This manual describes the installation, operation, and diagnostics of the PLX51-PBM
PROFIBUS DPV0/DPV1 Master/Slave module. The module will hereafter be collectively
referred to as PLX51-PBM.
The PLX51-PBM allows you to interface PROFIBUS DP to EtherNet/IP™.
The PLX51-PBM can operate as a PROFIBUS DPV0/DPV1 Master or multiple PROFIBUS
DPV0/DPV1 Slaves. This allows EtherNet/IP devices (e.g. Rockwell Logix platform) to exchange
process, alarming, and diagnostic data with PROFIBUS DP devices, as well as provide
parameterization and asset management of slave devices using Device Type Managers
(DTMs).
The PLX51-PBM slave feature can operate only as one or more PROFIBUS DPV0/DPV1 Slaves.
This allows EtherNet/IP devices to exchange process, alarming, and diagnostic data with other
PROFIBUS DP Master(s).
The PLX51-PBM can be set to operate as either a PROFIBUS DP Master or Slave.
The PLX51-PBM has two Ethernet ports allowing for either a Linear or Ring (Device Level Ring
– DLR) Ethernet topology. The Ethernet ports can also be set up for port mirroring allowing
for better fault analysis.
The PLX51-PBM can synchronize to an NTP Server, allowing for automatic time
synchronization. The PLX51-PBM also supports an onboard non-volatile event log for
improved fault finding.
PLX51-PBM as a PROFIBUS Master
The PLX51-PBM can exchange process data (DPV0) with up to 125 PROFIBUS DP slave devices,
providing up to 1536 cyclic bytes input and 1536 bytes output data. The data is formatted into
the engineering units for use in a Logix platform by using the automatically generated
mapping imports for Logix User Defined Data Types (UDTs).
The PLX51-PBM also provides DPV1 communication allowing you to exchange DPV1 Class 1
and Class 2 data with each slave device. The PLX51-PBM Gateway DTM can be used to
configure and parameterize each slave device using Device Type Manager (DTM) technology.
From a Logix controller, the PLX51-PBM allows you to monitor and extract DPV1 alarms from
each slave device on the connected PROFIBUS DP fieldbus.
PLX51-PBM as a PROFIBUS Slave
The PLX51-PBM can also be configured to emulate up to 10 PROFIBUS slave devices, providing
up to 1536 bytes of Input and Output Cyclic I/O data between EtherNet/IP devices and a
PROFIBUS DP master. Each slave device emulated by the PLX51-PBM can be configured to
provide DPV0 data exchange with a PROFIBUS Master on the network.
The data is formatted into the engineering units for use in a Logix platform by using the
automatically generated mapping imports for Logix User Defined Data Types (UDTs).
Each emulated slave can also be configured to exchange DPV1 Class 1 data by mapping Logix
tags for the relevant DPV1 data exchange. Each emulated slave is able to provide DPV1
alarming for the PROFIBUS Master.
The PLX51-PBM provides a range of statistics and tools to provide a detailed diagnostic
overview of each emulated slave which speeds up fault finding. The PLX50 Configuration
Utility allows you to perform a PROFIBUS DP packet capture of the running Fieldbus which
can be used to analyze the bus behaviour and packets received. The PLX51-PBM also provides
global and device specific statistics.
Page 9 of 162
Preface
ARCHITECTURE
The figure below provides an example of a typical network setup for a PLX51-PBM PROFIBUS
Master architecture using an EtherNet/IP interface.
Figure 1.3 – PLX51-PBM PROFIBUS Master to EtherNet/IP architecture
The figure below provide an example of the typical network setup for a PLX51-PBM PROFIBUS
Slave architecture using an EtherNet/IP interface.
Figure 1.4 – PLX51-PBM PROFIBUS Slave to EtherNet/IP architecture
Page 10 of 162
Preface
Resource
Link
PLX50 Configuration
Utility Installation
www.prosoft-technology.com
PLX51-PBM User Manual
PLX51-PBM Datasheet
www.prosoft-technology.com
Resource
Link
Contact Us link
www.prosoft-technology.com
Support email
support@prosoft-technology.com
ADDITIONAL INFORMATION
The following documents contain additional information that can assist you with installation
and operation.
