RISCO Group WL Supervised Smoke User Manual [en, it, fr, es]

WIRELESS SUPERVISED PHOTOELECTRIC SMOKE
DETECTOR
MODEL: WL T33S
2
Wireless Supervisor Photoelectric Smoke Detector
WIRELESS SUPERVISED
PHOTOELECTRIC SMOKE DETECTOR
Model: WL T33S
GENERAL DESCRIPTION
RISCO Group's smoke detector is single station, photoelectric smoke detector with a built-in supervised wireless transmitter. When sufficient smoke is detected, or the test feature is operated, the detector will sound its alarm horn and the transmitter will send an ALARM message. The Alarm output in the receiver will remain activated until the alarm condition clears. The smoke alarm base lock discourages unauthorized removal of the smoke alarm by requiring a screwdriver to remove the alarm from the base. The smoke alarm provides the following signals to the control panel:
Alarm Alarm restore Low battery Tamper Supervision
WARNINGS:
This smoke detector is designed for use in a single residential unit only, which means that it should be used inside a single family home or apartment. It is not meant to be used in lobbies, hallways, basements, or another apartment in multi-family buildings, unless there are already working detectors in each family unit. Smoke detectors, placed in common areas outside of the individual living unit, such as on porches or in hallways, may not provide early warning to residents. In multi-family buildings, each family living unit should set up its own detectors. This detector is not to be used in non-residential buildings. Warehouses, industrial or commercial buildings, and special purpose non-residential buildings require special fire detection and alarm systems. This detector alone is not a suitable substitute for complete fire detection systems for places where many people live or work, such as hotels or motels. The same is true of dormitories, hospitals; nursing homes or group homes of any kind, even if they were once single - family homes. Please refer NFPA 101, the Life Safety Code, NFPA71, 72A, 72B, 72C, 72D, and 72E for smoke detector requirements for fire protection in buildings not defined as “households”.
4
Wireless Supervisor Photoelectric Smoke Detector
SELECTING A LOCATION
Smoke detectors should be installed in accordance with the NFPA Standard 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02169). For complete coverage in residential units, smoke detectors should be installed in all rooms, halls, storage areas, basements, and attics in each family living unit. Minimum coverage is one detector on each floor and one in each sleeping area and attics in each family living unit. Minimum coverage is one detector on each floor and one in each sleeping area.
Install a smoke detector in the hallway
outside every separate bedroom area, as shown in Figure 1. Two detectors are required in homes with two bedroom areas, as shown in Figure 2.
Install a smoke detector on every floor
of a multi-floor home or apartment, as shown in Figure 3.
Install a minimum of two detectors in
any household.
Install a smoke detector inside every
bedroom.
Install smoke detectors at both ends of
a bedroom hallway if the hallway is more than 40 feet (12 meters) long.
Install a smoke detector inside every
room where one sleeps with the door partly or completely closed, since smoke could be blocked by the closed door and a hallway alarm may not wake up the sleeper if the door is closed.
Install basement detectors at the bottom
of the basement stairwell.
Install second-floor detectors at the top
of the first-to-second floor stairwell.
Be sure no door or other obstruction
blocks the path of smoke to the detector.
Install additional detectors in your living
room, dining room, family room, attic, utility and storage rooms.
Install smoke detectors as close to the
center of the ceiling as possible. If this is not practical, put the detector on the ceiling, no closer than 4 inches (10 cm) from any wall or corner, as shown in Figure 4.
If ceiling mounting is not possible and
Wireless Supervisor Photoelectric Smoke Detector 5
Figure 1: Locations for placing smoke
detectors for single residence with only
Figure 2: Locations for placing smoke
detectors for single-floor residence with
more than one sleeping area
one sleeping area
wall mounting is permitted by your local and state codes, put wall-mounted detectors between 4 and 6 inches (10 ~ 15 cm) from the ceiling, also see Figure 4.
If some of your rooms have sloped,
peaked, or gabled ceilings, try to mount detectors 3 feet (0.9 meter) measured horizontally from the highest point of the ceiling as shown in Figure 5.
