ProSoft Technology MVI69-EGD User Manual

MVI69-EGD
CompactLogix or MicroLogix Platform
GE Ethernet Global Data Communication Module
11/3/2008
USER MANUAL
Please Read This Notice
Successful application of this module requires a reasonable working knowledge of the Rockwell Automation CompactLogix or MicroLogix hardware, the MVI69-EGD Module and the application i n which th e combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to ensure that the information provided is accurate and a true reflection of the product's installation requirements. In order to ensure a complete understanding of the operation of the product, the user should read all applicable Rockwell Automation documentation on the operation of the Rockwell Automation hardware.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from ProSoft Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a commitment on the part of ProSoft Technology Improvements and/or changes in this manual or the product may be made at any time. These changes will be made periodically to correct technical inaccuracies or typograp hica l errors.
Battery Life Advisory
All modules in the MVI series use a rechargeable Lithium Vanadium Pentoxide battery to backup the 51 2K SRAM memory, real-time clock, and CMOS. The battery should last for the life of the module. The module must be powered for approximately twenty hours before it becomes fully charged. After it is fully charged, the battery provides backup power for the CMOS setup and configuration data, the real-time clock, and the 512K SRAM memory for approximately 21 days. Before you remove a module from its power source, ensure that the battery within the module is fully charged. A fully charged battery will hold the BIOS settings (after being removed from its power source) for a limited number of days. When the battery is fully discharged, the module will revert to the default BIOS settings.
Note: The battery is not user replaceable.
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about the product, documentation or support, please write or call us.
ProSoft Technology 1675 Chester Avenue, Fourth Floor Bakersfield, CA 93301 +1 (661) 716-5100 +1 (661) 716-5101 (Fax) http://www.prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2000 - 2008. All Rights Reserved. MVI69-EGD User Manual
11/3/2008 ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk® and RadioLinx ® are Registered Trademarks of ProSoft
Technology, Inc.
ProSoft® Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments. User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provide d on the enclosed CD and are available at no charge from our web site: http://www.prosoft-technology.com Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability. Asia Pacific: +603.7724.2080 Europe, Middle East, Africa: +33.5.34.36.87.20 Latin America: +1.281.298.9109 North America: +1.661.716.5100
Contents MVI69-EGD ♦ CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
Contents
Please Read This Notice 2
Battery Life Advisory...........................................................................................................................2
Your Feedback Please........................................................................................................................2
ProSoft® Product Documentation.......................................................................................................3
Guide to the MVI69-EGD User Manual 7
1 Start Here 9
1.1 System Requirements...............................................................................................9
1.2 Package Contents...................................................................................................10
1.3 Install ProSoft Configuration Builder Software........................................................11
1.4 Setting Jumpers ......................................................................................................12
1.5 Install the Module in the Rack.................................................................................13
1.6 Connect your PC to the Processor..........................................................................16
1.7 Download the Sample Program to the Processor...................................................17
1.8 Connect your PC to the Module..............................................................................20
2 Configuring the MVI69-EGD Module 21
2.1 ProSoft Configuration Builder..................................................................................21
2.2 [Module69]...............................................................................................................26
2.3 [SNTP Client]...........................................................................................................27
2.4 [EGD Exchanges]....................................................................................................28
2.5 [EGD Multicast Group List]......................................................................................33
2.6 Ethernet Configuration ............................................................................................33
2.7 Download the Project to the Module.......................................................................34
3 Ladder Logic 37
3.1 Adding the Module to an Existing CompactLogix Project.......................................37
3.2 Adding the Module to an Existing MicroLogix Project.............................................42
4 Diagnostics and Troubleshooting 45
4.1 Reading Status Data from the Module....................................................................45
4.2 LED Status Indicators..............................................................................................57
5 Reference 59
5.1 Product Specifications.............................................................................................59
5.2 Functional Overview................................................................................................61
5.3 Exchange Configuration Form ................................................................................85
ProSoft Technology, Inc. Page 5 of 96 November 3, 2008
Contents MVI69-EGD ♦ CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
6
Support, Service & Warranty 87
6.1 How to Contact Us: Technical Support................................................................... 87
6.2 Return Material Authorization (RMA) Policies and Conditions............................... 88
6.3 LIMITED WARRANTY............................................................................................ 90
Index 95
Page 6 of 96 ProSoft Technology, Inc. November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
Guide to the MVI69-EGD User Manual
Function Section to Read Details
Introduction (Must Do)
Verify Communication, Diagnostic and Troubleshooting
Reference Product Specifications Functional Overview Glossary
Support, Service, and Warranty
Index
Start Here (page 9)
Verifying Communication (page 57)
Diagnostics and Troubleshooting (page 45)
Reference (page 59) Functional Overview
(page 61) Product
Specifications (page
59)
Support, Service and Warranty (page
87)
This Section introduces the customer to the module. Included are: package contents, system requirements, hardware installation, and basic configuration.
