Rockwell Automation 1336F User Manual

1336 PLUS II Adjustable Frequency AC Drive
with
0.37-448 kW (0.5 - 600 HP)
Firmware 1.xxx - 6.xxx
User Manual
Important User Information
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss.
Attentions help you:
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is especially important for successful
application and understanding of the product.
Shock Hazard labels may be located on or inside the drive to alert people that dangerous voltage may be present.
StepLogic and SCANport are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes

New/Updated Information The information below summarizes the changes to the 1336 PLUS II

User Manual since the last release.
Description of Change Page(s)
TB1 info updated - D Frame 2–15
Updated Parameters:
[Load Loss Level]
[Phase Loss Level]
[Heatsink Temp]
[Drive Type]
New Parameters:
[Motor OL Ret] 6–35
Parameter Cross References updated
Parameter Record updated A–17
, B–18
6–26
6–35
6–39
6–42
A–8
soc–2 Summary of Changes
Notes

Table of Contents

Chapter 1
Information and Precautions Manual Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–1
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–2
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–2
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–2
Nameplate Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–4
Chapter 2
Installation/Wiring Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–1
Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–2
AC Supply Source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–3
Input Power Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–4
Input Fuses and Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–5
Input Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–9
Electrical Interference - EMI/RFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–9
RFI Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–10
CE Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–10
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–11
Power Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–14
Control and Signal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–24
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–25
Encoder Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–30
Pulse Input/Output Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–31
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–31
Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–32
Standard Analog I/O Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–33
Optional Analog I/O Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–34
Output Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–37
Cable Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–37
Selecting/Verifying Fan Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–38
Auxiliary Inputs - TB4, TB6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–39
Auxiliary Output - TB9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–40
Control Interface Board Installation and Removal. . . . . . . . . . . . . . . . . . 2–40
Adapter Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–41
Chapter 3
Human Interface Module HIM Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
HIM Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–4
Handheld HIM Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–13
Chapter 4
Flash Memory What is Flash Memory? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
Firmware Download Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
toc–ii Table of Contents
Chapter 5
Start-Up Start-Up Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
Assisted Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
Advanced Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
Chapter 6
Programming Function Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
Programming Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
Chapter Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
Chapter 7
Troubleshooting Fault Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–9
Appendix A
Specifications and
Supplemental Information
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–1
User Supplied Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–4
Derating Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–5
Parameter Cross Reference - By Number . . . . . . . . . . . . . . . . . . . . . . . . A–8
Parameter Cross Reference - By Name. . . . . . . . . . . . . . . . . . . . . . . . . . A–9
HIM Character Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–10
Communications Data Information Format . . . . . . . . . . . . . . . . . . . . . . A–11
Typical Programmable Controller Communications Configurations . . . . A–12
Typical Serial Communications Configurations . . . . . . . . . . . . . . . . . . . A–13
Encoder Interface Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–14
Read/Write Parameter Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A–17
Appendix B
Dimensions
Appendix C
CE Conformity Requirements for Conforming Installation . . . . . . . . . . . . . . . . . . . . . . . . C–2
Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–2
Electrical Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–3
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–4
Mechanical Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C–4

Chapter 1

Information and Precautions

Chapter 1 provides information on the general intent of this man­ual, gives an overall description of the 1336 Frequency AC Drive and provides a listing of key drive features.

Manual Objectives This publication provides planning, installation, wiring and diag-

nostic information for the 1336 ful installation and operation, the material presented must be thoroughly read and understood before proceeding. Particular attention must be directed to the Attention and Important state­ments contained within.
For J Frame information, refer to publication 1336F-IN014.
PLUS II Drive. To assure success-

Software Compatibility

Three-Phase Drive Rating
0.37-0.75 kW
0.5-1 HP
1.2-1.5 kW
1.5-2 HP
2.2-3.7 kW
3-5 HP
5.5 kW
7.5 HP
5.5-11 kW
7.5-15 HP
15-22 kW
20-30 HP
30-45 kW
40-60 HP
56-93 kW
75-125 HP
187-336 kW
187-448 kW
1
kW and HP are constant torque.
0.37-1.2 kW
0.5-1.5 HP
1.5-2.2 kW
2-3 HP
3.7 kW
5 HP
5.5-15 kW
7.5-20 HP
11-22 kW
15-30 HP
30-45 kW
40-60 HP
45-112 kW
60-150 HP
112-187 kW
150-250 HP
250-450 HP
250-600 HP
1
1.0 & Up A1
1.0 & Up A2
1.0 & Up A3
0.75-15 kW
1-20 HP
1.0 & Up B1/B2
18.5-45 kW
25-60 HP
56-93 kW
75-125 HP
112-224 kW
150-300 HP
261-298 kW
350-400 HP
224-448 kW
300-600 HP
PLUS II Adjustable
Compatible with
Version . . .
1.0 & Up A4
1.0 & Up C
1.0 & Up D
1.0 & Up E
1.0 & Up F
1.0 & Up G
Frame
Reference200-240V 380-480V 500-600V
1–2 Information and Precautions

General Precautions

ATTENTION: This drive contains ESD (Electrostatic
!
!
Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.
ATTENTION: Only personnel familiar with the 1336
PLUS II Adjustable Frequency AC Drive and associated
machinery should plan or implement the installation, start­up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: To avoid a hazard of electric shock, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the + & - terminals of TB1. The voltage must be
0.0V DC.
Conventions Used in this
Manual
!
!
To help differentiate parameter names and display text from other text the following conventions will be used:
Parameter Names will appear in [brackets]
Display Text will appear in “quotes”

Catalog Number Explanation The diagram on the following page describes the 1336 PLUS II