CAUTION: (As required by the California State Fire Marshall)
Early warning fire detection is best achieved by the
installation of fire detection equipment in all rooms and areas of the household as follows: (1) A smoke detector installed in each separate sleeping area (in the vicinity, but outside of the bedrooms), and (2) Heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and, storage rooms, basements and attached garages.” For your information, NFPA Standard 74, Section 2-4 reads as follows: “2-4.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces and unfinished attics. The provisions of 2-4.1.1 represent the minimum number of detectors required by this standard. It is recommended that the householder consider the use of additional smoke detectors for increased protection for those areas separated by a door from the areas protected by the required smoke detectors under 2-4.1.1 above. The recommended additional areas are living room, dining room, bedroom(s), kitchen, attic (finished or unfinished), furnace rooms, utility room, basement, integral or attached garage, and hallways not included in 2-4.1.1 above. However, the use of additional detectors remains the option of the householder.” We recommend complete coverage and use of additional smoke detectors.
Figure 3: Location for placing smoke
detectors for a multi-floor residence
Figure 4: Recommended best and
acceptable locations to mount
Figure 5: Recommended location to
mount smoke detectors in rooms with
sloped, gabled, or peaked ceiling
smoke detectors
6
Wireless Supervisor Photoelectric Smoke Detector
Where to Install Your Smoke Detectors in Mobile Homes and RVs
Mobile homes and RVs built after about 1978 were designed and insulated to be energy-efficient. In mobile homes and RVs built after 1978, smoke detectors should be installed as described above. Older mobile homes and RVs may have little or no insulation compared to current standards. Outside walls and roofs are often made of non-insulated metal, which can transfer thermal energy flow from outdoors. This makes the air right next to them hotter or colder than the rest of the inside air. These layers of hotter or colder air can keep smoke from reaching a smoke detector. Thereby, install smoke detectors in such units only on inside walls. Place them between 4 and 6 inches (10 ~ 15 cm) from the ceiling. If you are not sure how much insulation is in your mobile home or RV, then install the detector on an inside wall. If the walls or ceiling are unusually hot or cold, then install the detector on an inside wall. Install one detector as close to the sleeping area as possible for minimum security, or install one detector in each room for security. Before you install any detector, please read the following section on “Where not to install your smoke detectors”.
Where Not to Install Your Smoke Detectors
False alarms occur when smoke detectors are installed where they will not work properly. To avoid false alarms, do not install smoke detectors in the following situations: Combustion particles are by-products of something burning. Do not install
smoke detectors in or near areas where combustion particles are present, such as kitchens with few windows or poor ventilation, garages where there may be vehicle exhaust, near furnaces, hot water heaters and space heaters.
Do not install smoke detectors less than 6 meters (20 feet) away from places
where combustion particles are normally present, like kitchens. If a 20-foot distance is not possible, e.g. in a mobile home, try to install the detector as far away from the combustion particles as possible, preferably on the wall. To prevent false alarms, provide good ventilation in such places.
IMPORTANT:
Never try to avoid false alarms by disabling the detector.
Do not mount smoke detectors in the path of fresh air intake. The flow of fresh
Near paint thinner fumes. In close proximity to an automobile exhaust pipe; this will damage the detector. In damp or very humid areas or near bathrooms with showers. Moisture in
air in and out can drive smoke away from the smoke detector; thus reducing its efficiency. Figure 6 indicates the correct and incorrect locations concerning this problem.
humid air can enter the sensing chamber, then turns into droplets upon cooling, which can cause false alarms. Install smoke detectors at least 3 meters (10 feet) away from bathrooms.
Wireless Supervisor Photoelectric Smoke Detector 7
In very cold or very hot areas, including unheated buildings or outdoor rooms.
If the temperature goes above or below the operating range of smoke detector, it will not work properly. The temperature range for your smoke detector is 4°C to 38°C (40°F to 100°F).
In very dusty or dirty areas, dirt and dust can build up on the detector's sensing
chamber, to make it overly sensitive.
Additionally, dust or dirt can block openings to the sensing chamber and keep
the detector from sensing smoke.