This section describes how to verify communications with the network. Diagnostic and Troubleshooting procedures.
These sections contain general references associated with this product, Specifications, and the Functional Overview.
This section contains Support, Service and Warranty information.
Index of chapters.
ProSoft Technology, Inc. Page 7 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
Page 8 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
1 Start Here
In This Chapter
System Requirements.............................................................................9
Package Contents.................................................................................10
Install ProSoft Configuration Builder Software.......................................11
Setting Jumpers ....................................................................................12
Install the Module in the Rack ...............................................................13
Connect your PC to the Processor........................................................16
Download the Sample Program to the Processor..................................17
Connect your PC to the Module ............................................................20
Installing the MVI69-EGD module requires a reasonable working knowledge of the Rockwell Automation hardware, the MVI69-EGD Module and the application in which they will be used.
Caution: It is important that those responsible for implementation can complete the
application without exposing personnel, or equipment, to unsafe or inappropriate working conditions. Safety, quality and experience are key factors in a successful installation.
1.1 System Requirements
The MVI69-EGD module requires the following minimum hardware and software components:
Rockwell Automation CompactLogix or MicroLogix processor, with
compatible power supply and one free slot in the rack, for the MVI69-EGD module. The module requires 800mA of available power.
Important: The MVI69-EGD module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus).
Important: For 1769-L23x processors, please make note of the following limitations. 1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-EGD will use all 800mA of available power. No
other modules can be used with an MVI69 module connected to this processor).
1769-L23E-QB1B = 1000mA at 5Vdc (1 MVI69-EGD will use 800mA of available power. One
other module can be used on this rack provided it consumes less than 200mA at 5Vdc.
1769-L23E-QBFC1B = 450mA at 5Vdc (no MVI69 module can be used with this processor) Rockwell Automation RSLogix 5000 (CompactLogix) or RSLogix 500
(MicroLogix) programming software
Rockwell Automation RSLinx communication software
ProSoft Technology, Inc. Page 9 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
Supported operating systems:
o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3 o Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended 100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 × 768 recommended)
CD-ROM drive HyperTerminal or other terminal emulator program capable of file transfers
using Ymodem protocol.
1.2 Package Contents
The following components are included with your MVI69-EGD module, and are all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are
present.
Qty. Part Name Part Number Part Description
1
1 Cable
1 Cable
1
MVI69-EGD Module
inRAx Solutions CD
MVI69-EGD GE Ethernet Global Data Communication Module
Cable #15, RS232 Null Modem
RJ45 to DB9 Male Adapter
For RS232 Connection to the CFG Port
For DB9 Connection to Module's Port
Contains sample programs, utilities and documentation for the MVI69-EGD module.
If any of these components are missing, please contact ProSoft Technology Support for replacement parts.
Page 10 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
1.3 Install ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software in order to configure the MVI69-EGD module. You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology web site.
To install ProSoft Configuration Builder from the ProSoft Web Site
1 Open your web browser and navigate to http://www.prosoft-
technology.com/pcb
2 Click the Download Here link to download the latest version of ProSoft
Configuration Builder.
3 Choose "Save" or "Save File" when prompted. The following illustrations
show the file download prompt for two of the most common web browsers.
4 Make a note of the location where you saved the file, for example "Desktop",
or "My Documents", so you can start the installation program.
5 When the download is complete, locate and open the file, and then follow the
instructions on your screen to install the program.
If you do not have access to the Internet, you can install ProSoft Configuration Builder from the ProSoft Solutions CD-ROM, included in the package with your MVI69-EGD module.
To install ProSoft Configuration Builder from the CD-ROM
1 Insert the ProSoft Solutions CD-ROM into the CD drive of your PC. Wait for
the startup screen to appear.
2 On the startup screen, click Product Documentation. This action opens an
explorer window.
ProSoft Technology, Inc. Page 11 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
3 Click to open the Utilities folder. This folder contains all of the applications
and files you will need to set up and configure your module.
4 Double-click the ProSoft Configuration Builder Setup program and follow the
instructions on your screen to install the software on your PC.
Note: Many of the configuration and maintenance procedures use files and other utilities on the
CD-ROM. You may wish to copy the files from the Utilities folder on the CD-ROM to a convenient location on your hard drive.