catalog numbering scheme.
Information and Precautions 1–3
1336F
First Position
Bulletin Number
BR
Second Position
Vol ta ge
Letter Voltages
AQ 200-240V AC or
BR 380-480VAC or
CW 500-600V AC or
A 200-240V AC
B 380-480V AC
BP/BPR380-480V AC
BX Special Rating
C 500-600V AC
CP/CPR 500-600V AC
Q 310V DC
R 513-620V DC
RX Special Rating
W 775V DC
310V DC
513-620V DC
775V DC
(F Frame)
(F Frame)
F30
Third Position
Nominal HP Rating
Refer to table below for ratings and possible voltage combinations.
Voltage and Nominal HP Rating Combinations
Code Rating AQ BR CW A B
F05 0.37 (0.5) ●● F07 0.56 (0.75) ●● F10 0.75 (1) ●● ● F15 1.2 (1.5) ●● F20 1.5 (2) ●● ● F30 2.2 (3) ●● ● F50 3.7 (5) ●● ● F75 5.5 (7.5) ●● ● F100 7.5 (10) ●● F150 11 (15) ●● F200 15 (20) ●● 007 5.5 (7.5) ●● 010 7.5 (10) ●● 015 11 (15) ●● ●● 020 15 (20) ●● ●● 025 18.5 (25) ●● ●● 030 22 (30) ●● ●● 040 30 (40) ●● ● ● ●● ● ● 050 37 (50) ●● ●● 060 45 (60) ●● ● ● ●● ● ● 075 56 (75) ●● ●● 100 75 (100) ●● ●● 125 93 (125) ●● ●● 150 112 (150) ●●● ● 200 149 (200) ●●● 250 187 (250) ➁● 300 224 (300) ➁● 350 261 (350) ➁● 400 298 (400) ➁● 450 336 (450) ➁● 500 373 (500) ➁● 600 448 (600) ●●●
Language must be specified to ensure shipment of appropriate User Manual.
G Frame Standard Drives in enclosed construction are supplied through the Configured Drives
Program and will have an “A” suffix after the HP rating.
D through G Frame drives in IP 65 (NEMA Type 4) and IP 54 (NEMA Type 12) configurations are
supplied through the Configured Drives Program.
“xPR” has a “roll-in” type chassis. Not available with v5.001 & later.
BP/
BPR BX C
CP/
CPR Q R RX W
AA
Fourth Position
Enclosure Type
Code Type
AA IP 20 (NEMA 1)
AE IP 20 (NEMA 1)/EMC
AF IP 65 (NEMA 4)
AJ IP 54 (NEMA 12)
AN IP 00 (Open)
Code Description
Human Interface Module, Snap-In, IP20 (NEMA Type 1)
HASB Snap-In Cradle/Blank Plate
HASP Programmer Only
HCSP Programmer Only & Upload/Download Capability
HAS1 Programmer/Controller w/Analog Pot
HCS1 Programmer/Controller w/Analog Pot & Upload/Download Capability
HAS2 Programmer/Controller w/Digital Pot
HCS2 Programmer/Controller w/Digital Pot & Upload/Download Capability
Human Interface Module, IP65/54 (NEMA Type 4/12)
HJP Programmer Only
HJ2 Programmer/Controller w/Digital Pot
Communication Options –- B Frame & Up (Adapter 6)
GM1 Single Point Remote I/O B Frame
GM2 RS-232/422/485, DF1 & DH485 B Frame
GM5 DeviceNet™
GM6 Enhanced DeviceNet™
Communication Options –- All Frames (Adapter 1)
GMS1 GM1 with Snap-In Cradle
GMS2 GM2 with Snap-In Cradle
GMS5 GM5 with Snap-In Cradle
GMS6 GM6 with Snap-In Cradle
Control Interface Options
L4 TTL Contact
L4E TTL Contact & Encoder Feedback
L7E TTL Contact & Encoder Fdbck. for use with Encoder Loss Detection
L5 24V AC/DC
L5E 24V AC/DC & Encoder Feedback
L8E 24V AC/DC & Encoder Feedback for use with Encoder Loss Detection
L6 115V AC
L6E 115V AC & Encoder Feedback
L9E 115V AC & Encoder Feedback for use with Encoder Loss Detection
Analog Interface Options – Slot A
• Choose No More than One – Configurable Inputs/Outputs are 10V or 20mA
LA2 Two Isolated Configurable Inputs LA6 One Isolated Bi-polar Input (±10V or ±20mA) and One Isolated
LA7 One Isolated Bi-polar Input (±10V or ±20mA) and One Isolated
Analog Interface Options – Slot B
• Choose No More than One – Configurable Inputs/Outputs are 10V or 20mA
LA1 Single-ended, Non-isolated Configurable (including Pot) Input & 2
LA3 Two Isolated Configurable Outputs
LA4 One Isolated Configurable Input & Output
LA5 Isolated Pulse Input, Non-isolated Pulse Output & Single-ended,
Common Mode Choke –- F & G Frame (must be specified for F Frame)
CM Internal Common Mode Choke (factory installed)
NCM No Common Mode Choke
Thermistor Input
Configurable Input
Single-ended, Non-isolated Outputs (1 - Configurable, 1 - 20mA)
Non-isolated Configurable Output
EN
Fifth Position
Language Group
Code Language
EN English
FR French
DE German
IT Italian
ES Spanish
JP Japanese
MODS
Sixth Position
Options
1–4 Information and Precautions

Nameplate Location Figure 1.1

1336
PLUS II Nameplate Location
1
Refer to page 1-1 for frame reference classifications.
ESC SEL
JOG
Nameplate Located on
Bottom Portion of
Chassis Behind Cover
Frames1 A1, A2, A3, A4
Nameplate Located on
Mounting Plate of
Main Control Board
Frames
1
B - G

Chapter 2

Installation/Wiring

Chapter 2 provides the information you need to properly mount and wire the 1336 are the result of incorrect wiring, every precaution must be taken to assure that the wiring is done as instructed. All items must be read and understood before the actual installation begins.
ATTENTION: The following information is merely a guide for proper installation. The Allen-Bradley
!
Company cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
PLUS II Drive. Since most start-up difficulties

Mounting Minimum Mounting Requirements for Proper Heat Dissipation

(Dimensions shown are between drives or other devices)
152.4 mm (6.0 in.)
101.6 mm (4.0 in.)
ESC SEL
JOG
UP
152.4 mm (6.0 in.)
Important: A4 Frame drives should not be mounted on a combustible surface. However,
if the drive must be mounted on a combustible surface, 6.35 mm (0.25 in.) spacers must be provided under the mounting feet of the drive.
152.4 mm (6.0 in.)
ESC
JOG
152.4 mm (6.0 in.)
F Frame drives require a minimum of 152.4 mm (6.0 in.) between the drive back and mounting wall, if drives are mounted with sides touching another device or wall. A minimum of 76.2 mm (3.0 in.) is required on the sides if the back of the drive is mounted against a wall or other device.
2–2 Installation/Wiring

Installation Guidelines

GND
PE
R
GND
(L1)S(L2)T(L3)
CAT. NO.
FREQUENCY
POWER RATING
PRIMARY VOLTAGE
SECONDARY VOLTAGE
INSULATION CLASS
NO. OF PHASES
VENDOR PART NO.
AC Supply Source
ALLEN-BRADLEY
Input Power Conditioning
Input Fusing & Circuit Breakers
Input Devices
Input Filters
Electrical Interference
Page 2–3
Page 2–4
Page 2–5
Page 2–9
Page 2–10
Page 2–9
PE
GND
(T1)
U
ESC SEL
JOG
(T2)V(T3)
W
Grounding
Power Cabling
Control & Signal Cabling
Output Devices
Cable Termination
Motor
Page 2–11
Page 2–14
Page 2–24
Page 2–37
Page 2–37
Installation/Wiring 2–3

AC Supply Source 1336 PLUS II drives are suitable for use on a circuit capable of deliv-

ering up to a maximum of 200,000 rms symmetrical amperes, 600 volts. Refer to Table 2.A circuit breaker choice.
ATTENTION: To guard against personal injury and/or equipment damage caused by improper fusing, use only the
!
recommended line fuses specified in Tab l e 2. A
Unbalanced Distribution Systems
This drive is designed to operate on three-phase supply systems whose line voltages are symmetrical. Surge suppression devices are included to protect the drive from lightning induced overvoltages between line and ground. Where the potential exists for abnormally high phase-to-ground voltages (in excess of 125% of nominal), or where the supply ground is tied to another system or equipment that could cause the ground potential to vary with operation, suitable iso­lation is required for the drive. Where this potential exists, an isola­tion transformer is strongly recommended.
for actual interrupt ratings based on fuse or
.
Ungrounded Distribution Systems
All 1336 PLUS II drives are equipped with an MOV (Metal Oxide Varistor) that provides voltage surge protection and phase-to-phase plus phase-to-ground protection which is designed to meet IEEE 587. The MOV circuit is designed for surge suppression only (transient line protection), not continuous operation.
With ungrounded distribution systems, the phase-to-ground MOV connection could become a continuous current path to ground. Energy ratings are listed below. Exceeding the published phase-to­phase or phase-to-ground energy ratings may cause physical damage to the MOV. Refer to page A-1.
Joules (J)
Joules (J)
1234
Phase-to-Phase MOV Rating
Includes 2 Phase-Phase MOVs
Phase-to-Ground MOV Rating
Includes Phase-Phase & Phase-Ground MOVs
Three-Phase
AC Input
Ground
R
S
T
Joules (J)
Joules (J)
Frame Reference
Device Rating (V AC)
Phase-Phase Total Phase-Ground Total
A
240 480/600
160J 320J 220J 380J
B-C
240/480 600
280J 320J 360J 410J
D-G
240/480 600
280J 300J 360J 370J
2–4 Installation/Wiring
V