Near fresh air vents or very drafty areas like air conditioners, heaters or fans.
Fresh air vents and drafts can drive smoke away from smoke detectors.
Dead air spaces are often at the top of a peaked roof, or in the corners
between ceilings and walls. Dead air may prevent smoke from reaching a detector. See Figures 8 and 9 for recommended mounting locations.
In insect-infested areas. If insects enter a detector's sensing chamber, they
may cause a false alarm. Where bugs are a problem, get rid of them before putting up a detector.
Near fluorescent lights, electrical "noise" from fluorescent lights may cause
false alarms. Install smoke detectors at least 1.5 meters (5 feet) from such lights.
Bath
Bedroom
Bedroom
Correct Locatio n
Incorrect Locatio n
Figure 6: Recommended Smoke Detector Locations
Air EntryAir Return
Stove
Kitchen
Living Room
8
Wireless Supervisor Photoelectric Smoke Detector
w
INSTALLATION
The smoke detector is to be mounted on the ceiling or on the wall, if necessary. Since the smoke detector is a single-station type, it cannot be linked to other detectors.
Read the “Where To Install Your Smoke Detector” and “Where Not To Install Your Smoke Detectors sections in this Manual before installing. To install the detector, perform the following steps (see Figure 7).
Select the installation location. Remove locking pin securing the
Remove the mounting bracket from
Use the bracket as a template for
Using an appropriate drill, drill two
Using screws (supplied) attach the
Open the batteries compartment
Observing proper polarity, insert a
Write message is sent automatically,
Line up the side slot of the bracket
Pull the detector outward to make
WARNING:
Do not connect the smoke detectors to any other alarm or auxiliary device. Connecting anything else to this detector will prevent it from working properly.
mounting bracket to the unit (see Figure 7).
the unit by rotating it counterclockwise.
marking the mounting holes
holes at the marks and insert anchors.
bracket to the wall as in Figure 7.
cover (see Figure 8).
2xCR123 3V Lithium batteries (supplied) into the batteries compartment and close the compartment cover.
10 seconds after placing the batteries, or by pressing the detector’s tamper for a period of 3 seconds.
and the detector. Push the detector onto the mounting bracket and turn it clockwise to fix it into place. Insert the locking pin in order to secure the mounting bracket to the detector (see figure 7).
sure it is securely attached to the mounting bracket.
Locking Pin
Bracket
Screws
Figure 7: Smoke Detector Installation
Battery Compartment
Tamper
Figure 8: Batteries Compartment/Tamper
WARNING:
This detector is not suitable for installation in a hazardous location, as defined in the national electrical code. Do not use detector in an outlet controlled by a
all switch.
Detector
Wireless Supervisor Photoelectric Smoke Detector 9
RED INDICATOR
When the red LED indicator (see Figure 9) flashes once in 30 seconds, it indicates the detector is under normal operation. When the red LED flashes very frequently and an audible alarm sounds simultaneously, it indicates that the detector senses smoke.
NOTE:
The red LED behaves according to one of the following set modes: Mode 1: The red LED indicator will not reset automatically at the end of an alarm event. This means that after the smoke chamber is cleared, the audible alarm will stop automatically, but the red LED indicator will continue to flash, until it is manually restored by the user. To restore – press the test button for 2-3 seconds, the LED will stop flashing. Mode 2 (Default): The red LED will reset automatically at the end of an alarm event.
The user can check to which mode the detector is defined and switch between modes.
• To check the mode, press the Test button. The red LED will light up. If the red LED lights up continuously the detector is in Mode 1. If the red LED is blinking the detector is in Mode 2.
• To switch from one mode to another, press the Test button for 8 seconds. The buzzer will sound and the red LED will change its behavior either from a continuous light to a blinking light or from a blinking light to a continuous light.
TESTING YOUR SMOKE DETECTOR
To be sure that detector is working correctly test the detector weekly by performing the following procedure: Use your finger to firmly press the test button. If the detector is functioning correctly, the alarm horn sounds. To stop the alarm horn, press the test button again. If the detector fails to test properly, have it repaired or replaced immediately. If the alarm horn begins to beep once every 35 seconds, it means that the detector’s batteries are weak. Replace the batteries immediately. Keep fresh batteries on hand for this purpose.
