REMKO PWL User Manual

REMKO PWL
Ceiling-mounted air unit Heating/Cooling
Operation · Technology · Spare parts
Edition GB – Vo6
Contents
Safety information
Unit description
Mounting the unit
Mounting examples
Electrical connection
Hydraulic connection
Commissioning
Decommissioning
Care and maintenance
Repair
Fan motor
Condensate pump
4
4
5
6
7
8
8
9
10
10
11
12
12
Unit dimensions
Rating tables/Technical data PWL 101-103
Rating tables/Technical data PWL 201-203
Rating tables/Technical data PWL 301-303
Intended use
Customer service and warranty
Environmental protection and recycling
Exploded view
Spare parts list
Legend/Operating limits
Technical data
Carefully read these operating instructions before commissioning/ using the units!
13
14
16
18
20
20
20
21
21
22
23
Made by REMKO
These instructions are part of the unit and must always be kept near to the site of installation or at the unit.
We reserve the right to make changes; no liability for errors and misprints!
3
REMKO PWL
Planning information
For an optimal room temperature, several basic rules must be follo­wed for room heating and cooling planning.
Heating mode
The following data is required for room heating planning:
Room heat demand
QH (kW)
Basic room dimensions
(length, width, height)
Required air change
Required room temperature
Required heating medium tem-
perature for flow and return
The air inlet temperature of the units should not be below 34°C and not above 42°C. At an outlet temperature below 34°C, there is a risk of unpleasant, cool draughts in the area of workplaces.
Cooling mode
The following data is required for room cooling planning:
Room cooling load
Qk (kW)
Basic room dimensions
(length, width, height)
Required room temperature and
possible relative humidity
Required cooling medium tem-
peratures for flow and return
To avoid unpleasant draughts at workplaces, the air outlet tem­perature in cooling mode should be maximum 6 – 8 K below the ambient temperature.
An excessive temperature dif­ference (> 8 K) can lead to the formation of unpleasant “cold air
zones”.
The circulated total air volume of the units per hour should be about 4 to 5 times the room volume.
Safety information
The units were subjected to ex­tensive material, functional and quality inspections and tests prior to delivery.
The units can however constitute a hazard if used improperly by untrained persons or not for the intended purpose.
Always observe the following safe­ty information:
The locally applicable building
regulations must be observed.
The operator is responsible for
correct installation of the units, correct electrical installation and safe operation of the units.
The units must be installed
and operated in a manner that excludes any risk to persons through radiated heat.
The units must only be attached
to constructions or ceilings with sufficient load bearing capacity.
Attachment must take place
using suitable anchors to be attached to the unit.
If the outlet temperature is abo- ve 42°C, an increased upcurrent of hot air will occur in the ceiling area. The range of the hot air current is reduced and the air in the room is inadequately penetrated by the hot air current and intermixed.
Undesired “cold air zones“ form in the room, and in contrast, an excessive cushion of hot air forms in the ceiling area. This causes unnecessary heat losses.
4
With inadequate air circulation volume, the required room climate is achieved very slowly and with delay.
An excessive air circulation volume is preferable since the system is able to respond more dynamically and effectively.
The air circulation volume can be increased using external aids (e.g. ceiling fans).
Only trained specialists may
install and connect the heating medium, establish electrical con­nections and carry out mainte­nance.
The units must not be installed,
mounted and operated in loca­tions subject to fire and explosi­on hazards or exposed to dust­laden/aggressive atmospheres.
The units must be installed out-
side traffic zones, e.g. also the operating areas of cranes.
Unit description
The units must only be operated
in a completely assembled and mounted condition.
The units must only be opera-
ted within the specified capacity limits and with the approved operating media.
Safeguards, e.g. barriers must
not be removed or rendered inoperational.
The units must only be operated
within the specified capacity limits and with the approved operating media.
The air intake grilles must
always be kept free of dirt and loose objects and the air outlet must not be closed.
Never insert foreign objects into
the unit.
The units must not be exposed
to a direct jet of water.
Do not operate the units in wet
areas with high humidity (e.g. car wash).
All electric cables of the units
must be protected against da­mage e.g. animals, etc.
NOTE
Perfect functioning of the units is only ensured when the flow temperature at the unit inlet and the pump capacity cor­respond to the selected unit classification.
These units are stationary, indirect­ly recirculated air cooling/heating units with copper/aluminium fin heat exchangers for connection to a pumped cold/ hot water system up to max. 90°C.
The units are in an exclusive de­sign, compact, universal and are easy to install and service.
The units are suitable for heating/ cooling rooms with high or low ceilings and where special impor­tance is attached to exclusivity.
For example in large rooms such as:
Exhibition halls
Sales rooms
Shopping centres
Business premises
Warehouses
Production halls
Foremen’s offices
Large entrance areas
The units must be mounted hori­zontally on ceilings or roof struc­tures.
The units are fitted with an aero­dynamic, powerful two-speed axial flow fan with 400V/50Hz external rotor motor as standard.
The inner supporting unit con­struction is made of galvanised sheet steel. The heat exchangers have copper tubes with aluminium fins. For removal of the produced condensate in cooling operation, a ready to connect condensate pump is provided.
For an optimal air flow, individually adjustable louvres are provided at the top of the housing and fully adjustable louvre segments are provided at the bottom.
The air discharge direction (hori­zontal or vertical) can be individu­ally adjusted to suit the local requi­rements by changing the direction of rotation of the fan.
The plastic housing can be deta­ched completely from the sup­porting lower housing part by removing the securing clip. The integrated securing strips prevent the cover from falling.
The plastic housing of the units is made of self-extinguishing material (fire class V-0).
The heaters comply with the basic health and safety requirements of the pertinent EU regulations and are easy to operate.
5
REMKO PWL
Mounting the unit
The following information must be observed for safe unit installation:
The units must be arranged so
that accessed areas and work­places are not located in the direct air stream.
The units must only be moun-
ted on ceilings or roof struc­tures with sufficient load bearing capacity.
The units must be mounted
horizontally and free of stress.
The heat exchangers must be
connected so that no vibrations can be transferred from the unit to the pipe system or vice versa.
Suitable connection fittings,
shut-off valves, vent valves, etc. must be mounted locally.
Ensure that no persons are standing under suspended loads during instal­lation! For marking the points of attachment, please use the supplied template in the packaging. It must be ensured that sufficient space is available between the unit and ceiling for the media connections.
Fixed bracket (standard) Adjustable bracket (option)
The adjustable brackets (option) can be individually aligned for adjustment.