Input Power Conditioning In general, the 1336 PLUS II is suitable for direct connection to an AC

line of the correct voltage. Certain conditions can exist, however, that prompt consideration of a line reactor or isolation transformer ahead of the drive.
The basic rules to aid in determining whether a line reactor or isola­tion transformer should be considered are as follows:
1. If the AC source experiences frequent power outages or signifi-
cant voltage transients, users should calculate the VA mula below). If the source transformer VA exceeds the calculated
and the drive is installed close to the source, it is an indication
VA
max
that there may be enough energy behind these voltage transients to cause nuisance input fuse blowing, overvoltage faults or drive power structure damage. In these cases, a line reactor or isolation trans­former should be considered.
Z
VA
drive
max
(/Φ) =
(V
=
line-line
line-line
3 x Input Amps
)2 x % Source Leakage (5-6% typical)
x 0.01
Z
drive
(see for-
max
2. If the AC source does not have a neutral or one phase referenced
to ground (see Unbalanced Distribution Systems on page 2–3
), an
isolation transformer with the neutral of the secondary grounded is
highly recommended.
If the line-to-ground voltages on any phase
can exceed 125% of the nominal line-to-line voltage, an isolation transformer with the neutral of the secondary grounded, is highly
recommended.
3. If the AC line supplying the drive has power factor correction
capacitors that are switched in and out, an isolation transformer or 5% line reactor is recommended between the drive and capaci­tors. If the capacitors are permanently connected and not switched, the general rules above apply.
Installation/Wiring 2–5
Input Fuses and Circuit
Breakers
The 1336 PLUS II can be installed with either input fuses or an input circuit breaker. Local/national electrical codes may determine addi­tional requirements for these installations.
The tables on the following pages provide drive ratings and recom­mended AC line input fuse and circuit breaker information. Both types of short circuit protection are acceptable for UL and IEC requirements. Sizes listed are the recommended sizes based on 40 degree C and the U.S. N.E.C. Other country, state or local codes may require different ratings.
ATTENTION: The 1336 PLUS II does not provide input power short circuit protection. Specifications for the recom-
!
mended fuse or circuit breaker to provide drive input power protection against short circuits are provided.
Fusing
If fuses are chosen as the desired protection method, refer to the recommended types listed below. If available amp ratings do not match the tables provided, the closest drive rating should be chosen.
IEC – BS88 (British Standard) Parts 1 & 2 2, type gG or equivalent should be used.
UL – UL Class CC, T, RK1 or J must be used.
fuse rating that exceeds the
1
, EN60269-1, Parts 1 &
Circuit Breakers
The “non-fuse” listings in the following tables include both circuit breakers (inverse time or instantaneous trip) and 140M Self-Protect­ing Motor Starters. If one of these is chosen as the desired protec- tion method, the following requirements apply.
IEC and UL – Both types of devices are acceptable for IEC and UL installations
1. Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD,
DD, ED, EFS, EF, FF, FG, GF, GG, GH.
2–6 Installation/Wiring
Table 2.A 240 Volt Input Protection Devices
Drive Catalog Number 1336F- HP
Frame
Input Rating
Amps Amps Min.1Max.2Min.1Max.2Max.8Max.
Output Rating
Dual-Element Time Delay Fuse
Non-Time Delay Fuse
Circuit Breaker
A1 F05 0.5 2.8 2.3 4 5 4 6 15 3 140M-C2E-B40 140M-D8E-B40 –
F07 0.75 3.5 3.0 4 6 4 9 15 7 140M-C2E-B40 140M-D8E-B40 –
F10 1 5.4 4.5 6 9 6 12 15 7 140M-C2E-B63 140M-D8E-B63 –
A2 F15 1.5 7.3 6.0 8 12.5 8 15 20 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
F20 2 9.7 8.0 10 15 10 20 25 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
A3 F30 3 14.3 12.0 15 20 15 25 35 15 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
F50 5 21.3 18.0 25 30 25 45 60 30 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 140M-CMN-2500
F75 7.5 22.6 22.0 30 45 30 60 80 50 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 140M-CMN-2500
B 007 7.5 28.0 27.0 40 45 40 60 80 50 140M-F8E-C32 140M-CMN-4000
010 10 35.0 34.0 50 60 50 80 100 50 140M-CMN-4000
015 15 49.0 48.0 70 90 70 110 150 70 140M-CMN-6300
C 020 20 63.0 65.0 100 110 100 125 200 100 140M-CMN-9000
025 25 75.0 77.0 100 150 100 200 250 100 140M-CMN-9000
030 30 79.0 80.0 125 175 125 225 300 150 140M-CMN-9000
D 040 40 119.0 120.0 120 225 120 300 300 150
050 50 149.0 150.0 200 250 200 350 350 250
060 60 178.0 180.0 250 300 250 450 450 250
E 075 75 238.0 240.0 300 400 300 500 500 250
100 100 289.0 291.0 400 500 400 700 700 400
125 125 322.0 325.0 450 700 450 800 800 600
1
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
2
Maximum protection device size is the highest rated device that supplies drive protection.
3
Circuit Breaker - inverse time breaker.
4
Motor Circuit Protector - instantaneous trip circuit breaker.
5
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
6
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta systems.
7
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001B-EN-P.
8
Maximum rating allowed by US NEC. Exact size must be chosen for each installtion.
9
The Maximum Short Circuit Rating of a Cutler-Hammer Series HMCP is 100,000A at 240 volts, 65,000A at 480 volts and 25,000A at 575 volts.
Motor Circuit
3
Protector
4,9
140M Motor Starter with Adjustable Current Range
8
Available Catalog Numbers
7
5, 6
Installation/Wiring 2–7
Table 2.A (continued) 480 Volt Input Protection Devices
CT Ratings VT Ratings
Drive Catalog Number
1336F-
Frame
Input Output
HP
Amps Amps Amps Amps Min.
Input Output
HP
Dual Element Time Delay Fuse
1
Non-Time Delay Fuse
Max.2Min.1Max.2Max.8Max.8Available Catalog Numbers - 140 . . .
A1 F05 0.5 1.3 1.1 0.5 1.4 1.2 3 2.5 3 3 15 3 M-C2E-B16 –
F07 0.75 2.0 1.6 0.75 2.1 1.7 3 3 3 6 15 3 M-C2E-B25 –
F10 1 2.6 2.1 1 2.8 2.3 3 4.5 3 8 15 3 M-C2E-B40 M-D8E-B40 –
F15 1.5 3.3 2.8 1.5 3.5 3.0 4 6 4 12 15 7 M-C2E-B40 M-D8E-B40 –
A2 F20 2 4.6 3.8 2 4.8 4.0 5 6 5 12 15 7 M-C2E-C63 M-D8E-C63 –
F30 3 6.4 5.3 3 7.2 6.0 8 10 8 15 25 7 M-C2E-C10 M-D8E-C10 M-F8E-C10 –
A3 F50 5 10.0 8.4 5 10.7 9.0 12 15 12 30 35 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 –
