REMKO PWW User Manual

REMKO PWW
Warm water heaters
Operation · Technology · Spare Parts
Edition GB - T08
3
Contents
Unit description
Unit installation
Mounting examples
Electrical connection
Heating medium connection
Commissioning
Switching off
Care and maintenance
Repair
Air outlet accessories
Air inlet accessories
Accessory installation
4
4
5
6
7
8
9
9
10
10
11
12
14
Control units
Exploded drawing
Spare parts list
Intended use
Customer service and warranty
Environmental protection and recycling
Ratings tables/Characteristics
Calculation examples
Planning/Calculation/Units
Unit dimensions
Technical data
16
20
20
21
21
21
22
30
32
34
35
Made by REMKO
These operating instructions must be read thoroughly before commissioning/using the unit!
These instructions are part of the unit and must always be kept near to the site of installation or the unit.
Subject to changes; errors and typographical errors excepted!
4
REMKO PWW
Safety information
The units were subjected to ex­tensive material, functional and quality inspections and tests prior to delivery.
The units can however constitute a hazard if used improperly by untrained persons or not for the intended purpose.
Always observe the following safety information:
The locally applicable building
regulations must be observed.
The operator is responsible for
correct installation of the units, correct electrical installation and safe operation of the units.
The units must be installed
and operated in a manner that excludes any risk to persons through radiated heat.
The units must only be attached
to constructions or ceilings with sufficient load bearing capacity.
Attachment must take place
using suitable anchors to be at­tached to the unit.
Only trained specialists may
install and connect the heating medium, establish electrical con­nections and carry out mainte­nance.
The units must not be installed
and operated in locations where there is a risk of fire and explosion.
The units must only be operated
in a completely installed condition.
Safety components, e.g. protec-
tion grilles must not be removed or rendered inoperational.
The units must only be operated
within the specified capacity limits and with the approved operating media.
Observe rating plate!
The air intake grilles must
always be kept free of dirt and loose objects and the air outlet must not be closed.
Never insert foreign objects into
the unit.
The units must not be sprayed
with a direct jet of water.
Never allow water to enter the
unit.
All electrical cables of the units
must be protected against dam­age, e.g. animals, etc.
NOTE
Perfect functioning of the units is only ensured when the flow temperature at the unit inlet and the pump capacity cor­respond to the selected unit classification.
Unit description
These units are stationary, indi­rectly fed air heaters with copper/ aluminium fin heat exchanger for connection to a pumped hot water system up to max. 130°C.
The units are suitable for wall or ceiling mounting.
The units can be provided with diverse air inlet and air outlet accessories.
The units are provided with hori­zontal, individually adjustable air outlet fins as standard.
The units are provided with a low­noise, aerodynamically designed, sickle-shaped high-power axial fan, individually adjustable air out­let fins and electrical terminal box.
The units are fitted with a 400V/50Hz, two-speed external­rotor motor as standard.
The units comply with the basic health and safety requirements of the pertinent EU regulations and are easy to operate.
The units must be installed
outside traffic zones, e.g. also the operating areas of cranes. A protection zone of 1 m distance must be kept free.
5
Unit installation
The following information must be observed for safe unit installation.
The units must be arranged so
that accessed areas and work­places are not located in the direct air stream.
The units must only be mount-
ed on ceilings or roof construc­tions with sufficient load bear­ing capacity.
The heat exchangers must be
connected so that no vibrations can be transferred from the unit to the pipe system or vice versa.
For wall mounting, a minimum
height of 2.5 m to the bottom edge of the unit must be maintained.
For wall mounting above 4 m,
suction of the recirculated air should take place from the ground to ensure uniform heating.
For ceiling mounting below
4 m, the units should be fitted with an air outlet hood HG 4.
For ceiling mounting above
4 m, the units should be fitted with the ceiling air outlet nozzle AD.
Before connecting the units
to an existing water heating system, the boiler and pump must be checked for sufficient capacity.
For maintenance and repair
purposes, a repair switch should be mounted near to the unit.
The gap between the fan
impeller and housing must be checked for the same distance.
Units with fresh air inlet
must be fitted with anti-frost protection.
Brackets
Brackets (KO) for wall and ceiling mounting (2 per unit) must be inserted into the recesses in the rear wall of the unit and attached to the unit us­ing the enclosed screws.
Direct mounting parts such as mixed-air or filter box must be attached using a wall fastening bracket (WFM).
When using local bracket construc-
ATTENTION
The brackets must be screwed to the de-energised unit and wall or ceiling.
tions, the minimum wall distance
“e” must be maintained!
Bracket KO
for wall and ceiling mounting
e
d
b
d
c
a
e
in mm
f
f
in mm
KO (L
PWW
40 x 40 x 3)
30
50
80
100
ø 12.5
f
a
in mm
b
in mm
c
in mm
d
in mm
552 432 506 155 270 40
632 507 586 192 270 40
792 622 746 250 270 40
872 732 826 305 340 40
Heat exchanger copper/aluminium
The fin heat exchangers consist of copper pipes with pressed on
pipe adapters.
The water inlet (flow) is
generally the bottom. aluminium fins. The fin assembly is enclosed by a galvanised steel frame.
Collector, distributor and heating medium connections are made of
The maximum operating tem-
perature is 130°C.
The maximum operating pres-
sure is 16 bar. steel.
The heat exchangers are not
Heating medium connections
are established via threaded
suitable for operation with
steam or thermal oil.
6
REMKO PWW
Mounting examples
Circulation/fresh air operation via the roof.
ALH
Circulation/fresh air operation via the outside wall.
PWW
FK
SG
KA
MLK
4
KA
RK
ß
ß
KA
PWW
AG
1
2
WFM
ß
ß
FK
SG
KA
4
4
SG
2
MLK
WFM
UA
ß
ß
Wall opening appropriate to air
1
inlet grille size.
The mixed-air box must be fas-
2
tened using the wall bracket WFM to a load bearing outside wall.
UA
3
3
ß
ß
The air intake channel and
3
air inlet piece must be fastened to the outside wall locally.
The vertical part of this system
4
arrangement must be attached to the wall using brackets so that the flexible pipes are not subjected to weight.
7
U1
V1 W1 W2U2V2 11 12
TK TK
Electrical connection
Ceiling mounting
In circulation operation with bracket KC
KO
PWW
Wall mounting
In circulation operation with filter FK, mixed-air box MLK, bracket WFM and injection shutter.
MLK
FK
PWW
IJ
WFM
Legend:
AG = Fresh air inlet grille
ALH = Fresh air inlet hood
FK = Filter box
KA = Warmth channel interim piece
KO = Brackets
MLK = Mixed-air box
Electrical connections of the unit must only be established by au­thorised specialists in compliance with the applicable regulations of the local electricity supply compa­ny as well as the VDE installation requirements relating to the unit.
ATTENTION
Failure to observe the pertinent requirements, operating instruc­tions and electrical wiring dia­grams relating to the unit can give rise to malfunctions with consequential damage.
This will invalidate the warranty!
Unit connection
The units are fitted with two­speed, 400V three-phase axial fans as standard. With the appropriate control units (accessory), speed selection takes place via Y/D switching.
Motor protection is provided via built-in thermal contacts that drop out at a fan motor winding temperature of 130°C in conjunction with a suitable control unit (accessory).
Connection of the three-phase motors to the respective control units takes place via the associated electrical wiring diagrams.
ATTENTION
When the fan is stationary, the heating medium supply must be simultaneously interrupted.
Connection of several units
If necessary, several units (also dif­ferent sizes) can be operated paral­lel via a control unit (accessory).
The total capacity of the con­nected units must not exceed the maximum switching capacity of the respective control unit.
For thermal motor protection, the thermal contacts of all motors must be connected in series. See separate wiring diagrams.
Only one external control device (thermostat, day/night control, etc.) can be connected per control unit.
Terminal box on unit
Fuse protection in the supply to the control unit must be in compliance with the applicable regulations.
The connections in the terminal box must be connected to the respective control unit (accessory).
ATTENTION
Only trained specialists may establish electrical connections.
RK = Rain collar
SG = Flexible pipe
WFM= Wall bracket
IJ = Injection shutter
8
REMKO PWW
Heating medium connection
Connection to water heating system
Prior to connection to the heating system on-site, it must be en­sured that the respective capacity requirements of the unit can be made available at all times.
Connection of the unit on the
water side must take place on­site via suitable pipe fittings and shut-off valves in the flow and return.
The use of compensators and automatic deculators is recom­mended!
T he water inlet (flow) is gener-
ally at the “top“.
Air outlet
The fin heat exchangers must
be thoroughly vented after installation.
Air cushions in the heat exchanger will reduce the heating capacity!
The fin heat exchangers operate
in counterflow.
