Carefully read these operating instructions before commissioning/
using the units!
13
14
16
18
20
20
20
21
21
22
23
Made by REMKO
These instructions are part of the unit and must always be kept near
to the site of installation or at the unit.
We reserve the right to make changes; no liability for errors and misprints!
3
REMKO PWL
Planning information
For an optimal room temperature,
several basic rules must be followed for room heating and cooling
planning.
Heating mode
The following data is required for
room heating planning:
■ Room heat demand
QH (kW)
■ Basic room dimensions
(length, width, height)
■ Required air change
■ Required room temperature
■ Required heating medium tem-
perature for flow and return
The air inlet temperature of the
units should not be below 34°C
and not above 42°C.
At an outlet temperature below
34°C, there is a risk of
unpleasant, cool draughts in the
area of workplaces.
Cooling mode
The following data is required for
room cooling planning:
■ Room cooling load
Qk (kW)
■ Basic room dimensions
(length, width, height)
■ Required room temperature and
possible relative humidity
■ Required cooling medium tem-
peratures for flow and return
To avoid unpleasant draughts at
workplaces, the air outlet temperature in cooling mode should
be maximum 6 – 8 K below the
ambient temperature.
An excessive temperature difference (> 8 K) can lead to the
formation of unpleasant “cold air
zones”.
The circulated total air volume of
the units per hour should be about
4 to 5 times the room volume.
Safety information
The units were subjected to extensive material, functional and
quality inspections and tests prior
to delivery.
The units can however constitute
a hazard if used improperly by
untrained persons or not for the
intended purpose.
Always observe the following safety information:
■ The locally applicable building
regulations must be observed.
■ The operator is responsible for
correct installation of the units,
correct electrical installation and
safe operation of the units.
■ The units must be installed
and operated in a manner that
excludes any risk to persons
through radiated heat.
■ The units must only be attached
to constructions or ceilings with
sufficient load bearing capacity.
■ Attachment must take place
using suitable anchors to be
attached to the unit.
If the outlet temperature is abo-ve 42°C, an increased upcurrent
of hot air will occur in the ceiling
area.
The range of the hot air current is
reduced and the air in the room
is inadequately penetrated by the
hot air current and intermixed.
Undesired “cold air zones“ form
in the room, and in contrast, an
excessive cushion of hot air forms
in the ceiling area.
This causes unnecessary heat
losses.
4
With inadequate air circulation
volume, the required room climate
is achieved very slowly and with
delay.
An excessive air circulation volume
is preferable since the system is
able to respond more dynamically
and effectively.
The air circulation volume can be
increased using external aids (e.g.
ceiling fans).
■ Only trained specialists may
install and connect the heating
medium, establish electrical connections and carry out maintenance.
■ The units must not be installed,
mounted and operated in locations subject to fire and explosion hazards or exposed to dustladen/aggressive atmospheres.
■ The units must be installed out-
side traffic zones, e.g. also the
operating areas of cranes.
Unit description
■ The units must only be operated
in a completely assembled and
mounted condition.
■ The units must only be opera-
ted within the specified capacity
limits and with the approved
operating media.
■ Safeguards, e.g. barriers must
not be removed or rendered
inoperational.
■ The units must only be operated
within the specified capacity
limits and with the approved
operating media.
■ The air intake grilles must
always be kept free of dirt and
loose objects and the air outlet
must not be closed.
■ Never insert foreign objects into
the unit.
■ The units must not be exposed
to a direct jet of water.
■ Do not operate the units in wet
areas with high humidity (e.g.
car wash).
■ All electric cables of the units
must be protected against damage e.g. animals, etc.
NOTE
Perfect functioning of the units
is only ensured when the flow
temperature at the unit inlet
and the pump capacity correspond to the selected unit
classification.
These units are stationary, indirectly recirculated air cooling/heating
units with copper/aluminium fin
heat exchangers for connection to
a pumped cold/ hot water system
up to max. 90°C.