Table 1.1 - Additional Information
SUPPORT
Technical support is provided via the Web (in the form of user manuals, FAQ, datasheets etc.)
to assist with installation, operation, and diagnostics.
For additional support, use either of the following:
Table 1.2 – Support Details
Page 11 of 162
Page 12 of 162
Installation
2. INSTALLATION
MODULE LAYOUT
The PLX51-PBM has one RS485 PROFIBUS DP port as well as two Ethernet. The Ethernet cable
must be wired according to industry standards, which can be found in the Additional
Information section of this document.
The module provides six diagnostic LEDs, as shown in the front view figure below. These LEDs
are used to provide information regarding the module system operation, the Ethernet
interface, and the PROFIBUS network status.
Figure 2.1 – PLX51-PBM Side and Front view
Page 13 of 162
Installation
DIP Switch
Description
DIP 1
Used to force the module into “Safe Mode”. When in “Safe Mode”, the module will
not load the application firmware and will wait for new firmware to be downloaded.
This should only be used in the rare occasion when a firmware update was interrupted
at a critical stage.
DIP 2
This forces the module into DHCP mode which is useful when you have forgotten the
IP address of the module.
DIP 3
This is used to lock the configuration from being overwritten by the PLX50
Configuration Utility. When set, the PLX50 Configuration Utility will not be able to
download to the PLX51-PBM module.
DIP 4
When this is set, a module reboot will set the module Ethernet IP address to
192.168.1.100 and network mask 255.255.255.0. You can then switch the DIP switch
off and assign the module a static IP address if needed.
At the bottom of the PLX51-PBM module, there is one 3-way power connector.
Figure 2.2 – PLX51-PBM Power connector
The PLX51-PBM has an input voltage range of 10 to 36 VDC, applied to the module via the
power connector. The power connector also provides an Earth connection for the PLX51PBM.
NOTE: It is recommended to always have a good clean earth connected to the
module via the Earth connector on the power connector.
At the back of the module, there is slot for a SD memory card. The module provides four DIP
switches at the top of the enclosure as shown in the top view figure below.
Figure 2.3 – PLX51-PBM Top view
Table 2.1. - DIP Switch Settings
Page 14 of 162
Installation
MODULE MOUNTING
The PLX51-PBM provides a DIN rail clip to mount onto a 35mm DIN rail.
Figure 2.4 - DIN rail specification
The DIN rail clip is mounted at the back of the module as shown in the figure below. Use a flat
screw driver to pull the clip downward. Once the module is mounted onto the DIN rail, the
clip must be pushed upwards to lock the module onto the DIN rail.
Figure 2.5 - DIN rail mouting
Page 15 of 162
Installation
Pin
Signal
Description
1
-
Not connected
2
-
Not connected
3
RxD/TxD-P
Data received and transmit (+)
4
CNTR-P
Control signal to repeater (+)
5
DGND
Reference potential for +5Vdc
6
VP
+5Vdc for terminating resistors (active termination)
7
-
Not connected
8
RxD/TxD-N
Data received and transmit (-)
9
-
Not connected
PROFIBUS DP PORT (RS485)
The PROFIBUS DP port uses a female DB9 connector. This provides connection for the
communication conductors, cable shielding, and +5Vdc output power.
All PLX51-PBM network setup and configuration is done in the ProSoft PLX50 Configuration
Utility. This software can be downloaded from: www.prosoft-technology.com
The PLX51-PBM has DHCP (Dynamic Host Configuration Protocol) enabled as factory default.
Thus, a DHCP server must be used to provide the module with the required network
parameters (IP address, subnet mask, etc.). There are a number of DHCP utilities available,
however it is recommended that the DHCP server in the PLX50 Configuration Utility is used.
Within the PLX50 Configuration Utility environment, the DHCP server can be found under the
Tools menu.
Figure 3.2. - Selecting DHCP Server
Once opened, the DHCP server listens on all available network adapters for DHCP requests
and display their corresponding MAC addresses.
Figure 3.3. - DHCP Server
NOTE: If the DHCP requests are not displayed in the DHCP Server, it may be
due to the local PC’s firewall. During installation, the necessary firewall rules
are automatically created for the Windows firewall. Another possibility is that
another DHCP Server is operational on the network and it has assigned the IP
address.