Air inlet
Water outlet
Water inlet
See technical data for pipe con-
nection thread sizes.
NOTE
When tightening the screwed connections of the heating medium connection, a suitable tool must be used to prevent the connecting pipes rotating in order to avoid damage.
The connection side can be
either on right or left.
Draining if there is a risk of frost
It is not possible to statically drain the fin heat exchanger completely. The fin heat exchanger can only be drained completely using com­pressed air.
Important information on frost protection!
To prevent frost damage, anti-frost protection must be provided at temperatures below 0°C.
Where systems in rooms at risk from frost are not used for ex­tended periods, under no circum­stances must water be present in the heat exchanger.
If this is not possible, a suitable antifreeze agent must be added to the heating medium (water).
Venting
ATTENTION
Frost damage to the fin heat exchanger does not fall under the warranty!
Anti-frost thermostat
Water outlet
Pipe fitting
Water inlet
Draining
9
Commissioning Switching off
Prior to initial use
ATTENTION
Commissioning can only take place when it is ensured that mounting and electrical installation has been carried out in compliance with the pertinent requirements of the EC Directives.
1. Correct mechanical installation must be verified.
2. Correct connection to the heating system on-site must be verified.
3. It must be ensured that hot surfaces are protected against accidental contact.
4. It must be verified that the electrical wiring of the units has been carried out in compliance with the applicable directives and standards using the sup­plied wiring diagrams.
9. It must be ensured that the fan rotates in the direction of the arrow.
The direction of rotation can be changed by interchanging two phases.
10. It should be noted that when using a speed control (acces­sory) the power of the control unit must correspond to the power of the motor.
During initial commissioning
During initial commissioning, all regulating, control and safety devices must be checked for their proper functioning and correct adjustment.
1. The power consumption of the
fan must be measured.
The nominal current must not exceed the values on the rating plate at the respective opera­ting speeds.
Set the switch of the respective control unit to the “Off” or “0” position.
For extended periods of non­use:
Disconnect the electrical con-
nection in all poles.
Shut-off the heating medium
connection.
Where there is s risk of frost,
the entire system must be drained if no suitable antifreeze agent has been added.
NOTE
The heat exchanger can only be drained completely using compressed air.
5. The fan space as well as the inlet and outlet area must be checked for the presence of foreign bodies.
6. It must be ensured that all air outlets are open.
7. The fan must be checked for smooth operation.
8. Switch on the power to the con­trol unit (accessory) and switch on the unit via the control switch of the control.
2. Check the control/regulating function of the fan.
3. Check the motor protection function of the fan.
4. If fitted, check the function of the frost protection and room thermostats.
5. Check the complete system for de-energised installation and possible vibrations.
6. Check the heating medium sup­ply pipes for correct connection and tightness.
NOTE
After disconnecting the control unit from the power supply, in the event of a power failure or shutdown on faults, the con­trol switch must always first be switched to back to the “0 position.
10
REMKO PWW
Care and maintenance
The units are virtually mainte­nance-free in normal operation. However, to ensure trouble-free operation, they should be in­spected regularly and cleaned if necessary.
Important precautions to be taken before carrying out any maintenance:
The units must be disconnected
from the supply in all poles and locked to prevent unauthorised reconnection.
ATTENTION
It does not suffice to switch off the unit only via the switch!
Wait for the fan to stop.
Shut-off the water circuit and
lock to prevent unauthorised opening.
Allow the fin heat exchanger to
cool down.
NOTE
The fan impeller and alumini­um fins must not be damaged or bent.
Cleaning agents
The units must be cleaned only
dry or with a moist cloth and a small amount of soap solution if necessary.
Under no circumstances use
high-pressure cleaners or steam jet equipment.
Do not use caustic or solvent-
containing cleaning agents.
Cleaning the units
Clean all air inlets and air outlet
fins.
Clean the fan impeller. If ne-
cessary, remove the motor or protection grille.
Clean the heat exchanger fins
either by blowing out, suction or with a soft brush.
Remove heavy fouling on the
fan and aluminium fins with a soap solution.
Repair
Fan replacement
1. Disconnect the electrical con­nection of the motor.
2. Remove the protection grille with fan from the housing.
3. Remove the protection grille from the fan motor.
4. Carefully refit the new fan in reverse order.
5. Check the fan impeller for smooth operation and freedom of movement with respect to the fan housing.
6. Re-establish the electrical con­nection of the motor correctly.
Replacement of fin heat exchanger
1. Disconnect the electrical con-
nection of the unit.
2. Shut-off the water-sided unit
connection.
3. Drain the fin heat exchanger completely and disconnect the heating medium connections.
4. Remove any fitted air inlet and air outlet accessories and re­move the unit from the bracket (support).
5. Remove the rear wall (support plate) together with the fan.
6. Loosen the fin heat exchanger fastening screws and remove the heat exchanger towards the air inlet side.
7. Fit the new heat exchanger and reassemble the unit in reverse order including accessories.
8. Re-establish electrical connec­tions.
Checks after repairs:
The fan impeller must rotate
freely in the fan housing
The distance between the fan
impeller and fan housing must be the same
The fan motor must rotate in
the direction of the arrow and connected in correct phase
All screw connections must be
checked for tightness
ATTENTION
After completing all work on the units, an electrical safety test must be carried out in accordance with VDE 0701.
NOTE
Only suitable cleaning agents
must be used to remove heavy fouling.
Repair and maintenance work must only be carried out by authorised specialists.
11
Air outlet accessories
Standard type
The units are provided with horizontal, individually adjustable air outlet fins as standard.
The fins can easily be removed by unclipping.
Air outlet shutter B
Vertical, individually adjustable air outlet fins for wall and ceiling use. The air outlet shutter B is mounted directly in front of the horizon­tal air outlet fins. Use of the shutter enables a high blowing range.
The unit depth increases by 115 mm in the case of all unit types.
Retrofitting is easily possible.
W
Air outlet hood HG 4
This air outlet hood serves uniform air distribution in four directions at low mounting heights. The air outlet hood is not suitable for mounting hoods above 4 m.
For retrofitting, the standard horizontal air outlet fins of the unit
c
W
must be removed.
PWW
30 50 80
100
c
in mm
166 6 m 1.- Setting 9 m 2.- Setting 166 8 m 1.- Setting 11 m 2.- Setting 166 10 m 1.- Setting 13 m 2.- Setting 236 12 m 1.- Setting 15 m 2.- Setting
Blowing range W in metres
Ceiling air outlet nozzle AD
The ceiling air outlet nozzle serves for concentrated control of the hot air stream and must be used at mounting heights above 4 m in high halls.
For retrofitting, the standard horizontal air outlet fins of the unit
c
must be removed.
PWW
30 50
W
W
80
100
We reserve the right to make changes to dimensions and design in the interest of technical advances.
c
in mm
200 5.0 m 1.- Setting 6.5 m 2.- Setting 230 5.5 m 1.- Setting 6.5 m 2.- Setting 270 5.5 m 1.- Setting 7.0 m 2.- Setting 290 7.0 m 1.- Setting 9.0 m 2.- Setting
Blowing range W in metres
12
REMKO PWW
Air inlet accessories
Fresh air inlet grille AG
Fresh air inlet grille for fresh air intake through the outside wall
PWW
30
b1
b
50 80
100
a
For wall opening: Dimension a and b + about 15 mm
a
in mm
518 598 398 478 598 678 483 563 758 838 588 668 838 918 698 778
a1
in mm
b
in mm
b1
in mm
a1
Wall bracket WFM
for fastening the unit with air inlet accessories (PWW+FK+MLK or
a
d
b
c
PWW+FK) to the outside wall.
PWW
30 50 80
100
a
in mm
1115 490 55 60 1165 590 55 60 1215 690 55 60 1295 690 55 60
b
in mm
c
in mm
d
in mm
Mixed-air box MLK
for circulation/fresh air/and mixed air operation. With two shutter flaps working in opposite direction as standard, without servomo­tor (accessory). With the supplied variable cover, the air direction
b
a
c
can be freely selected.
PWW
30 50 80
100
in mm
560 440 300 640 515 350 800 630 400 880 740 450
a
b
in mm
c
in mm
Filter box FK
with pocket filter insert removable from the side (filter class G3, depth 100 mm)
b
PWW
30
a
c
50 80
100
a
in mm
560 440 400 640 515 400 800 630 400 880 740 400
b
in mm
c
in mm
We reserve the right to make changes to dimensions and design in the interest of technical advances.
