ProSoft Technology MVI69-DNPSNET User Manual

MVI69-DNPSNET
CompactLogix or MicroLogix Platform
Distributed Network Protocol Interface Module
11/3/2008
USER MANUAL
Please Read This Notice
Successful application of this module requires a reasonable working knowledge of the Rockwell Automation CompactLogix or MicroLogix hardware, the MVI69-DNPSNET Module and the applic ation in which the combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to ensure that the information provided is accurate and a true reflection of the product's installation requirements. In order to ensure a complete understanding of the operation of the product, the user should read all applicable Rockwell Automation documentation on the operation of the Rockwell Automation hardware.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from ProSoft Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a commitment on the part of ProSoft Technology Improvements and/or changes in this manual or the product may be made at any time. These changes will be made periodically to correct technical inaccuracies or typograp hica l errors.
Battery Life Advisory
All modules in the MVI series use a rechargeable Lithium Vanadium Pentoxide battery to backup the 51 2K SRAM memory, real-time clock, and CMOS. The battery should last for the life of the module. The module must be powered for approximately twenty hours before it becomes fully charged. After it is fully charged, the battery provides backup power for the CMOS setup and configuration data, the real-time clock, and the 512K SRAM memory for approximately 21 days. Before you remove a module from its power source, ensure that the battery within the module is fully charged. A fully charged battery will hold the BIOS settings (after being removed from its power source) for a limited number of days. When the battery is fully discharged, the module will revert to the default BIOS settings.
Note: The battery is not user replaceable.
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about the product, documentation or support, please write or call us.
ProSoft Technology 1675 Chester Avenue, Fourth Floor Bakersfield, CA 93301 +1 (661) 716-5100 +1 (661) 716-5101 (Fax) http://www.prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2000 - 2008. All Rights Reserved. MVI69-DNPSNET User Manual
11/3/2008 ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk® and RadioLinx ® are Registered Trademarks of ProSoft
Technology, Inc.
ProSoft® Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments. User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provide d on the enclosed CD and are available at no charge from our web site: http://www.prosoft-technology.com Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability. Asia Pacific: +603.7724.2080 Europe, Middle East, Africa: +33.5.34.36.87.20 Latin America: +1.281.298.9109 North America: +1.661.716.5100
Contents MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
Contents
Please Read This Notice 2
Battery Life Advisory...........................................................................................................................2
Your Feedback Please........................................................................................................................2
ProSoft® Product Documentation.......................................................................................................3
Guide to the MVI69-DNPSNET User Manual 7
1 Start Here 9
1.1 System Requirements...............................................................................................9
1.2 Package Contents...................................................................................................10
1.3 Install ProSoft Configuration Builder Software........................................................11
1.4 Setting Jumpers ......................................................................................................12
1.5 Install the Module in the Rack.................................................................................13
1.6 Connect your PC to the Processor..........................................................................16
1.7 Download the Sample Program to the Processor...................................................17
1.8 Connect your PC to the Module..............................................................................20
2 Configuring the MVI69-DNPSNET Module 21
2.1 ProSoft Configuration Builder..................................................................................21
2.2 [Backplane Configuration].......................................................................................26
2.3 [DNP ENET Slave]..................................................................................................27
2.4 [DNP Slave Binary Inputs].......................................................................................33
2.5 [DNP Slave Analog Inputs]......................................................................................34
2.6 [DNP Slave Float Inputs].........................................................................................34
2.7 [DNP ENET IP ADDRESSES] ................................................................................35
2.8 Ethernet Configuration ............................................................................................35
2.9 Download the Project to the Module.......................................................................36
3 Ladder Logic 37
3.1 Module Data Objects...............................................................................................37
3.2 Adding the Module to an Existing CompactLogix Project.......................................41
3.3 Adding the Module to an Existing MicroLogix Project.............................................45
4 Diagnostics and Troubleshooting 47
4.1 Reading Status Data from the Module....................................................................47
4.2 LED Status Indicators..............................................................................................58
