Rockwell Automation User Manual [en, de, es, fr, it]
Specifications and Main Features
Frequently Asked Questions
User Manual
1336 IMPACT Quick Start Guide
This Quick Start Guide summarizes the basic steps needed to install, start-up, and program the 1336 IMPACT Adjustable
Frequency AC Drive. The information provided Does Not replace the User Manual and is intended for qualified drive service
personnel only. Refer to the 1336 IMPACT User Manual (publication 1336 IMPACT-5.0) for details on other application
considerations and related precautions.
Power Wiring – TB1
TE
Ground
TE
(Not on all drives)(Not on all drives)
Required
Input Fusing
Conduit/4-Wire Cable
Nearest
Building Structure Steel
AC Input
to Drive
R
S
(L1)
(L2)T(L3)
Required Branch
Circuit Disconnect
PE
Ground
PEPE
Important: Verify motor insulation system peak voltage
Diagram shows connections that are common for all drives.
Drive Output
to Motor
U
(T1)V(T2)W(T3)
Common Mode Core*
Shield*
* Optional
rating. For cable lengths greater than 6.1
meters (20 feet), consult the User Manual.
Status
Rev/Fwd
Rev/Fwd
Rev/Fwd
Rev/Fwd
Rev/Fwd
Reverse
Reverse
MOP Incr
Reverse
Accel 1
Run Rev
Run Rev
Run Rev
Run Rev
Run Rev
Rev/Fwd
Rev/Fwd
Spd/Trq 3
Spd/Trq 3
Reverse
Spd/Trq 3
Run Rev
Run Rev
Run Rev
Run Rev
Rev/Fwd
MOP Incr
Reverse
Run Rev
Status
Spd Sel 3
Spd Sel 3
Decel 2*/1
MOP Decr
Loc/Rem
Jog
Spd Sel 3
Spd Sel 3
MOP Incr
Decel 1
Spd Sel 3
Spd Sel 3
Decel 2*/1
MOP Decr
Stop Type
Ramp Dis
Reset
Spd/Trq 1
Spd/Trq 1
Ramp Dis
Spd/Trq 1
Reset
Reset
Ramp Dis
Spd Sel 3
MOP Decr
Spd Sel 3
MOP Incr
MOP Decr
Encoder B
Status
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
MOP Decr
Decel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
PTrim En
Flux Enable
Reset
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
Spd Sel 2
MOP Decr
Spd Sel 2
Encoder A
Encoder NOT A
Encoder NOT B
(200mA max.)
+12V
Encoder Common
Status
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
Spd Sel 1
This start-up procedure co vers only the most commonly adjusted values using the 1 336 IMPACT “Startup” mode. Refer to the
User Manual for detailed information.
The following procedure is written for users who have a Human Interface Module (HIM) installed. For users without a HIM,
respective external commands and signals must be supplied. It is also assumed that all parameters are at factory default
settings.
ATTENTION:Power must be applied to the drive to perform the following. Some of the voltages present
are at incoming line potential. T o avoid a shock hazard or damage to equipment, only qualified driv e service
!
!
Publication 1336 IMPACT-5.5ML – May, 19993
personnel should perfo rm the fo l lowing procedure. Thoroughly read and under sta n d th e pro cedure before
beginning. If an e ven t does not occur while perfor ming this procedure, Do Not Proceed. Remo ve po wer b y
opening the branch circuit disconnect device and correct the malfunction before continuing.
ATTENTION:To avoid a hazard of electric shock when wiring or servicing the drive, verify that the
voltage on the bus capacitors has discharged. Measure the DC bus v oltage at the + and - terminals of TB1.
The voltage must be zero.
1336 IMPACT Quick Start Guide
1.Verify that AC line power and control power match the drive rating.
2.If an L option is installed, verify that the Stop and Enable interlock inputs are present. If this option is not installed, verify
that jumpers are installed at pins 3 and 4 and 17 and 18 on J5 on A Frame drives or J2 on B Frame and up drives. Ref er to
Jumper Locations.
3.If standard I/O is being used, verify that jumpers are wired correctly.
4.If Analog Option is installed, verify that parameters are properly configured (refer to the User Manual).
ATTENTION:In all of the following steps, rotation of the motor may occur. To guard against injury ,
incorrect rotation, and possible equipment damage, read each step carefully and perform with caution.
!