13
Air inlet accessories
Fresh air inlet hood ALH
for fresh air intake via roof.
e
d
b
a
15
c
PWW
30 50
d
80
100
a
in mm
b
in mm
c
in mm
d
in mm
in mm
520 240 260 20 215 600 310 290 20 215 760 360 290 20 215 840 410 400 20 325
e
Rain collar RK
with warmth channel interim piece in 1000 or 500 mm length
e
c
c1
PWW
30 50
d
b
a
d
d
80
100
Flexible pipe SG
a
in mmbin mmcin mmc1in mmdin mmein mm
520 240 1000 500 20 220 600 310 1000 500 20 220 760 360 1000 500 20 220 840 410 1000 500 20 220
Flexible conn. (vibration isolation) betw. unit and air channel system. (Dimension(s) for mounting on warmth channel intermediate piece).
(e)
b
PWW
30
c
a
d
50 80
100
a
in mm
b
in mm
c
in mm
d
in mm
in mm
520 400 120 20 240 600 475 120 20 310 760 590 120 20 360 840 700 120 20 410
e
b
d
a
d
Warmth channel interim piece KA
Warmth channel interim piece in 1000 or 500 mm length
c1
d
PWW
c
30 50 80
100
a
in mm
520 240 1000 500 20 600 310 1000 500 20 760 360 1000 500 20 840 410 1000 500 20
b
in mm
c
in mm
Circulation suction adapter UA
a
d
c
We reserve the right to make changes to dimensions and design in the interest of technical advances.
b
With air inlet protection grille for mounting on a channel as standard.
PWW
30 50 80
100
a
in mm
520 240 400 20 600 310 450 20 760 360 650 20 840 410 800 20
b
in mm
c
in mm
d
in mm
e
in mm
d
in mm
14
REMKO PWW
1
C
ϑ
2
Accessory installation
Mixed-air box MLK
The mixed-air box MLK is desi­gned for both wall and ceiling mounting. The ratio of fresh air to recirculated air can be continuously adjusted manually or with a flap servomotor (accessory). With the supplied variable cover, the direction of the air on the inlet side can be freely selected. For operation of the mixed-air box with flap servomotor, the mixed­air flaps must be checked regularly for easy movement and fouling.
Filter box FK
The filter box with pocket filter is designed for direct mounting on the units. The pocket filter can be removed from the side. The filter medium of the pocket filter can be regenerated and has the filter class G3. Further filter classes are available on request.
Filter maintenance
Depending on the operating con­ditions, the pocket filter must be checked regularly and cleaned or replaced if necessary.
Automatic monitoring
The degree of clogging of the pocket filter can be monitored via a differential pressure switch (special accessory).
Anti-frost thermostat FS
The anti-frost thermostat is a precise water temperature sensor, which can be subsequently moun­ted on the surface of pipes.
The thermostat is fitted with a precision sensitive switch. The supplied strap with clamp enables easy subsequent fitting without draining the heating sys­tem.
Installation
Prior to fitting, the pipe insulation in the contact area of the sensor must be removed.
The parts required for fitting, e.g. strap or clamp, etc., are supplied with the unit.
Wiring diagram
Mounting clips
Installation
Fastening of the mixed-air and filter box takes place with the sup­plied mounting clips (4 pieces).
When the final pressure difference is reached, the filters must be replaced with filters with the same quality class.
Spare pocket filter EF:
PWW 30 EDP No. 385405 PWW 50 EDP No. 385406 PWW 80 EDP No. 385407 PWW 100 EDP No. 385408
Contact 1 opens with a rise of temperature. Contact 2 closes with a rise of temperature.
Technical data:
Setting range 25 to 95°C Switching difference adjustable. Maximum ambient temperature 70°C.
NOTE
In order to ensure perfect func­tioning of the freeze protection control, the sensor must al­ways be mounted at the water outlet (return).
15
Typ KSH
N L1
230V/1~
1 2 3
Aderbezeichnung
Stellungsgeber 0-10V
Aderbezeichnung
1 2
3
5
N L1
y
N L1
230V/1~
1 2
3
U
vcc
4
Typ KSP
Injection shutter IJ
The injection shutter is a useful ex­tension for the REMKO PWW unit and is designed for direct moun­ting on the units.
The supply air is optimally blown in via the injection shutter. The posi­tion of the air directing fins influ­ences the air velocity and air outlet temperature of the total air flow. This technology provides for a hig­her blowing range and more rapid heating of the rooms. Intake of the already heated room air prevents the occurrence of varying air temperatures. The heat is distributed evenly throughout the room.
Installation
Unclip the existing fins and fix the injection shutter with four screws. The position of the fins can also be electrically regulated via an optio­nal control.
Servomotor KSH (open/closed)
The servomotor is mounted direct­ly on the flap shaft. It is provided with a universal terminal block and is fixed with the supplied locking element.
The drive is overload-proof and requires no limit switch. For manual actuation, the gear can be disengaged with a self-resetting pushbutton.
Wiring diagram
Technical data:
Servomotor Type KSH overload-proof Rating 2.5 W, 230V, 50Hz Degree of protection IP 54 Operating time about 150 seconds Maximum ambient temperature 50°C.
Servomotor KSP (variable speed)
The servomotor type KSP is sup­plied with 230V. A transformer converts the system voltage into a low voltage of 24V. The motor is controlled depending on the input voltage and position of the feedback potentiometer. The direction of rotation of the motor can be reversed with the rotary control switch. The connection of an electrical indicator for the flap position and further servomotors is possible.
Wiring diagram
Technical data:
Servomotor type KSP overload-proof Rating 3.5 W, 230V, 50Hz Degree of protection IP 54 Operating time about 150 seconds Maximum ambient temperature 50°C.
ATTENTION
Installation and repairs to the electrical installation must only be carried out by autho­rised electrical specialists for safety reasons.
NOTE
All electrical wiring terminals must be checked for tightness and retightened if necessary.
16
REMKO PWW
Switchgear SW 2 - 380 DI
Three-phase 400V, two-speed fan
maximum switching capacity 4 kW, surface mounting, motor protection by means of built-in thermal contacts in fan motor.
Design
Sturdy plastic housing, Degree of protection IP 54. Totally-insulated according to VDE.
Front plate with symbols for switch positions, supply and protective conductor terminals, main con­tactor, control switch with the functions “Off/Setting 1/Setting 2“, control fuse, indicator light (extinguishes on fan faults and/or
interruption of power supply to control unit), fault reset button, terminals for motor output, termi­nals for thermal contacts and room thermostat.
Reconnection after a fault
After each main break or fan fault, the “Fan fault reset button“ must be pressed once!
Multiple series connection
The control unit is suitable for multiple series connection. Several motors in the same circuit can be connected to a control unit The total rating of the connected motors must not exceed the per­missible switching capacity of the
control unit. The thermal contacts of all motors must be connected in series.
Note on safe operation
Earthing, multiple earthing or protection switching and mains protection must be carried out on-site according to VDE specifications and the regulations of the responsible electricity supply company. Only specialists may establish electrical connections based on the wiring diagrams in compliance with the applicable regulations, taking into account local regulations.
Circuit and wiring diagram
S1 = Fan fault reset button K2A = Auxiliary relay
We reserve the right to make changes to dimensions and design in the interest of technical advances.
F1 = Control fuse S2 = Control switch
K1M = Contactor for fan motor H1 = Indicator light
17
Control unit MSRD 2.5
0
D
U
1 2 3
4
7 8 9
10
11
12
13
14
15
16
17
18
5
6
S1
R1
K1
13
14
K1
F1
6,3 A
H1
X1
X2
K1
A1
A2
PE L1 L2 L3 N
PE U1 V1 W1 U2 V2 W2 TK TK
15
RT RT
16
4 4 4
11
1 3 5
13
2 4 6
14
Raumthermostat
Thermokontakte
im Motor
Einspeisung 400 V / 50 Hz
Erdung nach örtlichen Vorschriften
Motor 3~
Thermoschutz
für 2 Geräte
Thermoschutz
für 3 Geräte
Thermoschutz
für 4 Geräte
weitere Thermokontakte
in Reihe schalte n
13TK14
TK
13TK14
TK
13TK14
TK
6 7 8 9 10 11 12 14
13
1 2 3 4 5
1 3 5
2 4 6
Three-phase 400V, two-speed fan
maximum switching capacity 2.5 kW, surface mounting, motor
protection by means of built-in thermal contacts in fan motor.
Design
Sturdy plastic housing, Degree of protection IP 41. Totally-insulated according to VDE.
Front plate with symbols for switch positions, supply and protective conductor terminals, main con­tactor, control switch with the functions “Off/Setting 1/Setting 2”, control fuse, indicator light (extinguishes on fan faults and/or interruption of power supply to
control unit), fault reset button, terminals for motor output, termi­nals for thermal contacts and room thermostat.
Reconnection after a fault
In the event of a fault, the unit switches off and does not switch on again automatically. After clearing the fault, the unit can be switched on again by setting the control switch to “0” and waiting for about30 seconds.