5 Reference 63
5.1 Product Specifications.............................................................................................63
5.2 Functional Overview................................................................................................65
ProSoft Technology, Inc. Page 5 of 119 November 3, 2008
Contents MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
5.3 MVI69-DNPSNET Application Design.................................................................... 79
5.4 Cable Connections ................................................................................................. 93
5.5 MVI69-DNPSNET Status Data............................................................................... 96
5.6 MVI69-DNPSNET Module...................................................................................... 99
5.7 Device Profile........................................................................................................ 100
5.8 DNP Subset Definition.......................................................................................... 101
5.9 Event Size Computation....................................................................................... 107
6 Support, Service & Warranty 109
6.1 How to Contact Us: Technical Support................................................................. 109
6.2 Return Material Authorization (RMA) Policies and Conditions............................. 110
6.3 LIMITED WARRANTY.......................................................................................... 112
Index 117
Page 6 of 119 ProSoft Technology, Inc. November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
Guide to the MVI69-DNPSNET User Manual
Function Section to Read Details
Introduction (Must Do)
Verify Communication, Diagnostic and Troubleshooting
Reference Product Specifications Functional Overview Glossary
Support, Service, and Warranty
Index
Start Here (page 9)
Verifying Communication (page 58)
Diagnostics and Troubleshooting (page 47)
Reference (page 63) Functional Overview
(page 65) Product
Specifications (page
63)
Support, Service and Warranty (page
109)
This Section introduces the customer to the module. Included are: package contents, system requirements, hardware installation, and basic configuration.
This section describes how to verify communications with the network. Diagnostic and Troubleshooting procedures.
These sections contain general references associated with this product, Specifications, and the Functional Overview.
This section contains Support, Service and Warranty information.
Index of chapters.
ProSoft Technology, Inc. Page 7 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
Page 8 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
1 Start Here
In This Chapter
System Requirements.............................................................................9
Package Contents.................................................................................10
Install ProSoft Configuration Builder Software.......................................11
Setting Jumpers ....................................................................................12
Install the Module in the Rack ...............................................................13
Connect your PC to the Processor........................................................16
Download the Sample Program to the Processor..................................17
Connect your PC to the Module ............................................................20
Installing the MVI69-DNPSNET module requires a reasonable working knowledge of the Rockwell Automation hardware, the MVI69-DNPSNET Module and the application in which they will be used.
Caution: It is important that those responsible for implementation can complete the
application without exposing personnel, or equipment, to unsafe or inappropriate working conditions. Safety, quality and experience are key factors in a successful installation.
1.1 System Requirements
The MVI69-DNPSNET module requires the following minimum hardware and software components:
Rockwell Automation CompactLogix or MicroLogix processor, with
compatible power supply and one free slot in the rack, for the MVI69­DNPSNET module. The module requires 800mA of available power.
Important: The MVI69-DNPSNET module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus).
Important: For 1769-L23x processors, please make note of the following limitations. 1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-DNPSNET will use all 800mA of available
power. No other modules can be used with an MVI69 module connected to this processor).
1769-L23E-QB1B = 1000mA at 5Vdc (1 MVI69-DNPSNET will use 800mA of available power.
One other module can be used on this rack provided it consumes less than 200mA at 5Vdc.
1769-L23E-QBFC1B = 450mA at 5Vdc (no MVI69 module can be used with this processor) Rockwell Automation RSLogix 5000 (CompactLogix) or RSLogix 500
(MicroLogix) programming software
Rockwell Automation RSLinx communication software
ProSoft Technology, Inc. Page 9 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
Supported operating systems:
o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3 o Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended 100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 × 768 recommended)
CD-ROM drive HyperTerminal or other terminal emulator program capable of file transfers
using Ymodem protocol.
1.2 Package Contents
The following components are included with your MVI69-DNPSNET module, and are all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are
present.
Qty. Part Name Part Number Part Description
1
1 Cable
1 Cable
1
MVI69­DNPSNET Module
inRAx Solutions CD
MVI69-DNPSNET Distributed Network Protocol Interface Module
Cable #15, RS232 Null Modem
RJ45 to DB9 Male Adapter
For RS232 Connection to the CFG Port
For DB9 Connection to Module's Port
Contains sample programs, utilities and documentation for the MVI69-DNPSNET module.
