Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives
Important User Information
IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, PartnerNetwork, PowerFlex, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
The information below summarizes the changes to this manual since the last
release.
New and Updated
Information
Top icPag e
Added PowerFlex 525, PowerFlex 753, and PowerFlex 755 drives to the motor cable length cross
referenc e table.
Added motor cable length restriction tables for PowerFlex 525 drives.
Table 23, 400V (frames A…E)90
Table 24, 480V (frames A…E)91
Table 25, 600V (frames A…E)92
Updated motor cable length restriction tables for PowerFlex 700H drives.
Table 32, 600V (frames 9…13)100
Table 33, 690V (frames 9…13)100
Updated motor cable length restriction tables for PowerFlex 700S drives.
Table 44, 600V (frames 3…13)107
Table 45, 690V (frames 5…13)108
Added motor cable length restriction tables for PowerFlex 753 and 755 wall mount drives.
Table 46, 400V (frames 1 and 2)109
Table 47, 480V (frames 1 and 2)111
Table 48, 600V (frames 3…7)114
Table 49, 690V (frames 6 and 7)117
Added motor cable length restriction tables for PowerFlex 755 floor mount drives.
Table 50, 400V (frames 9 and 10)118
Table 51, 480V (frames 9 and 10)120
Table 52, 600V (frames 8…10)121
Table 53, 690V (frames 8…10)123
83
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 20143
Summary of Changes
Notes:
4Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 20147
Table of Contents
Notes:
8Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Preface
About This Publication
This manual provides the basic information needed to properly install, protect,
wire, and ground pulse width modulated (PWM) AC drives.
Intended Audience
This manual is intended for qualified personnel who plan and design installations
of PWM AC drives.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Safety Guidelines for the Ap plication, Installation and Maintenance of Solid State
Control, publication SGI-1.1
Don’t Ignore the Cost of Power Line Disturbance, publication 1321-TD001Provides technical data on Allen-Bradley power conditioning products.
IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical Noise
Inputs to Controllers from External Sources, publication IEEE 518.
Availa ble from IEEE Xplore Digital Librar y.
Recommended Practice for Powering and Grounding Electronic Equipment - IEEE
Emerald Book, publication IEEE STD 1100. Available from IEEE Xplore Digital Library
IEEE Recommended Practice for Grounding of Industrial and Commercial Power
Systems, publication IEEE Std 142-1991. Available from IEEE Xplore Digital Library
Cable Alternatives for PWM AC Drive Applications, publication IEEE Paper
No. PCIC-99-23. Available from IEEE Xplore Digital Library
EMI Emissions of Modern PWM AC Drives
IEEE Industry Applications Magazine
Electromagnetic Interference and Compatibility, Volume 3, by Donald R. J. WhiteThis book provides information EMI control methods and techniques.
Grounding, Bonding, and Shielding for Electronic Equipment and Facilities
(Military Handbook 419)
Noise Reduction Techniques in Electronic Systems by Henry W. OttThis book provides information on controlling emissions from electronic systems, and
Grounding for the Control of EMI by Hugh W. DennyThis book provides grounding guidelines for the control of EMI.
EMC for Product Designers by Tim WilliamsThis book provides the information needed to meet the requirements of the latest EMC
National Electrical Code (ANSI/NFPA 70)
Articles 250, 725-5, 725-15, 725-52 and 800-52 (www.nfpa.org)
Application Guide for AC Adjustable Speed Drive Systems,
NEMA (www.nema.org
IEC 60364-5-52 Selection and Erection of Electrical Equipment - Wiring systems, IEC
(www.iec.ch)
.
, Nov./Dec. 1999
).
Provides general guidelines for the application, installation, and maintenance of solid-state
control devices or assemblies.
Provides techniques for installing controllers and control systems so that proper operation
can be achieved in the presence of electrical noise.
Provides the recommended practices for powering and groundiing electronic equipment.
.
Provides recommended practices to ground power systems.
.
Describes an alternative solution for cables used with IGBT variable frequency drives (VFDs).
Provides an understanding of EMI issues and with pre-installation and post-installation
guidelines.
Provides grounding, bonding, and shielding applications for communication electronics
equipments and facilities.
techniques for providing electromagnetic compatibility (EMC).
directive.
Provides information on the installation of electrical components, signaling and
communication conductors and grounding.
Provides a NEMA applicatio n guide for AC drive systems.