Maximum mounting heights and operating limits
The maximum mounting heights depend on the maximum range and direction.
Heating mode
For mounting on ceilings and
in rooms with low and high ceilings, the maximum moun­ting heights of the unit must be observed.
Before connecting the units to
an existing hot water heating system, the boiler and pump must be checked for sufficient capacity.
For maintenance and repairs, a
suitable repair switch (accesso­ry) must be fitted.
The gap between the fan im-
peller and unit housing must be checked for the same distance.
The maximum mounting heights and ranges (at 0.2 m/s) apply to an air outlet temperature of 20K over the room temperature and ideal condi­tions of the primary air flow.
PWL
101-3
201-3
301-3
Mounting height and range
in m „vertical“ blowing direction
3.8 / range 2.3 2.5 / range 3.4
5.5 / range 4.0 3.8 / range 7.9
7.0 / range 5.5 5.7 / range 7.0
max. mounting height
Cooling mode
The maximum ranges apply to an air outlet temperature of 8K below room temperature and ideal prima­ry air flow conditions.
1)
Mounting height and range
in m „horizontal“ blowing direction
max. range
PWL max. range in mm
1)
101-3
201-3
301-3
Blowing direction horizontal +vertical
4.0
10.0
9.1
1)
1)
6
We reserve the right to make dimensional and design changes in the interest of technical advances.
Mounting examples
The unit are designed for use in rooms with high and low ceilings. The direction of the air flow can be individually adjusted to the suit, the building conditions or personal requirements by changing the di­rection of rotation of the fan (pole reversal).
In this way, the air flow, when using the units in rooms with low ceilings, can be controlled horizon­tally by means of the individually adjustable air louvres located at the top of the housing. This prevents persons being expo­sed to a direct air stream.
Heating mode
Rooms with low ceilings; horizontal
blowing direction
Cooling mode
Rooms with low ceilings; horizontal
blowing direction
Rooms with high ceilings; vertical
blowing direction
Rooms with high ceilings; vertical
Rooms with high ceilings; vertical
blowing direction
blowing direction
Heating and cooling combination options
The triangular shape of the units offers numerous individual mounting arrangements, so that even corner areas
are taken into account.
Window frontage
Window frontage
We reserve the right to make dimensional and design changes in the interest of technical advances.
7
REMKO PWL
Electrical connection
Electrical connections of the unit must only be established by autho­rised specialists in compliance with the applicable regulations of the local electricity supply company as well as the VDE installation requi­rements relating to the unit.
ATTENTION
Failure to observe the pertinent requirements, operating inst­ructions and electrical wiring diagrams relating to the unit can give rise to malfunctions with consequential damage.
This will invalidate the war­ranty!
Connection of the units
The units are fitted with two­speed, 400V three-phase axial flow fans as standard. Speed selection takes place with appropriate control units (accesso­ry). Changes in direction take place via a pole changing switch or special control unit (accessory).
Motor protection is provided via integrated thermal contacts in conjunction with a suitable control unit (accessory).
Connection of the three-phase motors to the respective control units takes place via the associated electrical wiring diagrams.
Connection of several units
If necessary, several units (also different sizes) can be operated parallel via a control unit (accesso­ry).
The total capacity of the con­nected units must not exceed the maximum switching capacity of the respective control unit.
For thermal motor protection, the thermal contacts of all motors must be connected in series. See separate wiring diagrams.
Only one external control device (thermostat, day/night control, etc.) can always be connected per control unit.
Terminals in the unit
5 678 9 10 11 12 13 14 15 16 17 18 19 20 21 22
1 3 42
W2 U2V2 TK PE
U1V1 W1 TK PE PE N L13 2
N
1
CÖS
Kondensatpumpe
Potenzialfreier Alarmkontakt
Kondensatpumpe
für Kühlbetrieb
Kondensatpumpe
Fuse protection in the supply to the control unit must be in compli­ance with the applicable regulati­ons.
The connections in the terminal box must be connected to the respective control unit (accessory).
Hydraulic connection
Connection to the local hy­draulic system
Prior to connection to the local hydraulic system, it must be en­sured that the respective capacity requirements of the unit can be provided at all times.
Connection of the unit on the
water side must take place local­ly via suitable pipe fittings and shut-off valves in the flow and return.
The use of compensators and automatic venting devices is recommended!
The connection side at the top
and the flow and return can be connected as required.
The pipe connection thread sizes
is R 1“ internal thread.
The fin heat exchangers must be
thoroughly vented after installa­tion.
Air cushions in the heat exchan­ger will reduce the heating or cooling capacity!
Water outlet
Water inlet
ATTENTION
When the fan is stationary, the hydraulic supply must be simultaneously interrupted.
8
ATTENTION
Only suitably trained specialists may establish electrical con­nections.
NOTE
In order to prevent damage due to twisting of the con­necting pipes, a suitable tool must be used to prevent the connecting pipes rotating while tightening the screwed connections.
Commissioning
Draining if there is a risk of frost
It is not possible to statically drain the fin heat exchanger completely in an installed condition. If necessary, draining is only possi­ble using compressed air.
Important information about frost protection
To prevent frost damage, anti-frost protection must be provided at temperatures below 0°C.
Where systems in rooms at risk from frost are not used for ex­tended periods, under no circum­stances must “only” water be present in the heat exchanger.
In such cases, a suitable antifreeze agent must be added to the hea­ting medium (water) in a mixing ratio that is adequate for the place of use. The hydraulic capacity loss must also be taken into account.
Before using for the first time
ATTENTION
Commissioning can only take place when it is ensured that mounting and electrical instal­lation has been carried out in compliance with the pertinent requirements of the EC Direc­tives.
Correct mechanical installation
must be verified.
Correct connection to the local
heating system must be veri­fied.
It must be ensured that hot
surfaces are protected against accidental contact.
It must be verified that the
electrical wiring of the units has been carried out in compliance with the applicable directives and standards using the sup­plied wiring diagrams.
It should be noted that when
using a speed control (acces­sory) the power of the control unit must correspond to the total power of the connected motors.
It must be ensured that all air
inlets and outlets are open.
Air flow
The louvres on the side of the top part of the housing (horizontal blowing or suction) can be adju­sted in 5 degree stages.
Venting
Screwed connections
Water outlet
Water inlet
Draining the heating/cooling medium
ATTENTION
Frost damage to the fin heat exchanger does not fall under the warranty!
The fan space as well as the
inlet and outlet area must be checked for the presence of foreign bodies.
The fan must be checked for
smooth operation.