Multiple series connection
The control unit is suitable for multiple series connection. Several motors in the same circuit can be connected to a control unit. The total rating of the connected
motors must not exceed the per­missible switching capacity of the control unit. The thermal contacts of all motors must be connected in series.
Note on safe operation
Earthing, multiple earthing or protection switching and mains protection must be carried out on-site according to VDE specifications and the regulations of the responsible electricity supply company. Only specialists may establish electrical connections based on the wiring diagrams in compliance with the applicable regulations, taking into account local regulations.
Circuit and wiring diagram
S1 = Control switch K1 = Contactor R1 = PTC element F1 = Control fuse H1 = Indicator light
We reserve the right to make changes to dimensions and design in the interest of technical advances.
18
REMKO PWW
PE L1 L2 L3 N PE U1 V1 W1U2 V2 W2X1 1 2 3 4 5 6 7 8 9 10 11 12X2 13 14 15
TK FS TF
Mischluft-
klappe
Potenzialfreier
Kontakt TK
Potenzialfreier
Kontakt FS
Potentiometer zum Abgleich des Temperaturfühlers
Spannungsversorgung Ventilatoranschluß
Control unit MAK-2
Three-phase 400V, two-speed fan
maximum switching capacity 8 kW Surface mounting, motor protec­tion by means of built-in thermal contacts in the fan motor, termi­nals for thermal contacts, room thermostats, anti-frost thermostat and mixed-air box servomotor.
Design
Sturdy plastic housing, Degree of protection IP 54. Totally-insulated according to VDE.
Fully electronic two-step control unit with digital display. Two modes are available, “Manu­al“ and “Automatic“. Operation takes place via a large sized membrane keyboard. In the automatic mode, the fan speeds are controlled according to the freely programmable tempera­ture difference. Day/night/temperature control in­cluding week programme provided as standard. Four switching times are available for day and night respectively. Available for motor protection are thermal contact terminals. Terminals for anti-frost thermostat
and continuously variable flap ser­vomotor are provided as standard.
Function
The mixed-air flaps can be conti­nuously controlled via flap servo­motor. When the unit is switched off, the flaps assume a “CLOSED“ position. The anti-frost thermostat also closes the flaps and switches off the fan.
Reconnection after a fault
After a power failure (up to three hours) the unit restarts automatically. After operation of the thermal contacts, the unit can be reset after cooling down via the “OFF“ button. The antifreeze sensor automatically starts the unit in the previously selected programme mode after a rise of temperature.
Multiple series connection
The control unit is suitable for multiple series connection. Several motors in the same circuit can be
connected to a control unit. The total capacity of the con­nected motors must not exceed the permissible switching capacity of the control unit. The thermal contacts of all motors must be connected in series.
Note on safe operation
Earthing, multiple earthing or pro­tection switching and mains pro­tection must be carried out on-site according to VDE specifications and the regulations of the respon­sible electricity supply company. Only specialists may establish electrical connections based on the wiring diagrams in compliance with the applicable regulations, taking into account local regulations.
Wiring diagram
We reserve the right to make changes to dimensions and design in the interest of technical advances.
19
Control unit, 5-stage
EG
TK
TK W2 U2 V2
W1V1U1
J
N
L1 L2
L3 U1
V1 W1
TK TKRT RT
N L1 L2 L3PE
J
FS FS
12
11 14
N L L
Raum- thermostat
Frostschutz- thermostat
250VAC max.2A
230VAC max.1A
Eingangsspannung 400V / 3~N / 50 Hz
3~ Motor mit Thermokontakten
Kontaktbelastung
Lüfter Aus/Ein
hohe Drehzahl
- Schaltung
niedere Drehzahl
Y - Schaltung
TK
W2 U2 V2
TK
U1
V1 W1
PE
L1 L2 L3
TK W2 U2 V2
TK
U1
V1 W1
PE
L1 L2 L3
Voltage Current
Degree of protection
Weight
Control unit V A IP kg
3 EG
5 EG
400 3.0 54 11.1
400 5.2 54 15.6
Wiring diagram five-stage control unit 3 EG/5 EG
Five-stage control units, 400V/50Hz, three-phase with indicator light. Motor protection takes place by the connection of thermal contacts.
In the event of a fault, (operati­on of the thermal contacts), the internal contactor drops out and disconnects the motor from the power supply.
After the motor has cooled down and the fault cleared, the mode se­lector switch must first be switched to the “0“ position and then back to the required operating position (speed position).
The control units have a connec­tion for external control devices, e.g. room thermostat, anti-frost thermostat, servomotor, recirculat­ing pump, indicator light, solenoid valve, mixer, etc. (observe contact rating).
Fan motor 400V, two-step
D / Y switching and thermal contacts Standard units
Wiring diagram
We reserve the right to make changes to dimensions and design in the interest of technical advances.
ATTENTION
Electrical heater connection must be carried out by au­thorised specialists as defined in DIN EN 60335-1 and VDE
0116.
NOTE
All electrical wiring terminals must be checked for tightness and retightened if necessary.
20
REMKO PWW
Exploded drawing
4
5
6
1 1a 1b
2
We reserve the right to make changes to dimensions and design in the interest of technical advances.
Spare parts list
No. Designation
PWW 30
EDP No.
3
7
PWW 50
EDP No.
PWW 80
EDP No.
PWW 100
EDP No.
1 Heat exchanger Bg. 2 1105211 1105215 1105219 1105223
1a Heat exchanger Bg. 3 1105212 1105216 1105220 1105224
1b Heat exchanger Bg. 4 1105213 1105217 1105221 1105225
2 Electrical terminal box 1105268 1105268 1105268 1105268 3 Housing 1105274 1105275 1105276 1105277 4 Fan protection grille 1105207 1105208 1105209 1105210 5 Fan 400V/two-speed 1105242 1105243 1105244 1105245 6 Support plate 1105264 1105265 1105266 1105267 7 Air outlet fin 1105284 1105285 1105286 1105287
When ordering spare parts, also quote the serial number of the unit (see rating plate) in addition to the EDP number!
21
Intended use
Customer service and warranty
Environmental Protection and Recycling
Owing to their design and equip­ment, the devices are intended solely for heating and ventilation purposes in industrial or commer­cial use (not for domestic heating).
The unit is designed for use with air inlet and air outlet accessories approved by the manufacturer.
The units must only be operated by suitably trained personnel.
The manufacturer disclaims all liability for any damage attributed to failure to observe relevant instructions, statutory re­quirements applicable at the place of use or unauthorised changes to the unit.
NOTE
A precondition for any warran­ty claims is that the dealer or his customer has completed and returned the enclosed “Warranty document“ to REMKO GmbH & Co. KG at the time of sale and commissioning.
The units were repeatedly tes­ted for perfect functioning at the factory. However, if faults should occur which cannot be cleared by the operator via troubleshooting measures, your specialised dea­ler or contract partner should be contacted.
NOTE
Disposal of packaging
Think of the environment when disposing of the packaging material. Our appliances are carefully pa­cked for transport and delivered in sturdy cardboard packaging and on a wooden pallet if necessary. The packaging materials are en­vironmentally-friendly and can be recycled. The reuse of packaging material makes a valuable contribution to the reduction of waste and the preservation of raw materials.
Dispose of packaging materials at the facilities provided.
Disposal of old unit
Our production is subject to cons­tant quality controls.
Use for any other purpose than that described in these operating instructions is not permitted. Failure to observe this rule will invalidate all liability and warranty.
Adjustment and maintenance must only be carried out by authorised specialists.
Only high-quality materials are used, the majority of which are recyclable.
Make your contribution towards environmental protection by dis­posing of your old appliance in an environmentally friendly manner.
Only dispose of old appliances at recycling sites or where suitable facilities exist.
22
REMKO PWW
PWW 30 ratings tables • Technical data
Type
Design
Speed
Electrical connection
Frequency
Power input
Nominal current
Air capacity
Sound pressure level
Blow. range ceiling*max.
Blow. range wall max.
Heating medium conn.