Page 18 of 162
Setup
To assign an IP address, click on the corresponding ASSIGN button. The Assign IP Address for MAC window opens.
Figure 3.4. - Assigning IP Address for MAC
The required IP address can be either entered, or a recently used IP address can be selected
by clicking on an item in the Recent list.
If the Enable Static checkbox is checked, the IP address will be set to static after the IP
assignment, thereby disabling future DHCP requests.
Once you click OK, the DHCP server will automatically assign the IP address to the module and
then read the Identity object product name from the device.
The successful assignment of the IP address by the device is indicated by the green
background of the associated row.
Figure 3.5. - Successful IP address assignment
It is possible to force the PLX51-PBM back into DHCP mode by powering up the device with
DIP switch 2 set to the On position.
Page 19 of 162
Setup
A new IP address can then be assigned by repeating the previous steps.
NOTE: It is important to return DIP switch 2 back to Off position, to avoid the
module returning to a DHCP mode after the power is cycled again.
In addition to the setting the IP address, a number of other network parameters can be set
during the DHCP process. These settings can be viewed and edited in the PLX50 Configuration
Utility Application Settings, in the DHCP Server tab.
Once the DHCP process is complete, the network settings can be set using the Ethernet Port Configuration via the Target Browser.
The Target Browser can be accessed under the Tools menu.
Figure 3.6. - Selecting the Target Browser
The Target Browser automatically scans the Ethernet network for EtherNet/IP devices.
Figure 3.7. - Target Browser
Page 20 of 162
Setup
Right-clicking on a device, reveals the context menu, including the Port Configuration option.
Figure 3.8. - Selecting Port Configuration
The Ethernet port configuration parameters can be modified using the Ethernet Port Configuration window.
Figure 3.9. - Port Configuration
Alternatively, these parameters can be modified using Rockwell Automation’s RSLinx
software.
Page 21 of 162
Setup
GSD FILE MANAGEMENT
Each PROFIBUS device has a GSD file that is required to provide information needed to
configure the device for data exchange. The PLX50 Configuration Utility manages the GSD
library which is used for adding devices to the PLX51-PBM.
1 The GSD File Management Tool is opened by selecting GSD File Management under
the Tool menu in the configuration utility.
Figure 3.10 – Launching the GSD File Management Tool
2 Once the tool opens, a list of registered slave devices are displayed, using their GSD
files.
Figure 3.11 – GSD File Management Tool
Page 22 of 162
Setup
3 To add a GSD file, select the Add option under the GSD File menu.
Figure 3.12 – GSD File Adding
4 Select the required GSD file and click OPEN.
Figure 3.13 – Adding GSD File
5 Once the file has been selected, the GSD File Management tool adds the slave device
to the device list and recompile the GSD catalog.
Page 23 of 162
Setup
A GSD catalog can be exported from another PLX50 Configuration Utility by exporting the GSD
catalog from one PLX50 Configuration Utility, and importing it in another. This is done by
selecting either Import or Export under the Catalog menu as shown below:
Figure 3.14 – GSD Catalog import/export
Page 24 of 162
Setup
CREATING A NEW PROJECT
1 Before you configure the module, a new PLX50 Configuration Utility project must be
created. Under the File menu, select New.
Figure 3.15 - Creating a new project
2A PLX50 Configuration Utility Design Tool project is created, showing the Project
Explorer tree view. To save the project use the Save option under the File menu.
3 A new device can now be added by selecting Add under the Device menu.
Figure 3.16 - Adding a new device
Page 25 of 162
Setup
4 In the Add New Device window, the PLX51-PBM and click the OK button.
Figure 3.17 – PLX51-PBM
5 The device appears in the Project Explorer tree and its configuration window opened.
The device configuration can be reopened by double-clicking the module in the Project Explorer tree, or right-clicking the module and selecting Configuration.
Figure 3.18 – PLX51-PBM configuration
Page 26 of 162
Setup
PLX51-PBM PARAMETERS
The PLX51-PBM parameters are configured by the PLX50 Configuration Utility.
Refer to the Additional Information section for documentation and installation links for
ProSoft’s PLX50 Configuration Utility.
GENERAL
The PLX51-PBM General configuration is opened by either double-clicking on the module in
the tree, or right-clicking the module and selecting Configuration.