A4 F75 7.5 13.6 13.3 10 15.7 15.4 20 30 20 50 50 30 M-C2E-C16 M-D8E-C16 M-F8E-C16 –
F100 10 16.4 16.1 15 22.4 22.0 30 40 30 80 80 30 M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
F150 15 24.5 24.0 20 24.5 24.0 35 60 35 100 100 50 M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
F200 20 28.0 27.0 20 28.0 27.0 35 60 35 100 100 50 M-F8E-C32 -CMN-4000
B 015 15 25.0 24.2 20 28.0 27.0 35 60 35 100 100 50 M-F8E-C32 -CMN-4000
020 20 32.0 31.0 25 35.0 34.0 45 70 45 125 125 50 M-F8E-C45 -CMN-4000
025 25 40.0 39.0 30 43.0 42.0 60 90 60 150 150 70 M-F8E-C45 -CMN-6300
030 30 46.0 45.0 30 49.0 48.0 70 90 70 150 150 70 -CMN-6300
C X040 40 61.0 59.0 40 61.0 59.0 80 110 80 200 200 70 -CMN-6300
040 40 58.0 60.0 50 63.0 65.0 80 125 80 250 250 100 -CMN-6300
050 50 73.0 75.0 60 75.0 77.0 100 150 100 300 300 100 -CMN-9000
X060 60 75.0 77.0 60 75.0 77.0 100 150 100 300 300 100 -CMN-9000
D 060 60 82.0 85.0 75 93.0 96.0 125 200 125 350 350 150
075 75 105.0 106.0 100 119.0 120.0 150 250 150 450 350 250
100 100 137.0 138.0 125 149.0 150.0 200 350 200 600 450 250
125 125 172.0 173.0 150 178.0 180.0 250 400 250 600 500 250
X150 150 178.0 180.0 150 178.0 180.0 250 400 250 600 500 250
E 150 150 197.0 199.0 200 238.0 240.0 300 500 300 700 700 400
200 200 261.0 263.0 250 290.0 292.0 400 600 400 800 800 400
250 250 322.0 325.0 250 322.0 325.0 450 600 450 800 800 400
F P250 250 322.0 325.0 300 357.0 360.0 450
P300 300 357.0 360.0 350 421.0 425.0 500
P350 350 421.0 425.0 400 471.0 475.0 600
P400 400 471.0 475.0 450 527.0 532.0 600
Refer to the 1336 Spare Parts list (publication 1336-6.5) for replacement information.
P450 450 527.0 532.0 700
G X250 250 322.0 325.0 300 357.0 360.0 450
300 300 357.0 360.0 350 421.0 425.0 450
350 350 421.0 425.0 400 471.0 475.0 500
400 400 471.0 475.0 450 521.0 525.0 600/630 –
450 450 521.0 525.0 500 585.0 590.0 800
500 500 585.0 590.0 600 664.0 670.0 800
600 600 664.0 670.0 600 664.0 670.0 900 -
1
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
2
Maximum protection device size is the highest rated device that supplies drive protection.
3
Circuit Breaker - inverse time breaker.
4
Motor Circuit Protector - instantaneous trip circuit breaker.
5
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
6
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta systems.
7
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001B-EN-P.
8
Maximum rating allowed by US NEC. Exact size must be chosen for each installtion.
9
The Maximum Short Circuit Rating of a Cutler-Hammer Series HMCP is 100,000A at 240 volts, 65,000A at 480 volts and 25,000A at 575 volts.
Motor
Circuit
Circuit
Breaker
Protector
3
4,9
140M Motor Starter with Adjustable Current Range
6
Semiconductor fuse supplied with drive.
Bussmann Type FWP, SPP, or 170M Series
Ferraz Shawmut Type A-70Q, A-70QS or A070URD Series
7
5,
2–8 Installation/Wiring
Table 2.A (continued) 575 Volt Input Protection Devices
CT Ratings
Drive Catalog Number
1336F-
Frame
A4 F10 1 2.4 2.0 3 3 3 6 15 3 140M-C2E-B25 –
F20 2 4.8 4.0 6 6 6 10 15 7 140M-C2E-C63 140M-D8E-C63 –
F30 3 7.2 6.0 10 12 10 15 15 7 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
F50 5 9.6 8.0 15 20 15 20 20 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
F75 7.5 10.0 10.0 15 20 15 30 35 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 –
F100 10 12.0 12.0 20 25 20 40 40 15 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 –
F150 15 19.0 19.0 25 35 25 60 60 30 140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 140-CMN-2500
F200 20 25.0 24.0 30 45 30 80 80 30 140M-C2E-C25 140M-D8E-C25 140M-F8E-C25 140-CMN-2500
C 025 25 31.0 30.0 40 60 40 100 100 50 140M-F8E-C32 140-CMN-4000
030 30 36.0 35.0 50 70 50 125 125 50 140M-F8E-C45 140-CMN-4000
040 40 44.0 45.0 60 90 60 150 150 70 140M-F8E-C45 140-CMN-6300
050 50 55.0 57.0 80 110 80 200 200 70 140M-CMN-6300
060 60 60.0 62.0 90 125 90 225 225 100 140M-CMN-6300
D 075 75 84.0 85.0 110 150 110 300 300 100 140M-CMN-9000
100 100 108.0 109.0 150 200 150 350 350 150 ––––
125 125 137.0 138.0 175 250 175 500 350 250 ––––
E 150 150 167.0 168.0 225 300 225 500 400 250 ––––
200 200 251.0 252.0 350 400 350 600 500 250 ––––
250 250 282.0 284.0 400 500 400 700 700 400 ––––
X300 300 295.0 298.0 400 600 400 800 800 400 ––––
F P350 350 347.0 350.0 450
P400 400 397.0 400.0 500
G 300 300 297.0 300.0 400
350 350 347.0 350.0 450
400 400 397.0 400.0 500
450 450 446.0 450.0 600/630
500 500 496.0 500.0 800
600 600 595.0 600.0 800
1
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
2
Maximum protection device size is the highest rated device that supplies drive protection.
3
Circuit Breaker - inverse time breaker.
4
Motor Circuit Protector - instantaneous trip circuit breaker.
5
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
6
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V
Input Output
HP
Amps Amps Min.
Dual Element Time Delay Fuse
1
Max.2Min.1Max.2Max.8Max.8Available Catalog Numbers
Non-Time Delay Fuse
Refer to the 1336 Spare Parts list (publication 1336-6.5) for replacement information.
or 600V Delta/Delta systems.
7
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001B-EN-P.
8
Maximum rating allowed by US NEC. Exact size must be chosen for each installtion.
9
The Maximum Short Circuit Rating of a Cutler-Hammer Series HMCP is 100,000A at 240 volts, 65,000A at 480 volts and 25,000A at 575 volts.
Circuit Breaker
3
Motor Circuit Protector
4,9
140M Motor Starter with Adjustable Current Range
Semiconductor fuse supplied with drive.
Bussmann Type FWP, SPP, or 170M Series
Ferraz Shawmut Type A-70Q, A-70QS or A070URD Series
7
5, 6
Table 2.B deleted

Input Devices Starting and Stopping the Motor

ATTENTION: The drive start/stop control circuitry in­cludes solid-state components. If hazards due to accidental
!
contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop cir­cuit may be required to remove AC line power to the drive. When AC power is removed, there will be a loss of inherent regenerative braking effect & the motor will coast to a stop. An auxiliary braking method may be required.
Repeated Application/Removal of Input Power
ATTENTION: The drive is intended to be controlled by control input signals that will start and stop the motor. A
!
device that routinely disconnects then reapplies line power to the drive for the purpose of starting and stopping the motor is not recommended.
Installation/Wiring 2–9
Bypass Contactors
!