Weight
Heating medium
50/40 °C
60/50 °C
70/50 °C
80/60 °C
90/70 °C
rpm Volt Hz kW A m³/h dB(A) m m Inch kg tL1 °C
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
PWW 30-2
two-speed
1340 1040
3 x 400 3 x 400
50 50
0.13 0.10
0.26 0.16
2250 1850
52 46
7.5 6.0 17 14
R ¾“ R ¾“
24 24
kW tL2 °C kW tL2 °C
13.1 2 10.6 2
12.0 5 10.7 7
10.9 9 9.7 10
0
0
0
0
0
9.6 12 8.6 14
8.3 16 7.5 18
7.0 20 6.4 21
5.9 23 5.3 24
4.5 26 4.0 27
16.5 5 14.0 5
15.1 9 12.9 9
13.8 12 11.8 12
12.7 16 10.7 16
11.5 20 9.6 20
10.1 23 8.6 24
8.7 27 7.5 27
7.4 30 6.4 30
17.3 6 14.7 6
15.9 9 13.4 9
14.4 13 12.1 13
13.1 16 10.7 16
11.8 21 9.8 20
10.4 24 8.6 24
8.5 26 7.2 26
7.1 29 5.8 29
20.3 10 17.5 10
18.8 13 16.1 13
17.3 16 14.7 16
15.9 19 13.4 19
14.4 24 12.1 24
13.1 27 10.7 27
11.8 31 9.8 30
10.4 34 8.6 34
23.2 13 20.4 15
21.7 17 18.9 18
20.3 20 17.5 20
18.8 23 16.1 23
17.3 28 14.7 28
15.9 31 13.4 31
14.4 34 12.1 34
13.1 37 10.7 37
tL1 Air inlet temperature tL2 Air outlet temperature* with ceiling air outlet nozzle AD
PWW 30-3
two-speed
1340 1040
3 x 400 3 x 400
50 50
0.13 0.10
0.26 0.16
2050 1640
53 48
7.0 5.5 16 13
R 1“ R 1“
26 26
kW tL2 °C kW tL2 °C
16.7 9 15.2 12
15.4 12 13.8 14
14.0 15 12.3 17
12.2 17 11.0 20
11.0 22 9.4 23
9.0 24 7.8 25
7.6 27 6.6 28
5.8 29 5.1 30
20.6 13 18.1 16
19.2 16 16.6 18
17.7 19 15.2 21
16.2 22 13.7 23
14.8 26 12.3 28
12.9 29 11.0 30
11.6 32 9.4 32
9.5 34 7.8 34
22.1 15 18.1 16
20.3 17 16.6 18
18.4 20 15.2 21
16.7 22 13.7 23
15.1 27 12.3 28
13.3 29 10.8 30
11.0 31 9.3 32
9.0 33 7.6 34
25.7 19 21.0 21
23.9 22 19.5 23
22.1 25 18.1 26
20.3 27 16.6 28
18.4 32 15.2 33
16.7 34 13.7 35
15.1 37 12.3 38
13.3 39 10.8 40
29.4 24 23.9 25
27.6 27 22.4 28
25.7 29 21.0 31
23.9 32 19.5 33
22.1 37 18.1 38
20.3 39 16.6 41
18.4 42 15.2 43
16.7 44 13.7 45
PWW 30-4
two-speed
1340 1040
3 x 400 3 x 400
50 50
0.13 0.10
0.26 0.16
1850 1500
55 49
6.5 5.0 15 12
R 1 ¼“ R 1 ¼“
27 27
kW tL2 °C kW tL2 °C
21.0 18 19.1 22
19.4 20 17.4 24
17.6 23 15.4 25
15.5 24 13.8 27
13.0 28 11.8 30
11.3 29 10.0 31
9.5 31 8.2 32
7.3 32 6.4 33
26.1 23 21.7 24
24.2 25 20.4 27
22.2 27 19.0 29
20.5 30 17.4 31
18.5 34 15.4 35
16.3 36 13.7 37
14.0 37 11.8 38
12.0 39 10.0 40
26.4 23 23.5 28
24.5 26 21.4 29
22.9 28 19.4 30
21.1 31 17.4 31
19.0 35 15.8 36
16.7 36 13.6 37
13.8 37 11.7 38
11.5 38 9.3 38
29.9 28 27.5 35
28.2 31 25.5 36
26.4 33 23.5 38
24.5 36 21.4 39
22.9 41 19.4 43
21.1 43 17.4 44
19.0 45 15.8 46
16.7 46 13.6 47
33.6 36 28.9 41
31.3 38 27.2 42
30.2 41 25.7 44
27.8 42 24.1 46
26.6 49 22.7 52
24.5 50 21.4 55
22.7 52 19.5 56
20.9 54 18.0 56
We reserve the right to make changes to dimensions and design in the interest of technical advances.
23
Characteristics • Heating medium resistances
Pressure difference values D of accessories:
1. Accessories mounted on suction side
Component Type D
Mixed-air box MLK 5
Filter box (filter clean) FK 2
moderate filter clogging FK 7
Warmth channel interim piece (per m)
Fresh air inlet grille AG 4
Circulation suction adapter UA 1
Fresh air inlet hood ALH 3
2. Accessories mounted on pressure side
Component Type D
Air outlet shutter B 4
KA 1
Air outlet hood HG 3
Ceiling air outlet nozzle AD 10
We reserve the right to make changes to dimensions and design in the interest of technical advances.
24
REMKO PWW
PWW 50 ratings tables • Technical data
Type
Design
Speed
Electrical connection
Frequency
Power input
Nominal current
Air capacity
Sound pressure level
Blow. range ceiling*max.
Blow. range wall max.
Heating medium conn.
Weight
Heating medium
50/40 °C
60/50 °C
70/50 °C
80/60 °C
90/70 °C
rpm Volt Hz kW A m³/h dB(A) m m Inch kg tL1 °C
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
- 15
- 10
- 5
+ 5 + 10 + 15 + 20
PWW 50-2
two-speed
1360 1020
3 x 400 3 x 400
50 50
0.26 0.18
0.52 0.29
3800 3180
55 50
8.0 7.0 22 18
R ¾“ R ¾“
31 31
kW tL2 °C kW tL2 °C
21.2 1 19.3 3
20.4 6 17.4 6
16.9 8 15.5 9
0
0
0
0
0
15.1 12 13.7 12
13.0 16 11.7 17
11.0 19 9.7 20
9.0 22 7.7 23
7.0 26 5.9 26
26.5 4 23.1 5
24.5 8 21.3 9
22.4 11 19.3 12
20.3 15 17.4 15
17.9 19 15.5 20
15.9 22 13.6 23
13.7 26 11.7 26
11.6 29 9.6 29
26.6 4 22.9 5
24.5 8 21.0 8
22.3 11 19.0 12
20.1 15 16.9 15
18.1 19 14.8 19
15.6 22 12.9 22
13.4 26 11.1 26
11.2 29 9.3 29
30.7 7 26.8 8
27.7 11 24.9 12
26.6 14 22.9 15
24.5 18 21.0 18
22.3 23 19.0 23
20.1 26 16.9 26
18.1 29 14.8 29
15.6 32 12.9 32
34.9 10 30.7 12
32.7 14 28.4 15
30.7 17 26.8 18
28.7 21 24.9 22
26.6 26 22.9 27
24.5 29 21.0 30
22.3 33 19.0 33
20.1 36 16.9 36
tL1 Air inlet temperature tL2 Air outlet temperature* with ceiling air outlet nozzle AD
PWW 50-3
two-speed
1360 1020
3 x 400 3 x 400
50 50
0.26 0.18
0.52 0.29
3400 2870
55 51
7.0 5.5 20 16.5
R 1“ R 1“
34 34
kW tL2 °C kW tL2 °C
27.3 8 24.7 10
24.9 11 22.2 12
22.3 14 19.8 15
19.7 17 17.4 18
17.1 21 14.8 21
14.4 23 12.5 24
11.8 26 10.1 26
9.2 29 7.7 28
34.8 13 29.4 13
32.1 16 27.1 16
28.8 18 24.7 19
26.2 21 22.2 21
23.5 26 19.8 26
20.7 28 17.4 28
18.1 31 14.8 30
15.3 33 12.5 33
34.9 13 29.4 13
32.2 16 26.8 16
29.4 19 24.3 18
26.5 21 21.8 21
23.8 26 19.4 25
20.9 28 16.6 27
17.3 30 14.5 30
13.8 32 11.9 32
40.1 17 34.2 18
37.6 20 31.8 21
34.9 23 29.4 23
32.2 26 26.8 26
29.4 31 24.3 30
26.5 33 21.8 33
23.8 36 19.4 35
20.9 38 16.6 37
45.1 21 38.8 22
42.3 24 35.9 24
40.1 27 34.2 28
37.6 30 31.8 31
34.9 36 29.4 36
32.2 38 26.8 38
29.4 41 24.3 40
26.5 43 21.8 43
PWW 50-4
two-speed
1360 1020
3 x 400 3 x 400
50 50
0.26 0.18
0.52 0.29
3150 2770
58 54
6.5 5.5 18 16
R 1 ¼“ R 1 ¼“
36 36
kW tL2 °C kW tL2 °C
36.1 18 32.8 19
32.8 20 29.3 21
29.5 22 26.1 22
25.9 24 23.0 24
22.6 27 19.6 27
19.0 29 16.6 29
15.6 31 13.5 30
12.0 32 10.1 31
45.9 24 38.8 24
42.3 26 35.8 26
38.1 28 32.7 27
34.6 30 29.3 29
31.1 34 26.0 33
27.3 36 22.9 35
23.8 37 19.5 36
20.1 39 16.5 38
46.1 25 38.8 24
42.6 27 35.3 25
38.8 28 32.2 27
34.9 30 28.8 29
31.4 34 25.7 33
27.6 36 21.9 34
22.8 36 19.0 36
18.2 37 15.8 37
52.9 31 45.1 30
49.7 33 42.1 32
46.1 35 38.8 34
42.6 37 35.3 35
38.8 41 32.2 40
34.9 43 28.8 41
31.4 44 25.7 43
27.6 46 21.9 44
54.0 31 48.5 33
50.8 34 44.9 35
48.1 36 42.8 37
45.1 39 39.8 39
41.9 44 36.8 45
38.6 46 33.5 46
35.3 48 30.4 48
31.8 50 27.8 51
We reserve the right to make changes to dimensions and design in the interest of technical advances.