IEC wiring systems.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 20149
Preface
Recommended Cable/Wire
General Precautions
The recommended wire and cable referenced in this publication can be obtained
from third-party companies found in our PartnerNetwork™ Encompass Program.
For further information on these suppliers and their products, follow these steps
to find recommended wire and cable for your drives.
1. Go to the Encompass website at http://www.rockwellautomation.com/
2. Under Find an Encompass Referenced Product, click FIND NOW.
3. In the Product Category pull-down list, choose Drive - Cables.
4. Click SEARCH.
ATT EN TI ON : To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the +DC and –DC terminals of the power
terminal block. The voltage must be zero.
10Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 1
Wire/Cable Types
AC drive installations have specific wire and cable requirements. This section
includes information about the major issues for proper selection of cable, and
provides recommendations to address these issues. Consider these conditions and
requirements when choosing cable material and construction for your
installation:
• Environment – such as moisture, temperature, and harsh or corrosive
chemicals.
• Mechanical needs – such as geometry, shielding, flexibility, and crush
resistance.
• Electrical characteristics – such as cable capacitance/charging current,
resistance/voltage drop, current rating, and insulation. Insulation can be
the most significant of these. Because drives can create voltages in excess of
line voltage, the industry standard cables that were used in the past are not
the best choice for variable speed drives. Drive installations benefit from
cable that is significantly different than cable used to wire contactors and
push buttons.
• Safety issues – such as electrical code requirements, grounding needs, and
others.
General
Choosing incorrect cabling can be costly and can adversely affect the
performance of your installation.
Material
Use only copper wire. The wire clamp-type terminals in Allen-Bradley drives are
made for use with copper wire. If you use aluminum wire, the connections can
loosen and cause premature equipment failure.
Wire gauge requirements and recommendations are based on 75 °C (167 °F)
rating. Do not reduce wire gauge when you use higher temperature wire.
Exterior Cover
Whether shielded or unshielded, the cable must meet all of the application
requirements. Consider insulation value and resistance to moisture,
contaminants, corrosive agents, and other invasive elements. Consult the cable
manufacturer and Figure 1 on page 12
for cable selection criteria.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201411
Chapter 1 Wire/Cable Types
XLPE
PVC
20 mil or > (1)
230V400/460V
15 mil
> 15.2 m (50 ft)
< 15.2 m (50 ft)
575V
Selecting Wire to Withstand Reflected Wave Voltage for New and Existing Wire Installations in
Conduit or Cable Trays
Conductor
Environment
Conductor
Insulation
Insulation
Thicknes s
DRY
(per NEC Article 100)
WET
(per NEC Article 100)
XLPE (XHHW-2)
Insulation for
< 600V AC
System
No RWR or
Ter mi na to r
Required
OK for < 600V AC
System
No RWR or
Terminator Required
Reflected Wave
Reducer?
RWR or
Ter m in a to r
No RWR or
Ter m in a to r
RWR or
Ter mi na to r
No RWR or
Ter mi na to r
Reflected Wave
Reducer?
Cable
Length
Number of
Drives in Same
Conduit or Wire
Tra y
15 mil PVC
in Not
Recommended.
Use XLPE
or > 20 mil
15 mil PVC
is Not
Recommended.
Use XLPE
or > 20 mil
Multiple Drives
in Single Conduit
or Wire Tray
Single Drive,
Single Conduit or
Wire Tray
See NEC Guidelines (Article 310
Adjustment Factors) for Maximum
Conductor Derating and Maximum
Wires in Con duit or Tray
(1) The minimum wire size for PVC cable with 20 mil or greater insulation is 10 gauge.
IMPORTANT
Figure 1 - Wire Selection Flowchart
Temperature Rating
In general, follow these temperature ratings for installations:
• In surrounding air temperature of 50 °C (122 °F), use 90 °C (194 °F) wire
(required for UL)
• In surrounding air temperature of 40 °C (104 °F), use 75 °C (167 °F) wire
(required for UL)
Refer to the user manual of the drive for other restrictions.
The temperature rating of the wire affects the required gauge. Verify that your
installation meets all applicable national, state, and local codes.
12Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Wire/ Cable Typ es Chapter 1
One Ground Conductor
Three Ground Conductors
Gauge
The correct wire size is determined by a number of factors. The user manual for
each drive lists a minimum and maximum wire gauge based on the amperage
rating of the drive and the physical limitations of the terminal blocks. Local or
national electrical codes also set the required minimum gauge based on motor
full load current (FLA). Follow both of these requirements.