Switch on the power to the
control unit (accessory) and switch on the unit via the con­trol switch of the control unit.
The direction of rotation of the
fan must be checked
The direction of rotation can
be changed by interchanging two phases or using an exter­nal control unit (accessory).
The three louvre segments in the bottom part of the housing (ver­tical blowing or suction) can be individually adjusted via a control.
9
REMKO PWL
Care and maintenance
During initial commissioning
During initial commissioning, all regulating, control and safety devices must be checked for their proper functioning and correct adjustment.
The power consumption of the
fan must be measured.
The nominal current must not exceed the values on the rating plate at the respective opera­ting speeds.
Check the motor protection
function of the fan.
Check the complete system for
de-energised installation and possible vibrations.
Check the heating/cooling
medium supply pipes for correct connection, tightness and insu­lation.
Decommissioning
Set the switch of the respective control unit to the „Off“ or „0“ position.
Precautions for extended periods of non-use
Disconnect the electrical con-
nection in all poles.
Shut-off the hydraulic connec-
tion.
Where there is a risk of frost,
the entire system must be drained if no suitable antifreeze agent has been added to the heating medium (water).
(See also page 9)
The units generally require no maintenance. The units and fin exchanger surfaces must be vi­sually inspected every six months and before the start of the heating period. In dust-laden environments, the units must be inspected at shorter intervals.
For this purpose, the cover of the unit must be detached from the supporting part of the unit by re­moving the 3 securing clips at the corners. For inspection purposes, the cover must be held under the supporting part with the aid of holding straps. The cover can be removed com­pletely from the unit if required by loosening the strap adjuster on the holding straps.
During removal, it must be en­sured that the suction hose and condensate pump sensor are also disconnected from the supporting part.
Securing clip
Important precautions to be taken prior to all maintenance
The units must be disconnected
from the supply in all poles and locked to prevent unauthorised reconnection.
ATTENTION
It does not suffice to switch off the unit only via the switch!
It must be ensured that no more
condensate is produced as in this case the condensate pump is also disconnected from the supply and no longer operatio­nal.
Wait for the fan to stop.
Shut-off the water circuit and
lock to prevent unauthorised opening.
Allow the fin heat exchanger to
cool down.
Cleaning the units
The surfaces of the units must
be cleaned only dry or with a moist cloth and a small amount of soap solution if necessary.
Under no circumstances use
high-pressure cleaners or steam jet equipment to clean the mounted unit.
Do not use caustic cleaning
agents or those containing solvents.
Only suitable cleaning agents
must be used even to remove heavy fouling.
Clean all air inlets and air outlet
louvres.
Clean the fan impeller. If ne-
cessary, remove the motor or protection grille.
Clean the heat exchanger fins
either by blowing out, suction or with a soft brush.
10
If the fin exchanger surface is
covered with grease or sooty particles, the exchanger ele­ment can be removed and cleaned with a steam-jet degre­aser using low pressure and a suitable cleaning agent.
Remove heavy fouling on the
fan and aluminium fins with a soap solution.
Clean the condensate tank in
the unit housing to remove dirt deposits.
To ensure complete drainage of the condensate tank, the suction opening of the condensate hose must be fixed at the lowest point of the cover. The condensate sensor must be arranged slightly above the suction opening.
Bottom edge of sensor = top edge of suction opening.
Routing must take place as show in the following diagram.
F = Sensor cable K = Condensate hose (internal ø 6)
Repair
NOTE
Only authorised specialists may undertake repairs and maintenance.
Fan replacement
1. Remove the cover of the unit. (See care and maintenance)
2. Disconnect the electrical con­nection of the fan.
3. Remove the protection grille with fan from the housing.
4. Carefully refit the new fan in reverse order.
5. Check the fan impeller for smooth operation and freedom of movement with respect to the fan housing.
6. Re-establish the electrical con­nection of the motor correctly.
ATTENTION
Prior to carrying out mainte­nance or repairs, the unit must always be disconnected from the mains supply and locked to prevent unauthorised recon­nection.
Replacing the fin heat exchanger
1. Remove the cover of the unit completely. (See care and maintenance)
2. Disconnect the electrical con-
nection of the fan.
3. Disconnect the hydraulic con-
nection.
4. Remove the bottom support plate (6 screws).
5. Remove the support plate with fin exchanger downwards.
6. Carefully re-install the replace­ment heat exchanger and all further components in reverse order.
ATTENTION
After carrying out all work on the units, an electrical safety test must be carried out in accordance with VDE 0701.
F
Recommended maintenance interval in normal unit operation
Inspection and possible cleaning of the condensate tank Every six months Inspection and possible cleaning of the condensate drain Every six months Functional check of the condensate pump and alarm sensor Every six months Inspection and possible cleaning of the air grille Annually Inspection of the electrical connections and earthing Annually Cleaning of the fin exchanger Annually Inspection of the fan for smooth operation and function
K
Annually
11
REMKO PWL
hohe Drehzahl
- Schaltung
niedere Drehzahl
Y - Schaltung
TK
W2 U2 V2
TK
U1
V1 W1
PE
L1 L2 L3
TK W2 U2 V2
TK
U1
V1 W1
PE
L1 L2 L3
Fan motor 400V, two-speed
Wiring Diagram
Standard units: /Y switching and thermal contacts.
Condensate pump
The compact condensate pump must pump out the produced con­densate in cooling operation. The pump is a self-priming rotary diaphragm pump.
The condensate is pumped out via a flexible PVC condensate hose with an internal diameter of 6 mm.
Safety information:
Disconnect the power supply
before connecting, removing or replacing the condensate pump.
Do not use the condensate
pump for pumping flammable and potentially explosive liquids such as petrol, heating oil, sol­vents, etc.
The condensate pump must
only be used for pumping liquids to which the pump ma­terial is resistant.
Do not use the condensate
pump in potentially explosive atmospheres.
Electrical connection must take
place as shown in the wiring diagram. Ensure that the power supply is earthed in compliance with the statutory require­ments.
Ensure that the condensate
pump is not installed higher than 7 m (maximum suction head) above the drip tray outlet and not deeper than 20 m (maximum delivery head) be­low the top of the condensate drain.
NOTE
Prior to using the system, the function of the condensate pump must be tested with respect to the delivery head. Fill the condensate tank of the unit housing with water and test the function of the pump. Ensure that the pump switches off after pumping.
ATTENTION
Electrical connection of the unit must be carried out by authorised specialists as de­fined in DIN EN 60335-1 and VDE 0116.