25
Characteristics • Heating medium resistances
Pressure difference values D of accessories:
1. Accessories mounted on suction side
Component Type D
Mixed-air box MLK 5
Filter box (filter clean) FK 2
moderate filter clogging FK 7
Warmth channel interim piece (per m)
Fresh air inlet grille AG 5
Circulation suction adapter UA 2
Fresh air inlet hood ALH 4
2. Accessories mounted on pressure side
Component Type D
Air outlet shutter B 5
KA 1
Air outlet hood HG 4
Ceiling air outlet nozzle AD 10
We reserve the right to make changes to dimensions and design in the interest of technical advances.
26
REMKO PWW
PWW 80 ratings tables • Technical data
Type
Design
Speed rpm
Electrical connection
Frequency
Power input
Nominal current
Air capacity
Sound pressure level
Blow. range ceiling*max.
Blow. range wall max.
Heating medium conn.
Weight
Heating medium tL1 °C
50/40 °C
60/50 °C
70/50 °C
80/60 °C
90/70 °C
Volt Hz kW A m³/h dB(A) m m inch kg
- 15
- 10
- 5
+ 5
+ 10
+ 15 + 20
- 15
- 10
- 5
+ 5
+ 10
+ 15 + 20
- 15
- 10
- 5
+ 5
+ 10
+ 15 + 20
- 15
- 10
- 5
+ 5
+ 10
+ 15 + 20
- 15
- 10
- 5
+ 5
+ 10
+ 15 + 20
PWW 80-2
two-speed
880 670
3 x 400 3 x 400
50 50
0.42 0.28
0.76 0.46
5800 4400
55 49
8.5 6.5 25 19
R 1“ R 1“
44 44
kW tL2 °C kW tL2 °C
35.2 3 32.1 6
31.9 6 29.0 9
28.5 9 25.9 12
0
0
0
0
0
25.2 13 22.7 15
22.0 17 19.8 19
18.6 20 16.8 22
15.7 23 14.3 25
12.2 27 11.0 28
44.3 6 38.3 9
40.7 9 35.2 12
37.2 13 32.1 15
33.7 16 28.9 18
30.1 21 25.8 22
26.6 24 22.7 25
23.2 27 19.8 28
19.6 30 16.7 32
45.9 7 39.2 9
42.5 10 36.3 13
39.2 14 33.4 16
35.7 17 30.5 19
32.5 22 27.6 24
28.9 25 24.6 27
25.4 28 21.0 29
21.8 31 17.4 32
52.7 10 44.8 13
49.3 13 42.1 16
45.9 17 39.2 19
42.5 20 36.3 23
39.2 25 33.4 28
35.7 28 30.5 31
32.5 32 27.6 34
28.9 35 24.6 37
60.0 14 50.7 17
56.7 17 47.7 20
52.7 20 44.8 23
49.3 23 42.1 26
45.9 29 39.2 32
42.5 32 37.0 35
39.2 35 33.4 38
35.7 38 30.5 41
Air inlet temperature tL2 Air outlet temperature* with ceiling air outlet nozzle AD
t
L1
PWW 80-3
two-speed
880 670
3 x 400 3 x 400
50 50
0.42 0.28
0.76 0.46
5400 4300
55 49
8.0 6.0 23 18.5
R 1 ¼“ R 1 ¼“
47 47
kW tL2 °C kW tL2 °C
44.8 9 39.2 11
40.7 12 35.8 14
36.5 15 32.1 17
32.3 17 28.5 19
28.1 21 24.7 23
23.8 24 21.0 25
20.1 27 17.6 28
15.6 29 13.7 30
56.1 14 46.6 15
51.7 17 42.9 18
47.3 19 39.2 20
42.9 22 35.5 23
38.6 27 32.1 27
34.2 29 28.4 30
29.6 32 24.7 32
25.5 34 21.0 35
58.7 15 50.2 17
54.4 18 46.5 20
50.1 21 42.7 22
45.8 24 39.0 25
41.6 28 35.3 30
37.0 31 31.5 32
32.5 33 26.9 34
27.9 36 22.2 35
67.2 20 57.7 22
63.0 22 54.0 25
58.7 25 50.2 27
54.4 28 46.5 30
50.1 33 42.7 35
45.8 36 39.0 37
41.6 38 35.3 40
37.0 41 31.5 42
75.8 24 65.2 27
71.5 27 61.5 29
67.2 30 57.7 32
63.0 32 54.0 35
58.7 38 50.2 40
54.4 40 46.5 42
50.1 43 42.7 45
45.8 46 39.0 47
PWW 80-4
two-speed
880 6700
3 x 400 3 x 400
50 50
0.42 0.28
0.76 0.46
4730 3700
55 49
7.0 5.5
20.5 16
R 1 ¼“ R 1 ¼“
51 51
kW tL2 °C kW tL2 °C
58.0 21 49.1 24
52.6 22 44.4 37
47.1 24 39.7 47
41.7 26 35.1 37
36.3 29 30.6 40
30.8 30 26.0 39
26.0 32 22.2 40
20.1 33 17.1 40
72.7 27 58.4 28
67.0 29 53.7 30
61.2 31 49.0 31
55.5 32 44.3 33
49.8 36 39.6 37
44.0 38 34.9 38
38.3 39 30.5 40
32.6 41 25.9 41
74.2 28 63.1 32
68.7 30 58.4 33
63.2 32 53.7 35
57.7 34 49.0 36
52.3 38 44.2 41
46.6 39 39.5 42
40.9 41 33.9 42
35.3 42 28.4 43
85.2 35 72.5 39
79.7 36 67.8 40
74.2 38 63.1 42
68.7 40 58.4 43
63.2 45 53.7 48
57.7 46 49.0 50
52.3 48 44.2 51
46.6 49 39.5 52
91.0 38 77.6 43
85.8 40 73.2 44
80.6 42 68.7 46
75.6 44 64.3 48
70.4 48 59.5 51
65.3 50 55.3 53
60.1 52 50.8 54
55.0 54 46.4 56
We reserve the right to make changes to dimensions and design in the interest of technical advances.
27
Characteristics • Heating medium resistances
Pressure difference values D of accessories:
1. Accessories mounted on suction side
Component Type D
Mixed-air box MLK 5
Filter box (filter clean) FK 3
moderate filter clogging FK 7
Warmth channel interim piece (per m)
Fresh air inlet grille AG 4
Circulation suction adapter UA 2
Fresh air inlet hood ALH 4
2. Accessories mounted on pressure side
Component Type D
Air outlet shutter B 5
KA 1
Air outlet hood HG 4
Ceiling air outlet nozzle AD 9
We reserve the right to make changes to dimensions and design in the interest of technical advances.
28
REMKO PWW
PWW 100 ratings tables • Technical data
Type
Design
Speed
Electrical connection
Frequency
Power input
Nominal current
Air capacity
Sound pressure level
Blow. range ceiling*max.
Blow. range wall max.
Heating medium conn.