5.Apply AC power and control voltages to the drive. The LCD display should light and display a drive status of “Stopped”
and an output frequency of “+0.00 Hz.” If the drive detects a fault, a statement relating to the fault will be shown on the
display. Record the information, remove power, and correct the fault source before proceeding.
6.From the Status Display, press the Enter key (or any key). “Choose Mode” will be displayed . Pres s the Increment (or
Decrement) key until “Startup is displayed. Press Enter.
Important: All questions can be answered Yes or No. Pressing Enter will select the default (“Y” or “N”). Pressing the
Increment (or Decrement) key will change the selection. Press Enter to select. Choosing “Y” allows you to proceed
through the step, and choosing “No” will advance you to th e next step . The figure below shows the steps involved.
Startup
Quick Motor
Tune?
No
Configure
Digital?
No
Configure
Analog?
No
Done
Yes
Enter Motor
Data?
Relay
YesYes
Output
InputsOutputs
YesYes
YesYesYesYes
Encoder?
L Option
Regen/
Brake?
Phase
Rotation?
Autotune?
Important: Pleas e note the following:
•The “Startup” mode can be e xit ed at an y time by pressing ESCape until the Status Display i s shown. If you wish
to re-enter the “Startup” mode, simply select “Reset Sequence” to start from the beginning. Selecting “Continue”
allows you to resume from the point where you left off.
•Completing the last action in any step will automatically take you to th e next step.
•Pressing SELect will activate line 2 of the display. This must be done for all values.
•Press the Increment (or Decrement) key to adjust a value (skip if value is correct). Press Enter to store the value
or retain existing value. Pressing Enter again will cause you to move to the next step (parameter)
7.Cycle power to acti v ate changes. This completes the “Assisted Startup” procedure. Depending o n your application, furt her
parameter programming and/or “Advanced Startup” may be required. Refer to the User Manual for details.
4Publication 1336 IMPACT-5.5ML – May, 1999
1336 IMPACT Quick Start Guide
Drive Dimensions
To determine the size of your drive, refer to the following illustration and table.
Depth
HIM Operation
Width
Height
Frame
A1
A2
A3
A4
B
C
D
E-Enclosed
E-Open
F
G
H
➀
Fan height (635.0 (25.00)) not included.
Width x Height x Depth
Millimeters (inches)
215.9 (8.50) x 290.0 (11.42) x 160.0 (6.30)
215.9 (8.50) x 290.0 (11.42) x 180.5 (7.10)
215.9 (8.50) x 290.0 (11.42) x 207.0 (8.15)
260.0 (10.24) x 350.0 (13.78) x 212.0 (8.35)
276.4 (10.88) x 476.3 (18.75) x 225.0 (8.86)
301.8 (11.88) x 701.0 (27.60) x 225.0 (8.86)
381.5 (15.02) x 1240.0 (48.82) x 270.8 (10.66)
511.0 (20.12) x 1498.6 (59.00) x 477.5 (18.80)
511.0 (20.12) x 1498.6 (59.00) x 372.6 (14.67)
762.0 (30.00) x 2286.0 (90.00) x 635.0 (25.00)
762.0 (30.00) x 2387.6 (94.0) x 635.0 (25.00)
1270.0 (50) x 2324.1 (91.50)➀ x 635.0 (25)
Parameter programming or viewing is accomplished through the Program or Display modes shown below.
1.From the Status Display, press to display “Choose Mode.”
2.Press or to display “Program” (or “Display”).
3.Press .
4.Press or until the desired file is displayed.
5.Press .
6.Press or until the desired group is displayed.
7.Press .
8.Press or to scroll to the desired pa rameter.
