writes to Battery backed Random Access Memory (BRAM).
voltage applied to the ControlNet Adapter Board. The voltage must be either 24V DC or 120V AC.
To set this input: To either:
DIS
J3
EN
BRAM
Terminal Block Locations
"
Choose:
EN (Enabled) Allow writes to BRAM. DIS (Disabled) Not allow writes to BRAM.
Two terminal blocks, TB20 and TB21, are provided at the bottom of the ControlNet Adapter Board for discrete and analog I/O wiring.
To make the connections more easily, you can pull apart the terminal blocks when connecting the cables.
Both terminal blocks accept a maximum wire size of 3.3 mm AWG) and a minimum wire size of 0.60 mm torque is 0.79 N–m (7 lb–in). Recommended control signal wire is:
Belden
number:
8760 0.750 mm2 (18 AWG), twisted pair, shielded 8770 0.750 mm2 (18 AWG), 3–conductor, shielded 9460 0.750 mm2 (18 AWG), twisted pair, shielded
Description for equivalent:
To:
2
(12
2
(30 AWG). Maximum
Publication 1336 FORCE–5.18 ––March, 1999
1–4 Installing and Wiring Your ControlNet Adapter Board
Discrete I/O
10
1
TB20
FAULT NO (10) FAULT COM (9) FAULT NC (8)
(7) INPUT COM (6) (5)
EXT FAULT N.C. (4) NORM STOP N.C. (3) MOTOR THERMO N.C. (2) DRIVE ENABLE N.O. (1)
Terminal block TB20 provides the discrete I/O capabilities.
Discrete Outputs
Fault outputs from the 1336 FORCE are supplied at terminal block TB20 on the ControlNet Adapter Board. Fault outputs provide warning or fault signals based on drive status.
The Fault NC, Fault Com, and Fault NO outputs are relay contacts that provide fault signals. If a contact is closed (energized), then there is no fault. If a contact is open, there is a fault.
The following values are the contact ratings for the Fault NC, Fault Com, and Fault NO relays:
2A at 115V AC 2A at 30V DC
The typical digital output connections can be shown as follows:
TB20
FAULT N.O. (DIGITAL OUT)
10
FAULT COM (DIGITAL OUT)
FAULT N.C. (DIGITAL OUT)
9
8
Discrete Inputs
Discrete inputs to the 1336 FORCE are supplied through the ControlNet Adapter Board at terminal block TB20. Discrete inputs enable and stop the drive as well as providing checks on drive and motor operation.
The typical digital input connections when using an external power source can be shown as follows:
TB20
INPUT COM (DIGITAL COMMON)
EXT FAULT (DIGITAL IN)
NORM STOP (DIGITAL IN)
6
4
EXTERNAL FAULT
3
STOP
(COMMON)
AC/+ 24V DC (HIGH)
115V
Publication 1336 FORCE–5.18 ––March, 1999
MOTOR THERMO (DIGITAL IN)
DRIVE ENABLE (DIGITAL IN)
2
MOTOR THERMO
1
ENABLE
The following are the signals that may be used:
1–5Installing and Wiring Your ControlNet Adapter Board
This signal:
DRIVE ENABLE
MOTOR THERMO
NORM STOP
EXT FAULT
Has the following meaning:
A drive enable signal must be present before the drive will acknowledge a start command. If LED D11 drive enable on the CNA Board is illuminated, the drive has received an enable signal allowing drive logic to accept a start command.
A motor thermo signal allows you to connect an NC motor thermal switch to the 1336 FORCE. Motor Thermo LED D9 on the CNA Board illuminates if a motor over–temperature condition occurs. The drive issues a fault or warning based on the fault configuration defined by VP Fault Select (parameter 88) and VP Warn Select (parameter 89).
ATTENTION: The drive start/stop
control circuitry includes solid–state
!
components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas, or solids exist, an additional hardwired stop circuit is required to remove ac line power to the drive. When you remove ac input power, there is loss of inherent regenerative braking effect and the motor coasts to a stop. An auxiliary braking method may be required.
A normal stop signal specifies an NC maintained stop input that stops the drive according to the stop mode you specified using parameter 59. The drive responds the same way it would if the stop bit were set in any logic command. When a stop signal is present, the Norm Stop LED D7 on the CNA Board is illuminated, and the drive cannot run until the stop signal is removed.