NOTE
All electrical wiring terminals must be checked for tightness and retightened if necessary.
Pump control
Power supply: 230 V/50 Hz Brown wire: L Blue wire: N Green/yellow wire: PE The mains connection of the pump must be protected with a 1 A mini­ature fuse.
Floating alarm contact:
black: common wire
yellow: contact closed in operation/open on
alarm
red: contact open in operation/closed on
alarm
Performance diagram
20
16
12
8
Förderhöhe in Meter
4
0
0 10 20 30 40 50 60
Liter pro Stunde
Max. flow rate: 50 l/h Max. delivery head: 20 m Max. suction head: 7 m Connection internal Ø: 6 mm Temperature protection at: 130 °C
12
We reserve the right to make changes to dimensions and design in the interest of technological advances.
Unit dimensions
„A“
M 8
Hydraulic connection R 1“
D
B
Condensate hose
A
90
B
NOTE
The flow and return can be connected as required.
80
B
16
{
90
C
Condensate pump
44
217
H
View „A“
Dimen-
sions
A 985 mm 1084 mm 1178 mm
B 632 mm 963 mm 1043 mm
C 229 mm 229 mm 229 mm
D 989 mm 1073 mm 1160 mm
H 465 mm 485 mm 504 mm
Mounting distance between unit and ceiling minimum 80 mm!
PWL 101-103 HK PWL 201-203 HK PWL 301-303 HK
We reserve the right to make changes to dimensions and design in the interest of technological advances.
13
REMKO PWL
PWL 101-103 - Heating • Rating tables • Technical Data
Type PWL 101-H PWL 102-H PWL 103-H
Type 2-speed 2-speed 2-speed
Speed rpm 920 750 920 750 920 750
Electrical connection V 400/3~N
Frequency Hz 50
Power consumption kW 0.1/0.07
Nominal current A 0.26/0.13
Air capacity m³/h 2030 1685 1960 1610 1885 1530
Sound pressure level1)dB (A) 56 47 56 47 56 47
max. mounting height m 2.8 2.7 2.5
max. range
Hydraulic connection Inch R 1“ R 1“ R 1“
Water volume l 1.0 1.6 2.5
Weight kg 31 35 38
PWW heating medium
50 / 40 °C
60 / 50 °C
70 / 50 °C
80 / 60 °C
90 / 70 °C
2)
m 3.4 3.2 3.0
t
L1
°C
kW
t
L2
°C
kW
t °C
L2
kW
t °C
L2
kW
t °C
L2
kW
t °C
L2
kW
0 9.2 13 8.2 13 14.7 21 13.3 23 19.0 28 16.4 30
5 8.0 16 7.2 17 12.9 24 11.7 26 16.7 30 14.4 32 10 6.9 20 6.2 21 11.1 26 10.1 28 14.4 32 12.5 33 15 5.8 23 5.2 24 9.4 29 8.6 31 12.2 34 10.5 35 20 4.7 27 4.2 27 7.6 32 7.1 33 10.0 36 8.7 37
0 11.4 16 10.2 17 18.2 26 16.4 28 23.4 34 20.2 37
5 10.2 19 9.1 20 16.4 29 14.8 31 21.0 37 18.2 39 10 9.1 23 8.1 24 14.6 31 13.2 33 18.7 39 16.2 40 15 8.0 27 7.1 27 12.8 34 11.6 36 16.4 41 14.2 42 20 6.9 30 6.1 31 11.0 37 10.0 39 14.2 45 12.3 44
0 12.0 16 10.7 18 19.5 28 17.8 31 25.4 37 22.0 40
5 10.8 20 9.7 21 17.6 30 16.1 33 23.0 39 19.9 42 10 9.7 24 8.6 25 15.8 33 14.5 36 20.6 41 17.9 44 15 8.5 27 7.6 28 14.0 36 12.9 38 18.3 43 15.9 45 20 7.4 31 6.6 32 12.2 39 11.3 41 16.0 45 13.9 47
0 14.3 20 12.7 21 23.1 33 20.9 36 29.9 44 25.8 47
5 13.1 23 11.7 25 21.2 36 19.2 39 27.4 46 23.7 49 10 11.9 27 10.6 28 19.3 38 17.6 41 25.0 48 21.7 51 15 10.8 31 9.6 32 17.5 41 15.9 44 22.7 50 19.6 52 20 9.6 34 8.6 35 15.7 44 14.3 46 20.4 52 17.6 54
0 16.5 23 14.7 24 26.7 38 24.1 41 34.4 51 29.7 54
5 15.3 26 13.7 28 24.7 41 22.3 44 31.9 53 27.5 56 10 14.1 30 12.6 32 22.8 43 20.6 47 29.4 55 25.4 58 15 13.0 34 11.6 35 21.0 46 19.0 49 27.0 57 23.3 60 20 11.8 37 10.5 39 19.1 49 17.3 52 24.7 59 21.3 61
t °C
L2
tL1 = air inlet temperature/tL2 = air outlet temperature
2)
at t 20 K (difference in temperature between air inlet and air outlet)
14
We reserve the right to make dimensional and design changes in the interest of technical advances.