NOTE:
Cooking smoke or a dusty furnace (sometimes called “friendly fires”) can cause the alarm to sound. If this happens, open a window or fan the air to remove the smoke or dust. The alarm will turn off as soon as the air is completely clear. Do not disconnect the batteries from the detector. This will cancel your protection from fire.
Buzzer Openings
Test / Silence Button
Figure 9: Smoke Detector Cover
LED Indicator (Red)
Detector
10
Wireless Supervisor Photoelectric Smoke Detector
TAKING CARE OF YOUR SMOKE DETECTOR
To keep your detector in good working condition, you must test the detector weekly, according to the “Testing Your Smoke Detector” section.
CLEANING THE SMOKE DETECTOR
Clean the housing with a dry or damp cloth to remove dust and dirt. If necessary, open the smoke chamber and clean the interior of the detector.
1. Remove the detector from the detector base.
2. Remove the batteries.
3. Using a flat screwdriver release the smoke detector cover.
4. Using a flat screwdriver lift the smoke chamber housing slightly.
5. Use a fine paintbrush to remove dirt from the chamber.
6. After cleaning, close the smoke chamber, fix the housing and remount the detector on the ceiling.
DO NOT FORGET TO REPLACE THE BATTERIES! BATTERY REPLACEMENT
Replace the detector batteries once a year or immediately when the low battery “beep” signal sounds once every 35 seconds. The low-battery "beep" should last at least 30 days before the batteries die out completely.
NOTE:
If false alarms keep coming from the detector, you should check whether the detector’s location is adequate. Refer to section “WHERE TO INSTALL SMOKE DETECTORS.” Have your detector moved if it is not located properly. Clean the detector as described above.
WARNING! LIMITATIONS OF SMOKE ALARMS
Wireless smoke alarms are very reliable, but may not work under all conditions. No fire alarm provides total protection of life or property. Smoke alarms are not a substitute for life insurance. Smoke alarms require a source of power to work. This smoke alarm will not operate and the alarm will not sound if batteries are dead or not installed properly. Smoke alarms may not be heard. A sound sleeper or someone who has taken drugs or alcohol may not awaken if the alarm is installed outside a bedroom. Closed or partially closed doors and distance can block sound. This alarm is not designed for the hearing impaired. Smoke alarms may not always activate and provide warning early enough. Smoke alarms only activate when enough smoke reaches the alarm. If a fire starts in a chimney, wall, roof, on the other side of closed doors, or on a different level of the property enough smoke may not reach the alarm for it to alarm.
Smoke alarms are a significant help in reducing loss, injury and even death. However, no matter how good a detection device is, nothing works perfectly under every circumstance and we must warn you that you cannot expect a smoke alarm to ensure that you will never suffer any damage or injury.
Wireless Supervisor Photoelectric Smoke Detector 11
Specifications
Voltage: Typical Average Standby Current: Typical Test Current: Typical Alarm Current: Peak Trouble Pulse Current: Peak Pulse Current: Typical Battery Life: Battery Type: Low Battery Threshold: Low Battery Beep rate: Low Battery Life: Operating Temperature: Operating Humidity: Color: Dimensions:
Alarm Sound Level:
Transmitter Characteristics:
Nominal Center Frequency
Supervision Time
In order to continue improving the product, RISCO Group reserves the right to change specifications and/or designs without prior notice.