The units are in an exclusive design, compact, universal and are
easy to install and service.
The units are suitable for heating/
cooling rooms with high or low
ceilings and where special importance is attached to exclusivity.
For example in large rooms such
as:
■ Exhibition halls
■ Sales rooms
■ Shopping centres
■ Business premises
■ Warehouses
■ Production halls
■ Foremen’s offices
■ Large entrance areas
The units must be mounted horizontally on ceilings or roof structures.
The units are fitted with an aerodynamic, powerful two-speed axial
flow fan with 400V/50Hz external
rotor motor as standard.
The inner supporting unit construction is made of galvanised
sheet steel.
The heat exchangers have copper
tubes with aluminium fins.
For removal of the produced
condensate in cooling operation,
a ready to connect condensate
pump is provided.
For an optimal air flow, individually
adjustable louvres are provided at
the top of the housing and fully
adjustable louvre segments are
provided at the bottom.
The air discharge direction (horizontal or vertical) can be individually adjusted to suit the local requirements by changing the direction
of rotation of the fan.
The plastic housing can be detached completely from the supporting lower housing part by
removing the securing clip. The
integrated securing strips prevent
the cover from falling.
The plastic housing of the units is
made of self-extinguishing material
(fire class V-0).
The heaters comply with the basic
health and safety requirements of
the pertinent EU regulations and
are easy to operate.
5
REMKO PWL
Mounting the unit
The following information must be
observed for safe unit installation:
■ The units must be arranged so
that accessed areas and workplaces are not located in the
direct air stream.
■ The units must only be moun-
ted on ceilings or roof structures with sufficient load
bearing capacity.
■ The units must be mounted
horizontally and free of stress.
■ The heat exchangers must be
connected so that no vibrations
can be transferred from the unit
to the pipe system or vice versa.
■ Suitable connection fittings,
shut-off valves, vent valves, etc.
must be mounted locally.
Ensure that no persons are standing under suspended loads during installation!
For marking the points of attachment, please use the supplied template
in the packaging. It must be ensured that sufficient space is available
between the unit and ceiling for the media connections.
The adjustable brackets (option) can be individually aligned for adjustment.
Maximum mounting heights and operating limits
The maximum mounting heights depend on the maximum range and
direction.
Heating mode
■ For mounting on ceilings and
in rooms with low and high
ceilings, the maximum mounting heights of the unit must be
observed.
■ Before connecting the units to
an existing hot water heating
system, the boiler and pump
must be checked for sufficient
capacity.
■ For maintenance and repairs, a
suitable repair switch (accessory) must be fitted.
■ The gap between the fan im-
peller and unit housing must be
checked for the same distance.
The maximum mounting heights and ranges (at 0.2 m/s) apply to an air
outlet temperature of 20K over the room temperature and ideal conditions of the primary air flow.
PWL
101-3
201-3
301-3
Mounting height and range
in m „vertical“ blowing direction
3.8 / range 2.32.5 / range 3.4
5.5 / range 4.03.8 / range 7.9
7.0 / range 5.55.7 / range 7.0
max. mounting height
Cooling mode
The maximum ranges apply to an
air outlet temperature of 8K below
room temperature and ideal primary air flow conditions.
1)
Mounting height and range
in m „horizontal“ blowing direction
max. range
PWLmax. range in mm
1)
101-3
201-3
301-3
Blowing direction horizontal +vertical
4.0
10.0
9.1
1)
1)
6
We reserve the right to make dimensional and design changes in the interest of technical advances.
Mounting examples
The unit are designed for use in
rooms with high and low ceilings.
The direction of the air flow can
be individually adjusted to the suit,
the building conditions or personal
requirements by changing the direction of rotation of the fan (pole
reversal).
In this way, the air flow, when
using the units in rooms with low
ceilings, can be controlled horizontally by means of the individually
adjustable air louvres located at
the top of the housing.