If any of these components are missing, please contact ProSoft Technology Support for replacement parts.
Page 10 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
1.3 Install ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software in order to configure the MVI69-DNPSNET module. You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology web site.
To install ProSoft Configuration Builder from the ProSoft Web Site
1 Open your web browser and navigate to http://www.prosoft-
technology.com/pcb
2 Click the Download Here link to download the latest version of ProSoft
Configuration Builder.
3 Choose "Save" or "Save File" when prompted. The following illustrations
show the file download prompt for two of the most common web browsers.
4 Make a note of the location where you saved the file, for example "Desktop",
or "My Documents", so you can start the installation program.
5 When the download is complete, locate and open the file, and then follow the
instructions on your screen to install the program.
If you do not have access to the Internet, you can install ProSoft Configuration Builder from the ProSoft Solutions CD-ROM, included in the package with your MVI69-DNPSNET module.
To install ProSoft Configuration Builder from the CD-ROM
1 Insert the ProSoft Solutions CD-ROM into the CD drive of your PC. Wait for
the startup screen to appear.
2 On the startup screen, click Product Documentation. This action opens an
explorer window.
ProSoft Technology, Inc. Page 11 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
3 Click to open the Utilities folder. This folder contains all of the applications
and files you will need to set up and configure your module.
4 Double-click the ProSoft Configuration Builder Setup program and follow the
instructions on your screen to install the software on your PC.
Note: Many of the configuration and maintenance procedures use files and other utilities on the
CD-ROM. You may wish to copy the files from the Utilities folder on the CD-ROM to a convenient location on your hard drive.
1.4 Setting Jumpers
Note: The Setup Jumper acts as "write protection" for the module's flash memory. In "write
protected" mode, the Setup pins are not connected, and the module's firmware cannot be overwritten. Do not jumper the Setup pins together unless you are directed to do so by ProSoft Technical Support.
Page 12 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
1.5 Install the Module in the Rack
This section describes how to install the module into a CompactLogix or MicroLogix rack
Before you attempt to install the module, make sure that the bus lever of the adjacent module is in the unlocked (fully right) position.
Warning: This module is not hot-swappable! Always remove power from the rack before
inserting or removing this module, or damage may result to the module, the processor, or other connected devices.
1 Align the module using the upper and lower tongue-and-groove slots with the
adjacent module and slide forward in the direction of the arrow.
2 Move the module back along the tongue-and-groove slots until the bus
connectors on the MVI69 module and the adjacent module line up with each other.
ProSoft Technology, Inc. Page 13 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
3 Push the module's bus lever back slightly to clear the positioning tab and
move it firmly to the left until it clicks. Ensure that it is locked firmly in place.
4 Close all DIN rail latches.
Page 14 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
5 Press the DIN rail mounting area of the controller against the DIN rail. The
latches will momentarily open and lock into place.
ProSoft Technology, Inc. Page 15 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
1.6 Connect your PC to the Processor
1 Connect the right-angle connector end of the cable to your controller at the
communications port.
2 Connect the straight connector end of the cable to the serial port on your
computer.
Page 16 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
1.7 Download the Sample Program to the Processor
Important: For most applications, the sample program will work without modification. Note: The key switch on the front of the CompactLogix processor must be in the REM position.
1 If you are not already online to the processor, open the Communications
menu, and then choose Download. RSLogix will establish communication with the processor.
2 When communication is established, RSLogix will open a confirmation dialog
box. Click the Download button to transfer the sample program to the processor.
3 RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
4 When the download is complete, RSLogix will open another confirmation
dialog box. Click OK to switch the processor from Program mode to Run mode.
Note: If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.
ProSoft Technology, Inc. Page 17 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
1.7.1 Configuring RSLinx
If RSLogix is unable to establish communication with the processor, follow these steps:
1 Open RSLinx. 2 Open the Communications menu, and choose Configure Drivers.
This action opens the Configure Drivers dialog box.