1.4 Setting Jumpers
Note: The Setup Jumper acts as "write protection" for the module's flash memory. In "write
protected" mode, the Setup pins are not connected, and the module's firmware cannot be overwritten. Do not jumper the Setup pins together unless you are directed to do so by ProSoft Technical Support.
Page 12 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
1.5 Install the Module in the Rack
This section describes how to install the module into a CompactLogix or MicroLogix rack
Before you attempt to install the module, make sure that the bus lever of the adjacent module is in the unlocked (fully right) position.
Warning: This module is not hot-swappable! Always remove power from the rack before
inserting or removing this module, or damage may result to the module, the processor, or other connected devices.
1 Align the module using the upper and lower tongue-and-groove slots with the
adjacent module and slide forward in the direction of the arrow.
2 Move the module back along the tongue-and-groove slots until the bus
connectors on the MVI69 module and the adjacent module line up with each other.
ProSoft Technology, Inc. Page 13 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
3 Push the module's bus lever back slightly to clear the positioning tab and
move it firmly to the left until it clicks. Ensure that it is locked firmly in place.
4 Close all DIN rail latches.
Page 14 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
5 Press the DIN rail mounting area of the controller against the DIN rail. The
latches will momentarily open and lock into place.
ProSoft Technology, Inc. Page 15 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
1.6 Connect your PC to the Processor
1 Connect the right-angle connector end of the cable to your controller at the
communications port.
2 Connect the straight connector end of the cable to the serial port on your
computer.
Page 16 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
1.7 Download the Sample Program to the Processor
Important: For most applications, the sample program will work without modification. Note: The key switch on the front of the CompactLogix processor must be in the REM position.
1 If you are not already online to the processor, open the Communications
menu, and then choose Download. RSLogix will establish communication with the processor.
2 When communication is established, RSLogix will open a confirmation dialog
box. Click the Download button to transfer the sample program to the processor.
3 RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
4 When the download is complete, RSLogix will open another confirmation
dialog box. Click OK to switch the processor from Program mode to Run mode.
Note: If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.
ProSoft Technology, Inc. Page 17 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
1.7.1 Configuring RSLinx
If RSLogix is unable to establish communication with the processor, follow these steps:
1 Open RSLinx. 2 Open the Communications menu, and choose Configure Drivers.
This action opens the Configure Drivers dialog box.
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the
Available Driver Types list. The recommended driver type to choose for serial communication with the processor is "RS-232 DF1 Devices".
Page 18 of 96 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
3 Click to select the driver, and then click Configure. This action opens the
Configure Allen-Bradley DF1 Communications Device dialog box.
4 Click the Auto-Configure button. RSLinx will attempt to configure your serial
port to work with the selected driver.
5 When you see the message "Auto Configuration Successful", click the OK
button to dismiss the dialog box.
Note: If the auto-configuration procedure fails, verify that the cables are connected correctly
between the processor and the serial port on your computer, and then try again. If you are still unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooting steps.
ProSoft Technology, Inc. Page 19 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module
1.8 Connect your PC to the Module
With the module securely mounted, connect your PC to the Configuration/Debug port using an RJ45-DB-9 Serial Adapter Cable and a Null Modem Cable.
1 Attach both cables as shown. 2 Insert the RJ45 cable connector into the Configuration/Debug port of the
module.
3 Attach the other end to the serial port on your PC or laptop.
Page 20 of 96 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-EGD Module MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
2 Configuring the MVI69-EGD Module
In This Chapter
ProSoft Configuration Builder................................................................21
[Module69].............................................................................................26
[SNTP Client].........................................................................................27
[EGD Exchanges]..................................................................................28
[EGD Multicast Group List]....................................................................33
Ethernet Configuration ..........................................................................33
Download the Project to the Module......................................................34
2.1 ProSoft Configuration Builder
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.
ProSoft Technology, Inc. Page 21 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Configuring the MVI69-EGD Module GE Ethernet Global Data Communication Module
2.1.1 Set Up the Project
To begin, start ProSoft Configuration Builder. If you have used other Windows configuration tools before, you will find the screen layout familiar. ProSoft Configuration Builder's window consists of a tree view on the left, an information pane and a configuration pane on the right side of the window. When you first start ProSoft Configuration Builder, the tree view consists of folders for Default Project and Default Location, with a Default Module in the Default Location folder. The following illustration shows the ProSoft Configuration Builder window with a new project.
Your first task is to add the MVI69-EGD module to the project. 1 Use the mouse to select "Default Module" in the tree view, and then click the
right mouse button to open a shortcut menu.