Operation with range restriction
PWL 101-103 - Cooling • Rating tables • Technical Data
Type PWL 101-HK PWL 102-HK PWL 103-HK
Type 2-speed 2-speed 2-speed
Speed
Electrical connection
Frequency
Power consumption
Nominal current
Air capacity
Sound pressure level
Hydraulic connection
Water volume
Condensate max. l/h 2.8 2.6 4.3 4.1 6.3 5.7
Weight
PKW coolant
4 / 8 °C
6 / 10 °C
8 / 14 °C
10 / 16 °C
12 / 18 °C
rpm 920 750 920 750 920 750
400/3~N
Hz 50
kW 0.1/0.07
A 0.26/0.13
m³/h 2030 1685 1960 1610 1885 1530
1)
dB (A) 56 47 56 47 56 47
Inch R 1“ R 1“ R 1“
l 1.0 1.6 2.5
kg 31 35 38
t
L1/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
24/60 5.0 19/72 7.1 19/73 7.9 16/80 7.1 16/82 10.6 14/87 9.3 13/89 26/50 5.1 21/63 4.6 20/64 8.0 17/74 7.2 17/75 10.7 14/82 9.4 13/84 28/45 5.5 22/59 5.0 22/60 8.6 18/71 7.7 17/72 11.5 15/79 10.0 14/82 30/40 5.8 23/55 5.3 23/56 9.1 19/67 8.2 18/69 12.2 16/78 10.7 15/79 32/40 6.7 25/55 6.1 24/56 10.5 20/67 9.4 19/69 13.9 16/77 12.2 15/80
24/60 4.2 20/72 3.8 20/72 6.6 17/80 6.0 17/81 9.1 15/87 7.9 14/88 26/50 5.2 23/63 3.9 21/64 6.7 18/74 6.0 18/75 9.1 15/82 8.0 15/84 28/45 4.7 22/59 4.2 22/60 7.3 19/70 7.0 19/69 9.9 16/79 8.7 15/81 30/40 5.0 24/54 4.5 23/55 7.8 20/67 7.0 19/69 10.5 17/77 9.3 16/79 32/40 5.9 25/55 5.3 25/56 9.2 21/67 8.3 20/69 12.3 18/77 10.8 16/79
24/60 2.5 21/71 2.3 21/72 4.1 19/80 3.7 18/81 5.9 17/86 5.3 16/88 26/50 2.6 22/63 2.3 22/64 4.2 20/74 3.8 19/75 6.0 17/82 5.3 17/83 28/45 3.1 23/59 2.7 23/60 4.9 20/71 4.3 20/72 6.8 17/82 6.1 17/81 30/40 3.5 25/54 3.1 24/56 5.6 21/67 4.8 21/69 7.5 18/77 6.6 18/79 32/40 4.2 26/55 3.8 26/56 6.7 23/67 6.0 22/69 9.3 19/77 8.2 19/79
24/60 1.8 21/71 1.6 21/72 3.0 19/80 2.7 19/81 4.0 18/86 3.5 18/88 26/50 2.2 23/61 2.0 22/62 3.7 20/70 3.2 20/72 4.9 18/81 4.3 17/84 28/45 2.7 24/57 2.4 24/58 4.3 21/67 3.8 21/69 5.7 19/79 4.9 18/82 30/40 3.1 25/52 2.7 25/53 4.9 22/63 4.4 22/65 6.5 19/75 5.6 19/79 32/40 3.5 27/54 3.1 26/55 5.6 23/67 4.9 23/69 7.4 20/77 6.6 20/79
24/60 1.4 22/68 1.3 22/69 2.4 20/79 2.1 20/76 3.3 19/83 2.9 18/85 26/50 1.8 23/59 1.6 23/60 3.1 21/66 2.7 21/68 4.1 19/75 3.6 19/77 28/45 2.3 25/55 2.0 24/56 3.7 22/63 3.3 22/65 4.9 20/72 4.3 19/75 30/40 2.7 26/51 2.4 26/51 4.3 23/60 3.8 23/61 5.7 21/70 4.9 20/72 32/40 3.1 27/52 2.7 27/53 4.9 24/63 4.4 24/65 6.5 21/75 5.6 21/78
t
L2/r.H.
°C/%
tL1 = air inlet temperature/ tL2 = air outlet temperature
1)
LpA 1m, noise measurement DIN 45635 - 01 - CATEGORY 3
We reserve the right to make dimensional and design changes in the interest of technical advances.
15
REMKO PWL
PWL 201-203 - Heating • Rating tables • Technical Data
Type PWL 201-H PWL 202-H PWL 203-H
Type 2-speed 2-speed 2-speed
Speed rpm 920 750 920 750 920 750
Electrical connection V 400/3~N
Frequency Hz 50
Power consumption kW 0.28/0.18
Nominal current A 0.67/0.37
Air capacity m³/h 3110 2580 2900 2400 2850 2350
Sound pressure level1)dB (A) 61 53 61 56 61 56
max. mounting height m 5.5 5.3 5.2
max. range 2) m 7.9 5.8 5.0
Hydraulic connection Inch R 1“ R 1“ R 1“
Water volume l 1.0 1.8 2.9
Weight kg 32 35 38
PWW heating medium
t
°C
L1
kW
0 11.4 10 10.2 11 20.1 19 17.9 21 26.0 25 22.8 27 5 9.8 14 8.8 15 17.6 22 15.7 23 22.8 28 20.0 29
50 / 40 °C
10 8.3 18 7.5 18 15.2 25 13.5 26 19.6 30 17.3 31
15 6.9 22 6.2 22 12.8 28 11.4 29 16.5 32 14.5 33
20 5.4 25 4.9 26 11.0 31 9.3 32 13.5 34 11.9 35
0 14.5 13 13.0 14 24.9 24 22.1 26 32.2 31 28.3 33 5 12.9 17 11.6 18 22.4 27 19.9 28 28.9 34 25.4 35
60 / 50 °C
10 11.4 21 10.2 21 19.9 30 17.7 31 25.7 36 22.5 38
15 9.9 24 8.9 25 17.5 33 15.5 34 22.5 38 19.8 40
20 8.4 28 7.5 29 15.1 35 13.4 37 19.4 40 17.1 42
0 14.5 13 13.0 14 26.6 25 23.7 27 34.5 34 30.4 36 5 12.9 17 11.6 18 24.1 28 21.4 30 31.2 36 27.4 38
70 / 50 °C
10 11.4 21 10.2 19 21.6 31 19.2 33 27.9 38 24.6 40
15 9.9 24 8.9 25 19.1 34 17.0 36 24.7 40 21.8 42
20 8.5 28 7.6 29 16.7 37 14.9 38 21.6 43 19.0 44
0 17.7 16 15.8 17 31.5 30 28.0 32 40.8 40 35.9 42 5 16.1 20 14.4 21 28.9 33 25.7 35 37.4 42 32.9 45
80 / 60 °C
10 14.5 23 13.0 16 26.4 36 23.4 38 34.0 44 30.0 47
15 13.0 27 11.7 28 23.9 39 21.2 41 30.9 47 27.1 49
20 11.5 31 10.3 32 21.4 42 19.0 44 27.7 49 24.3 51
0 20.8 19 18.7 20 36.3 35 32.3 37 47.2 46 41.4 49 5 19.2 22 17.2 24 33.7 38 30.0 40 43.7 48 38.4 51
90 / 70 °C
10 17.7 26 15.8 28 31.1 41 27.7 43 40.3 51 35.4 53
15 16.1 30 14.4 31 28.6 44 25.4 46 37.0 53 32.5 55
20 14.6 34 13.0 35 26.1 47 23.2 49 33.7 55 29.6 57
tL1 = air inlet temperature/ tL2 = air outlet temperature
2)
at t 20 K (difference in temperature between air inlet and air outlet)
t
L2
°C
kW
t °C
L2
kW
t °C
L2
kW
t
L2
kW
°C
Operation with range restriction
t °C
L2
kW
t °C
L2
16
We reserve the right to make dimensional and design changes in the interest of technical advances.