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the
Available Driver Types list. The recommended driver type to choose for serial communication with the processor is "RS-232 DF1 Devices".
Page 18 of 119 ProSoft Technology, Inc.
November 3, 2008
Start Here MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
3 Click to select the driver, and then click Configure. This action opens the
Configure Allen-Bradley DF1 Communications Device dialog box.
4 Click the Auto-Configure button. RSLinx will attempt to configure your serial
port to work with the selected driver.
5 When you see the message "Auto Configuration Successful", click the OK
button to dismiss the dialog box.
Note: If the auto-configuration procedure fails, verify that the cables are connected correctly
between the processor and the serial port on your computer, and then try again. If you are still unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooting steps.
ProSoft Technology, Inc. Page 19 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Start Here Distributed Network Protocol Interface Module
1.8 Connect your PC to the Module
With the module securely mounted, connect your PC to the Configuration/Debug port using an RJ45-DB-9 Serial Adapter Cable and a Null Modem Cable.
1 Attach both cables as shown. 2 Insert the RJ45 cable connector into the Configuration/Debug port of the
module.
3 Attach the other end to the serial port on your PC or laptop.
Page 20 of 119 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-DNPSNET Module MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
2 Configuring the MVI69-DNPSNET Module
In This Chapter
ProSoft Configuration Builder................................................................21
[Backplane Configuration] .....................................................................26
[DNP ENET Slave] ................................................................................27
[DNP Slave Binary Inputs].....................................................................33
[DNP Slave Analog Inputs]....................................................................34
[DNP Slave Float Inputs].......................................................................34
[DNP ENET IP ADDRESSES]...............................................................35
Ethernet Configuration ..........................................................................35
Download the Project to the Module......................................................36
2.1 ProSoft Configuration Builder
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.
ProSoft Technology, Inc. Page 21 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Configuring the MVI69-DNPSNET Module Distributed Network Protocol Interface Module
2.1.1 Set Up the Project
To begin, start ProSoft Configuration Builder. If you have used other Windows configuration tools before, you will find the screen layout familiar. ProSoft Configuration Builder's window consists of a tree view on the left, an information pane and a configuration pane on the right side of the window. When you first start ProSoft Configuration Builder, the tree view consists of folders for Default Project and Default Location, with a Default Module in the Default Location folder. The following illustration shows the ProSoft Configuration Builder window with a new project.
Your first task is to add the MVI69-DNPSNET module to the project. 1 Use the mouse to select "Default Module" in the tree view, and then click the
right mouse button to open a shortcut menu.
Page 22 of 119 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-DNPSNET Module MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
2 On the shortcut menu, choose "Choose Module Type". This action opens the
Choose Module Type dialog box.
3 In the Product Line Filter area of the dialog box, select MVI69. In the Select
Module Type dropdown list, select MVI69-DNPSNET, and then click OK to save your settings and return to the ProSoft Configuration Builder window.
Adding a Project
To add a project to an existing project file:
1 Select the Default Project icon. 2 Choose Project from the Project menu, then choose Add Project. A new
project folder appears.
Adding a Module
To add a module to your project:
1 Double-click the Default Module icon to open the Choose Module Type dialog
box.
2 On the Choose Module Type dialog box, select the module type. Or
1 Open the Project menu and choose Location. 2 On the Location menu, choose Add Module.
ProSoft Technology, Inc. Page 23 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Configuring the MVI69-DNPSNET Module Distributed Network Protocol Interface Module
To add a module to a different location:
1 Right-click the Location folder and choose Add Module. A new module icon
appears.
Or
1 Select the Location icon. 2 From the Project menu, select Location, then select Add Module.
2.1.2 Set Module Parameters
Notice that the contents of the information pane and the configuration pane changed when you added the MVI69-DNPSNET module to the project.
At this time, you may wish to rename the "Default Project" and "Default Location" folders in the tree view.
To rename an object:
1 Select the object, and then click the right mouse button to open a shortcut
menu. From the shortcut menu, choose Rename.