Page 22 of 96 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-EGD Module MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
2 On the shortcut menu, choose "Choose Module Type". This action opens the
Choose Module Type dialog box.
3 In the Product Line Filter area of the dialog box, select MVI69. In the Select
Module Type dropdown list, select MVI69-EGD, and then click OK to save your settings and return to the ProSoft Configuration Builder window.
Adding a Project
To add a project to an existing project file:
1 Select the Default Project icon. 2 Choose Project from the Project menu, then choose Add Project. A new
project folder appears.
Adding a Module
To add a module to your project:
1 Double-click the Default Module icon to open the Choose Module Type dialog
box.
2 On the Choose Module Type dialog box, select the module type. Or
1 Open the Project menu and choose Location. 2 On the Location menu, choose Add Module.
ProSoft Technology, Inc. Page 23 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Configuring the MVI69-EGD Module GE Ethernet Global Data Communication Module
To add a module to a different location:
1 Right-click the Location folder and choose Add Module. A new module icon
appears.
Or
1 Select the Location icon. 2 From the Project menu, select Location, then select Add Module.
2.1.2 Set Module Parameters
Notice that the contents of the information pane and the configuration pane changed when you added the MVI69-EGD module to the project.
At this time, you may wish to rename the "Default Project" and "Default Location" folders in the tree view.
To rename an object:
1 Select the object, and then click the right mouse button to open a shortcut
menu. From the shortcut menu, choose Rename.
2 Type the name to assign to the object. 3 Click away from the object to save the new name.
Page 24 of 96 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-EGD Module MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
Module Entries
To configure module parameters
1 Click on the plus sign next to the icon
to expand module
information.
2 Double-click the
icon to open the Edit dialog box.
3 To edit a parameter, select the parameter in the left pane and make your
changes in the right pane.
4 Click OK to save your changes.
Comment Entries
To add comments to your configuration file:
1 Click the plus sign to the left of the
icon to expand the Module
Comments.
2 Double-click the
icon. The Edit - Module Comment dialog
appears.
3 Enter your comment and click OK to save your changes.
Printing a Configuration File
To print a configuration file:
1 Select the Module icon, and then click the right mouse button to open a
shortcut menu.
2 On the shortcut menu, choose View Configuration. This action opens the
View Configuration window.
3 On the View Configuration window, open the File menu, and choose Print.
This action opens the Print dialog box.
4 On the Print dialog box, choose the printer to use from the dropdown list,
select printing options, and then click OK.
ProSoft Technology, Inc. Page 25 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Configuring the MVI69-EGD Module GE Ethernet Global Data Communication Module
2.2 [Module69]
This section designates database addresses for input and output on the module and on the processor, and identifies the method of failure for the communications for the module if the processor is not in run mode.
2.2.1 Read Register Start
Range 0 to 3999 This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0 to 3999.
2.2.2 Read Register Count
Range 0 to 3999 This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999.
2.2.3 Write Register Start
0 to 3999 This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module.
2.2.4 Write Register Count
Range 0 to 3999 This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999
2.2.5 Failure Flag Count
0 to 65535 This parameter specifies the number of successive transfer errors that must
occur before the communication ports are shut down. If the parameter is set to 0, the communication ports will continue to operate under all conditions. The value range should be between 0 and 6900.
2.2.6 Block Transfer Size
60, 120 or 240 This read-only parameter specifies the number of words in each block transferred
between the module and processor. Valid values for this parameter are 60, 120 and 240.
Page 26 of 96 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-EGD Module MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
2.3 [SNTP Client]
The [SNTP CLIENT] section of the CFG file is used to specify the parameters for the Simple Network Time Protocol (SNTP) client provided with the protocol driver. This client is required in order to keep the driver's internal clock set correctly. This version of the driver supports the unicast implementation of the SNTP Revision 3 and stratum between 1 and 14.
The module can be configured to periodically synchronize its clock with a remote SNTP server. Approximately every 6 minutes the module sends 10 consecutive requests to the remote SNTP client (at approximately 6 second intervals). You can check these requests and responses by looking at the SNTP Client Configuration Menu (press the N key at the Configuration/Debug Main Menu). If the module receives a valid response from the SNTP server, the computations value will be also be incremented. After 10 consecutive successful requests and responses, the module will synchronize its internal clock (an average is performed based on all 10 responses for better accuracy). The Time Set Cnt value is incremented every time the clock is synchronized.
After the synchronization is performed, the time valid register is set to Yes. If the module cannot connect to the remote SNTP server after 3 consecutive attempts, the time valid register is set to No. You can also configure the GMT settings to use, and the database address where the date and time information can be copied.