Publication 1336 IMPACT-5.5ML – May, 19995
HIM Structure
1336 IMPACT Quick Start Guide
Power-Up and
Status Display
orororor
Choose Mode
EEPromSearchPasswordDisplayProcess
Save Values
Recall Values
Reset Defaults
Drive to HIM
HIM to Drive
Parameters
Links
Control
Status
Control Logic
Reset Drive1
Fault Queue
Warning Queue
Login
Logout
Modify
Process Display
Program
Operator Level
Mode Level
LinkStart Up
Set Links
Clear All Links
Monitor
Motor Status
Drive/Inv Status
SCANport Status
Fault Status
Testpoints
Digital Config
Analog Inputs
Analog Outputs
SCANport Config
SCANport Status
SCANport Analog
Gateway Data In
Gateway Data Out
Parameters
(See Next Page)
Motor/
Inverter
Motor Nameplate
Encoder Data
Inverter
Motor Constants
File Level
ApplicationAutotune
Group Level
Flux Braking
DC Braking/Hold
Max Mtr Current
Fast Flux Up
Start Dwell
Prog Function
Bus Reg/Control
Process Trim
Flying Start
Autotune Setup
Autotune Status
Autotune Results
Drive to HIM
HIM to Drive
Element Level
Publication 1336 IMPACT-5.5ML – May, 19996
1336 IMPACT Quick Start Guide
Parameters - Files, Groups, and Elements
NameNo.Min./Max. ValueNameNo.Min./Max. Value
MonitorNeg Mtr Cur Lim73Calc/0.0%
Motor StatusPos Torque Lim740.0%/Calc
Motor Speed81-8 x BMS/+8 x BMSNeg Power Lim75Calc/0.0%
Motor Frequency89-250.000/+250.000 HzRegen Power Lim76-800.0%/0.0%
Motor Current830.0/6553.5 ampsCurrent Rate Lim77Calc/200.0%
Motor Voltage850/+3000 voltsMax Mtr Current1950/1
Motor Voltage %2340/800%Min Speed Limit2150.0
Motor Torque %86-800.0/+800.0%
Speed/Torq Mode
Motor Flux %8812.5/100.0%Spd/Trq Mode Sel680/5
Motor Power%90-800.0/+800.0%
Speed Reference
Enc Pos Fdbk Low2270/65535Speed Ref 129-8x/+8xBMS rpm
Enc Pos Fdbk Hi2280/65535Speed Scale 130-3.9999/+3.9999
Int Torque Ref229-800/+800%Speed Ref 231-8x/+8xBMS rpm
Drive/Inv StatusSpeed Ref 332-8x/+8xBMS rpm
DC Bus Voltage840/1000VSpeed Ref 433-8x/+8xBMS rpm
Logic Input Sts14Bit selectionSpeed Ref 534-8x/+8xBMS rpm
Drive/Inv Status15Bit selectionSpeed Ref 635-8x/+8xBMS rpm
Drive/Inv Sts 2196Bit selectionSpeed Ref 736-8x/+8xBMS rpm
Run Inhibit Sts16Bit selectionSpeed Scale 737-3.9999/+3.9999
Command Spd Sts82-8 x BMS/+8 x BMSJog Speed 138-8x/+8xBMS rpm
Torque Limit Sts87Bit selectionJog Speed 239-8x/+8xBMS rpm
Spd Reg Output225-300.0/+300.0%
Accel/Decel
Spd Error226-8 x BMS/+8 x BMSAccel Time 1420.0/6553.5 sec
SCANport StatusAccel Time 2430.0/6553.5 sec
Dir/Ref Owner128Bit selectionDecel Time 1440.0/6553.5 sec
Start/Stop Owner129Bit selectionDecel Time 2450.0/6553.5 sec
Jog1/Jog2 Owner130Bit selectionS-Curve Percent470.0/100.0%
Ramp/ClFlt Owner131Bit selection
Feedback Device
Ncfg Flt Status220Bit selectionFdbk Device Type641/3
Fault Status 1221Bit selectionEncoder PPR8Calc/20000 ppr
Fault Status 2222Bit selection
Speed Feedback
Warning Status 1223Bit selectionScaled Spd Fdbk63-32767/+32767
Warning Status 2224Bit selectionFdbk Filter Sel650/4
TestpointsFdbk Filter Gain66-5.00/+5.00
Test Data 192-32768/+32767Fdbk Filter BW670.2/900.0 rad/sec
Test Select 1930/65535Notch Filtr Freq1855.0/135.0 Hz
Test Data 294-32768/+32767Notch Filtr Q1862/500
Test Select 2950/65535
SCANport Status
Line Undervolts2710.0/90.0%Dir/Ref Owner128Bit selection
TestpointsStart/Stop Owner129Bit selection