This prevents persons being exposed to a direct air stream.
Heating mode
Rooms with low ceilings; horizontal
blowing direction
Cooling mode
Rooms with low ceilings; horizontal
blowing direction
Rooms with high ceilings; vertical
blowing direction
Rooms with high ceilings; vertical
Rooms with high ceilings; vertical
blowing direction
blowing direction
Heating and cooling combination options
The triangular shape of the units offers numerous individual mounting arrangements, so that even corner areas
are taken into account.
Window frontage
Window frontage
We reserve the right to make dimensional and design changes in the interest of technical advances.
7
REMKO PWL
Electrical connection
Electrical connections of the unit
must only be established by authorised specialists in compliance with
the applicable regulations of the
local electricity supply company as
well as the VDE installation requirements relating to the unit.
ATTENTION
Failure to observe the pertinent
requirements, operating instructions and electrical wiring
diagrams relating to the unit
can give rise to malfunctions
with consequential damage.
This will invalidate the warranty!
Connection of the units
The units are fitted with twospeed, 400V three-phase axial
flow fans as standard.
Speed selection takes place with
appropriate control units (accessory).
Changes in direction take place via
a pole changing switch or special
control unit (accessory).
Motor protection is provided via
integrated thermal contacts in
conjunction with a suitable control
unit (accessory).
Connection of the three-phase
motors to the respective control
units takes place via the associated
electrical wiring diagrams.
Connection of several units
If necessary, several units (also
different sizes) can be operated
parallel via a control unit (accessory).
The total capacity of the connected units must not exceed the
maximum switching capacity of
the respective control unit.
For thermal motor protection, the
thermal contacts of all motors
must be connected in series. See
separate wiring diagrams.
Only one external control device
(thermostat, day/night control,
etc.) can always be connected per
control unit.
Terminals in the unit
5 678 9 10 11 12 13 14 15 16 17 18 19 20 21 22
13 42
W2U2V2TK PE
U1V1W1TK PE PE NL13 2
N
1
CÖS
Kondensatpumpe
Potenzialfreier Alarmkontakt
Kondensatpumpe
für Kühlbetrieb
Kondensatpumpe
Fuse protection in the supply to
the control unit must be in compliance with the applicable regulations.
The connections in the terminal
box must be connected to the
respective control unit (accessory).
Hydraulic connection
Connection to the local hydraulic system
Prior to connection to the local
hydraulic system, it must be ensured that the respective capacity
requirements of the unit can be
provided at all times.
■
Connection of the unit on the
water side must take place locally via suitable pipe fittings and
shut-off valves in the flow and
return.
The use of compensators and
automatic venting devices is
recommended!
■
The connection side at the top
and the flow and return can be
connected as required.
■
The pipe connection thread sizes
is R 1“ internal thread.
■
The fin heat exchangers must be
thoroughly vented after installation.
Air cushions in the heat exchanger will reduce the heating or
cooling capacity!
Water outlet
Water inlet
ATTENTION
When the fan is stationary,
the hydraulic supply must be
simultaneously interrupted.
8
ATTENTION
Only suitably trained specialists
may establish electrical connections.
NOTE
In order to prevent damage
due to twisting of the connecting pipes, a suitable tool
must be used to prevent the
connecting pipes rotating
while tightening the screwed
connections.
Commissioning
Draining if there is a risk of
frost
It is not possible to statically drain
the fin heat exchanger completely
in an installed condition.
If necessary, draining is only possible using compressed air.
Important information about frost
protection
To prevent frost damage, anti-frost
protection must be provided at
temperatures below 0°C.
Where systems in rooms at risk
from frost are not used for extended periods, under no circumstances must “only” water be
present in the heat exchanger.
In such cases, a suitable antifreeze
agent must be added to the heating medium (water) in a mixing
ratio that is adequate for the place
of use.