Weight
Heating medium
50/40 °C
60/50 °C
70/50 °C
80/60 °C
90/70 °C
rpm Volt Hz kW A m³/h dB(A) m m Inch kg tL1 °C
- 15
- 10
- 5 0
+ 5 + 10 + 15 + 20
- 15
- 10
- 5 0
+ 5 + 10 + 15 + 20
- 15
- 10
- 5 0
+ 5 + 10 + 15 + 20
- 15
- 10
- 5 0
+ 5 + 10 + 15 + 20
- 15
- 10
- 5 0
+ 5 + 10 + 15 + 20
PWW 100-2
two-speed
870 650
3 x 400 3 x 400
50 50
0.76 0.47
1.50 0.81
9050 7400
58 54
10.5 9.0 35 29.5
R 1 ¼“ R 1 ¼“
58 58
kW tL2 °C kW tL2 °C
53.2 2 50.1 5
48.6 6 45.7 8
43.8 9 40.9 11
38.9 12 36.2 14
34.0 17 31.6 18
28.9 20 27.0 21
23.9 23 22.3 24
18.9 27 17.7 27
66.6 5 59.3 7
61.4 9 54.7 10
56.2 12 50.0 14
51.4 16 45.5 17
46.2 20 40.8 22
41.1 24 36.2 25
35.9 27 31.6 28
30.5 30 27.0 31
67.3 6 59.6 7
62.1 9 54.9 10
56.9 12 50.1 14
51.6 16 45.4 17
46.4 20 40.7 21
41.2 24 35.9 25
36.1 27 31.2 28
30.9 30 26.4 31
77.6 9 69.2 11
72.7 12 64.5 14
67.3 16 59.6 17
62.1 19 54.9 20
56.9 24 50.1 25
51.6 27 45.4 28
46.4 30 40.7 31
41.2 34 35.9 35
88.2 12 78.7 14
82.8 15 73.9 17
77.6 19 69.2 21
72.6 22 64.5 24
67.3 27 59.6 29
62.1 31 54.9 32
56.9 34 50.1 35
51.6 37 45.4 38
tL1 Air inlet temperature tL2 Air outlet temperature* with ceiling air outlet nozzle AD
PWW 100-3
two-speed
870 650
3 x 400 3 x 400
50 50
0.76 0.47
1.50 0.81
8250 6620
58 54
10.0 8.0 32 26
R 1 ½“ R 1 ½“
60 60
kW tL2 °C kW tL2 °C
67.9 9 62.3 12
61.7 12 56.6 15
55.3 14 51.1 17
49.1 17 45.4 20
42.9 21 40.4 24
36.5 24 33.8 26
30.4 27 28.1 28
24.0 29 22.2 30
84.7 13 73.4 16
78.2 16 67.8 18
71.6 19 62.2 21
65.1 22 56.5 24
58.4 26 51.0 28
51.9 29 45.3 31
45.3 31 40.2 33
38.6 34 33.7 35
86.3 14 75.7 17
79.4 17 69.9 19
72.5 19 63.9 22
65.8 22 58.1 24
58.8 26 52.2 29
52.0 29 46.8 31
45.1 31 40.4 33
38.2 34 34.6 36
100.0 19 87.5 22
93.2 21 81.6 24
86.3 24 75.7 27
79.4 27 69.9 29
72.5 31 63.9 34
65.8 34 58.1 36
58.8 36 52.2 39
52.0 39 46.8 4
113.7 23 99.3 26
106.8 26 93.4 29
100.0 29 87.5 32
93.2 31 81.6 34
86.3 36 75.7 39
79.4 39 69.9 42
72.5 41 63.9 44
65.8 44 58.1 46
PWW 100-4
two-speed
870 650
3 x 400 3 x 400
50 50
0.76 0.47
1.50 0.81
7670 6180
59 55
9.0 7.0 30 25
R 1 ½“ R 1 ½“
68 68
kW tL2 °C kW tL2 °C
85.6 17 78.5 22
77.8 19 71.4 24
69.7 21 64.4 25
61.9 23 57.3 27
54.0 27 50.8 31
46.0 29 42.7 32
38.3 31 35.3 33
30.3 32 28.1 34
106.6 23 92.4 26
98.6 25 85.4 28
90.3 27 78.3 30
82.1 29 71.1 32
73.7 34 64.2 36
65.4 35 57.1 38
57.1 37 50.7 40
48.6 39 42.5 41
108.7 24 95.3 27
100.0 26 88.1 29
91.3 28 80.5 31
82.8 30 73.1 33
74.1 34 65.8 37
65.5 36 58.9 39
56.9 37 50.9 40
48.1 39 43.6 41
126.0 30 110.3 34
117.5 32 102.8 36
108.7 34 95.3 37
100.0 36 88.1 39
91.3 41 80.5 44
82.8 42 73.1 45
74.1 44 65.8 47
65.5 46 58.9 49
135.3 36 117.2 27
127.1 36 110.2 39
119.0 38 103.3 41
110.9 40 96.3 43
102.7 45 89.3 48
94.5 47 82.5 50
86.3 49 75.4 51
78.3 51 66.8 52
We reserve the right to make changes to dimensions and design in the interest of technical advances.
29
Characteristics • Heating medium resistances
Pressure difference values D of accessories:
1. Accessories mounted on suction side
Component Type D
Mixed-air box MLK 6
Filter box (filter clean) FK 3
moderate filter clogging FK 8
Warmth channel interim piece (per m)
Fresh air inlet grille AG 4
Circulation suction adapter UA 2
Fresh air inlet hood ALH 4
2. Accessories mounted on pressure side
Component Type D
Air outlet shutter B 6
KA 1
Air outlet hood HG 4
Ceiling air outlet nozzle AD 10
We reserve the right to make changes to dimensions and design in the interest of technical advances.
30
REMKO PWW
Calculation example and explanation
The heat outputs shown in the ratingtables are subject to variation as a result of:
Reduced air volumes with additionally mounted accessories such as (mixed-air box, filter box, air outlet nozzle, etc.). Observe pressure difference values!
Determination of heat output and air volume when using accessories:
Actual: Unit type PWW 80-3
with filter box FK with ceiling air outlet nozzle AD Heating medium PWW 90/70 Air inlet temperature t
= 15°C
L1
Required: Air volume V
Heat output Q Air outlet temperature t Heating medium resistance p
1. Determination of the air volume VL (m3/h)
The following data is provided in the ratings tables (page 30).
Air capacity V = 5400/4300 m Heat output Q = 50.1/42.7 kW Air outlet temp. t
this results in an air heating of
∆t = 28/30 K
The individual pressure difference values D (see page 31) are added:
Filter box FK 7 Air outlet nozzle AD 9
(m3/h)
L
L
L2
= 43/45°C
L2
(kw)
(°C)
W
(kPa)
3
/h
Total difference = 16
Solution from the diagram:
= 3400/2400 m3/h
V
L
We reserve the right to make changes to dimensions and design in the interest of technical advances.
31
Calculation example and explanation
2. Heat output Q
(kW)
L
In the ratio VL to air volume V (ratings table value), the heat output factor can be determi­ned from the “heat output factor correction” f
diagram.
Q
The heat output from the ratings table multiplied by the factor f
Q
results in the effective heat output
Q
(kW).
L
3. Air outlet temperature tL2 (°C)
For the calculation example, this results in:
Higher speed:
Air volume ratio =
Heat output correction factor f
VL 3400
V 5400
= 0.75
Q
= 0.63
Effective heat output QL = 50.1 x 0.75 = 37.6 kW
Lower speed:
V
= 2400
Air volume ratio =
Heat output correction factor f Effective heat output Q
L
V 4300
= 0,67
Q
= 42.7 x 0.67 = 28.6 kW
L
= 0.56
Solution: Heat output QL = 37.6/28.6 kW
For the calculation example, this results in:
From the ratio V
to air volume V
L
(ratings table value), the air hea­ting factor can be determined. The air heating from the ratings table (t
- tL1) multiplied by the
L2
air heating factor fL results in the effective air heating.
4. Heating medium resistance
Higher speed:
Air volume ratio 0.63 (see above) Air heating factor f Effective air heating
= 1.20
L
= 28°C x 1.20 = 33.6°C [34°C]
t
L
Air outlet temperature tL2 = 34 + 15 = 49°C
Lower speed:
Air volume ratio 0.56 (see above) Air heating factor f Effective air heating
= 1.25
L
= 30°C x 1.25 = 37.5°C [37°C]
t
L
Air outlet temperature tL2 = 37 + 15 = 52°C
Solution:
Air outlet temperature t
= 49/52°C
L2
The heating medium volume VW is calculated from:
Q
= 860 x (litre/h)
V
W
= 90 – 70 = 20 °C
t
W
= 37.6 (see solution under 2.))
Q
L
This results in: V
L
t
W
= 860 x = 1620 l/h
W
37.6 20
For the calculation example, given from the diagram (see Page 31) is the heating medium resistance for the unit type 80-3:
= 2.8 kPa
Dp
W
We reserve the right to make changes to dimensions and design in the interest of technical advances.
32
REMKO PWW
Planning • Calculation • Units
■
■
Planning and selection criteria
■
Total heat requirement of room to be heated.
■
Number of units necessary to cover the heat requirement and to also ensure sufficient fine heat and air distribution in the room. In any event, it is advantageous to use several smaller units in or­der to achieve a more favourable temperature distribution, lower air velocities and a lower noise level.
Required mode of operation (circulation, mixed-air or fresh air operation).