Test Data 192-32768/+32768Jog1/Jog2130Bit selection
Test Select 1930/65535Ramp/CIFlt Owner131Bit selection
Test Data 294-32768/+32767Flux/Trim Owner132Bit selection
Test Select 2950/65535
SCANport Analog
Interface/CommSP An In1 Select1331/16
Digital ConfigSP An In1 Value134-32767/+32767
Relay Config1140/38SP An In1 Scale135-1.000/+1.000
Relay Config 1115-800.0/+800.0%Sp An In2 Select1361/16
Relay Config 21870/36Sp An In2 Value137-32767/+32767
Relay Setpoint 2188800.0/+800.0Sp An In2 Scale138-1.000/+1.000
Relay Config 31890/36Sp An Output139-32767/+32767
Relay Setpoint 3190-800.0/+800.0
Gateway Data In
Relay Config 41910/36Data In A1140-32767/+32767
Relay Setpoint 4192-800/+800.0%Data In A2141-32767/+32767
L Option Mode1161/25Data In B1142-32767/+32767
L Option In Sts117Bit SelectionData In B2143-32767/+32767
Mop Increment1180.0/BMSData In C1144-32767/+32767
Mop Value1190.0/BSMNAData In C2145-32767/+3276
Pulse In PPR120500/2000Data In D1146-32767/+32767
Pulse In Scale1210.01/10.00Data In D2147-32767/+32767
Pulse In Offset122-BMS/+BMS
Gateway Data Out
Pulse In Value1230.0/+8xBMSData Out A1148-32767/+32767
Analog InputsData Out A2149-32767/+32767
An In 1 Value96-32767/+32767Data Out B1150-32767/+32767
An In 1 Offset97-19.980/+19.980 voltsData Out B2151-32767/+32767
An In 1 Scale98-16.000/+16.000Data Out C1152-32767/+32767
An In 1 Filter BW1820.0/200.0 rad/secData Out C2153-32767/+32767
An In 2 Value99-32767/+32767Data Out D1154-32767/+32767
An In 2 Offset100-19.980/+19.980 voltsData Out D2155-32767/+32767
An In 2 Scale101-16.000/+16.000
An In2 Filter BW1830.0/200.0 rad/sec
mA Input Value102-32767/+32767
mA In Offset103-32.000/+32.000 mA
mA In Scale104-16.00
mA In Filter BW1840.0/200.0 rad/sec
Analog Outputs
An Out 1 Value +0105-32767/+32767
An Out 1 Offset106-20.000/+20.000
An Out 1 Scale107-1.000/+1.000
An Out 2 Value108-32767/+32767
An Out 2 Offset109-19.980/+19.980 volts
An Out 2 Scale110-1.000/+1.000
mA Out Value111-32767/+32767
mA Out Offset112-32.000/+32.000 mA
mA Out Scale113-1.000/+1.000
8Publication 1336 IMPACT-5.5ML – May, 1999
1336 IMPACT Quick Start Guide
NameNo.Min./Max. ValueNameNo.Min./Max. Value
Motor InverterFunction Sel2120/27
Bus Reg Control
Namplate Hz61.0/250.0 HzBus/Brake Option13Bit selection
Motor Poles72/40 poles
Process Trim
Service Factor91.00/2.00PTrim Output48-800.0/+800.0%
Encoder DataPTrim Reference49-800.0/+800.0%
Encoder PPR8Calc/2000 pprPTrim Feedback50-800.0/+800.0%
InverterPTrim Select51Bit selection
PWM Frequency101000 Hz/From drivePTrim Filter BW520.0/240.0 rad/sec
Inverter Amps110.1 amps/From drivePTrim Preload53-800.0/+800.0%
Inverter Volts1275/575 voltsPTrim Ki540.000/16.000
Motor ConstantsPTrim Kp550.000/16.000
Stator Resistance1660.00/100.00%PTrim Lo Limit58-800.0/+800.0%
Leak Inductance1670.00/100.00%PTrim Hi Limit59-800.0/+800.0%
Flux Current1680.00/75.00%PTrim Out Gain60-8.000/+8.000
Slip Gain1690.0/400.0%Max Rev Spd Trim61-6 x /0.0 BMS rpm
Motor Poles72/40 polesMax Fwd Spd Trim620.0 rpm/+6xBMS rpm
ApplicationFlying Start
Flux BrakingFStart Select2160/2
Bus/Brake Option 13Bit selectionFStart Speed217P40/P41
DC Braking/HoldAutotune
Bus/Brake Option 13Bit selectionAutotune Setup
DC Brake Current790.0%/CalcAutotune/Dgn Sel173Bit selection