The hydraulic capacity loss must
also be taken into account.
Before using for the first time
ATTENTION
Commissioning can only take
place when it is ensured that
mounting and electrical installation has been carried out in
compliance with the pertinent
requirements of the EC Directives.
■
Correct mechanical installation
must be verified.
■
Correct connection to the local
heating system must be verified.
■
It must be ensured that hot
surfaces are protected against
accidental contact.
■
It must be verified that the
electrical wiring of the units has
been carried out in compliance
with the applicable directives
and standards using the supplied wiring diagrams.
■
It should be noted that when
using a speed control (accessory) the power of the control
unit must correspond to the
total power of the connected
motors.
■
It must be ensured that all air
inlets and outlets are open.
Air flow
The louvres on the side of the top
part of the housing (horizontal
blowing or suction) can be adjusted in 5 degree stages.
Venting
Screwed connections
Water outlet
Water inlet
Draining the
heating/cooling
medium
ATTENTION
Frost damage to the fin heat
exchanger does not fall under
the warranty!
■
The fan space as well as the
inlet and outlet area must be
checked for the presence of
foreign bodies.
■
The fan must be checked for
smooth operation.
■
Switch on the power to the
control unit (accessory) and
switch on the unit via the control switch of the control unit.
■
The direction of rotation of the
fan must be checked
The direction of rotation can
be changed by interchanging
two phases or using an external control unit (accessory).
The three louvre segments in the
bottom part of the housing (vertical blowing or suction) can be
individually adjusted via a control.
9
REMKO PWL
Care and maintenance
During initial commissioning
During initial commissioning, all
regulating, control and safety
devices must be checked for their
proper functioning and correct
adjustment.
■
The power consumption of the
fan must be measured.
The nominal current must not
exceed the values on the rating
plate at the respective operating speeds.
■
Check the motor protection
function of the fan.
■
Check the complete system for
de-energised installation and
possible vibrations.
■
Check the heating/cooling
medium supply pipes for correct
connection, tightness and insulation.
Decommissioning
Set the switch of the respective
control unit to the „Off“ or „0“
position.
Precautions for extended periods
of non-use
■
Disconnect the electrical con-
nection in all poles.
■
Shut-off the hydraulic connec-
tion.
■
Where there is a risk of frost,
the entire system must be
drained if no suitable antifreeze
agent has been added to the
heating medium (water).
(See also page 9)
The units generally require no
maintenance. The units and fin
exchanger surfaces must be visually inspected every six months
and before the start of the heating
period.
In dust-laden environments, the
units must be inspected at shorter
intervals.
For this purpose, the cover of the
unit must be detached from the
supporting part of the unit by removing the 3 securing clips at the
corners.
For inspection purposes, the cover
must be held under the supporting
part with the aid of holding straps.
The cover can be removed completely from the unit if required by
loosening the strap adjuster on the
holding straps.
During removal, it must be ensured that the suction hose and
condensate pump sensor are also
disconnected from the supporting
part.
Securing clip
Important precautions to be taken
prior to all maintenance
■
The units must be disconnected
from the supply in all poles and
locked to prevent unauthorised
reconnection.
ATTENTION
It does not suffice to switch off
the unit only via the switch!
■
It must be ensured that no more
condensate is produced as in
this case the condensate pump
is also disconnected from the
supply and no longer operational.
■
Wait for the fan to stop.
■
Shut-off the water circuit and
lock to prevent unauthorised
opening.
■
Allow the fin heat exchanger to
cool down.
Cleaning the units
■
The surfaces of the units must
be cleaned only dry or with a
moist cloth and a small amount
of soap solution if necessary.
■
Under no circumstances use
high-pressure cleaners or steam
jet equipment to clean the
mounted unit.
■
Do not use caustic cleaning
agents or those containing
solvents.
■
Only suitable cleaning agents
must be used even to remove
heavy fouling.