2 Type the name to assign to the object. 3 Click away from the object to save the new name.
Page 24 of 119 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-DNPSNET Module MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
Module Entries
To configure module parameters
1 Click on the plus sign next to the icon
to expand module
information.
2 Double-click the
icon to open the Edit dialog box.
3 To edit a parameter, select the parameter in the left pane and make your
changes in the right pane.
4 Click OK to save your changes.
Comment Entries
To add comments to your configuration file:
1 Click the plus sign to the left of the
icon to expand the Module
Comments.
2 Double-click the
icon. The Edit - Module Comment dialog
appears.
3 Enter your comment and click OK to save your changes.
Printing a Configuration File
To print a configuration file:
1 Select the Module icon, and then click the right mouse button to open a
shortcut menu.
2 On the shortcut menu, choose View Configuration. This action opens the
View Configuration window.
3 On the View Configuration window, open the File menu, and choose Print.
This action opens the Print dialog box.
4 On the Print dialog box, choose the printer to use from the dropdown list,
select printing options, and then click OK.
ProSoft Technology, Inc. Page 25 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Configuring the MVI69-DNPSNET Module Distributed Network Protocol Interface Module
2.2 [Backplane Configuration]
This section of the file describes the database setup and module level parameters.
2.2.1 Module Name
0 to 80 characters This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the configuration file.
2.2.2 Read Register Start
0 to 8899 This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0 to 8899.
2.2.3 Read Register Count
0 to 8900 This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 8900.
2.2.4 Write Register Start
0 to 8899 This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module. Valid range for this parameter is 0 to 8899.
2.2.5 Write Register Count
0 to 8900 This parameter specifies the number of registers to transfer from the processor to
the module. Valid entry for this parameter is 0 to 8900.
2.2.6 Block Transfer Size
60, 120 or 240 This read-only parameter specifies the number of words in each block transferred
between the module and processor. Valid values for this parameter are 60, 120 and 240.
Page 26 of 119 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-DNPSNET Module MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
2.2.7 Failure Flag Count
0 to 65535 This parameter specifies the number of successive transfer errors that must
occur before the communication ports are shut down. If the parameter is set to 0, the communication ports will continue to operate under all conditions. The value range should be between 0 and 6900.
2.2.8 Error Offset
0 to 8899 This parameter specifies the register location in the module's database where
module status data will be stored. If a value less than 0 is entered, the data will not be stored in the database. If the value specified is in the range of 0 to 8966, the data will be placed in the modules database.
2.2.9 Initialize Output Data
Yes or No This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to N, the output data will be initialized to 0. If the value is set to Y, the data will be initialized with data from the processor.
2.3 [DNP ENET Slave]
This section provides information required to configure a slave application with the module. Most entries contained within this section are self explanatory with the possible exception of the Use IP List directive. This directive instructs the module to verify the address of the received message and ignore the message if it is not on our list of acceptable clients.
2.3.1 Internal Slave ID
0 to 65534 This is the DNP address for the module. All messages with this address received
from the master will be processed by the module.
2.3.2 Use IP List
Y or N This parameter specifies if the IP address of the host connected to the system
will be validated. If the parameter is set to N, any host may connect to the unit. If the parameter is set to Y, only hosts in the IP list will be permitted to connect to the module. All other IP addresses will be ignored by the module and the module will issue a RST to the TCP/IP connection.
ProSoft Technology, Inc. Page 27 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Configuring the MVI69-DNPSNET Module Distributed Network Protocol Interface Module
DNP Database Definition Note: The databases are in the memory of the module in this sequence
and are placed directly adjacent to each other. In other words when you change the size of a database you must adjust the transfer commands to accommodate the new location.
2.3.3 Binary Inputs
0 to 500 words This parameter specifies the number of digital input points to configure in the
DNP slave device based on a word count. The valid range is 0 to 500 words.
2.3.4 Analog Inputs
0 to 500 points This parameter sets the number of analog input points to configure in the DNP
slave device. Each point will occupy a one-word area in the module memory.