Electrical Interference - EMI/RFI Immunity

The immunity of 1336 PLUS II drives to externally generated interfer- ence is good. Usually, no special precautions are required beyond the installation practices provided in this publication.
It is recommended that the coils of DC energized contactors associ­ated with drives be suppressed with a diode or similar device, since they can generate severe electrical transients.
ATTENTION: An incorrectly applied or installed bypass system can result in component damage or reduction in product life. The most common causes are:
• Wiring AC line to drive output or control terminals.
• Improper bypass or output circuits not approved by Allen-Bradley.
• Output circuits which do not connect directly to the motor.
Contact Allen-Bradley for assistance with application or wiring.
2–10 Installation/Wiring
Emission
Careful attention must be given to the arrangement of power and ground connections to the drive to avoid interference with nearby sen­sitive equipment. The cable to the motor carries switched voltages and should be routed well away from sensitive equipment.
The ground conductor of the motor cable should be connected to the drive ground (PE) terminal directly. Connecting this ground conduc­tor to a cabinet ground point or ground bus bar may cause high fre­quency current to circulate in the ground system of the enclosure. The motor end of this ground conductor must be solidly connected to the motor case ground.
Shielded or armored cable may be used to guard against radiated emissions from the motor cable. The shield or armor should be con­nected to the drive ground (PE) terminal and the motor ground as outlined above.
Common mode chokes at the drive output can help reduce common mode noise on installations that do not use shielded cable. Common mode chokes can also be used on analog or communication cables. Refer to page 2–37
for further information.
An RFI filter can be used and in most situations provides an effective reduction of RFI emissions that may be conducted into the main supply lines.
If the installation combines a drive with sensitive devices or circuits, it is recommended that the lowest possible drive PWM carrier fre­quency be programmed.

RFI Filtering 1336 PLUS II drives can be installed with an RFI filter, which controls

radio-frequency conducted emissions into the main supply lines and ground wiring.
If the cabling and installation recommendation precautions described in this manual are adhered to, it is unlikely that interference problems will occur when the drive is used with conventional industrial elec­tronic circuits and systems. However, a filter may be required if there is a likelihood of sensitive devices or circuits being installed on the same AC supply.
Where it is essential that very low emission levels must be achieved or if conformity with standards is required the optional RFI filter must be used. Refer to Appendix C and instructions included with the filter for installation and grounding information.

CE Conformity Refer to Appendix C.

Installation/Wiring 2–11

Grounding Refer to the grounding diagram on page 2–13. The drive must be con-

nected to system ground at the power ground (PE) terminal provided on the power terminal block (TB1). Ground impedance must conform to the requirements of national and local industrial safety regulations (NEC, VDE 0160, BSI, etc.) and should be inspected and tested at appropriate and regular intervals.
In any cabinet, a single, low-impedance ground point or ground bus bar should be used. All circuits should be grounded independently and directly. The AC supply ground conductor should also be con­nected directly to this ground point or bus bar.
Sensitive Circuits
It is essential to define the paths through which the high frequency ground currents flow. This will assure that sensitive circuits do not share a path with such current. Control and signal conductors should not be run near or parallel to power conductors.
Motor Cable
The ground conductor of the motor cable (drive end) must be con­nected directly to the drive ground (PE) terminal, not to the enclosure bus bar. Grounding directly to the drive (and filter, if installed) can provide a direct route for high frequency current returning from the motor frame and ground conductor. At the motor end, the ground con­ductor should also be connected to the motor case ground.
If shielded or armored cables are used, the shield/armor should also be grounded at both ends as described above.
Encoder & Communications Cabling
If encoder connections or communications cables are used, the wiring must be separated from power cabling. This can be accomplished with carefully routed, shielded cable (ground cable shield at the drive end only) or a separate steel conduit (grounded at both ends).
Discrete Control and Signal Wiring
The control and signal wiring must be grounded at a single point in the system, remote from the drive. This means the 0V or ground terminal should be grounded at the equipment end, not the drive end. If shielded control and signal wires are used, the shield must also be grounded at this point.
If the control and signal wires are short, and contained within a cabinet which has no sensitive circuits, the use of shielded control and signal wiring may not be necessary, but is always recommended.
2–12 Installation/Wiring
Shield Termination - TE (True Earth)
The TE terminal block (not available on A Frame drives) is used for all cable shields at the drive. It must be connected to an earth ground by a separate continuous lead. TE connections may exist on power and/or control terminal blocks to terminate shield cables for both power and control. Refer to Figure 2.1
for locations.
Safety Ground - PE (Potential Earth)
This is the safety ground required by code. This point must be con­nected to adjacent building steel (girder, joist) or a floor ground rod, provided grounding points comply with national or local electric code regulations. If a cabinet ground bus is used, refer to Grounding on page 2–11
.
RFI Filter
Important: Using an optional RFI filter may result in relatively high
ground leakage currents. Surge suppression devices are also incorporated in the filter. Therefore, the filter must be permanently installed and solidly grounded to the supply neutral. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. The integrity of this connection should be periodically checked.
General Grounding
Installation/Wiring 2–13
Conduit/4-Wire Cable
Nearest
Building Structure Steel
R (L1)
S (L2)
ESC SEL
T (L3)
PE
RIO/DH+ or Analog
Common
Mode Core*
To Computer/Position Controller
(for TE shield ground, see "
Control and Signal Wiring"
Single-Point Grounding/Panel Layout
R (L1)
S (L2)
Common
Mode
U (T1)
Core*
V (T2)
JOG
W (T3)
PE/Gnd.
Shield
Motor Frame
PE
Ground per
Motor
Local Codes
Terminator*
* Options that can be
installed as needed.
)
To Nearest Building
Structure Steel
Nearest
Building Structure Steel
T (L3)
TE – Zero Volt Potential Bus
(Isolated from Panel)
PE Ground Bus
(Grounded to Panel)
For Programmable Controller grounding recommendations, refer to publication 1770-4.1
1336 FORCE 1336 PLUS
ESC SEL
JOG
Logic
PE TE
Logic
PE
Nearest Building
Structure Steel
Important: Grounding requirements will vary with the drives being used. Drives with True Earth (TE) terminals must have a zero potential bus, separate from potential earth (PE) ground bus. Note that buses can be tied together at one point in the control cabinet or
brought back separately to the building ground grid (tied within 3 meters
(10 feet)).
2–14 Installation/Wiring