■
Clean all air inlets and air outlet
louvres.
■
Clean the fan impeller. If ne-
cessary, remove the motor or
protection grille.
■
Clean the heat exchanger fins
either by blowing out, suction
or with a soft brush.
10
■
If the fin exchanger surface is
covered with grease or sooty
particles, the exchanger element can be removed and
cleaned with a steam-jet degreaser using low pressure and a
suitable cleaning agent.
■
Remove heavy fouling on the
fan and aluminium fins with a
soap solution.
■
Clean the condensate tank in
the unit housing to remove dirt
deposits.
To ensure complete drainage of
the condensate tank, the suction
opening of the condensate hose
must be fixed at the lowest point
of the cover.
The condensate sensor must be
arranged slightly above the suction
opening.
Bottom edge of sensor = top edge
of suction opening.
Routing must take place as show
in the following diagram.
F = Sensor cable
K = Condensate hose (internal ø 6)
Repair
NOTE
Only authorised specialists
may undertake repairs and
maintenance.
Fan replacement
1. Remove the cover of the unit.
(See care and maintenance)
2. Disconnect the electrical connection of the fan.
3. Remove the protection grille
with fan from the housing.
4. Carefully refit the new fan in
reverse order.
5. Check the fan impeller for
smooth operation and freedom
of movement with respect to
the fan housing.
6. Re-establish the electrical connection of the motor correctly.
ATTENTION
Prior to carrying out maintenance or repairs, the unit must
always be disconnected from
the mains supply and locked to
prevent unauthorised reconnection.
Replacing the fin heat exchanger
1. Remove the cover of the unit
completely.
(See care and maintenance)
2. Disconnect the electrical con-
nection of the fan.
3. Disconnect the hydraulic con-
nection.
4. Remove the bottom support
plate (6 screws).
5. Remove the support plate with
fin exchanger downwards.
6. Carefully re-install the replacement heat exchanger and all
further components in reverse
order.
ATTENTION
After carrying out all work on
the units, an electrical safety
test must be carried out in
accordance with VDE 0701.
F
Recommended maintenance interval in normal unit operation
Inspection and possible cleaning of the condensate tankEvery six months
Inspection and possible cleaning of the condensate drainEvery six months
Functional check of the condensate pump and alarm sensorEvery six months
Inspection and possible cleaning of the air grilleAnnually
Inspection of the electrical connections and earthingAnnually
Cleaning of the fin exchangerAnnually
Inspection of the fan for smooth operation and function
K
Annually
11
REMKO PWL
hohe Drehzahl
∆- Schaltung
niedere Drehzahl
Y- Schaltung
TK
W2U2V2
TK
U1
V1W1
PE
L1L2L3
TKW2U2V2
TK
U1
V1W1
PE
L1L2L3
Fan motor 400V, two-speed
Wiring Diagram
Standard units: ∆/Y switching and thermal contacts.
Condensate pump
The compact condensate pump
must pump out the produced condensate in cooling operation.
The pump is a self-priming rotary
diaphragm pump.
The condensate is pumped out via
a flexible PVC condensate hose
with an internal diameter of 6 mm.
Safety information:
■
Disconnect the power supply
before connecting, removing or
replacing the condensate pump.
■
Do not use the condensate
pump for pumping flammable
and potentially explosive liquids
such as petrol, heating oil, solvents, etc.
■
The condensate pump must
only be used for pumping
liquids to which the pump material is resistant.
■
Do not use the condensate
pump in potentially explosive
atmospheres.
■
Electrical connection must take
place as shown in the wiring
diagram. Ensure that the power
supply is earthed in compliance
with the statutory requirements.
■
Ensure that the condensate
pump is not installed higher
than 7 m (maximum suction
head) above the drip tray outlet
and not deeper than 20 m
(maximum delivery head) below the top of the condensate
drain.
NOTE
Prior to using the system, the
function of the condensate
pump must be tested with
respect to the delivery head.