■
Mounting site (wall or ceiling).
■
Permissible sound pressurelevel.
■
Air inlet temperature in accessed areas (guide value = 35-40°C).
■
Circulated total air flow in relation to volume (guide value 2-3-fold air circulation).
Determination of the required heat output, fresh air volume and air outlet temperature
Mixed-air or fresh-air that utilise the required fresh air volumes for the number of air changes necessary for the room size.
■
Horizontal and vertical penetra­tion depth of air blast required to provide sufficient heat in the room.
Heat capacity:
Fresh air volume:
The heating capacity Q of the REMKO heater takes into account the following components:
1. Heat requirement QH of room to be heated. (Calculation according to DIN 4701 and 4108)
2. Heat requirement QAL to heat fresh air to room temperature.
QAL = VAL · cPL · fL· (tL2 - tL1) in [kW]
Q = Q
The required fresh air volume VAL de­pends on the system requirements and building regulations.
The following values are guide values and recommendations from the technical literature
Type of room Air changes x per hour Noise level dB(A)
Workshop, general 3 .... 6 70 .... 80
Warehouses 2 .... 4 60 .... 70
Textile industry 4 .... 20 about 90
Pickling shop, dye shop 5 .... 15 60 .... 70
Office rooms, small businesses 4 .... 8 about 45
Garages 4 .... 5 60 .... 70
Canteen kitchens 10 .... 30 50 .... 60
Large sales rooms, supermarkets 8 .... 10 about 60
Tennis halls 1 .... 2 45 .... 55
+ QAL in [kW]
H
VAL = X · L · W · H in [m3/h]
Air outlet temperatures: Note:
Extreme air outlet temperatures can produce uneven heat distribution and tempera­tures in the room. In order to provide comfortable conditions in accessed areas, we recommend the following max. air outlet temperatures:
The data shown in the ratings tables take into account the following values:
t
L1
f
L
We reserve the right to make changes to dimensions and design in the interest of technical advances.
Comfort range 30-40°C / Industrial range 35-45°C
-15 -10 0 +15 +20
[°C]
kg
1.37 1.34 1.29 1.23 1.20
[ ]
3
m
as well as the specific heat capacity CPL
of air with 1
sure of 1013 hPa
kWs
at constant air pres-
kg · K
33
Planning • Calculation • Units
Symbol Unit Explanation
Q kW Heating capacity of air heater
Q
H
Q
AL
Q
L
V m
V
L
V
AL
V
W
t
L1
t
L2
t
t
W
t
C
PL
ϕ
L
kW Heating requirement for room to be heated
kW Heat requirement to heat fresh air to room temperature
kW
m3/h
Effective heating capacity of air heater with mounted accessory components Air volume flow of air heater without mounted
3
/h
accessory components Effective air volume flow of air heater with mounted accessory components
m3/h Fresh air volume flow
l/h Heating medium volume flow
°C Air inlet temperature at air heater
°C Air outlet temperature at air heater
°C Air inlet/outlet temperature difference at air heater
°C Heating medium inlet/outlet temperature difference at air heater
°C
kWs
———
kg · K
kg
m
Effective air inlet/outlet temperature difference at air heater with mounted accessory components
Specific heat capacity of air at constant pressure
Dry air density
3
Q = QH + Q
AL
QAL = VAL · CPL ·
VL = V · f
V
VAL = X · B · L
860 · Q
VW =
∆t = t
t
W
t
L
1 ———
– t
L2
= tW1 – t
=
t · f
kWs
kg · K
t
W
L1
W2
L
t
L m Length of room to be heated
W m Width of room to be heated
H m Height of room to be heated
X 1/h Number of air changes in room to be heated
f
Q
f
V
f
L
P
W
P
ST
- Heat output factor
- Air capacity ratio
- Air heating factor
kPa Heating medium resistance (pressure loss on water-side)
Pa Static pressure difference with mounted accessory components
D - Pressure difference value with mounted accessory components
We reserve the right to make changes to dimensions and design in the interest of technical advances.
fQ = QL / Q
fV = VL / V
34
REMKO PWW
Unit dimensions
A
R
E
V
F
G
G
V = Water inlet (flow)
R = Water outlet (return)
B
98
167
C
D
The water inlet (flow) is always at the “BOTTOM.
Even if the units are turned during installation and connected from the other side.
Dim.
in
mm
A 560 640 800 880
B 440 515 630 740
C 360 360 360 390
D 403 406 412 452
E 344 419 534 644
F 80 80 80 80
G 45 45 45 45
Dim.
in
Inch
V R ¾“ R 1“ R 1¼“ R ¾“ R 1“ R 1¼“ R 1“ R 1¼“ R 1¼“ R 1¼“ R 1½“ R 1½“
R R ¾“ R 1“ R 1¼“ R ¾“ R 1“ R 1¼“ R 1“ R 1¼“ R 1¼“ R 1¼“ R 1½“ R 1½“
PWW 30 PWW 50 PWW 80 PWW 100
30-2 30-3 30-4 50-2 50-3 50-4 80-2 80-3 80-4 100-2 100-3 100-4
Unit type
Unit type
We reserve the right to make changes to dimensions and design in the interest of technical advances.
35
Technical data
Series PWW 30-2 PWW 30-3 PWW 30-4 PWW 50-5 PWW 50-3 PWW 50-4
Elec. connection V 400/3~N 400/3~N 400/3~N 400/3~N 400/3~N 400/3~N
Frequency
Power input
HZ 50 50 50 50 50 50
kW 0.13/0.10 0.13/0.10 0.13/0.10 0.26/0.18 0.26/0.18 0.26/0.18
Nominal current A 0.26/0.16 0.26/0.16 0.26/0.16 0.52/0.29 0.52/0.29 0.52/0.29
Speed
Air capacity
Sound press. level
Heating medium conn.
Heating medium
Operat. press. max.
rpm 1340/1040 1340/1040 1340/1040 1360/1020 1360/1020 1360/1020
3
/h 2250/1850 2050/1640 1850/1500 3800/3180 3400/2870 3150/2770
m
1)
dB(A) 52/46 53/48 55/49 55/50 55/51 58/54
Inch R ¾“ R 1“ R 1¼“ R ¼“ R 1“ R 1¼“
Pumped warm water or pumped hot water up to maximum 130°C
bar 16 16 16 16 16 16
Weight kg 24 26 27 31 34 36
Series PWW 80-2 PWW 80-3 PWW 80-4 PWW 100-2 PWW 100-3 PWW 100-4
Elec. connection
Frequency
Power input
Nominal current
Speed
Air capacity
Sound press. level
1)
Heating medium conn.
V
HZ
kW
A
rpm
m
dB(A)
Inch
400/3~N 400/3~N 400/3~N 400/3~N 400/3~N 400/3~N
50 50 50 50 50 50
0.42/0.28 0.42/0.28 0.42/0.28 0.76/0.47 0.76/0.47 0.76/0.47
0.76/0.46 0.76/0.46 0.76/0.46 1.50/0.81 1.50/0.81 1.50/0.81
880/670 880/670 880/670 870/650 870/650 870/650
3
5800/440 5400/4300 4730/3700 9050/7400 8250/6620 7670/6180
/h
55/49 55/49 55/49 58/54 58/54 58/54
R 1“ R 1¼“ R 1¼“ R 1¼“ R 1½“ R 1½“
Heating medium Pumped warm water or pumped hot water up to maximum 130°C
Operat. press. max.
Weight
1)
Measurement at a distance of 5m, volume of measurable space 800m 3, average reverberation time 1.4s
We reserve the right to make changes to dimensions and design in the interest of technical advances.
bar 16 16 16 16 16 16
kg 44 47 51 58 60 68
REMKO EUROPE-WIDE
… and somewhere near you!
Take advantage of our experience and consulting services
Consulting
Through intensive training, we ensu­re that the expert knowledge of our consultants is always up-to-date. This has given us the reputation of being more than just a good, reliable supplier: REMKO, a partner, that helps solve problems.
Sales
REMKO not only provides an extensive sales network in Germany and abroad, but also unusually highly qualified sales experts. REMKO sales representatives are more than just salespeople: they are also customer consultants in the area of air conditioning and heating technology.
Customer service
Our units operate precisely and reli­ably. If a fault should occur, REMKO Customer Service is there to help you. Our extensive network of experienced specialised dealers guarantees you a fast and reliable service.
REMKO GmbH & Co. KG Air Conditioning and Heating Technology
Im Seelenkamp 12 · D-32791 Lage P.O. Box 1827 ·D-32777 Lage Telephone +49 52 32 606-0 Fax +49 5232 606-2 60 E-mail info@remko.de Internet www.remko.de
Subject to technical changes, errors and omissions excepted!
Loading...