DC Brake Time800.0/6553.5 secTrans Dgn Config172Bit selection
400% Mtr CurrentAutotune Torque64250%/100.0%
Max Mtr Current1950/1Autotune Speed1650.3 x BMS/BMS
Fast Flux UpAutotune Status
Bus/Brake Option13Bit selectionAutotune Status156Bit selection
Fast Flux Level78100.0%/CalcInverter Dgn 1174Bit selection
Start DwellInverter Dgn 2175Bit selection
Start Dwell Spd193-0.1 x / +0.1 x BMSAutotune Errors176Bit selection
Start Dwell Time1940.0/10.0 sec
Autotune Results
Prog FunctionStator Resistance1660.00/100.00%
Function In1198VariesLeak Inductance1670.00/100.00%
Func 1 Mask/Val199VariesFlux Current1680.00/75.00%
Func 1 Eval Sel2000/17Slip Gain1690.0/400%
Function In2201VariesTotal Inertia1570.0/655.00 sec
Func 2 Mask/Val202VariesSpd Desired BW1610.00/Calc rad/sec
Func 2 Eval Sel2030/17
Function In3204Varies
Func 3 Mask/Val205Varies
Func 3 Eval Sel2060/17
Function In4207Varies
Function In5208Varies
Function In6209Varies
Function In7210Varies
Function In8211Bit selection
Publication 1336 IMPACT-5.5ML – May, 19999
1336 IMPACT Quick Start Guide
This Page Intentionally Blank
10Publication 1336 IMPACT-5.5ML – May, 1999
1336 IMPACT Kurzanleitung
In dieser Kurzanleitung wird beschrieben, wie Sie d en Frequenzum richt er 133 6 IMPACT inst alli eren , in B etri eb nehmen u nd
Verdrahtung der Netzanschlüsse – TB1
Brückenpositionen
programmieren. Die hierin enthaltenen Informati onen si nd jedoch k ein Ers a tz fü r das Benu tzerhand buch und sind nur für
qualifiziertes FU-Wartungspersonal vorgesehen. Detailli erte Inf ormati onen ü ber andere Anwend ungs aspekte und di e
entsprechenden sicherheitstechnischen Hinweise finden Sie im 1336 IMPACT-Benutzerhandbuch ( Publi kation 1336
IMPACT-5.0).
TE
Erde
TE
(nicht bei allen Antrieben)(nicht bei allen Antrieben)
Erforderliche
Eingangssicherung
Leitung/Vierleiterkanal
Nächstgelegene
Gebäude-Stahlkonstruktion
FU-Netzeingang
R
S
(L1)
(L2)T(L3)
Erforderlicher
Zweigtrennschalter
PE
Erde
PEPE
Wichtig: Überprüfen Sie die Motorisolationsspannung. Wenn
Die Abbildung zeigt Anschlüsse, die für alle FUs gleich sind.
Detaillierte Informationen finden Sie im Benutzerhandbuch.
FU-Ausgang
zum Motor
U
(T1)V(T2)W(T3)
Ferritringkern*
Abschirmung*
* Optional
Motorabschlußwiderstand*
das Kabel über 6,1 m lang ist, ziehen Sie das
Benutzerhandbuch zu Rate.
Dynamische Bremse
DC
DC
+
–
Motorgehäuse
BRK
–
PE
Erde gem. lokalen
Vorschriften
J4 (TB4)
J5
J7 (TB7)
LANGUAGE MODULE
ALLEN-BRADLEY
J10 (TB10)
Baugröße A1 – A4
Publikation 1336 IMPACT-5.5DE – Mai 1999
L-Options-
platinen-Brücke
J2
TB10
TB11
LANGUAGE MODULE
ALLEN-BRADLEY
ESC
SEL
JOG
Alle anderen Baugrößen
1336 IMPACT Kurzanleitung
Verdrahtungs-E/A – Baugröße A
Verdrahtungs-E/A – Alle anderen Baugrö ßen
J7 (TB7)
J4 (TB4)
Analogeingang 1
Analogeingang 2
4 bis 20 mA
Impulsquelle
Abschirmung
Abschirmung
Abschirmung
Abschirmung
+
-
+
-
+
-
+
-
1
Bezugspotential
2
3
4
5
Analogausgang 1
6
7
8
Analogausgang 2
9
10
11
12
+10V
-10V
Abschirmung
Abschirmung
Abschirmung
4 bis 20 mA
+
-
+
-
+
-
1
2
3
4
5
6
7
8
9
10
11
12
Gleichstrom-
netzteil*
J10 (TB10)
123456789101112
Stromver-
sorgung
Relais 1
Voreinstellung:
Bei Drehzahl
Aktiviert (in Betrieb)
* Das Netzteil ist nur zur Verwendung
für den FU-Eingang vorgesehen.