PWL 201-203 - Cooling • Rating tables • Technical Data
Type PWL 201-HK PWL 202-HK PWL 203-HK
Type 2-speed 2-speed 2-speed
Speed rpm 920 750 920 750 920 750
Electrical connection V 400/3~N
Frequency Hz 50
Power consumption kW 0.28/0.18
Nominal current A 0.67/0.37
Air capacity m³/h 3110 2580 2900 2400 2850 2350
Sound pressure level1)dB (A) 61 53 61 56 61 56
Hydraulic connection Zoll R 1“ R 1“ R 1“
Water volume l 1.0 1.8 2.9
Condensate max. l/h 2.3 2.2 5.6 5.2 7.6 7.1
Weight kg 32 35 38
PKW coolant
4 / 8 °C
6 / 10 °C
8 / 14 °C
10 / 16 °C
12 / 18 °C
t
L1/r.H.
°C/%
24/60 5.3 26/53 4.9 20/71 10.6 17/79 9.6 16/80 13.9 15/85 12.4 14/87 26/50 5.4 25/53 4.9 21/63 10.7 17/72 9.7 17/74 14.0 15/80 12.5 15/82 28/45 5.9 23/58 5.4 23/58 11.5 19/69 10.4 18/70 15.0 16/77 13.5 15/79 30/40 6.3 22/62 5.8 24/54 12.2 20/65 11.1 19/67 15.9 17/74 14.3 16/78 32/40 7.5 20/70 6.8 26/54 14.0 21/65 12.7 20/67 18.3 18/75 16.4 17/77
24/60 4.3 21/70 3.9 21/71 9.0 18/79 8.1 17/80 11.7 16/85 10.5 15/86 26/50 4.3 22/60 4.0 22/63 9.0 19/72 8.2 18/73 11.8 16/80 10.6 16/81 28/45 4.8 24/58 4.4 23/59 9.9 20/69 8.9 19/70 12.8 17/77 8.9 16/79 30/40 5.3 25/53 4.8 25/54 10.5 21/65 9.5 20/66 13.7 18/74 12.3 17/76 32/40 6.4 27/53 5.8 26/54 12.3 22/65 11.2 21/67 16.1 19/74 14.4 18/76
24/60 2.2 22/68 2.0 22/69 5.6 19/79 5.1 19/80 7.2 18/85 6.5 17/86 26/50 2.8 23/59 2.5 23/60 5.9 20/73 5.2 20/73 7.3 18/80 6.6 18/81 28/45 3.3 25/54 3.0 24/55 6.8 21/69 5.9 21/70 8.7 19/79 7.6 18/79 30/40 3.8 26/50 3.4 26/51 7.6 22/65 6.8 21/67 9.8 20/75 8.4 19/76 32/40 4.3 28/51 3.9 27/52 9.0 23 65 8.2 23/66 11.7 21/74 10.5 20/76
24/60 1.8 22/66 1.6 22/67 4.2 20/78 3.7 19/80 5.3 18/85 4.7 18/87 26/50 2.3 24/57 2.1 24/58 5.1 21/69 4.5 20/70 6.5 19/76 5.7 19/78 28/45 2.8 25/53 2.5 25/54 5.9 22/65 5.3 21/67 7.6 20/73 6.7 19/76 30/40 3.3 27/48 3.0 27/49 6.8 23/61 6.0 22/63 8.7 21/70 7.6 20/72 32/40 3.8 28/50 3.5 29/51 7.6 24/64 6.8 23/67 9.8 21/75 8.6 21/78
24/60 1.3 23/65 1.2 23/65 3.3 21/74 2.9 20/75 4.2 20/79 3.7 19/80 26/50 1.8 24/55 1.6 24/56 4.2 22/65 3.7 21/66 5.4 20/71 4.7 20/72 28/45 2.3 26/51 2.1 26/52 5.1 23/62 4.5 22/63 6.5 21/68 5.7 21/70 30/40 2.8 27/47 2.5 27/48 5.9 24/58 5.3 23/60 7.6 22/65 6.7 21/67 32/40 3.4 29/48 3.0 28/49 6.8 25/61 6.0 24/63 8.7 23/69 7.6 22/72
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
tL1 = air inlet temperature/ tL2 = air outlet temperature
1)
LpA 1m, noise measurement DIN 45635 - 01 - CATEGORY 3
We reserve the right to make dimensional and design changes in the interest of technical advances.
17
REMKO PWL
PWL 301-303 - Heating • Rating tables • Technical Data
Type PWL 301-H PWL 302-H PWL 303-H
Type 2-speed 2-speed 2-speed
Speed rpm 920 750 920 750 920 750
Electrical connection 400/3~N
Frequency Hz 50
Power consumption kW 0.36/0.22
Nominal current A 0.84/0.46
Air capacity m³/h 4300 2650 4150 2400 3900 1710
Sound pressure level1)dB (A) 66 59 66 59 68 61
max. mounting height m 7.0 6.5 6.0
max. range
Hydraulic connection Inch R 1“ R 1“ R 1“
Water volume l 1.1 2.0 3.3
Weight kg 43 46 48
PWW heating medium
50 / 40 °C
60 / 50 °C
70 / 50 °C
80 / 60 °C
90 / 70 °C
tL1 = air inlet temperature/tL2 = air outlet temperature
2)
at t 20 K (difference in temperature between air inlet and air outlet)
2)
m 5.0 7.0 6.2
t
L1
°C
kW
t °C
L2
kW
t
L2
°C
kW
t
L2
°C
kW
t °C
L2
kW
t
°C
L2
kW
0 14.7 21 11.1 12 24.0 16 17.2 20 33.7 24 19.1 31
5 12.8 13 9.6 15 20.8 19 15.0 23 29.6 26 16.8 33 10 10.9 17 8.2 19 17.7 22 12.8 25 25.5 29 14.5 34 15 9.0 21 6.8 23 14.7 25 10.6 28 21.5 31 12.2 36 20 7.1 25 5.4 28 11.7 28 8.5 31 17.6 33 10.0 37
0 18.7 12 14.0 15 30.4 20 21.7 25 41.7 30 23.6 38
5 16.7 16 12.5 18 27.1 23 19.4 28 37.5 32 21.2 40 10 14.7 20 11.1 22 24.0 27 17.1 31 33.3 35 18.8 42 15 12.8 24 9.6 26 20.9 30 14.9 33 29.2 37 16.5 43 20 10.9 28 8.2 29 17.8 33 12.8 36 25.2 39 14.3 45
0 18.8 12 14.3 15 31.0 21 22.3 26 44.8 32 25.6 41
5 16.9 16 12.7 19 27.8 24 20.0 29 40.5 34 23.2 43 10 14.9 20 11.3 22 24.6 27 17.8 31 36.3 37 20.8 45 15 13.0 24 9.8 26 21.5 30 15.6 34 32.1 39 18.4 46 20 11.1 28 8.4 29 18.5 33 13.4 37 28.1 41 16.1 48
0 22.9 15 17.2 18 37.5 25 26.9 31 52.9 38 30.1 49
5 20.9 19 15.7 22 34.2 28 24.6 34 48.6 40 27.6 51 10 18.9 23 14.2 25 31.0 31 22.3 37 44.3 43 25.2 52 15 16.9 27 12.8 29 27.8 35 20.0 39 40.1 45 22.8 54 20 15.0 30 11.3 33 24.7 38 17.8 42 35.9 47 20.5 56
0 26.9 17 20.3 21 44.0 29 31.5 36 61.1 43 34.7 56
5 24.9 21 18.7 25 40.7 33 29.1 39 56.6 46 32.1 58 10 22.9 25 17.2 29 37.4 36 26.8 42 52.3 48 29.6 60 15 20.9 29 15.7 32 34.2 39 24.5 45 48.0 51 27.2 61 20 18.9 33 14.0 36 31.0 42 22.2 48 43.8 53 24.8 63
Operation with range restriction
t
°C
L2
18
We reserve the right to make dimensional and design changes in the interest of technical advances.