Number of Conductors
Local or national electrical codes can determine the required number of
conductors. Generally, these configurations are recommended:
• Figure 2
for drives up to and including 200 Hp (150 kW).
• Figure 3
for drives larger than 200 Hp (150 kW).
Space the ground conductors symmetrically around the power conductors. Verify
that the ground conductors are rated for full drive ampacity.
shows cable with a single ground conductor that is recommended
shows cable with three ground conductors that is recommended
Figure 2 - Cable with One Ground Conductor
W
G
BR
Figure 3 - Cable with Three Ground Conductors
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201413
Chapter 1 Wire/Cable Types
Unacceptable
Accepta ble
Insulation Thickness and Concentricity
Wire must have an insulation thickness of ≥ 15 mil (0.4 mm/0.015 in.). The wire
insulation must not have significant variations of concentricity around the wire.
Figure 4 - Insulation Concentricity
Geometry
The physical relationship between individual conductors is important in drive
installations.
Individual conductors in conduit or cable trays have no fixed relationship and are
subject to cross coupling of noise, induced voltages, excess insulation stress, and
other possible interference.
Fixed geometry cable (cable that keeps the spacing and orientation of the
individual conductors constant) offers significant advantages over individual
loose conductors, including reduced cross-coupling noise and insulation stress.
Three types of fixed geometry, multi-conductor cables are discussed in this
section. See Unshielded Cable on page 15
Armored Cable on page 17
Table 1 - Recommended Cable Design
TypeMax Wire SizeWhere UsedRating/TypeDescription
Type 12 AWGStandard installations
100 Hp or less
Type 22 AWGStandard installations
100 Hp or less
with brake conductors
Type 3500 MCM AWGStandard installations
150 Hp or more
Type 4500 MCM AWGWater, caustic chemical,
crush resistance
Type 5500 MCM AWG690V applicationsTray-rated 2000V, 90 °C (194 °F) Three tinned copper conductors with XLPE insulation. Three bare copper
600V, 90 °C (194 °F)
XHHW2/RHW-2
600V, 90 °C (194 °F)
RHH/RHW-2
Tray-rated 600V, 90 °C (194 °F)
RHH/RHW-2
Tray-rated 600V, 90 °C (194 °F)
RHH/RHW-2
.
Four tinned copper conductors with cross-linked polyethylene (XLPE)
insulation
Four tinned copper conductors with XLPE insulation plus one shielded pair of
brake conductors.
Three tinned copper conductors with XLPE insulation and three bare copper
grounds and polyvinyl chloride (PVC) jacket.
Three bare copper conductors with XLPE insulation and three copper grounds
on 10 AWG and smaller. Acceptable in Class I and II, Division I and II locations.
grounds and PVC jacket.
IMPORTANT: If terminator network or output filter is used, connector
insulation must be XLPE, not PVC.
, Shielded Cable on page 16, and
14Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Wire/ Cable Typ es Chapter 1
Typ e 1 I nst al latio n, w ithout Brake Conductors
G
R
B
W
Single Ground
Conduc tor
PVC Outer
Sheath
Filler
Multiple Ground
Conducto rs
PVC Outer
Sheath
Filler
Unshielded Cable
Properly designed multi-conductor cable can provide superior performance in
wet applications, significantly reduce voltage stress on wire insulation, and reduce
cross coupling between drives.
The use of cables without shielding is generally acceptable for installations where
electrical noise created by the drive does not interfere with the operation of other
devices, such as communication cards, photoelectric switches, weigh scales, and
others. Verify that the installation does not require shielded cable to meet specific
electromagnetic compatibility (EMC) standards for CE, C-Tick, or FCC
requirements. Cable specifications depend on the installation type.
Type 1 and Type 2 Installation
Type 1 or Type 2 installations require 3-phase conductors and a fully rated
individual ground conductor with or without brake leads. Refer to Table 1 on
page 14 for detailed information and specifications on these installations.
Figure 5 - Type 1 Unshielded Multi-conductor Cable without Brake Leads
Type 3 Installation
Type 3 installation requires three symmetrical ground conductors whose
ampacity equals the phase conductor. Refer to Table 1 on page 14
information and specifications on this installation.
Figure 6 - Type 3 Unshielded Multi-Conductor Cable
G
B
W
G
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201415
G
R
for detailed
Chapter 1 Wire/Cable Types
Shield
Drain Wire
Chose the outer sheathing and other mechanical characteristics to suit the
installation environment. Consider the surrounding air temperature, chemical
environment, flexibility, and other factors in all installation types.