6 volt
0.04mA
55mA 55mA
4.73mA
0.074mA 3 years 2xCR123 3V Lithium battery
5.2 Volt One beep every 30 seconds At least 30 days from warning signal
-10°C to 40°C (14°F - 104°F) 10% to 85% RH, no condensation or icing White Diameter: 148 mm (5.83”) Height: 53 mm (2”) Exceeds 85dB at 3m (10 feet)
RWT33S86800A and 74015 : 868.65 MHz RWT33S43300A: 433.92 MHz 15 min. for 868.65 MHz / 65 min. for 433.92 MHz
Note:
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
12
Wireless Supervisor Photoelectric Smoke Detector
RIVELATORE FOTOELETTRICO
DI FUMO SUPERVISIONATO
Modello: WL T33S
ISTRUZIONI DI INSTALLAZIONE
DESCRIZIONE GENERALE
Il rivelatore di fumo è un sensore fotoelettrico alimentato a batteria che integra un trasmettitore radio supervisionato. Quando il rivelatore rileva fumo a sufficienza o quando viene premuto il pulsante di test, il sensore attiva il suo cicalino interno e il trasmettitore trasmette un messaggio di ALLARME. L’uscita d’allarme del ricevitore resterà attiva fino a quando la condizione d’allarme non viene ripristinata e il rivelatore non rileva più fumo. La base auto-bloccante del sensore scoraggia tentativi non autorizzati di rimuovere il rivelatore poichè è necessario un cacciavite per effettuare questa operazione. Il rivelatore di fumo segnala i seguenti eventi:
Allarme Ripristino allarme Basso livello batteria Tamper Supervisione
14
Rivelatore Fotoelettrico di Fumo Supervisionato
SCELTA DELLA POSIZIONE PER L'INSTALLAZIONE
La scelta del posizionamento del sensore è molto importante per la corretta rilevazione del fumo. Questa apparecchiatura dovrebbe essere installata in conformità agli Standard vigenti relativi ai sistemi di rilevazione incendio. Consultare l’esempio della Figura 1.
IMPORTANATE:
La regolamentazione riguardante i sistemi di rilevazione incendio varia da Paese a Paese. Per maggiori informazioni contattare le Autorità locali.
Quelle che seguono sono alcune regole generali per il posizionamento dei rivelatori di fumo. Posizionare i rivelatori di fumo con
supporto da soffitto al centro della stanza da proteggere o su di un lato della stanza ma non più vicino di 10 cm dalla parete, come mostrato in Figura 2.
Posizionare i rivelatori con
supporto a parete a 10 - 15 cm di distanza dal soffitto, come mostrato in Figura 2.
Posizionare i rivelatori in un
ambiente che abbia le seguenti caratteristiche:
Temperatura compresa tra
4°C e 38°C
Umidità compresa tra 0 e
95% senza condensa
Posizionare l’unità lontano da
condizionatori, ventilatori, o altre apparecchiature che potrebbero interferire con l’ingresso del fumo all’interno della camera di rilevazione del rivelatore.
Montare i rivelatori di fumo su
superfici fisse permanentemente.
Posizionare i rivelatori lontano da
grandi oggetti metallici, computer, apparecchi televisivi che potrebbero interferire con la parte trasmittente dell’unità.
Se ci sono locali con soffitti
particolarmente inclinati, posizionare il rivelatore a 90 cm calcolati orizzontalmente dal punto più alto del soffitto, come mostrato in Figura 3.
Rivelatore Fotoelettrico di Fumo Supervisionato
Sala da Pranzo Cucina
Soggiorno
Sensori di Fumo per una minima protezione
Sensori di Fumo aggiuntivi per una maggiore protezione
Figura 1: Posizionamento dei rivelatori di fumo
Soffitto
Centro d el
Soffitto
Figura 2: Posizione perfetta e accettabile di
installazione dei rivelatori di fumo
Figura 3: Posizione consigliata di installa zione
dei rivelatori di fumo nei locali con soffitti
Qui Mai
Posizione perfetta
Posizione accettabile
Distanza orizzontale dal punto
particolarmente inclinati
Camera
Minimo
10 cm
90 cm
più alto del soffitto
Camera
Camera matrim.
Minimo
10 cm
Massimo
15 cm
Rivelatore
15
DOVE NON INSTALLARE I RIVELATORI DI FUMO
I falsi allarmi possono avvenire se i rivelatori vengono installati dove non funzionerebbero correttamente. Per evitare i falsi allarmi, non installare i rivelatori di fumo nelle seguenti situazioni: Non installare i rivelatori di fumo all’interno o vicino ad aree dove sono presenti
particelle di combustione, come cucine senza finestre o scarsa ventilazione, autorimesse dove ci possono essere fumi di scarico di veicoli, vicino a fornaci, caldaie e locali con un’elevata temperatura.