Das hier beschriebene Inbetriebnahmeverfahren umfaßt nur die i m 1336 IMPACT „Start“-Modus am häufigst en ei ngest ellt en
Werte. Detailliertere Informationen finden Sie im Benutzerhandbuch.
Die folgenden Anleitungen gelten für Benutzer, die eine Bedieneinheit (HIM) verwenden. Wenn keine Bedieneinheit installiert
ist, sind die entsprechenden externen Befehle und Sig nale erford er lich. F erner wird dav on ausg eg angen, daß di e werkseitig
eingestellten Parameter verwendet werden.
!
!
Publikation 1336 IMPACT-5.5DE – Mai 19993
ACHTUNG:
Zur Durchführung der folgenden Schritte muß der FU mit St rom v er sorgt werden. Hierbei
ist zu beachten, daß die Netzspannung anliegen kann. Um der Gefahr eines elektrischen Schlags oder eines
Geräteschadens vorzubeugen, sollten die folg enden Schr it t e nur von q uali fiz iertem Wartungsper sonal
durchgeführt werden. Lesen Sie zuerst die nachstehenden Anleitungen. W enn ein hierin beschriebenes Ereignis
bei der Durchführung dieses Verfahrens ni cht eintritt, fahren Sie nicht fort. Schalten Sie die Stromzufuhr durch
Öffnen des Leistungsschalters aus, und beheben Sie den Fehler.
ACHTUNG:
Um der Gefahr eines elektrischen Schlags bei der Durchführung von Wartungsarbeiten
vorzubeugen, überprüfen Sie, ob die Buskondensatoren entladen wurden. Messen Sie die
Zwischenkreisspannung an der + und - Klemme von TB1. Die Spannung muß Null betragen.
1336 IMPACT Kurzanleitung
1.Überprüfen Sie, ob die Netzspannung und die Steuerspannung der FU-Nennleistung entsprechen.
2.Falls eine L-Option installiert wurde, überprüfen Sie, ob die Stopp- und Freigabeeingänge vorhanden sind. Wurde diese
Options nicht installiert, überprüfen Sie, ob die Brücken bei FUs der Baugröße A an den Stiften 3 und 4 sowie 17 und
18 von J5 bzw. bei FUs der Baugröße B und höher von J2 angebracht wurden. Siehe „Brückenpositionen“.
3.Bei Verwendung von Standard-E/A überprüfen Sie, ob die Brücken ordnungsgemäß angebracht wurden.
4.Wurde eine Analogoptionskarte installiert, überprüfen Sie, ob die Parameter ordnungsgemäß konfigur iert sind (siehe
Benutzerhandbuch).
ACHTUNG: Bei allen nachstehend beschriebenen Schritten kann es zur Drehung des Motors kommen.
Um Verletzungen, falscher Drehrichtung bzw. einem Geräteschaden vorzubeugen, lesen Sie alle Schritte
!
genau, und lassen Sie Vorsicht walten.
5.Schalten Sie die Netz- und Steuerspannung ein. Jetzt sollte die LED-Anzeige leuchten und den FU-Status „Gestoppt“
sowie die Ausgangsfrequenz „+0,00 Hz“ anzeigen . Wenn der FU einen Fehler feststellt, wird eine entsprech ende Meldung
eingeblendet. Zeichnen Sie die eingeblend eten In for mationen auf , schalten Sie d ie Stromzu fuh r au s, un d b eheben Sie den
Fehler, bevor Sie fortfahren.
6.Drücken Sie bei eingeblendeter Statusanzeige die Eingabetaste (oder eine beliebige andere Taste). Jetzt wird „Modus
wählen“ eingeblendet. Drücken Sie die Aufwärts- oder Abwärtstaste, bis „Inbetriebnahme“ angezeigt wird. Drücken
Sie die Eingabetaste.
Wichtig: Alle Fragen können mit Ja oder Nein beantwortet werden. Durch Drücken der Eingabetaste wird der
Vorgabewert gewählt („Ja“ oder „Nein“). Durch Drücken der Aufwärts- oder Abwärtstaste wird der Wert geändert drücken Sie die Eingabetaste, um die entsprechende Auswahl anzunehmen. Wenn Sie „Ja“ drücken, fahren Sie mit
dem jeweiligen Schritt fort. Wenn Sie „Nein“ drücken, gelangen Sie zum nächsten Schritt. In der nachfolgenden
Abbildung werden die einzelnen Schritte dargestellt.