2.3.5 Float Inputs
0 to 150 Number of floating-point input points to configure in the DNP slave device. Each
point will occupy a two-word area in the module memory.
2.3.6 Counters
0 to 250 points This parameter sets the number of counter points to configure in the DNP slave
device. Each point will occupy a two-word area in the module memory. This number corresponds to the number of frozen counters. The application maps the counters to the frozen counters directly. Valid values are 0 to 250 points.
2.3.7 Binary Outputs
0 to 500 words Number of digital output points to configure in the DNP slave device based on a
word count. Each word stores 16 points. Therefore, if the parameter is set to 2, 32 binary outputs will be defined for the application.
2.3.8 Analog Outputs
0 to 500 points Number of analog output points to configure in the DNP slave device. Each point
will occupy a one word area in the module memory.
2.3.9 Float Outputs
0 to 150 points Number of floating-point output points to configure in the DNP slave device. Each
point will occupy a two- word area in the module memory.
Page 28 of 119 ProSoft Technology, Inc.
November 3, 2008
Configuring the MVI69-DNPSNET Module MVI69-DNPSNET CompactLogix or MicroLogix Platform Distributed Network Protocol Interface Module
2.3.10 BI Class
0=disable, else 1 to 3 This parameter specifies the default class to be utilized for all the binary input
points in the DNP database that are not defined in the override list section.
2.3.11 AI Class
0=disable, else 1 to 3 This parameter specifies the default class to be utilized for all the analog input
points in the DNP database that are not defined in the override list section.
2.3.12 Float Class
0=disable, else 1 to 3 This parameter specifies the default class to be utilized for all the floating-point
input points in the DNP database that are not defined in the override list section.
2.3.13 AI Deadband
0 to 32767 data units This value sets the global deadband for all analog input points. When the current
value for an analog input point is not within the deadband limit set based on the last event for the point, an event will be generated.
2.3.14 Float Deadband
0 to 32767 data units This parameter specifies the default deadband value assigned to all points not
defined in the override list for the floating-point input point type in the DNP database.
2.3.15 Select/Operate Arm Time
1 to 65535 milliseconds This parameter sets the time period after select command received in which
operate command will be performed. After the select command is received, the operate command will only be honored if it arrives within this period of time. Valid arm timeout values are 1 to 65535 milliseconds. This example shows the value set to 2000 milliseconds.
2.3.16 Write Time Interval
0 to 1440 minutes This parameter sets the time interval to set the need time IIN bit (0=never), which
will cause the master to write the time. Stored in milliseconds in the module memory.
ProSoft Technology, Inc. Page 29 of 119 November 3, 2008
MVI69-DNPSNET CompactLogix or MicroLogix Platform Configuring the MVI69-DNPSNET Module Distributed Network Protocol Interface Module
2.3.17 App Layer Confirm Tout
1 to 65535 milliseconds Event data contained in the last response may be sent again if not confirmed
within the millisecond time period set. If application layer confirms are used with data link confirms, ensure that the application layer confirm timeout is set long enough.
2.3.18 Unsolicited Response
Yes or No This parameter is set if the slave unit will send unsolicited response messages. If
set to N, the slave will not send unsolicited responses. If set to Y, the slave will send unsolicited responses.
2.3.19 Class 1 Unsol Resp Min
1 to 255 events Minimum number of events in Class 1 required before an unsolicited response
will be generated.
2.3.20 Class 2 Unsol Resp Min
1 to 255 events Minimum number of events in Class 2 required before an unsolicited response
will be generated.
2.3.21 Class 3 Unsol Resp Min
1 to 255 events Minimum number of events in Class 3 required before an unsolicited response
will be generated.
2.3.22 Unsol Resp Delay
0 to 65535 milliseconds Maximum number of 1 millisecond intervals to wait after an event occurs before
sending an unsolicited response message. If set to 0, only use minimum number of events.
2.3.23 Uresp Master Address
0 to 65534 DNP destination address where unsolicited response messages are sent.
Page 30 of 119 ProSoft Technology, Inc.
November 3, 2008
Loading...
+ 89 hidden pages