Mitsubishi PLH-1.6KKHB.UK, PLH-2.5KKHB.UK, PLH-2KKHB.UK Service Manual

0 (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1997

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPLIT-TYPE, HEAT PUMP, AIR CONDITIONERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. OC147

TECHNICAL & SERVICE MANUAL

Series PLH Ceiling Cassettes

Indoor unit [Model names]

PLH-1.6KKHB

PLH-2KKHB

PLH-2.5KKHB

[Service Ref.]

PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK

This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150 and this manual in a set.

[Service Ref.] PUH-1.6VKA3·UK PUH-2VKA2·UK PUH-2.5VKA2·UK

INDOOR UNIT

FILTER

CHECK MODE

TEST RUN

CONTENTS

 

1.

FEATURES..........................................

2

2. PART NAMES AND FUNCTIONS ......

3

3.

SPECIFICATIONS...............................

6

4.

DATA ...................................................

9

5. OUTLINES AND DIMENSIONS........

13

6. WIRING DIAGRAM ...........................

15

7.

REFRIGERANT SYSTEM DIAGRAM .....

16

8. OPERATION FLOW-CHART ............

17

9. MICROPROCESSOR CONTROL.....

21

10. TROUBLESHOOTING ......................

43

11. 4-WAY AIR FLOW SYSTEM .............

51

12. SYSTEM CONTROL .........................

52

13. DISASSEMBLY PROCEDURE .........

57

14.

PARTS LIST......................................

60

15.

OPTIONAL PARTS ...........................

64

REMOTE CONTROLLER

The Slim Line.

From Mitsubishi Electric.

1 FEATURES

Series PLH Ceiling Cassettes

FILTER

CHECK MODE

TEST RUN

 

Indoor unit

Remote controller

 

 

 

 

 

Service Ref.

Cooling capacity/Heating capacity

 

 

W

Btu/h

 

 

 

 

PLH-1.6KKHB.UK

4,400/4,650[6,050]

15,000/15,900[20,600]

 

 

 

PLH-2KKHB.UK

5,400/5,800[7,200]

18,400/19,800[24,600]

 

 

 

PLH-2.5KKHB.UK

6,300/[7,200/9,300]

21,500/24,600[31,700]

 

 

 

1.PURSUING CONPACTNESS

(1)Panel size and body volume reduced to 64% of previous models

The width and depth of the panel have been reduced by 19cm respectively, resulting in a compact model which fits smaller environments (like shops) perfectly.

(2)Multi-application panels flexibly adapt to installation conditions.

Space panel and Wide panel may be installed on ceilings with shallow depth using the exiting opening .

2."SMUDGE-FREE", PRECISELY TARGETED AIRFLOW SYSTEM

The new control system regulates airflow to prevent smudging. A projection inside the air passage distributes air evenly over the top and bottom of the vane. Two projections on the air outlet work to prevent cooled air from rising to the celling, and also to stop outside air being dragged into the cooled air stream.

3.AIRFLOW ADJUSTABLE TO ANY INDOOR ENVIRONMENT

Airflow can be adjusted according to celling height and the number of air outlets. "Wide Zoming Flow" creates anoptimum airflow for any indoor environment.

4.A FURTHER REFINEMENT OF COMFORT WITH NOISE SUPPRESION

The celling 4-way airflow cassette has a special "silent-design". The "2-Tap"system allows a choice between silent and standard modes according to the height of the cellig. For ordinary residenced which have a low celling, selection of the silent mode will result in remarkable noise reductions.

5.ECONOMICAL AND EASY MAINTENANCE

(1)Push-open grill

Filter clogging is widely recognized as a cause of reduced perfomance, but up until now it has been troublesome to clean filters. With the "push-open grill" the fillter can be smoothly opened out at the push of a button, enabling speedy cleaning.

(2)An unprecedented level of vane-cleaning

The unique airflow system prevents the intake of indoor air. Dewing therefore does not occur, and the vane is flockless. The resulting level of dirt on the vane due to tobacco smoke, dust, etc. is very light,and can be wiped off easily with a neutral detergent

(3)Long-life fillter

This new celling 4-way airflow cassette employs a long life fillter which requires no maintenance for up to 2,500 hours of operation in general office environments. It adds uo to an ideal blend of comfort and low maintenance.

2

6.COMPACT DIMENSIONS MEAN EASY INSTALLATION

(1)Carefree suspension work with lightweight unit

The new unit weighs in at 20kg (9kg lighter than the previous model) and is easy to handle and install. What's more, suspension work is facillitated by compact dimensions ensuring a snug fit.

(2)Smooth installation with "one-direction"bolts

Suspension bolts can be fixes consistently from one direction easing suspension work.

(3)Trouble-free fitting work with slender refrigerant piping

Refrigerant piping has been reduced in size, and pipe-curving work at the installation site can now be completed quickly and economically. In addition, refrigerant and drain piping are set at different corners, which means that flare connections and drain piping heat insulation work can be smoothly and reliably implemented.