Inbetriebnahme
SchnelltuningVerfahren?
Nein
Digital
konfigurieren?
Nein
Analog
konfigurieren?
Nein
Fertig
Ja
Motordaten
eingeben?
RelaisausgangL-Option
JaJa
EingängeAusgänge
JaJa
JaJaJaJa
Encoder?
Regen./
Bremse?
Phasenrotation?
Autotune?
Wichtig: Bitte die folgenden Hinweise beachten:
•Der Modus „Inbetriebnahme“ kann jederzeit beendet werden, indem die ESC-Taste gedrückt wird, bis
die Statusanzeige erscheint. Soll wieder in den Modus „Inbetriebnahme“ gewechselt werden, einfach
„Rücksetzfolge“ auswählen, um nochmals von vorne zu beginnen. Durch Auswahl von „Weiter“ kann
das Verfahren an dem Punkt wiederaufgenommen werden, an dem es abgebrochen wurde.
•Wenn ein Schritt abgeschlossen ist, gelangen Sie automatisch zum nächsten Schritt.
•Durch Drücken von „Auswählen“ wird Zeile 2 der Anzeige aktiviert. Dies muß für alle Werte erfolgen.
•Mit den Aufwärts- oder Abwärtstasten kann ein bestimmter Wert gewählt werden (Wenn der Wert bereits richtig
ist, diesen Schritt auslassen). Danach die Eingabetaste drücken, u m den Wert zu speichern oder den vo rhandenen
Wert beizubehalten. Durch erneutes Betätigen der Eingabetaste wird zum nächsten Schritt (Parameter)
übergeleitet.
4Publikation 1336 IMPACT-5.5DE – Mai 1999
1336 IMPACT Kurzanleitung
7.Das Gerät aus- und wieder einschalten, um die vorgenommenen Änderungen zu aktivieren. Damit ist das
FU-Abmessungen
Bedieneinheit (HIM)
Baugröße
Breite x Höhe x Tiefe
Millimeter
A1
A2
A3
A4
B
C
D
E (IP20)
E (IP00)
F
G
H
Inbetriebnahmeverfahren beendet. Je nach Anwendung können eine weitere Parameterprogrammierung und/oder
eine erweiterte Inbetriebnahme erforderlich sein. Einzelheiten finden Sie im Benutzerhandbuch.
Ziehen Sie zur Feststellung der Größe des Frequenzumri chter s die fol gende Abbild ung und Tabelle zu Rate.
Tiefe
Breite
Höhe
➀
Lüfterhöhe (635, 0) ni cht inbegriffen
215,9 x 290,0 x 160,0
215,9 x 290,0 x 180,5
215,9 x 290,0 x 207,0
260,0 x 350,0 x 212,0
276,4 x 476,3 x 225,0
301,8 x 701,0 x 225,0
381,5 x 1240,0 x 270,8
511,0 x 1498,6 x 477,5
511,0 x 1498,6 x 372,6
762,0 x 2286,0 x 635,0
762,0 x 2387,6 x 635,0
1270,0 x 2324,1➀ x 635,0
Das Programmieren (oder Lesen) der Parameter erfolgt über den nachfolgend ab gebildet en Pr ogrammi er- bzw. Anzeigemodus.
1.Auf der Statusanzeige drücken, um „Modus wählen“ anzuzeigen.
2. oder drücken, um „Programmieren“ (oder „Anzeigen“) anzuzeigen.
Publikation 1336 IMPACT-5.5DE – Mai 19995
3. drücken.
4. oder drücken, bis die gewünschte Datei angezeigt wird.
5. drücken.
6. oder drücken, bis die gewünschte Gruppe angezeigt wird.
7. drücken.
8. oder drücken, um den gewünschten Parameter zu wählen.
1336 IMPACT Kurzanleitung
Struktur der Bedieneinheit (HIM)
Inbetriebnahmemodus
und Statusanzeige
oderoderoderoder
Modus wählen
Bedienerebene
Modusebene
EEPromSuchenKennwortAnzeigeProzeß
Werte speichern
Werte aufrufen
Std. wert rücks.
FU - HIM
HIM - FU
Monitor
Status Motor
Status Antrb/WR
Status SCANport
Status Fehler
Testpunkte