Fill the condensate tank of the
unit housing with water and
test the function of the pump.
Ensure that the pump switches
off after pumping.
ATTENTION
Electrical connection of the
unit must be carried out by
authorised specialists as defined in DIN EN 60335-1 and
VDE 0116.
NOTE
All electrical wiring terminals
must be checked for tightness
and retightened if necessary.
Pump control
Power supply: 230 V/50 Hz
Brown wire: L
Blue wire: N
Green/yellow wire: PE
The mains connection of the pump
must be protected with a 1 A miniature fuse.
Floating alarm contact:
black: common wire
yellow: contact closed in operation/open on
alarm
red: contact open in operation/closed on
alarm
Performance diagram
20
16
12
8
Förderhöhe in Meter
4
0
01020 30405060
Liter pro Stunde
Max. flow rate: 50 l/h
Max. delivery head: 20 m
Max. suction head: 7 m
Connection internal Ø: 6 mm
Temperature protection at: 130 °C
12
We reserve the right to make changes to dimensions and design in the interest of technological advances.
Unit dimensions
„A“
M 8
Hydraulic connection R 1“
D
B
Condensate hose
A
90
B
NOTE
The flow and return can be
connected as required.
80
B
16
{
90
C
Condensate pump
44
217
H
View „A“
Dimen-
sions
A985 mm1084 mm1178 mm
B632 mm963 mm1043 mm
C229 mm229 mm229 mm
D989 mm1073 mm1160 mm
H465 mm485 mm504 mm
Mounting distance between unit and ceiling minimum 80 mm!
PWL 101-103 HKPWL 201-203 HKPWL 301-303 HK
We reserve the right to make changes to dimensions and design in the interest of technological advances.
13
REMKO PWL
PWL 101-103 - Heating • Rating tables • Technical Data
We reserve the right to make dimensional and design changes in the interest of technical advances.
19
REMKO PWL
Intended use
Due to their design and equipment, the units are intended solely
for heating and cooling purposes
in industrial or commercial use.
The units must only be operated
by suitably trained personnel.
The manufacturer disclaims all
liability for any damage attributed
to failure to observe relevant instructions, statutory requirements
applicable at the place of use or
unauthorised changes to the unit.
Customer service and
warranty
A precondition for any warranty claims is that the dealer or his
customer has completed and
returned the enclosed “Warranty document“ to REMKO GmbH &
Co. KG at the time of sale and
commissioning.
The units were repeatedly tested
for perfect functioning at the
factory.
If problems should occur which
cannot be remedied by troubleshooting by the operator, your
specialised dealer or contract partner should be contacted.
Environmental
protection and
recycling
Disposal of packaging
When disposing of the packaging
material, please think of the environment.
Our units are carefully packed for
transport and delivered in sturdy
cardboard packaging on a wooden
pallet, if necessary.
The packaging materials are
environmentally-friendly and can
be recycled.
By reusing packaging materials,
you make a valuable contribution
towards waste reduction and the
conservation of raw materials.
Only dispose of packaging material at the facilities provided.
NOTE
Operation for any other purpose than that described in
these operating instructions
is not permitted. Failure to
observe this requirement will
result in all liability being
disclaimed and the warranty
rendered invalid.
ATTENTION
Copyright
Any copying of this docu-
ment in whole or part or use
for purposes other than the
intended is strictly forbidden
without the prior written
permission of
REMKO GmbH & Co.
KG
Disposal of old unit
The production of our units is sub-
NOTE
Adjustments and maintenance
must only be carried out by
authorised specialists.
.
ject to constant quality controls.
Only high-quality materials are
used, the majority of which are
recyclable.
Make your contribution towards
environmental protection by disposing of your old unit in an environmentally-friendly manner.
Only dispose of your old unit at
an authorised recycling facility or
similar.
