Emergency Stop Relays, Safety Gate PNOZ
Category 4, EN 954-1
PNOZ e1p
Technical details PNOZ e1p
Electrical data
Supply voltage 24 VDC
Tolerance 80 ... 125 %
Power consumption no load: 2 W
Residual Ripple DC 20 %
Outputs 2 safety outputs
1 auxiliary output
Switching capability UB <26.5 V: 24 V/2 A/50 W
UB >26.5 V: 24 V/1.5 A/40 W
2 Safety outputs parallel:
24 V/3 A/80 W
Voltage and current at
input and reset circuits and
feedback control loop 24 VDC, 5 mA
Emergency stop relay and safety
gate monitor in accordance with
VDE 0113-1, 11/98, EN 60204-1,
12/97 and IEC 204-1, 11/98
Features
● Monitored manual or automatic
reset can be selected
● 2 safe semiconductor outputs
● 1 auxiliary semiconductor out-
put
● Auxiliary output can also be
used as a diagnostic output
● Option for detecting shorts
across the input contacts
● Applications in accordance with
EN 954-1, 07/96, category 2, 3
or 4
● Self-test after UB is supplied
● Continuous self-monitoring
● Regular switch-off test of the
safety outputs
Approval
auxiliary output and test pulse outputs 24 VDC/0.5 A
Times
Delay-on energisation manual reset: 180 ms
automatic reset: 100 ms
Delay-on de-energisation max. 35 ms
Switch-on delay
Simultaneity channel 1/2
Max. Supply Interruption before max. 20 ms
de-energisation
Environmental data
Storage temperature -25 ... 70 °C
Mechanical data
Max. cross section of external conductor,
single core
multi-core conductor (2 conductors with
identical cross section) flexible with crimp connector without
Torque setting for terminals 0.5 ... 0.6 Nm (screws)
Dimensions (H x W x D) 87 x 22.5 x 121 mm
Weight 170 g
3 s (on initial reset once UBis supplied)
¥
fl
exible without crimp connector:
0.2 ... 2.5 mm
flexible with crimp connector:
0.25 ... 2.5 mm
plastic sleeve: 0.25 ... 1 mm
flexible with TWIN crimp connector with
plastic sleeve: 0.5 ... 1.5 mm
1
2
2
2
2
PNOZ e1p
●
●
●
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-289-09/01
Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

Emergency Stop Relays, Safety Gate
Category 4, EN 954-1
PNOZ e1p
Description
● 22.5 mm P-99 housing,
DIN-Rail mounting
● Semiconductor outputs,
short-circuit proof:
– 2 safety outputs
– 1 auxiliary output
– 2 test pulse outputs
● Connections for
– E-STOP button
– safety gate limit switch
– Pressure mat, light barrier and
proximity switch evaluation
devices
– Reset button
● Auxiliary output can also be used
as a diagnostic output
It is possible to program the driver
for reading diagnostic data
yourself. However, the CD „PLC
Drivers for PNOZelog“ is also
Internal wiring diagram
Input
circuit
B
U
A2
A1
available. This contains preprogrammed drivers for the
following controllers:
- SIMATIC S7
● LEDs for switching status and
faults in channel 1/2 and for
supply voltage
● Shorts across the input contacts
are detected by means of test
pulse outputs
● Increase in the number of safety
contacts available by connecting
expander modules
Operating modes
● Single-channel operation
● Dual-channel operation
● Automatic reset
● Monitored manual reset
Reset circuit/
feedback
control loop
S34
S12
S22
Mode
Y4
Auxiliary
output
Y32
Y5
Test pulse
outputs
S21
S11
Safety
outputs
Power
supply
&
14
24
&
&
Input circuit
µController 1
µController 2
Test pulse
outputs
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-289-09/01
Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

Emergency Stop Relays, Safety Gate
14
K2 K3
24
1L1
1L2
A1
A2
A1 S34
K3
K2
S3
PNOZ e1p
Category 4, EN 954-1
PNOZ e1p
External wiring
● Example 1
Single-channel emergency stop
wiring with monitored manual reset
without short-circuit recognition
A1
A1
S1
S3
S34
S12 S22A1Y4
● Example 2
Dual-channel emergency stop wiring
with monitored manual reset without
short-circuit recognition
A1 A1
S1
A1
A1
S3
● Example 4
Dual-channel safety gate control with
automatic reset without start-up test
and without short-circuit recognition
A1
S11
A1
S1S1
S12
S22
S2
Y4
S34
A1
● Example 5
Dual-channel safety gate control with
monitored manual reset without
short-circuit recognition
A1
A1
A1
S1S3S1
S12
S22
S2
– Key
S1/S2: E-STOP or safety gate switch
S3: Reset button
Switch operated
Gate open
Gate closed
● Increase in the number of contacts
The number of output contacts can
be increased by using expander
modules or relays/contactors with
positive-guided contacts.
1
S12 S22
S34
Y4
● Example 3
Dual-channel emergency stop wiring
with monitored manual reset and
shorts across the input contacts are
detected
S11 S21
S1
S12 S22
A1
A1
S3
S34
Y4
Y4
S34
A1
● Example 6
Dual-channel safety gate control with
automatic reset and start-up test,
shorts across the input contacts are
detected
S11
S21
S1S1
S12
S22
S2
S21
S34A1Y4
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-289-09/01
Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

Emergency Stop Relays, Safety Gate
Category 4, EN 954-1
PNOZ e1p
General details
Unless stated otherwise in the technical details for the specific unit
Electrical data
AC frequency range 50 ... 60 Hz
DC residual ripple 160 %
Contact material AgSnO
Continuous duty 100 %
Environmental data
EMC EN 50081-1, 01/92, EN 50082-2, 03/95
Vibration in accordance with
EN 60068-2-6, 04/95 Frequency: 10 ... 55 Hz,
Climatic suitability DIN IEC 60068-2-3, 12/86
Airgap creepage DIN VDE 01101 Part 1, 04/97
Ambient temperature -10 ... +55 °C
Storage temperature -40 ... +85 °C
Mechanical data
Torque setting for connection terminals 0.6 Nm (screws)
Mounting position Any
Housing material Thermoplastic Noryl SE 100
Protection types Mounting: IP 54
2
Amplitude: 0.35 mm
Housing: IP 40
Terminals: IP 20
The units were tested in accordance with the standards applicable at the
time of development.
Order reference
Type U
PNOZ e1p 24 VDC 774 130
Order references accessories
Description Order number
PLC Drivers for PNOZelog 874 130...
1)
When ordering, please state the type of licence you require after the order number
(..B for basic licence, ..K for copy licence, ..G for general licence, ..U for update licence),
e.g. 301 400B.
B
Order number
1)
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-289-09/01
Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de