Shielded Cable
Shielded cable contains all of the general benefits of multi-conductor cable with
the added benefit of a copper-braided shield that can contain much of the noise
generated by a typical AC drive. Use shielded cable for installations with sensitive
equipment, such as weigh scales, capacitive proximity switches, and other devices
that can be affected by electrical noise in the distribution system. Applications
with large numbers of drives in a single location, imposed EMC regulations, or a
high degree of communication/networking, are also good candidates for shielded
cable.
Shielded cable can also help reduce shaft voltage and induced bearing currents for
some applications. In addition, the increased size of shielded cable can help
extend the distance that the motor can be from the drive without the addition of
motor protective devices, such as terminator networks. Refer to Chapter 5
information regarding reflected wave phenomena.
for
Consider all of the general specifications dictated by the environment of the
installation, including temperature, flexibility, moisture characteristics, and
chemical resistance. In addition, include a braided shield specified by the cable
manufacturer as having coverage of at least 75%. An additional foil shield can
greatly improve noise containment.
Type 1 Installation
An acceptable shielded cable for Type 1 installations has four XLPE insulated
conductors with a 100% coverage foil and an 85% coverage copper braided shield
(with drain wire) surrounded by a PVC jacket. For detailed specifications and
information on Type 1 installations, refer to Table 1 on page 14
Figure 7 - Type 1 Installation — Shielded Cable with Four Conductors
W
G
.
BR
16Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Wire/ Cable Typ es Chapter 1
B
R
G
W
Drain Wire for Brake
Conduc tor Shiel d
Shield for Brake
Condu ctors
TIP
Type 2 Installation
An acceptable shielded cable for Type 2 installations is essentially the same cable
as Type 1, plus one shielded pair of brake conductors. For more information on
Typ e 2 in sta llat io ns, re fe r to Table 1 on page 14
Figure 8 - Type 2 Installation — Shielded Cable with Brake Conductors
.
Type 3 Installation
These cables have 3 XLPE insulated copper conductors, 25% minimal overlap
with helical copper tape, and three bare copper grounds in PVC jacket.
Other types of shielded cable are available, but the selection of these types can
limit the allowable cable length. Particularly, some of the newer cables twist four
conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and reduce
the overall drive performance. Unless specified in the individual distance tables
as tested with the drive, these cables are not recommended and their
performance against the lead length limits supplied is not known. For more
information about motor cable lead restrictions, refer to, Conduit on page 67
Moisture on page 72
, Effects On Wire Types on page 73, and Appendix A.
,
Armored Cable
Cable with continuous aluminum armor is often recommended in drive system
applications or specific industries. Armored cable offers most of the advantages of
standard shielded cable and also combines considerable mechanical strength and
resistance to moisture. It can be installed in concealed and exposed manners and
removes the requirement for conduit (electrical metallic tubing [EMT]) in the
installation. It can also be directly buried or embedded in concrete.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201417
Chapter 1 Wire/Cable Types
IMPORTANT
Cable with Three Ground Conductors
Cable with a Single Ground Conductor
G
R
B
W
Conduc tors wit h XLPE
Insulation
Optional Foil/Copper Tape
and/or Inner PVC Jacket
Armor
Optional PVC Outer Sheath
Because noise containment can be affected by incidental grounding of the armor
to building steel when the cable is mounted, we recommend that the armored
cable has an overall PVC jacket (see Chapter 2
).
Interlocked armor is acceptable for shorter cable runs, but continuous welded
armor is preferred. General recommendations for ground conductors are listed
here:
• Cable with a single ground conductor is sufficient for drive sizes up to and
including 200 Hp (150 kW).
• Cable with three ground conductors is recommended for drive sizes larger
than 200 Hp (150 kW).
Space the ground conductors symmetrically around the power conductors. Verify
that the ground conductors are rated for full drive ampacity.
G
B
W
G
G
R
Figure 9 - Armored Cable with Three Ground Conductors
A good example of cable for Type 5 installation is Anixter 7V-5003-3G. This
cable has three XLPE insulated copper conductors, 25% minimal overlap with
the helical copper tape, and three bare copper grounds in PVC jacket.
If a terminator network or output filter is used, the connector insulation must
be XLPE, and not PVC.
18Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Wire/ Cable Typ es Chapter 1
Stranded Neutral
PVC Outer
Sheath
Filler
European Style Cable
Cable used in many installations in Europe must conform to Low Voltage
Directive (LVD) 2006/95/EC. Generally recommended are flexible cables with a
bend radius of 20 times the cable diameter for movable cable, and 6 times the
cable diameter for fixed installations, with a screen (shield) of 70…85% coverage.
Insulation for both conductors and the outer sheath is PVC.
The number and color of individual conductors can vary, but the
recommendation is for three phase conductors (customer-preferred colors) and
one ground conductor (green/yellow).
Ölflex Classic 100SY, or Ölflex Classic 110CY, are examples.
Figure 10 - European Style Multi-conductor Cable
B
W
Input Power Cables
R
In general, the selection of cable for AC input power to a drive has no special
requirements. Some installations suggest shielded cable to prevent coupling of
noise onto the cable (see Chapter 2
), and in some cases shielded cable can be
required to meet noise standards, such as CE for Europe, C-Tick for Australia/
New Zealand, and others. This can be especially true if an input filter is required
to meet a standard. The user manual for the drive has the requirements for
meeting these types of standards. Additionally, individual industries can have
required standards due to environment or experience.
For AC variable frequency drive applications that must satisfy EMC standards
for CE, C-Tick, FCC, or others, we recommend the same type of shielded cable
that is specified for the AC motors be used between the drive and transformer.
Check the individual user manuals or system schematics for specific additional
requirements to meet EMC standards.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201419
Chapter 1 Wire/Cable Types
182.9 (600)
91.4 (300)91.4 (300)
15.2 (50)
167.6 (550)152.4 (500)
15.2 (50)15.2 (50)
All examples represent motor cable length of 182.9 m (600 ft)
IMPORTANT
Motor Cables
The majority of recommendations regarding drive cables are for issues caused by
the nature of the drive output. A PWM drive creates AC motor current by
sending DC voltage pulses to the motor in a specific pattern. These pulses affect
the wire insulation and can be a source of electrical noise. Consider the rise time,
amplitude, and frequency of these pulses when choosing a wire/cable type.
Consider these factors when choosing a cable:
• The effects of the drive output once the cable is installed.
• The need for the cable to contain noise caused by the drive output.
• The amount of cable charging current available from the drive.
• Possible voltage drop (and subsequent loss of torque) for long wire runs.
Keep the motor cable lengths within the limits set in the user manual for the
drive. Various issues, including cable charging current and reflected wave voltage
stress, can exist. If the cable restriction is listed because of excessive coupling
current, apply the methods to calculate total cable length, as shown in Figure 11
If the restriction is due to voltage reflection and motor protection, refer to
Appendix A
Figure 11 - Motor Cable Length for Capacitive Coupling
for exact distances allowed.
.
20Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
For multi-motor applications, review the installation carefully. Consult your
distributor drive specialist or Rockwell Automation when considering a
multi-motor application with greater than two motors. In general, most
installations have no issues. However, high peak cable charging currents can
cause drive over-currents or ground faults.
Wire/ Cable Typ es Chapter 1
Cable for Discrete Drive I/O
Analog Signal and Encoder
Cable
Discrete I/O, such as start and stop commands, can be wired to the drive with a
variety of cabling. We recommend shielded cable to reduce cross-coupled noise
from power cables. Standard individual conductors that meet the general
requirements for type, temperature, gauge, and applicable codes are acceptable if
they are routed away from higher voltage cables to minimize noise coupling.
However, multi-conductor cable can be less expensive to install. Separate control
wires from power wires by at least 0.3 m (1 ft)
Table 2 - Recommended Control Wire for Digital I/O
(1)
Type
UnshieldedPer US NEC or applicable national or local code–300V, 60 °C
ShieldedMulti-conductor shielded cable0.750 mm
(1) The cable choices shown are for 2-channel (A and B) or 3-channel (A,B, and Z) encoders. If high resolution or other types of
feedback devices are used, choose a similar cable with the correct gauge and number of conductor pairs.
Wire Type(s)DescriptionMinimum
2
3-conductor, shielded.
(18 AWG),
Insulation Rating
(140 °F)
Always use shielded cable with copper wire. We recommend wire with an
insulation rating of 300V or greater. Separate analog signal wires from power
wires by at least 0.3 m (1 ft). Run encoder cables in a separate conduit. If signal
cables must cross power cables, cross at right angles. Terminate the shield of the
shielded cable as recommended by the manufacturer of the encoder or analog
signal device.