Power Cabling Input and output power connections are performed through terminal

block, TB1 (see Figure 2.1
Important: For maintenance and setup procedures, the drive may be
operated without a motor connected.
Table 2.C
TB1 Signals
Terminal Description
PE Potential Earth Ground
TE True Earth Ground
R (L1), S (L2), T (L3) AC Line Input Terminals
+DC, -DC DC Bus Terminals
U (T1), V (T2), W (T3) Motor Connection
ATTENTION: The National Codes and standards (NEC,
!
VDE, BSI etc.) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment dam­age.
for location).
TB1
Power Terminal Block
TB2
Control & Signal Wiring
TB3
Control Interface Option
TB4
24V DC Auxiliary Input
TB6
High Voltage DC Auxiliary Input
TB9
480 or 600V Auxiliary Output (F Frame Only)
TE
Control & Signal Shield Terminals
TB3
Option
Control Interface
TB1
Frames A1-A4
1
TB2
TB1
Control Interface
Option
TB1
Frames B, C
1
TB4 TB6
TB3
TB2
TB1
Figure 2.1 Terminal Block Locations
TB3
Control Interface
Option
TB1
Location
Frames D, E
TB4
TB2
TE
TB6
TB1
1
TB1 Location
1
Frame F
R, S, T
TB9
TB3
TB2
TE
TB1
Brake Terminals
TB1
Location
Frame G
TB3
TB2
TE
U, V, W & Brake Terminals
PE Ground
1
1
Refer to page 1–1 for frame reference classifications and Figure 2.2 for TB1 details.
Installation/Wiring 2–15
Table 2.D TB1 Specifications
Drive Frame
Size
Max./Min. Wire Size
mm2 (AWG)
1
A1-A4 (page 2–21) 5.3/0.8 (10/18) 1.81 (16)
B1 (page 2–21
B2 (page 2–21
C (page 2–21
D (page 2–22
E (page 2–22)
F (page 2–23
G (page 2–23
1
Wire sizes given are maximum/minimum sizes that TB1 will accept - these are not recommendations.Use Copper wire only. Wire gauge requirements and recommendations are based on 75 degree C. Do not reduce wire gauge when using higher temperature wire.
2
Applies to 30 kW (40 HP) 200-240V, 45 & 56 kW (60 & 75 HP) 380-480V, 56 kW (75 HP) 500-600V drives only.
3
These configurations of TB1 are stud type terminations and require the use of lug type connectors to terminate field installed conductors. Lug kits are available for use with these configurations. Wire size used is determined by selecting the proper lug based on the drive catalog number. Refer to Table 2.E.
4
One TE terminal is present – Max./Min. Wire Size is the same as other terminals.
5
Two TE terminals are present – Max./Min. Wire Size is the same as the D Frame terminal block.
) 8.4/0.8 (8/18) 1.81 (16)
) 13.3/0.5 (6/20) 1.70 (15)
) 26.7/0.8 (3/18) 5.65 (50)
3, 4
)
3, 5
3
)
3
)
120.0/2.1 (4/0 /14)
67.4/2.1 (00/14)
2
253.0/2.1 (500 MCM/14) 10.00 (87)
303.6/2.1 (600 MCM/14) 23.00 (200)
303.6/2.1 (600 MCM/14) 23.00 (200)
Maximum Torque
N-m (lb.-in.)
6.00 (52)
6.00 (52)
Lug Kits
D, E, F and G Frame drives have stud type terminals and/or bus bars/ bolts that require standard “crimp type” connectors for cable termina-
tion. Connectors such as T & B Color-Keyed lent) are recommended. The following table shows the lug selection for one possible cable choice. Connectors for each installation should be chosen based on desired cable sizes, the application requirements and all applicable national, state and local codes. See the minimum/ maximum values for wire size per Tabl e 2.D
connectors (or equiva-
2–16 Installation/Wiring
Table 2.E Lug Selection
AC Input R, S, T/Output U, V, W and PE DC+/DC–
Drive Catalog
Number
Cable (per Phase)
Qty. mm2 (AWG)
T&B Part No.
Qty. Number
1336F-A040 (1) 53.5 (1/0) (8) 54153
1336F-A050 (1) 85.0 (3/0) (8) 54163
1336F-A060 (1) 107.2 (4/0) (8) 54168
1336F-A075 (2) 53.5 (1/0) (8) 54109T
3
Cable (per Phase)
Qty. mm2 (AWG)
1
(1) 13.3 (6) (2) 54135
1
(1) 13.3 (6) (2) 54135
1
(1) 13.3 (6) (2) 54135
(1) 33.6 (2) (2) 54109 (1) 21.2 (4) (1) 54139
(8) 54109B
1336F-A100 (2) 85.0 (3/0) (8) 54111T
(1) 42.4 (1) (2) 54148 (1) 33.6 (2) (1) 54142
(8) 54111B
1336F-A125 (2) 107.2 (4/0) (8) 54112T
(1) 67.4 (2/0) (2) 54110 (1) 33.6 (2) (1) 54142
(8) 54112B
1336F-B060 (1) 42.4 (1) (8) 54147
1336F-B075 (1) 53.5 (1/0) (8) 54153
1336F-B100 (1) 85.0 (3/0) (8) 54163
1336F-B125 (1) 107.2 (4/0) (8) 54168
1336F-BX150 (1) 107.2 (4/0) (8) 54168
1336F-B150 (2) 53.5 (1/0) (8) 54109T
1
(1) 8.4 (8) (2) 54131
1
(1) 13.3 (6) (2) 54135
1
(1) 13.3 (6) (2) 54135
1
(1) 26.7 (3) (2) 54147
1
(1) 26.7 (3) (2) 54147
(1) 33.6 (2) (2) 54110 (1) 21.2 (4) (1) 54139
(8) 54109B
1336F-B200 (2) 85.0 (3/0) (8) 54111T
(1) 42.4 (1) (2) 54148 (1) 26.7 (3) (1) 54142
(8) 54111B
1336F-B250 (2) 107.2 (4/0) (8) 54112T
(1) 67.4 (2/0) (2) 54110 (1) 33.6 (2) (1) 54142
(8) 54112B
1336F-BX250 (3) 53.5 (1/0) (24) 54109 (1) 67.4 (2/0) (2) 54110 NA NA
1336F-BP/BPR250 (3) 53.5 (1/0) (24) 54109 (1) 67.4 (2/0) (2) 54110 NA NA
1336F-B300 (3) 67.4 (2/0) (24) 54110 (1) 42.4 (1) (2) 54148 NA NA
1336F-BP/BPR300 (3) 67.4 (2/0) (24) 54110 (1) 42.4 (1) (2) 54148 NA NA
1336F-B350 (3) 85.0 (3/0) (24) 54111 (1) 42.4 (1) (2) 54148 NA NA
1336F-BP/BPR350 (3) 85.0 (3/0) (24) 54111 (1) 42.4 (1) (2) 54148 NA NA
1336F-B400 (3) 107.2 (4/0) (24) 54112 (1) 42.4 (1) (2) 54148 NA NA
1336F-BP/BPR400 (3) 107.2 (4/0) (24)54112 (1) 42.4 (1) (2) 54148 NA NA
1336F-B450 (3) 127.0 (250 MCM) (24) 54174 (1) 42.4 (1) (2) 54148 NA NA
1336F-BP/BPR450 (3) 127.0 (250 MCM) (24) 54174 (1) 42.4 (1) (2) 54148 NA NA
1336F-B500 (3) 152.0 (300 MCM) (24) 54179 (1) 53.5 (1/0) (2) 54109 NA NA
1336F-B600 (3) 152.0 (300 MCM) (24) 54179 (1) 53.5 (1/0) (2) 54109 NA NA
1
1336F-C075 (1) 33.6 (2) (8) 54142
1336F-C100 (1) 53.5 (1/0) (8) 54153
1336F-C125 (1) 67.4 (2/0) (8) 54158
(1) 13.3 (6) (2) 54135
1
(1) 13.3 (6) (2) 54135
1
(1) 26.7 (3) (2) 54147
1336F-C150 (1) 107.2 (4/0) (8) 54111 (1) 42.4 (1) (2) 54148 (1) 13.3 (6) (1) 54135
1336F-C200 (2) 67.4 (2/0) (8) 54110T
(1) 42.4 (1) (2) 54148 (1) 26.7 (3) (1) 54142
(8) 54110B
1336F-C250 (2) 85.0 (3/0) (8) 54111T
(1) 67.4 (2/0) (2) 54110 (1) 26.7 (3) (1) 54142
(8) 54111B
1336F-CX300 (3) 85.0 (3/0) (16) 54111
1336F-C300 (3) 85.0 (3/0) (16) 54111 NA NA
1336F-C350 (3) 53.5 (1/0) (24)54109 NA NA