An Ext Fault signal allows you to wire an external signal into an AC input 1336 FORCE. If external fault input voltage is removed, the External Fault LED D5 on the CNA Board is illuminated. The drive then issues a fault or warning based on the fault configuration defined by parameters 88 and 89. (Ext Fault is not available on common DC bus input drives.)
Publication 1336 FORCE–5.18 ––March, 1999
1–6 Installing and Wiring Your ControlNet Adapter Board
Analog I/O Connections
19
TB21
1
– 10V (19)
COM (18)
+ 10V (17)
IN4 – (16) IN4 + (15)
IN3 – (14) IN3 + (13) IN2 – (12) IN2 + (11) IN1 – (10)
IN1 + (9)
COM4 (8)
OUT4 (7)
COM3 (6)
OUT3 (5)
COM2 (4)
OUT2 (3)
COM1 (2) OUT1 (1)
You can access the analog I/O connections at terminal block TB21. There are four analog inputs and four analog outputs. Each of the analog I/O parameter have scale and offset parameters. The analog inputs can be linked to any linkable sink parameter, and the analog outputs can receive information from any parameter in the drive. The drive increments the analog I/O every two milliseconds.
Analog Inputs
The ControlNet Adapter Board has 4 analog inputs that have a range of ±10V and a digital resolution of 12 bits. These inputs are differential inputs with noise rejection filtering. Each input has a gain and offset adjustment.
REF
The A/D converter is a 12-bit device where an input value of +10V results in a digital value of 2048. Likewise, an input value of -10V results in a digital output value of -2048.
ADC
Chapter 2, Starting Up, describes the parameters associated with scaling analog values.
DAC
For an analog input to control a function, you need to:
1. Link the analog input parameter(s) to a parameter such as
velocity reference.
2. Set up the scale and offset parameters associated with that analog
input parameter.
The typical analog input connections for unidirectional operation are shown as follows:
TB21
– 10V
DC (POWER SUPPLY)
COM (POWER SUPPLY COMMON)
DC (POWER SUPPLY)
+ 10V
IN + (ANALOG IN)
ADC
IN – (ANALOG IN)
Note: Connect to Only One Set of Inputs — IN4+ and IN4–IN3+ and IN3–IN2+ and IN2–IN1+ and IN1–
19
18
17
Connect to Either 17 or 19 (ONLY ONE)
TO TE (SIGNAL GROUND TERMINAL BLOCK)
REFERENCE POT
2.5 k MINIMUM
Publication 1336 FORCE–5.18 ––March, 1999
1–7Installing and Wiring Your ControlNet Adapter Board
(SIGNAL GROUND TERMINAL BLOCK)
The typical analog input connections for bidirectional operation can be shown as follows:
DC (POWER SUPPLY)
– 10V
COM (POWER SUPPLY COMMON)
+ 10V
DC (POWER SUPPLY)
IN + (ANALOG IN)
ADC
IN – (ANALOG IN)
Note: Connect to Only One Set of Inputs — IN4+ and IN4–IN3+ and IN3–IN2+ and IN2–IN1+ and IN1–
Forward
TB21
19
18
17
Reverse
R
Reverse
Relay
REVERSE
FORWARD
TO TE (SIGNAL GROUND TERMINAL BLOCK)
REFERENCE POT
2.5 k MINIMUM
The following table shows the analog input specifications:
Specifications:
Value:
Differential impedance Greater than 1 Ohm Single ended impedance 20K Ohm Maximum voltage
±10V
Analog Outputs
The ControlNet Adapter Board has 4 analog outputs that have a range of ±10V and a digital resolution of 12 bits. Chapter 2, Starting Up, describes the parameters associated with scaling analog values.
The typical analog output connections can be shown as follows:
TB21
OUT (ANALOG OUT)
DAC
COM (ANALOG OUT)
Note: Connect to Only One Set of Outputs — COM4 and OUT4COM3 and OUT3COM2 and OUT2COM1 and OUT1
TO TE
DC
0 to ±10V 1mA Maximum
100 Ohm Maximum Impedance
Publication 1336 FORCE–5.18 ––March, 1999
1–8 Installing and Wiring Your ControlNet Adapter Board
Determining Your Communications Configuration
Fiber Optic Cable Installation
"
The CNA Board provides a single ControlNet channel with a redundant connection available.
You can use the DIP switch U3 to configure the primary and redundant channel node address.