The following parameters in the configuration file set up the SNTP client:
[SNTP CLIENT] NTP SERVER IP ADDRESS : 132.163.4.102 #IP address for NIST, Boulder, Colorado TIME ZONE : 7 #Number of hours from GMT (-11 to +11) USE DAYLIGHT SAVINGS TIME: No #Yes or No DATABASE REGISTER : 2500 #database word location to store time # (-1=ignore). #This register value should be an even # number
The database register parameter defines a database register where the SNTP time and date values are copied. It occupies 4 words as follows:
Word Offset Description
0 and 1 Date and time in Unix format (long integer) 2 and 3 Microseconds (long integer)
2.3.1 NTP Server IP Address
Enter in dotted notation This parameter sets the IP address of the NTP server to contact for time
acquisition. Select an NTP server with the greatest accuracy that is available all the time from your network. Set this IP address to 0.0.0.0 to disable SNTP server requests.
ProSoft Technology, Inc. Page 27 of 96 November 3, 2008
MVI69-EGD CompactLogix or MicroLogix Platform Configuring the MVI69-EGD Module GE Ethernet Global Data Communication Module
2.3.2 Time Zone
-11 to 11 This parameter sets the time zone offset from UTC. Positive values are for time
zones west of UTC, and negative values are for time zones east of UTC. Set this value to 0 to use UTC in the module.
2.3.3 Use Daylight Savings Time
Yes or No This parameter specifies if daylight savings time will be used in the time
computation.
2.3.4 Database Register
-1 or 0 to 3992 as an even value This parameter specifies if the NTP time computed by the driver is to be placed
into the module's database. If a value of -1 is specified, the time will not be placed into the database. If the value is between 0 and 3992, the time will be placed in the database. The first 4 bytes represent the seconds since 1/1/1970, and the second 4 bytes represent the number of microseconds. An even value should be used for the register value in order for the data to be stored correctly.
2.4 [EGD Exchanges]
In order to interface the module with EGD devices, you must construct an exchange list. The exchanges specify messages that will be produced or consumed at a user-defined frequency using the module's internal database. Messages can be broadcast to all nodes on the network, sent to a multicast group on the network or associated with a single node on the network. Up to 100 exchanges can be defined for the driver. Up to 680 word registers can be produced or consumed in a single exchange.
The [EGD Exchanges] section defines the messages that will be produced and consumed by the driver. The UDP protocol on the IP network is used to transport these over Ethernet between all the EGD devices.
For the exchanges to operate correctly, the other EGD devices must be configured and correctly set up. The primary reason for user problems with the module is failure to provide devices that are correctly configured. Before trying to connect the module to the network, the remote device must be able to communicate with ProSoft Configuration Builder. You must understand and document all parameters.
Page 28 of 96 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-EGD Module MVI69-EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module
2.4.1 Exch Type
Producer: exchange will be producing data to other stations Consumer: exchange will be consuming data from another station
The Exchange Type field defines the type of exchange used in the exchange as either producer or consumer. Producer exchanges (P) are generated by the driver using the module's database. Consumer exchanges (C) are those received from other EGD devices with the data in the message being placed in the module's database.
2.4.2 Cast Type
When the Exchange Type is Producer, the cast type field determines if the exchange is a unicast ('U' = point-to-point) exchange, multicast ('M'=multicast group) or a broadcast ('B' = all nodes) exchange.
Producer Unicast - produce message to another station Producer Multicast - produce message to a group of stations. In order to use
this option you need to configure the same Multicast IP address used in the exchange also at the EGD MULTICAST ADDRESS section.
Important: For Multicast mode, use transmit rates of 1 or 2 for best results.
Producer Broadcast - produce message to all stations (set exchange IP
address to 255.255.255.255)
When the Exchange Type is Consumer, the cast type field determines how the local database area associated to this exchange will be updated in case an RF Error (timeout) occurs.
Consumer No DB Change on RF Error Consumer Set DB to -1 On RF Error Consumer Set DB to 0 On RF Error Consumer Set DB to 1 On RF Error
2.4.3 DB Reg
The DB Register field defines the starting database register in the module where data sourced (produced data) or placed (consumed data) is determined by the value entered in the DB Reg column. This parameter can have a value of 0 to
3999. The validity of the entry is dependent on the number of registers (Reg Count) to be produced or consumed. The sum of the two values cannot exceed 4000, as this would be outside the range of the module's database.
2.4.4 Reg Count
Number of database registers to transfer/accept in message.
ProSoft Technology, Inc. Page 29 of 96 November 3, 2008
Loading...
+ 67 hidden pages