1336F-C400 (3) 67.4 (2/0) (24) 54110 NA NA
1336F-C450 (3) 85.0 (3/0) (24) 54111 NA NA
1336F-C500 (3) 107.2 (4/0) (24)54112 NA NA
1336F-C600 (3) 127.0 (250 MCM) (24) 54174 NA NA
1
5/16” Stud. All other studs are 3/8”.
2
Lugs shown for DC+/– are based on dynamic brake sizing of 50% of (motor rating X 1.25). Select proper lugs based on required braking torque. Refer to 1336-5.64 or 1336-5.65 for additional information.
3
T & B COLOR-KEYED Connectors require T & B WT117 or TBM-6 Crimper tool or equivalent. Lugs should be crimped according to manufacturer’s tool instructions. If required, Rockwell Automation can supply lug kits for lugs shown above. Kits do not include crimping tools. Consult factory for kit information.
2
Consult Factory
T&B Part No.
Qty. Number
1
1
1
1
1
1
1
1
1
1
1
TE
3
Cable (per Phase)
Qty. mm2 (AWG)
(1) 13.3 (6) (1) 54135
(1) 13.3 (6) (1) 54135
(1) 21.2 (4) (1) 54139
(1) 13.3 (6) (1) 54135
(1) 13.3 (6) (1) 54135
(1) 13.3 (6) (1) 54135
(1) 21.2 (4) (1) 54139
(1) 21.2 (4) (1) 54139
(1) 8.4 (8) (1) 54131
(1) 13.3 (6) (1) 54135
(1) 13.3 (6) (1) 54135
NA NA
T&B Part No.
Qty. Number
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
Installation/Wiring 2–17
Motor Cables
A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 ft.) for every 10 meters (32.8 ft.) of length. In all cases, long parallel runs must be avoided. Do not use cable with an insulation thickness less than or equal to 15 mils (0.4 mm/0.015 in.).
The cable should be 4-conductor with the ground lead being con­nected directly to the drive ground terminal (PE) and the motor frame ground terminal. See table below.
Unshielded
THHN, THWN or similar wire is acceptable for drive installation in dry environments provided adequate free air space and/or conduit fill rates limits are provided. Do not use THHN or similarly coated wire in wet areas. Any wire chosen must have a minimum insulation thickness of 15 mils and should not have large variations in insulation concentricity.
Shielded/Armored Cable
Shielded cable is recommended if sensitive circuits or devices are connected or mounted to the machinery driven by the motor (see table).
Recommended Shielded Wire
Location Rating/Type Description
Standard
(Option 1)
Standard
(Option 2)
Class I & II;
Division I & II
600V, 90° C (194°F)
XHHW2/RHW-2
Anixter B209500-
B209507, Belden 29501-
29507, or equivalent Tray rated 600V, 90° C (194° F) RHH/RHW-2
Anixter OLF-7xxxxx or
equivalent Tray rated 600V, 90° C (194° F) RHH/RHW-2
Anixter 7V-7xxxx-3G or
equivalent
• Four tinned copper conductors with XLP insulation.
• Copper braid/aluminum foil combination shield and
tinned copper drain wire.
• PVC jacket.
• Three tinned copper conductors with XLPE insulation.
• 5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with shield.
• PVC jacket.
• Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded alu-
minum armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.
Conduit
If metal conduit is preferred for cable distribution, the following guidelines must be followed.
• Drives are normally mounted in cabinets and ground connections are made at a common ground point in the cabinet. Normal installa­tion of conduit provides grounded connections to both the motor frame ground (junction box) and drive cabinet ground. These ground connections help minimize interference. This is a noise reduction recommendation only, and does not affect the require­ments for safety grounding (refer to pages 2–11
and 2–12).
2–18 Installation/Wiring
• No more than three sets of motor leads can be routed through a sin­gle conduit. This will minimize “cross talk” that could reduce the effectiveness of the noise reduction methods described. If more than three drive/motor connections per conduit are required, shielded cable as described above must be used. If practical, each conduit should contain only one set of motor leads.
ATTENTION: To avoid a possible shock hazard caused by
!
induced voltages, unused wires in the conduit must be grounded at both ends. For the same reason, if a drive shar­ing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will eliminate the pos­sible shock hazard from “cross coupled” drive motor leads.
Motor Lead Lengths
Installations with long cables to the motor may require the addition of output reactors or cable terminators to limit voltage reflections at the motor. Excessive cable charging current can also reduce the amount of current available to produce rated motor torque. Refer to Tables 2.F and 2.G
for the maximum cable length allowed for various installa­tion techniques. Shaded distances are restricted by cable capacitance charging current. The figure below demonstrates how total cable length is calculated. Failure to follow these guidelines can result in poor motor performance and nuisance drive overcurrent or overload tripping. For installations that exceed the recommended maximum lengths listed, contact the factory.
Please note that the cable lengths shown are guidelines. Your applica­tion may be restricted to a shorter cable length due to wire type, wire placement, line reactor and type of motor.
How to Measure Motor Cable Lengths Limited by Capacitance
ESC SEL
JOG
91.4 (300)
91.4 (300)
All examples represent motor cable length of 189.2 meters (600 feet).
15.2 (50)
ESC SEL
JOG
167.6 (550)
ESC SEL
JOG
182.9 (600)
ESC SEL
JOG
152.4 (500)
15.2 (50) 15.2 (50)
Installation/Wiring 2–19
Table 2.F
Maximum Motor Cable Length Restrictions in meters (feet) - 380V-480V Drives
Any CableShld.
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
2
No External Devices w/1204-TFB2 Term. w/1204-TFA1 Terminator Reactor at Drive
Motor Motor Motor Motor
1600V or
A B 1329
Drive Frame
Drive kW (HP)
Motor kW (HP)
Any Cable
A1 0.37 (0.5) 0.37 (0.5) 12.2
(40)
0.75 (1) 0.75 (1) 12.2 (40)
0.37 (0.5) 12.2 (40)
1.2 (1.5) 1.2 (1.5) 12.2 (40)