PWL 301-303 - Cooling • Rating tables • Technical Data
Type PWL 301-HK PWL 302-HK PWL 303-HK
Type 2-speed 2-speed 2-speed
Speed rpm 920 750 920 750 920 750
Electrical connection 400/3~N
Frequency Hz 50
Power consumption kW 0.36/0.22
Nominal current A 0.84/0.46
Air capacity m³/h 4300 2650 4150 2400 3900 1710
Sound pressure level1)dB (A) 66 59 66 59 68 61
Hydraulic connection Inch R 1“ R 1“ R 1“
Water volume l 1.1 2.0 3.3
Condensate max. l/h 3.0 2.7 4.2 4.1 9.5 6.7
Weight kg 43 46 48
PKW coolant
4 / 8 °C
6 / 10 °C
8 / 14 °C
10 / 16 °C
12 / 18 °C
t
L1/r.H.
°C/%
24/60 6.9 21/70 5.5 20/72 8.9 18/71 8.4 17/81 17.8 15/84 10.9 15/82 26/50 7.0 22/61 5.5 21/63 11.1 19/70 8.5 18/74 18.0 16/79 11.0 13/86 28/45 7.7 23/57 6.0 23/59 12.1 20/67 9.2 19/71 19.3 17/76 11.8 13/83 30/40 8.2 25/52 6.5 24/55 12.9 22/63 9.9 20/68 20.4 18/73 12.5 14/81 32/40 9.6 26/52 7.6 25/55 15.1 23/63 11.5 21/68 23.5 19/73 14.3 15/82
24/60 5.6 21/70 4.4 20/71 8.9 19/77 6.8 18/80 15.0 16/84 9.3 14/89 26/50 5.7 22/61 4.5 22/63 9.0 20/71 6.9 19/74 15.1 17/78 9.3 14/85 28/45 6.3 24/57 5.0 23/59 10.0 21/67 7.7 20/71 16.5 18/76 10.1 15/83 30/40 6.8 25/52 5.4 24/55 10.8 22/63 8.3 20/68 17.6 18/73 10.8 15/81 32/40 8.3 27/52 6.5 26/55 13.0 23/63 10.0 22/68 29.1 19/73 12.7 16/81
24/60 3.0 22/68 2.3 21/70 8.4 17/81 3.6 19/79 9.4 18/84 6.0 16/89 26/50 3.7 23/58 2.8 23/61 8.5 18/74 4.4 20/70 9.9 18/80 6.1 16/85 28/45 4.3 25/54 3.3 24/56 9.2 19/71 5.2 21/67 11.3 19/77 7.0 17/83 30/40 5.0 26/49 3.8 26/52 9.9 20/68 6.0 22/63 12.8 20/73 7.7 17/81 32/40 5.7 28/51 4.3 27/53 11.5 21/68 6.7 23/66 15.0 21/73 9.5 18/81
24/60 2.4 22/66 1.8 22/68 6.8 18/80 2.9 20/75 7.0 19/84 4.0 17/89 26/50 3.0 24/57 2.3 23/59 6.9 19/74 3.7 21/66 8.5 19/74 4.9 17/85 28/45 3.7 25/53 2.8 25/55 7.7 20/71 4.5 22/63 9.9 20/72 5.7 18/83 30/40 4.4 27/48 3.3 26/50 8.3 20/68 5.2 23/59 11.3 21/68 6.5 18/80 32/40 5.1 28/49 3.8 28/52 10.0 22/68 6.0 24/63 12.8 22/72 7.6 19/81
24/60 1.7 23/65 1.3 23/66 3.6 19/79 2.2 21/71 5.5 20/78 3.2 18/85 26/50 2.4 24/55 1.8 24/57 4.4 20/70 3.0 22/63 7.0 21/69 4.1 19/78 28/45 3.1 26/51 2.3 25/53 5.2 21/67 3.7 23/60 8.5 21/69 4.9 19/76 30/40 3.7 27/47 2.9 27/40 6.0 22/63 4.5 24/56 9.9 22/63 5.7 20/73 32/40 4.4 29/48 3.4 28/50 6.7 23/66 5.3 25/59 11.3 23/68 6.5 20/80
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
kW
t
L2/r.H.
°C/%
tL1 = air inlet temperature/tL2 = air outlet temperature
1)
LpA 1m, noise measurement DIN 45635 - 01 - CATEGORY 3
We reserve the right to make dimensional and design changes in the interest of technical advances.
19
REMKO PWL
Intended use
Due to their design and equip­ment, the units are intended solely for heating and cooling purposes in industrial or commercial use.
The units must only be operated by suitably trained personnel.
The manufacturer disclaims all liability for any damage attributed to failure to observe relevant in­structions, statutory requirements applicable at the place of use or unauthorised changes to the unit.
