Pilz PNOZ XV1P Data Sheet

E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Safety relay for monitoring E-STOP pushbuttons and safety gates.
PNOZ XV1P
Unit features
` Positive-guided relay outputs:
– 2 safety contacts (N/O), instanta-
neous
– 1 safety contact (N/O), delay-on
de-energisation
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Plug-in connection terminals (either
cage clamp terminal or screw termi­nal)
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
The max. category the safety contacts can achieve in accordance with EN 954-1 is stated in the technical details.
Safety features
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The unit has an electronic fuse.
Block diagram
A1 A2
=
Power
=
S11
S14
S12 S32
InputInput
StartStart
S21 S22
Input
K3
K1
K4
K2
13 23
14 24S33 S34
37
38
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Function description
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
Timing diagram
POWER
Reset/Start
Input
Output safe
Output safe del
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.
1 2
t1 t2
t1
t3 t2
t3
t4
t1
` Automatic start: Unit is active once
the input circuit has been closed.
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
t2t1
t3
t4 t3
t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S14-S32,
S33-S34
` Reset tv: Y39-Y40 ` Input: Input circuits S11-S12, S12-
S32, S21-S22
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 37-38 are delay-on de-en-
ergisation safety contacts.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resist-
R
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Output safe: Safety contacts, in-
stantaneous 13-14, 23-24
` Output safe del: Safety contacts,
delayed 37-38
` Å: Automatic reset ` Ç: Monitored reset
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` t1: Switch-on delay ` t2: Delay-on de-energisation ` t3: Delay time ` t4: Waiting period
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Preparing for operation
` Supply voltage
Supply voltage AC DC
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
Safety gate without detection of shorts across con­tacts
S21
S22
S21
S22
S11
S12
S32
S11
S12
S32
S1
S11
S12
S1
A1
A2
S12
S21
S22 S32
L+
L-
S1
Safety gate with detection of shorts across contacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S11
S12
S21 S22
S12
S32
S1
S2
NSG-D-2-308-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
` Reset circuit
Reset circuit E-STOP wiring, safety gate Safety gate (dual-channel) Automatic reset
S11
S14
Monitored reset
S33
S34
S3
` Feedback loop
Feedback loop Automatic reset Monitored reset Contacts from external contactors
S11 S14
13 (23) 14 (24)
K5
K6
K5
K6
L1
N
` Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
S11
S14
S33
S34 13 (23) 14 (24)
K5
K6
K5
K6
S2S1
S3
L1
N
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Terminal configuration
Installation
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
Dimensions
* with cage clamp terminals
94 (3.70")
* 101 (3.98")
121 (4.76")
22,5
(0.88")
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Notice
Service life graph
This data sheet is only intended for use during configuration. For installation
10
and operation, please refer to the op­erating instructions supplied with the unit.
D Nennbetriebstrom (A)
GB Nominal operating current (A)
F Courant coupé (A)
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
Technical details
Electrical data
Supply voltage Supply voltage U Voltage tolerance -15 %/+10 % Power consumption at U Residual ripple DC 20 % Voltage and current at Input circuit DC: 24.0 V 35.0 mA Reset circuit DC: 24.0 V 35.0 mA Feedback loop DC: 24.0 V 3.5 mA Number of output contacts Safety contacts (S) instantaneous: 2 Safety contacts (N/O), delayed: 1 Category of output contacts in accordance with EN 954-1 Safety contacts (S) instantaneous: 4 Delay time <30 s 3 Delay time >30 s 1 Order no.: 777602, 787602 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Safety contacts, delayed: AC1 at 240 V I
Safety contacts, delayed: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Safety contacts, delayed: AC15 at 230 V I Safety contacts, delayed: DC13 at 24 V (6 cycles/min) I Contact material AgSnO2 + 0.2 µm Au
DC 24 V
B
DC 3.5 W
B
DC13: 24 V
1
0.1
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
: 0.01 A , I
min
P
: 1250 VA
max
: 0.01 A , I
min
P
: 125 W
max
: 0.01 A , I
min
: 1250 VA
P
max
: 0.01 A , I
min
P
: 125 W
max
: 1.5 A
max
: 2.0 A
max
: 2.0 A
max
: 4.0 A
max
3
AC15: 230 V
3
: 5.0 A
max
: 5.0 A
max
: 5.0 A
max
: 5.0 A
max
3
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10 NL Aantal schakelingen x 10
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Electrical data
External contact fuse protection (IK = 1 kA) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 6 A Safety contacts, delayed: 6 A Blow-out fuse, slow Safety contacts: 4 A Safety contacts, delayed: 4 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 4 A Safety contacts, delayed: 4 A Max. overall cable resistance R input circuits, reset circuits single-channel at U dual-channel without detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U
Times
Switch-on delay with automatic reset typ. 300 ms with automatic reset max. 550 ms with automatic reset after power on typ. 350 ms with automatic reset after power on max. 750 ms on monitored reset with rising edge typ. 30 ms on monitored reset with rising edge max. 60 ms Delay-on de-energisation with E-STOP typ. 15 ms with E-STOP max. 30 ms with power failure typ. 100 ms with power failure max. 200 ms Recovery time at max. switching frequency 1/s after E-STOP 50 ms +tv after power failure 300 ms Delay time tv selectable 0,1 – 3 s Order no.: 77601, 787601
DC 100 Ohm
B
lmax
DC 150 Ohm
B
DC 15 Ohm
B
1 – 30 s Order no.: 77602, 787602
Repetition accuracy 2 % Time accuracy -20 %/+20 % Waiting period with a monitored reset 300 ms Min. start pulse duration with a monitored reset 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 20 ms
Environmental data
EMC EN 60947-5-1, EN 61000-6-2, EN 61000-6-3 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage EN 60947-1 Ambient temperature -10 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV1P
Mechanical data
Max. cross section of external conductors with screw terminals 1 core flexible 0.25 - 2.50 mm² , 24 - 12 AWG Order no.: 777601, 777602 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25 - 1.00 mm² , 24 - 16 AWG Order no.: 777601, 777602 without crimp connectors or with TWIN crimp connectors 0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 777601, 777602 Torque setting with screw terminals 0.50 Nm Order no.: 777601, 777602 Max. cross section of external conductors with cage clamp termi­nals/spring-loaded terminals: Flexible without crimp connectors Cage clamp terminals/spring-loaded terminals: Terminal points per connection Stripping length 8 mm Order no.: 787601, 787602 Dimensions Height 101.0 mm Order no.: 787601, 787602
Width 22.5 mm Depth 121.0 mm Weight 225 g Order no.: 787601, 787602
0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 787601, 787602
2 Order no.: 787601, 787602
94.0 mm Order no.: 777601, 777602
230 g Order no.: 777601, 777602
The standards current on 09/03 apply.
Conventional thermal current
(A) at UBDC
I
th
1 contact 5.00 A 2 contacts 3.70 A 3 contacts 3.00 A
Order reference
Type Features Terminals Order no.
PNOZ XV1P 24 VDC 3 s selectable Screw terminals 777 601 PNOZ XV1P C 24 VDC 3 s selectable Cage clamp terminals 787 601 PNOZ XV1P 24 VDC 30 s selectable Screw terminals 777 602 PNOZ XV1P C 24 VDC 30 s selectable Cage clamp terminals 787 602
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-308-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-8