Chapter 2, Starting Up, provides information for setting the ControlNet Node Address using DIP switch U3.
If you are installing the fiber optic cable for ControlNet for the first time, or are removing and reinstalling the cable, special note should be taken of the following:
1. You must maintain a minimum cable bend radius of 1 inch at all
times. If it is impossible to maintain this bend radius due to cabinet constraints, you must remove the cable strain relief to maintain bend radius as detailed in step 2. Follow step 3 in determining cable orientation with the strain relief removed.
2. If you are installing a new cable, it will be necessary to remove
the strain relief/latching cover (as shown in the following figure) before attempting to plug the cable into the ControlNet board. The cover can be removed by squeezing the two latches inward and lifting the upper half off from the cable end (bottom) of the cover assembly.
Strain Relief/Cover
Incoming Fiber Optic Cables
3. When installing (or reinstalling) the loose fiber optic cables, it
will be necessary to determine the correct orientation of the cable connectors to establish ControlNet communication. The blue connector must be plugged into the dark grey connection on the board. The black connector plugs into the light grey connection on the board. The cable with the black connector is the transmit cable (TX) and the cable with the blue connector is the receive (RX) cable. Reset the drive and the ControlNet system should be ready to operate.
Fiber Optic Connectors
Latches
Publication 1336 FORCE–5.18 ––March, 1999
1–9Installing and Wiring Your ControlNet Adapter Board
4. On some applications, it may be necessary to provide some form
of cable support after removing the strain relief. If your application involves a long cable droop, or a heavy unsupported wire bundle, it is recommended you zip tie the fiber optic cable at a point that will prevent the weight of the cable from being solely supported by the plug in connectors.
5. If the cable is kinked or nicked during installation, it MUST be
replaced. A kinked or damaged cable greatly reduces signal strength and could cause the drive to fault.
Cable Type – Recommended cables are shown in the following table. These cables are available in precut, popular lengths for ease of use.
Micron Fiber Optic Cable Selection
Description
200 Micron Cable Assembly 10 meters 200 Micron Cable Assembly 20 meters 200 Micron Cable Assembly 60 meters 200 Micron Cable Assembly 100 meters 200 Micron Cable Assembly 200 meters 200 Micron Cable Assembly 300 meters
Catalog Number
1786 – FS10 1786 – FS20 1786 – FS60 1786 – FS100 1786 – FS200 1786 – FS300
IMPORTANT: Only use cables that are approved for ControlNet Applications. Refer to Bulletin 1786 ControlNet documentation for details.
Associated Hardware – The 1786-RPA module converts the coax cable through a CNet coax tap to up to four of the 1786-RPFS modules. The 1786 RPFS X has two connectors to receive the 200 Micron cable. The Drive ControlNet adapter board also has two connectors to receive the 200 Micron cable.
Module Selection
Description
Catalog Number
ControlNet Modular Repeater Adapter Short Distance Fiber Module – 300 meters
Note: The 1786-RPA must be powered from a 24 volt power supply
1786 – RPA 1786 – RPFS
For additional information on repeater modules refer to the following publications: 1786-2.12 ControlNet Network System Overview 1786-5.12 ControlNet Modular Repeater Short-Distance Fiber Modular Installation Instructions. 1786–5.13 ControlNet Modular Repeater Adapter Installation Instructions.
Publication 1336 FORCE–5.18 ––March, 1999
1–10 Installing and Wiring Your ControlNet Adapter Board
This Page Intentionally Blank
Publication 1336 FORCE–5.18 ––March, 1999
1–11Installing and Wiring Your ControlNet Adapter Board
Publication 1336 FORCE–5.18 ––March, 1999
Starting Up
Chapter
2
Chapter Objectives
Setting the DIP Switches
Chapter 2 provides the following information:
setting the DIP switch to configure the Primary and Redundant
channels
setting up the analog I/O
a description of the SCANport capabilities
a description of the pre-configured links
The ControlNet Adapter Board contains four address switches . Only switch U3 is used on the CNA board to set the Node Address. Switches U2, U4 and U5 are NOT used in this application. Changes to switch settings will not take effect until power is re-applied.
ATTENTION: Use a blunt, pointed instrument (such
!
!
as a ball point pen) to set DIP switches. Do not use a pencil. Pencil lead (graphite) may damage switch assemblies.