Table 3 - Recommended Signal Wire
Signal Type/
Where Used
Standard analog I/O–0.750 mm2 (18 AWG), twisted pair, 100% shield
(1) If the wires are short and contained within a cabinet that has no sensitive circuits, the use of shielded wire is not always necessary,
but is recommended.
Wire
Type( s)
Combined0.196 mm
Signal0.196 mm2 (24 AWG), individually shielded
Power0.750 mm
Combined0.330 mm
Signal0.196 mm2 (24 AWG), individually shielded
Power0.750 mm
Combined0.750 mm
DescriptionMinimum
(1)
with drain
2
(24 AWG), individually shielded
2
(18 AWG)
2
or 0.500 mm
2
(18 AWG)
2
(18 AWG), individually shielded pair
2
Insulation Rating
300V,
75…90 °C
(167…194 °F)
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201421
Chapter 1 Wire/Cable Types
Communication
This section provides cable recommendations for these communication
protocols:
• DeviceNet on page 22
• ControlNet on page 23
• Ethernet on page 23
• Remote I/O and Data Highway Plus (DH+) on page 24
• Serial (RS-232 and RS-485) on page 24
DeviceNet
DeviceNet cable options, topology, distances allowed, and techniques are specific
to the DeviceNet network. For more information, refer to DeviceNet Media
Design and Installation Guide, publication DNET-UM072
In general, the four cable types for DeviceNet media meet these criteria:
• Round (thick) cable with an outside diameter of 12.2 mm (0.48 in.);
normally used for trunk lines, but can also be used for drop lines.
• Round (thin) cable with an outside diameter of 6.9 mm (0.27 in.);
normally used for drop lines, but can also be used for trunk lines.
• Flat cable, normally used for trunk lines.
• KwikLink drop cable, used only in KwikLink systems.
.
Round cable contains these five wires:
• One twisted pair (red and black) for 24V DC power.
• One twisted pair (blue and white) for signal.
• One drain wire (bare).
Flat cable contains these four wires:
• One pair (red and black) for 24V DC power.
• One pair (blue and white) for signal.
Drop cable for KwikLink is a 4-wire, unshielded, gray cable.
The distance between points, installation of terminating resistors, and chosen
baud rate are significant to the installation. For more information, refer to the
DeviceNet Media Design and Installation Guide, publication DNET-UM072
.
22Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Wire/ Cable Typ es Chapter 1
ControlNet
ControlNet cable options, topology, distances allowed, and techniques are
specific to the ControlNet network. For more information, refer to the
ControlNet Coax Media Planning and Installation Guide, publication
CNET-IN002
Depending on the environment at the installation site, there are several types of
RG-6 quad shield cables that can be appropriate. The standard cable
recommended is Allen-Bradley catalog number 1786-RG6, Quad Shield coax.
Country, state, or local codes, such as the U.S. NEC, govern the installation.
Installation EnvironmentUse this Cable Type
Light industrial• Standard PVC
Heavy ind ustrial• Lay-on armored
High/Low temperature or corrosive (harsh chemicals)• Plenum-FEP
Festooning or flexing• High flex
Moistu re: direct bu rial, with fl ooding compound, fungus resistant• Flood burial
.
• CM-CL2
• Light interlocking armor
• CMP-CL2P
The allowable length of segments and installation of terminating resistors play a
significant part in the installation. Refer to the ControlNet Coax Media
Planning and Installation Guide, publication CNET-IN002
, for details.
Ethernet
Ethernet communication interface wiring is very detailed for the type of cable,
connectors, and routing. In general, Ethernet systems use shielded twisted pair
(STP) cable, or unshielded twisted pair (UTP) cable, with RJ45 connectors that
meet the IP67 standard and are appropriate for the environment. Use cables that
meet Telecommunications Industry Association/Electronic Industries Alliance
(TIA/EIA) standards at industrial temperatures.
Shielded cable is recommended when the installation can include welding,
electrostatic processes, drives over 10 Hp, motor control centers (MCCs), high
power RF radiation, or devices carrying current in excess of 100 A. Shield
handling and single-point grounding, also discussed in this document, are also
important for the proper operation of Ethernet installations.
There are also important distance and routing limitations published in detail.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201423
Chapter 1 Wire/Cable Types
IMPORTANT
IMPORTANT
Remote I/O and Data Highway Plus (DH+)
Only Allen-Bradley catalog number 1770-CD shielded twinaxial cabling is
tested and approved for remote I/O and DH+ installations.
The maximum cable length depends on the baud rate.