0.75 (1) 12.2 (40)
0.37 (0.5) 12.2 (40)
A2 1.5 (2) 1.5 (2) 7.6
(25)
1.2 (1.5) 7.6 (25)
0.75 (1) 7.6 (25)
0.37 (0.5) 7.6 (25)
2.2 (3) 2.2 (3) 7.6 (25)
1.5 (2) 7.6 (25)
0.75 (1) 7.6 (25)
0.37 (0.5) 7.6 (25)
A3 3.7 (5) 3.7 (5) 7.6
(25)
2.2 (3) 7.6 (25)
1.5 (2) 7.6 (25)
0.75 (1) 7.6 (25)
0.37 (0.5) 7.6 (25)
A4 5.5-15
(7.5-20)
B 11-22
(15-30)
C 30-45
(X40-X60)
D 45-112
(60-X150)
E 112-187
(150-250)
F 187-336
(250-450)
G 187-448
(X250-600)
5.5-15
(7.5-20)
11-22 (15-30)
30-45 (40-60)
45-112 (60-150)
112-187 (150-250)
187-336 (250-450)
187-448 (250-600)
7.6 (25)
7.6 (25)
7.6 (25)
12.2 (40)
12.2 (40)
18.3 (60)
18.3 (60)
Any Cable
33.5 (110)
33.5 (110)
33.5 (110)
33.5 (110)
33.5 (110)
33.5 (110)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
12.2 (40)
30.5 (100)
53.3 (175)
53.3 (175)
53.3 (175)
1329R/L (1850V) A or B 1329 A B 1329 A B or 1329
Any
Any
Cable
Cable
91.4
91.4
(300)
(300)
91.4
91.4
(300)
(300)
91.4
91.4
(300)
(300)
91.4
91.4
(300)
(300)
91.4
91.4
(300)
(300)
114.3
121.9
(375)
(400)
91.4
91.4
(300)
(300)
114.3
182.9
(375)
(600)
114.3
182.9
(375)
(600)
114.3
182.9
(375)
(600)
91.4
91.4
(300)
(300)
114.3
182.9
(375)
(600)
114.3
182.9
(375)
(600)
114.3
182.9
(375)
(600)
114.3
182.9
(375)
(600)
114.3 Contact factory for
(375)
advice on cable
114.3 lengths over 182.9
(375)
(600).
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
6
3
Unshld. Shld.3Unshld. Shld.3Unshld.
Use 1204-TFA1 30.5
91.4
91.4
(300)
(300)
91.4
182.9
(300)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
Cable Type
Cable Type Cable Type
Any Cable
30.5
61.0
(100)
(200)
30.5
30.5
(100)
(100)
61.0
(100)
(200)
30.5
30.5
(100)
(100)
30.5
30.5
(100)
(100)
30.5
30.5
(100)
(100)
91.4
30.5 (100)
30.5 (100)
30.5 (100)
30.5 (100)
30.5 (100)
30.5 (100)
30.5 (100)
30.5 (100)
(300)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
30.5
61.0
(100)
(200)
30.5
30.5
(100)
(100)
30.5
61.0
(100)
(200)
61.0
61.0
(200)
(200)
61.0
61.0
(200)
(200)
61.0
61.0
(200)
(200)
91.4
61.0
(300)
(200)
91.4
61.0
(300)
(200)
91.4
61.0
(300)
(200)
91.4
61.0
(300)
(200)
Use 1204-TFB2
Any Cable
91.4 (300)
91.4 (300)
91.4 (300)
91.4 (300)
91.4 (300)
121.9 (400)
91.4 (300)
182.9 (600)
182.9 (600)
182.9 (600)
Any Cable
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
22.9 (75)
24.4 (80)
24.4 (80)
76.2 (250)
61.0 (200)
182.9 (600)
182.9 (600)
182.9 (600)
Type A Motor Characteristics: No phase paper or misplaced phase paper, lower quality insulation systems, corona inception voltages between 850 and 1000 volts. Type B Motor Characteristics: Properly placed phase paper, medium quality insulation systems, corona inception voltages between 1000 and 1200 volts. 1329R/L Motors: These AC variable speed motors are “Control-Matched” for use with Allen-Bradley Drives. Each motor is designed to meet or exceed
the requirements of the Federal Energy Act of 1992. All 1329R/L motors are optimized for variable speed operation and include premium inverter grade insulation systems which meet or exceed NEMA MG1. Part 31.40.4.2.
1
2–20 Installation/Wiring
Table 2.G
Maximum Motor Cable Length Restrictions in meters (feet) - 500V-600V Drives
No External Devices w/1204-TFB2 Terminator w/1204-TFA1 Terminator Reactor at Drive
Motor Motor Motor Motor
1329R/L
5
AB
Any
Any
Cable
Cable
Drive Frame
Drive kW (HP)
Motor kW (HP)
AB
Any
Any
Cable
Cable
Motors
Any Cable
A4 0.75 (1) 0.75 (1) NR NR NA NR 182.9
(600)
0.37 (0.5) NR NR
NA NR 182.9
(600)
1.5 (2) 1.5 (2) NR NR
NA NR 182.9
(600)
1.2 (1.5) NR NR
NA NR 182.9
(600)
0.75 (1) NR NR 182.9
0.37 (0.5) NR NR 182.9
2.2 (3) 2.2 (3) NR NR
(600)
(600)
NA NR 182.9
NR 182.9
(600)
NR 182.9
(600)
(600)
1.5 (2) NR NR
NA NR 182.9
(600)
0.75 (1) NR NR 182.9
0.37 (0.5) NR NR 182.9
3.7 (5) 3.7 (5) NR NR
(600)
(600)
NA NR 182.9
NR 182.9
(600)
NR 182.9
(600)
(600)
2.2 (3) NR NR
NA NR 182.9
(600)
5.5-15 (7.5-20)
C 18.5-45
(25-60)
D 56-93
(75-125)
E 112-224
(150-X300)
F 261-298
(350-400)
G 224-448
(300-600)
1.5 (2) NR NR 182.9 (600)
0.75 (1) NR NR 182.9 (600)
0.37 (0.5) NR NR 182.9 (600)
5.5-15
(7.5-20)
18.5-45
(25-60)
56-93 (75-125)
112-224 (150-X300)
261-298 (350-400)
224-448 (300-600)
NR 9.1
(30)
NR 9.1
(30)
NR 9.1
(30)
NR 9.1
(30)
NR 9.1
(30)
NR 9.1
(30)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
NR 182.9
(600)
NR 182.9
(600)
NR 182.9
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
1600V or 1329R/L (1850V)5AB
Any Cable
335.3
Any Cable
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
335.3
NR 61.0
(1100)
182.9
NR 61.0
(600)
182.9
NR 61.0
(600)
182.9
NR 61.0
(600)
182.9
NR 61.0
(600)
182.9
NR 61.0
(600)
182.9
NR 61.0
(600)
1600V or 1329R/L (1850V)5AB
Any
Any
Cable
Cable
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
182.9
(200)
(600)
Any Cable
30.5 (100)
30.5 (100)
61.0 (200)
182.9 (600)
182.9 (600)
182.9 (600)
NR = Not Recommended NA = Not Available at time of printing
1
Values shown are for 480V nominal input voltage, drive carrier frequency of 2 kHz and ambient temperature at the motor of 40 degrees C. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply values by 0.85 for high line conditions. For input voltages of 380, 400 or 415V AC, multiply the table values by
1.25, 1.20 or 1.15, respectively.
2
A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn-turn insulation rating of 2100 volts or higher.
3
Includes wire in conduit.
4
Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply values by 0.85 for high line conditions.
5
When used on 600V systems, 1329R/L motors have a corona inception voltage rating of approximately 1850V.
6
These distance restrictions are due to charging of cable capacitance and may vary from application to application.
2
1600V or 1329R/L (1850V)
Any
Any
Cable
Cable
Not
Recommended
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
91.4
182.9
(300)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
4
5
Loading...
+ 182 hidden pages