Figure 3.19 – PLX51-PBM General configuration
Page 27 of 162
Setup
Parameter
Description
Instance Name
This parameter is a user defined name to identify between various PLX51-PBM
modules.
Description
This parameter is used to provide a more detailed description of the application
for the module.
IP Address
The IP address of the module.
Mode
The PLX51-PBM can operate in one of three modes:
Quiet
This mode allows you to connect the PLX51-PBM to an active bus and run a DP
packet capture. In this mode, the PLX51-PBM will not communicate on the DP
Bus, but rather only listen.
Standalone Master
In this mode, the PLX51-PBM is the DP Master on the PROFIBUS network.
Slave
In this mode, the PLX51-PBM will emulate multiple PROFIBUS Slave devices.
Primary Interface
This is the network the PLX51-PBM will interface the PROFIBUS network.
EtherNet/IP (Logix)
The General configuration consists of the following parameters:
Table 3.1 - General configuration parameters
Page 28 of 162
Setup
Parameter
Description
Basic Settings
Station Address (TS)
PROFIBUS Station Address for the PLX51-PBM module. TS should be unique on the
PROFIBUS network, it should also be less-than or equal to the HSA below:
Min: 0
Max: 126
Default: 1
Highest Address (HSA)
Highest Station Address. This is the highest station address of the active stations
(masters). Passive stations (slaves) can have a higher address than the HSA.
A low HSA is better for PROFIBUS performance.
Min: 1
Max: 126
Default: 126
Baud Rate
Baud Rate (in Kbps) of the PROFIBUS network: 9.6, 19.2, 45.45,
93.75, 187.5, 500, 1500, 3000, 6000 or 12000 Kbps. The baud rate should be
supported by all slaves in the configuration. The baud rate should be
selected depending on the cable length, see chapter “PROFIBUS DP”.
PROFIBUS–MASTER MODE
The PLX51-PBM PROFIBUS configuration is opened by either double-clicking on the module
in the tree, or right-clicking the module and selecting Configuration. Then select the
PROFIBUS tab.
The PROFIBUS configuration consists of the following parameters:
Page 29 of 162
Setup
Advanced Settings
Logix Comms Fail
Specifies the PROFIBUS Master behavior when losing communication with Logix,
either:
Force to Offline
Force to Clear
Logix Program Mode
Specifies the PROFIBUS Master behavior when Logix is set in Program mode, either:
Force to Offline
Force to Clear
Extra DPV1 Poll / Cycle
The number of additional DPV1 Polls (Class 2) per PROFIBUS Cycle.
Increasing this parameter results in faster Asset Management DTM updates.
Error Management
Token Retry Limit
Token Retry Limit is the number of times that a PROFIBUS Master tries to pass the
token before deciding that a station is not there. Value must be in the following
range:
Min: 0
Max: 15
Default: 3
Message Retry Limit
Message Retry Limitis the number of telegram repetitions if the address doesn’t
react. Value must be in the following range:
Min: 0
Max: 15
Default: 1
Timing
TTR
Target Rotation Time indicates the maximum time available for a token circulation
(time for PROFIBUS token to be passed to another master and be back). It takes in
account the number of slaves with their IO size (data exchanges telegram), different
telegrams needed and their duration times (FDL status, global control, pass token),
all mandatory timing with respect to the PROFIBUS standard (time slot, min and
max Tsdr, Tqui, Tset, …) and a safety margin which allows bandwidth for acyclic
messages (DPV1, …).
Min: 0
Max: 16777215
Slot Time (TSL)
Slot Time (in tbits) is the maximum time the PLX51-PBM will wait, after the
transmission of a request, for the reception of the first byte (Tchar) of an answer.
(It allows detecting a timeout.) It can be increased when repeaters are used in the
PROFIBUS network topology. The value must respect the rule:
Min: 37
Max: 16383
Gap Update Factor
Gap Update Factor: The range of addresses between 2 consecutive active stations
is called GAP. This GAP is submitted to a cyclic check during which the system
identifies the station condition (not ready, ready or passive).
Min: 1
Max: 100
Quiet Time (TQUI)
Quiet time (in tbits) is the time that a station may need to switch from sending to
receiving. It must respect the rule:
TQUI < MIN_TSDR
Min: 0
Max: 255
Page 30 of 162
Loading...
+ 132 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.