ATTENTION: The CNA Board uses both input and output image table words for drive control. The CNA Board is not compatible with complementary I/O configurations. Failure to check connections and switch settings for application compatibility when configuring the CNA Board could result in personal injury and /or equipment damage due to unintended or undesirable drive or process equipment operation.
"
If you encounter any operating faults once switch settings have been applied, refer to Chapter 7, Troubleshooting.
NOTE: DIP Switch orientation on the CNA board is as follows:
CLOSED = “ON” = “1” OPEN = “OFF” = “0”
Closed
Open
ON ON OffOff
Publication 1336 FORCE–5.18 ––March, 1999
2–2 Starting Up
*Reserved
Switch settings for Node Address (switch U6):
Switch positions 2-8 determine the node address of the CNA adapter. Refer to Table 2.A for details. Node Address position 1 is reserved for the PLC.
Table 2.A Switch settings for Node Address (U3 )
ControlNet
Address
1*
2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off
2
1
Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off
Switch positions
345 67
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Off
Off
Off
On
On
Off
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Off
Off
On
Off
On
Off
Off
On
Off
On
Off
Off
Off
On
On
Off
Off
Off
On
On
Off
Off
On
On
On
Off
Off
On
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Off
On
Off
Off
On
Off
On
Off
Off
On
Off
Off
On
Off
On
Off
Off
On
Off
On
Off
On
On
Off
On
Off
On
On
Off
On
Off
Off
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
Off
On
Off
On
On
Off
Off
On
On
On
Off
Off
On
On
On
Off
On
On
On
On
Off
On
On
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
On
On
Off
Off
Off
On
On
Off
Off
Off
On
Off
On
Off
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
On
On
Off
Off
On
Off
Off
On
Off
On
Off
Off
On
Off
On
On
Off
On
Off
On
On
Off
On
Off
On
Off
On
On
Off
On
Off
On
On
Off
On
On
On
On
Off
On
8
On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off
Publication 1336 FORCE–5.18 ––March, 1999
Table 2.A Switch settings for Node Address (U3 ) cont.
ControlNet Address
47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off
2 345 67
1
Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On
Switch positions
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off
On
Off
On
Off
On
Off
On
On Off Off Off Off Off Off Off Off On On On On On On On On Off Off Off Off Off Off Off Off On On On On On On On On Off Off Off Off Off Off Off Off On On On On On On On On Off Off Off Off
On Off Off Off Off On On On On Off Off Off Off On On On Off On Off Off Off On On On On Off Off Off Off On On On On Off Off Off Off On On On On Off Off Off Off On On On On Off Off Off Off
On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On Off Off On On
2–3Starting Up
8
On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On Off On
Publication 1336 FORCE–5.18 ––March, 1999
2–4 Starting Up
Setting Up the Analog I/O
Before you can transfer data between the ControlNet Adapter Board and the analog I/O, you need to do the following:
1. Hard wire the analog I/O to the CNA Board terminals.
2. Set up the analog input and output configuration parameters in
the drive.
3. Create any user links, if appropriate.
"
Note: The ControlNet Adapter Board has been pre-configured for your convenience. The pre-configured links are listed later in Figure
2.4. Each terminal has parameters associated with it as shown here in the
analog I/O block diagram.
TB21
Analog Out #1 Analog Out 1
Analog Out #2 Analog Out 2
Analog Out #3 Analog Out 3
OUT1 1 Par 401 Scale COM1 2 Par 400 Offset
OUT2 3 Par 403 Scale COM2 4 Par 402 Offset
OUT3 5 Par 405 Scale COM3 6 Par 404 Offset
387
388
389
Analog Out #4 Analog Out 4
Analog In #1 Analog In 1
Analog In #2 Analog In 2
Analog In #3 Analog In 3
Analog In #4 Analog In 4
OUT4 7 Par 407 Scale COM4 8 Par 406 Offset
IN1+ 9 Par 393 Scale IN1– 10 Par 392 Offset
IN2+ 11 Par 395 Scale IN2– 12 Par 394 Offset
IN3+ 13 Par 397 Scale IN3– 14 Par 396 Offset
IN4+ 15 Par 399 Scale IN4– 16 Par 398 Offset
+10V REF 17 REF COM 18 –10V REF 19
Power Supply
390
339
340
341
342
Publication 1336 FORCE–5.18 ––March, 1999
Loading...
+ 187 hidden pages