Non installare i rivelatori a meno di 6 metri da posti dove sono normalmente
presenti particelle di combustione, come per esempio le cucine. Se non è possibile mantenere una distanza di 6 metri, per evitare falsi allarmi, provvedere ad effettuare una buona ventilazione all’interno di questi locali.
In prossimità di fumi di scarico di automobili; questo danneggerà il rivelatore. Vicino a vapori di solventi. In locali molto sporchi o polverosi, la sporcizia e la polvere possono
depositarsi sulla camera di rilevazione del rivelatore e renderlo eccessivamente sensibile.
Inoltre, la sporcizia e la polvere possono ostruire le fessure di rilevazione della
camera del rivelatore e impedire che il rivelatore rilevi il fumo.
In aree infestate da insetti. Se gli insetti si introducono nella camera di
rilevazione del rivelatore, possono causare falsi allarmi. Quando gli insetti possono essere un problema, disinfestare l’area prima di installare i rivelatori.
Vicino a luci fluorescenti, il rumore elettrico delle luci fluorescenti può causare
falsi allarmi. Installare i rivelatori di fumo ad almeno 1,5 metri da queste luci.
IMPORTANATE:
Non provare ad evitare i falsi allarmi escludendo il rivelatore.
16
Rivelatore Fotoelettrico di Fumo Supervisionato
INSTALLAZIONE DEL RIVELATORE
Il rivelatore di fumo può essere installato a soffitto o a parete, se necessario.
Per installare il rivelatore, eseguire le seguenti fasi (vedi Figure 4):
Scegliere il luogo di installazione. Rimuovere la linguetta di blocco
Rimuovere la base di montaggio
Utilizzare la base come dima per
Utilizzando un trapano appropriato,
Utilizzando le viti (fornite) avvitare la
Aprire il vano porta-batteria (vedi
Inserire 2 batterie al litio da 3 Volt
Il messaggio di “Trasmissione
Allineare la fessura sul bordo della
Tirare il rivelatore verso il basso per
ATTENZIONE:
Non collegare i rivelatori di fumo a nessun altro rivelatore o dispositivo ausiliario. Collegando altri dispositivi a questo rivelatore verrà impedito il suo corretto funzionamento.
Linguetta di b locco
posta su un lato della base di montaggio dell’unità (vedi Figura 6).
dall’unità ruotandolo in senso antiorario.
segnare i punti di fissaggio.
effettuare due fori nei punti marcati e inseri re i tas selli.
base alla parete, come in Figura 4.
Figura 5).
tipo CR123 (fornite) nel vano porta­batteria prestando attenzione alla polarità, poi chiudere il coperchio del vano.
Indirizzo” (WRITE) viene trasmesso automaticamente dall’unità, 10 secondi dopo aver inserito le batterie, o premendo il tamper del rivelatore per almeno 3 secondi.
base di montaggio con la fessura situata sul rivelatore. Spingere il rivelatore verso la base e girare in senso orario per fissarlo alla base. Inserire la linguetta di blocco in modo da serrare la base di montaggio al rivelatore (vedi Figura 4).
assicurarsi che sia agganciato saldamente alla base.
Base di montaggio
Figura 4: Installazione del Rivelatore di Fumo
Tamper
Linguetta
per aprire il
coperchio
Figure 5. Tamper/Vano porta-batteria
IMPORTANTE:
il rivelatore non può essere agganciato alla base di supporto se la batteria non è stata installata.
Viti
Vano porta-batteria
ATTENZIONE:
Questo rivelatore deve essere installato in conformità agli Standard vigenti relativi ai sistemi di rilevazione incendio.
Rivelatore
INDICATORE ROSSO
Quando l’indicatore LED rosso (vedi Figura 6) lampeggia una volta ogni 30 secondi, indica che il rivelatore è in condizione di funzionamento normale. Quando
Rivelatore Fotoelettrico di Fumo Supervisionato
17
Loading...
+ 39 hidden pages