20
Exploded View
10
6
1a
1b
2
1c
2
7
9
9
5
3
8
4
8
Spare Parts List
No.DesignationPWL 101-103 HKPWL 201-203 HKPWL 301-303 HK
2Electrical Terminal box111070311107141110725
3Unit housing111070411107151110726
4Fan protection grille111070511107161110727
5Fan 400V/2-speed111070611107171110728
6Top support plate111070711107181110729
7Bottom support plate111070811107191110730
8Side air grille111070911107201110731
9Bottom air segment111071011107211110732
10Condensate pump111073511107351110735
without illustr.
Condensate sensor111073611107361110736
We reserve the right to make changes to dimensions and design in the interest of technological advances.
When ordering spare parts, please always quote the EDP No. and serial number (see rating plate)!
21
REMKO PWL
Legend/Operating limits
Fin heat exchanger
The copper/aluminium fin heat exchangers consist of circular copper pipes with aluminium fins. The connecting pipes
of thick-wall steel tube are lead out of the housing on the slanted sides. The twistproof connections have a 1“ internal thread.
The heat exchanger and type of housing determine the operating limits.
The maximum flow temperature in heating operation must not exceed 90°C.
The minimum flow temperature in cooling operation must not fall below 4°C.
An operating pressure in the heating/cooling circuit of 16 bar must not be exceeded.
In the immediate vicinity of the units, the temperature must not exceed 70°C (accumulated heat).
Fan and motor
The fan is driven by an external-rotor motor which simultaneously forms the fan hub.
With the external-rotor motor, the impeller with its drive motor is an optimal unit for applications in the field of
heating and ventilation.
The axial flow fan is statically and dynamically balanced.
The rotor housing is made of cast aluminium.
■
Three-phase drive 400 V/50 Hz
■
Temperature class: F
■
Degree of protection: IP 54
■ Motor protection
■
The star (Y) winding connection is the low speed setting.
■
The delta (D) winding connection is the high speed setting.
Operating range of motors with insulation class „F“
■
Heating medium flow temperature up to max. 90 °C
■
Ambient temperature (suction temperature) up to max. 40 °C
Motor protection
Thermal contacts are embedded in the motor windings.
These thermal contacts (temperature monitors) open when the maximum winding temperature of 135°C is exceeded (fault). Where the units are used in combination, all thermal contacts must be connected in series. This
theoretically allows any number of motors to be protected with a motor protection device.
However, the number of air heaters is generally limited by the switching capacity of the control units.
: Thermal contact (TK)
22
We reserve the right to make dimensional and design changes in the interest of technical advances.
Cooling/heating medium°CPumped cold/hot water from 4°C to max. 90 °C
Operating pressure max.bar161616
Weightkg31/35/3832/35/3843/46/48
1)
Noise measurement DIN 45635 - 01 - Category 3
2)
Water volume of fin heat exchanger tube bank
We reserve the right to make dimensional and design changes in the interest of technical advances.
23
REMKO INTERNATIONAL
… and somewhere near you!
Take advantage of our experience and consulting services
Consulting
Through intensive training, we ensure
that the expert knowledge of our consultants is always up-to-date. This has
given us the reputation of being more
than just a good, reliable supplier:
REMKO, a partner that helps solve
problems.
Sales
REMKO not only has an extensive
sales network in Germany and abroad,
but also unusually highly qualified
sales experts.
REMKO field representatives are
more than just salesmen: they are also
customer consultants in the area of air
conditioning and heating technology.
Customer service
Our units operate precisely and reliably. If a fault should occur, REMKO
Customer Service is there to help you.
Our extensive network of experienced
specialised dealers guarantees you a fast
and reliable service.
REMKO GmbH & Co. KG
Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage
Postfach 1827 D-32777 Lage
Telephone +49 52 32 6 06-0
Telefax +49 5232 606-260
E-mai info@remko.de
Website www.remko.de
Subject to technical changes, information supplied without liability!
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.