Customer service and warranty
A precondition for any warran­ty claims is that the dealer or his customer has completed and returned the enclosed “Warranty document“ to REMKO GmbH & Co. KG at the time of sale and commissioning.
The units were repeatedly tested for perfect functioning at the factory. If problems should occur which cannot be remedied by trouble­shooting by the operator, your specialised dealer or contract part­ner should be contacted.
Environmental protection and recycling
Disposal of packaging
When disposing of the packaging material, please think of the envi­ronment. Our units are carefully packed for transport and delivered in sturdy cardboard packaging on a wooden pallet, if necessary. The packaging materials are environmentally-friendly and can be recycled. By reusing packaging materials, you make a valuable contribution towards waste reduction and the conservation of raw materials.
Only dispose of packaging materi­al at the facilities provided.
NOTE
Operation for any other pur­pose than that described in these operating instructions is not permitted. Failure to observe this requirement will result in all liability being disclaimed and the warranty rendered invalid.
ATTENTION
Copyright
Any copying of this docu-
ment in whole or part or use
for purposes other than the
intended is strictly forbidden
without the prior written
permission of
REMKO GmbH & Co.
KG
Disposal of old unit
The production of our units is sub-
NOTE
Adjustments and maintenance must only be carried out by authorised specialists.
.
ject to constant quality controls.
Only high-quality materials are used, the majority of which are recyclable.
Make your contribution towards environmental protection by dispo­sing of your old unit in an environ­mentally-friendly manner.
Only dispose of your old unit at an authorised recycling facility or similar.
20
Exploded View
10
6
1a 1b
2
1c
2
7
9
9
5
3
8
4
8
Spare Parts List
No. Designation PWL 101-103 HK PWL 201-203 HK PWL 301-303 HK
EDV No. EDV No. EDV No.
1a Heat exchanger Bg. 1 1110700 1110711 1110722 1b Heat exchanger Bg. 2 1110701 1110712 1110723
1c Heat exchanger Bg. 3 1110702 1110713 1110724
2 Electrical Terminal box 1110703 1110714 1110725 3 Unit housing 1110704 1110715 1110726 4 Fan protection grille 1110705 1110716 1110727 5 Fan 400V/2-speed 1110706 1110717 1110728 6 Top support plate 1110707 1110718 1110729 7 Bottom support plate 1110708 1110719 1110730 8 Side air grille 1110709 1110720 1110731 9 Bottom air segment 1110710 1110721 1110732
10 Condensate pump 1110735 1110735 1110735
without illustr.
Condensate sensor 1110736 1110736 1110736
We reserve the right to make changes to dimensions and design in the interest of technological advances.
When ordering spare parts, please always quote the EDP No. and serial number (see rating plate)!
21
REMKO PWL
Legend/Operating limits
Fin heat exchanger
The copper/aluminium fin heat exchangers consist of circular copper pipes with aluminium fins. The connecting pipes of thick-wall steel tube are lead out of the housing on the slanted sides. The twistproof connections have a 1“ inter­nal thread.
The heat exchanger and type of housing determine the operating limits. The maximum flow temperature in heating operation must not exceed 90°C. The minimum flow temperature in cooling operation must not fall below 4°C. An operating pressure in the heating/cooling circuit of 16 bar must not be exceeded.
In the immediate vicinity of the units, the temperature must not exceed 70°C (accumulated heat).
Fan and motor
The fan is driven by an external-rotor motor which simultaneously forms the fan hub. With the external-rotor motor, the impeller with its drive motor is an optimal unit for applications in the field of heating and ventilation. The axial flow fan is statically and dynamically balanced. The rotor housing is made of cast aluminium.
Three-phase drive 400 V/50 Hz
Temperature class: F
Degree of protection: IP 54
Motor protection
The star (Y) winding connection is the low speed setting.
The delta (D) winding connection is the high speed setting.
Operating range of motors with insulation class „F“
Heating medium flow temperature up to max. 90 °C
Ambient temperature (suction temperature) up to max. 40 °C
Motor protection
Thermal contacts are embedded in the motor windings. These thermal contacts (temperature monitors) open when the maximum winding temperature of 135°C is ex­ceeded (fault). Where the units are used in combination, all thermal contacts must be connected in series. This theoretically allows any number of motors to be protected with a motor protection device. However, the number of air heaters is generally limited by the switching capacity of the control units.
: Thermal contact (TK)
22
We reserve the right to make dimensional and design changes in the interest of technical advances.
Technical data
Series PWL 101-103 HK PWL 201-203 HK PWL 301-303 HK
Electrical connection V 400/3~N 400/3~N 400/3~N
Frequency Hz 50 50 50
Power consumption kW 0.10/0.07 0.28/0.18 0.36/0.22
Nominal current A 0.26/0.13 0.67/0.37 0.84/0.46
Speed rpm 920/750 920/750 920/750
Air capacity Bg.1 m3/h
Air capacity Bg.2 m3/h
Air capacity Bg.3 m3/h
Sound pressure level
LpA 1m
1)
dB(A 56/47 61/56 66/59
2030/1685 3110/2580 4300/2650 1960/1610 2900/2400 4150/2400 1885/1530 2580/2350 3900/1710
Hydraulic connection Inch R 1“ IG R 1“ IG R 1“ IG
Water volume
2)
litre 1.0/1.6/2.5 1.0/1.8/2.9 1.1/2.0/3.3
Cooling/heating medium °C Pumped cold/hot water from 4°C to max. 90 °C
Operating pressure max. bar 16 16 16
Weight kg 31/35/38 32/35/38 43/46/48
1)
Noise measurement DIN 45635 - 01 - Category 3
2)
Water volume of fin heat exchanger tube bank
We reserve the right to make dimensional and design changes in the interest of technical advances.
23
REMKO INTERNATIONAL
… and somewhere near you!
Take advantage of our experience and consulting services
Consulting
Through intensive training, we ensure that the expert knowledge of our con­sultants is always up-to-date. This has given us the reputation of being more than just a good, reliable supplier: REMKO, a partner that helps solve problems.
Sales
REMKO not only has an extensive sales network in Germany and abroad, but also unusually highly qualified sales experts. REMKO field representatives are more than just salesmen: they are also customer consultants in the area of air conditioning and heating technology.
Customer service
Our units operate precisely and reli­ably. If a fault should occur, REMKO Customer Service is there to help you. Our extensive network of experienced specialised dealers guarantees you a fast and reliable service.
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 52 32 6 06-0 Telefax +49 5232 606-260 E-mai info@remko.de Website www.remko.de
Subject to technical changes, information supplied without liability!
Loading...