Baud RateMaximum Cable Length
57.6 Kbps3048 m (10,000 ft)
115.2 Kbps1524 m (5000 ft)
230.4 Kbps762 m (2500 ft)
All three connections (blue, shield, and clear) must be connected at each node.
Do not connect in a star topology. Only two cables can be connected at any
wiring point. Use either series or daisy chain topology at all points.
Serial (RS-232 and RS-485)
Follow these recommended standard practices for serial communications wiring:
• One twisted pair and one signal common for RS-232.
• Two twisted pair, with each pair individually shielded, for RS-485.
24Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2
Power Distribution
This chapter discusses different power distribution schemes and factors that can
affect drive performance.
System Configurations
The type of transformer and the connection configuration feeding the drive have
an important role in drive performance and safety. This section includes a brief
description of some of the more common configurations and their qualities and
shortcomings.
Delta/Wye with Grounded Wye Neutral
Delta/Wye wi th Grounde d Wye Neutr al is the most common type of
distribution system. It provides a 30° phase shift. The grounded neutral provides
a direct path for common mode current caused by the drive output (see
Chapter 3
Rockwell Automation recommends the use of grounded neutral systems for these
reasons:
and Chapter 6).
• Controlled path for common mode noise current
• Consistent line-to-ground voltage reference that minimizes insulation
stress
• Accommodation for system surge protection schemes
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201425
Chapter 2 Power Distribution
or
Single-phase Loads
Single-phase Loads
Three-phase
Loads
Delta/Delta with Grounded Leg,
or Four-wire Connected Secondary Delta
Delta/Delta with Grounded Leg or Four-wire Connected Secondary Delta is a
common configuration with no phase shift between input and output. The
grounded center tap provides a direct path for common mode current caused by
the drive output.
Three-phase Open Delta with Single-phase Center Tapped
Three-phase Open Delta with Single-phase Center Tapped is a configuration
providing a Three-phase delta transformer with one side tapped. This tap (the
neutral) is connected to earth. The configuration is called the antiphase
grounded (neutral) system.
The open delta transformer connection is limited to 58% of the 240V,
single-phase transformer rating. Closing the delta with a third single-phase,
240V transformer provides full rating for the two single-phase, 240V
transformers.
The phase leg opposite the midpoint has an elevated voltage when compared to
earth or neutral. The hottest high leg must be positively identified throughout
the electrical system. Make the hottest high leg the center leg in any switch, motor
control, three-phase panel board, and so on. The NEC requires orange color tape
to identify this leg.
26Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Power Distribution Chapter 2
Ungrounded Secondary
ATT EN TI ON : Grounding the transformer secondary is essential to the safety of
personnel and safe operation of the drive. Leaving the secondary floating
causes dangerous high voltages between the chassis of the drive and the
internal power structure components. Exceeding the voltage rating of the
drive’s input metal oxide varistor (MOV) protection devices can cause a
catastrophic failure. In all cases, the input power to the drive is referenced to
ground.
If the system is ungrounded, other general precautions, such as a system level
ground fault detector or system level line to ground suppressor, can be necessary.
Or consider an isolation transformer with the secondary of the transformer
grounded.
Refer to local codes regarding safety requirements. Also refer to Surge Protection
MOVs and Common Mode Capacitors on page 45.
High Resistance Ground
Grounding the Wye Secondary Neutral through a resistor is an acceptable
method of grounding. Under a short circuit secondary condition, any of the
output phases to ground do not exceed the normal line-to-line voltage. This is
within the rating of the MOV input protection devices on the drive. The resistor
is often used to detect ground current by monitoring the associated voltage drop.
Because high frequency ground current can flow through this resistor, be sure to
properly connect the drive motor leads by using the recommended cables and
methods. In some cases, multiple drives (that can have one or more internal
references to ground) on one transformer can produce a cumulative ground
current that can trigger the ground fault interrupt circuit. Refer to Surge
Protection MOVs and Common Mode Capacitors on page 45.
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201427
Chapter 2 Power Distribution
L1
L2
L3
PEN or N
PE
IMPORTANT
TN-S Five-wire System
TN-S Five-wire distribution systems are common throughout Europe, with the
exception of the United Kingdom and Germany. Leg-to-leg voltage (commonly
at 400V) powers three-phase loads. Leg-to-neutral voltage (commonly at 230V)
powers single-phase loads. Neutral is a current conducting wire, and connects
through a circuit breaker. The fifth wire is a separate ground wire. There is a
single connection between ground and neutral, typically in the distribution
system. Do not make connections between ground and neutral within the system
cabinets.
AC Line Voltage
AC Line Impedance
In general, all Allen-Bradley drives are tolerant to a wide range of AC line voltage.
Check the individual specifications for the drives you are installing.
Incoming voltage imbalances >2% can cause large unequal currents in a drive. Use
an input line reactor when line voltage imbalances are >2%.
To prevent excess current that can damage drives during events such as line
disturbances or certain types of ground faults, provide a minimum amount of
impedance in front of the drives. In many installations, this impedance comes
from the supply transformer and the supply cables. In some cases, an additional
transformer or reactor is recommended. If any of these conditions exist, consider
adding impedance (line reactor or transformer) in front of the drive:
• Installation site has switched power factor correction capacitors.
• Installation site has lightning strikes or voltage spikes in excess of 6000V
peak.
• Installation site has power interruptions or voltage dips in excess of
200V AC.
• The transformer is too large in comparison to the drive. See impedance
recommendations on Table 4 on page 30
through Table 13 on page 41.
Tab le s 4 through 13 define the largest transformer size for each product
and rating based on specific differences in construction, and is the
28Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
preferred method to follow.
Power Distribution Chapter 2
% impedance is the nameplate impedance of the transformer.
Typical values range from 0.03 (3%) to 0.06 (6%).
Z
xfmr
=
(V
line-line
)
2
VA
* % Impedance
or
% impedance is the nameplate impedance of the transformer.
Typical values range from 0.03 (3%) to 0.06 (6%).
Otherwise, use one of the following more conservative methods:
• For drives without built-in inductors – add line impedance whenever the
transformer kVA is more than 10 times larger than the drive kVA, or the
percent source impedance relative to each drive is less than 0.5%.
• For drives with built-in inductors – add line impedance whenever the
transformer kVA is more than 20 times larger than the drive kVA, or the
percent source impedance relative to each drive is less than 0.25%.
To identify drives with built-in inductors, see the product specific information in
Table 4 on page 30
through Table 13 on page 41. The shaded rows identify
products ratings without built-in inductors.
Use these equations to calculate the impedance of the drive and transformer:
Drive Impedance (in ohms)
V
Z
=
drive
3 * I
line-line
input-rating
Transformer Impedance (in ohms)
V
line-line
Z
=
xfmr
3 * I
* % Impedance
xfmr-rated
Transformer Impedance (in ohms)
V
line-line
Z
=
xfmr
3 * I
* % Impedance
xfmr-rated
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 201429
Chapter 2 Power Distribution
EXAMPLE
IMPORTANT
Z
xfmr
Z
drive
0.2304
102.6
= 0.00224 = 0.22%=
The drive is rated 1 Hp, 480V, 2.7A input.
The supply transformer is rated 50,000 VA (50 kVA), 5% impedance.
V
(V
line-line
3 * I
input-rating
2
)
line-line
* % Impedance =
VA
Z
=
drive
=
Z
xfmr
480V
= = 102.6 Ohms
3 * 2.7
2
480
* 0.05 = 0.2304 Ohms
50,000
Note that the percent (%) impedance has to be in per unit (5% becomes 0.05)
for the formula.
0.22% is less than 0.5%. Therefore, this transformer is too big for the drive.
Consider adding a line reactor.
Grouping multiple drives on one reactor is acceptable; however, the reactor
percent impedance must be large enough when evaluated for each drive
separately, not evaluated for all loads connected at once.
These recommendations are advisory and do not address all situations. Site
specific conditions must be considered to assure a quality installation.
Table 4 - AC Line Impedance Recommendations for Bulletin 160 Drives
Bulletin
Number
160
(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
Drive Catalog
Number
-AA022400.37(0.5) 153R4-B6.54
-AA032400.55 (0.75) 203R4-A34
-AA042400.75 (1)303R4-A34
-AA082401.5 (2)503R8-A1.58
-AA122402.2 (3)753R12-A1.2512
-AA182403.7 (5)1003R18-A0.818
-BA014800.37(0.5) 153R2-B202
-BA024800.55 (0.75) 203R2-A122
-BA034800.75 (1)303R2-A122
-BA044801.5 (2)503R4-B6.54
-BA064802.2 (3)753R8-B38
-BA104803.7 (5)1003R18-B1.518
VoltskW (H p) Max Sup ply
(1)
kVA
(2)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
30Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.