(4)Easy-access terminal and control panels for efficient wiring

When performing wiring work, progress can be checked on the power source terminal and control panels simply by removing the electrical parts cover. Adress setting can also be done easily from beneath at a convenient angle.

(5)"One-push"to provisionally position front panel

Panel weight has been redused from 7kg to 3.7kg. The previous 3-step process for provisionally positioning the panel has been streamlined, and now a simple "one-push" action at the diagonal corners fixed it into place, resulting in major time-saving.

2 PART NAMES AND FUNCTIONS

Indoor (Main) Unit

PLH-1.6KKHB·UK

PLH-2KKHB·UK

PLH-2.5KKHB·UK

Horizontal Air Outlet

Sets airflow horizontal automatically during cooling or dehumidifying.

Downward Air Outlet Sets airflow downward automatically during heating.

Filters

Remove dust and pollutants from inhaled air

Grill

Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.

Air Intake

Inhales air from room.

3

Remote controller

Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

Operation buttons

 

button

button

This switches between

This sets or switches the

continuous operation and the

current time. start time and

timer operation.

stop time.

button

 

Press this button to switch

 

the cooler electronic dry

 

(dehumidify) automatic and

 

heater modes.

 

 

 

 

FILTER

 

 

CHECK MODE

 

 

TEST RUN

TEMP button

 

This sets the room

 

temparature The temparature

 

setting can be performed in

 

1°C units

 

 

Setting range

4

Cooler

19°C to 30°C

 

Heater

17°C to 28°C

 

This model name of the

button

remote controller is indicated.

This switches the horizontal

 

 

 

 

fan motion ON and OFF.

 

 

(This button dose not operate in

 

 

this model)

button

This sets the ventilation fan speed.

ON/OFF button

This switches between the operation and stop modes each time it is pressed. The lamp on this butoon lights during operation.

button

This adjusts the vertical angle of the ventilation.

FILTER button

This resets the filter service indication display.

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation. Do not use it for normal operation.

4

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

display

The current time , start time and stop time can be displayed in tensecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.

In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.

display

This displays the air direction.

display

This indicates when the continous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

This indicates when the standby mode is set from the time the sleep

operation starts until the heating air 240KA is discharged.

DEFROST display

This indicates when the defrost operation is performed.

CHECK display

display

This indicates when a malfunction has occurred in the unit which should

This displays the selected setting

be checked.

temperature.

 

display

 

The selected fan speed is displayed.

 

display

 

The temperature of the suction air is

 

displayed during operation. The

FILTER

display range is 8° to 39°C. The

CHECK MODE

display flashes 8°C when the actual

TEST RUN

temperature is less than 8° and

 

 

flashes 39°C when the actual

 

temperature is greater than 39°C.

 

Operation lamp

 

This lamp lights during operation,

 

goes off when the unit stops and

 

flashes when amalfunction occurs.

display

This lamp lights when electricity is supplied to the unit.

FILTER Display

This lamp lights when the filter need to be cleaned.

CHECK MODE

display

TEST RUN

This display lights in the check mode or when a test operation is performed.

Caution

Only the display lights when the unit is stopped and power supplied to the unit.

When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and TEMP button do not operate.

“NOT AVAILABLE” is displayed when the k button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

5

3

 

SPECIFICATIONS

 

 

 

 

 

 

Service Ref.

 

 

 

 

 

Item

 

 

 

 

 

Function

 

 

 

Capacity

 

 

Btu/h

 

 

W

 

 

 

 

 

Total input

 

 

kW

 

Service Ref.

 

 

 

 

Power supply(phase, cycle,voltage)

 

 

 

Input

 

 

kW

 

 

Running current

 

 

A

 

 

Starting current

 

 

A

 

External finish

 

 

 

UNIT

Heat exchanger

 

 

kW

 

Fan motor output

 

 

 

 

Fan(drive) x No.

 

 

 

INDOOR

Booster heater

 

 

kW

 

 

Airflow(Low-High)

 

 

K/min(CFM)

 

 

External static pressure

 

mmAq,Pa

 

Operation control & Thermostat

 

 

 

 

 

 

 

 

Noise level(Low-High)

 

 

dB(A)

 

Cond. drain conn. O.D.

 

 

mm,(in.)

 

 

 

W

 

mm,(in.)

 

Dimensions

D

 

mm,(in.)

 

 

 

H

 

mm,(in.)

 

Weight

 

 

kg,(lbs)

 

Service Ref.

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Input

 

 

kW

 

 

Running current

 

 

A

 

 

Starting current

 

 

A

 

External finish

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

UNIT

 

Model

 

 

 

 

Motor output

 

 

kW

OUTDOOR

 

Fan(drive) x No.

 

 

 

 

 

Starter type

 

 

 

 

 

Protection devices

 

 

 

 

Heat exchanger

 

 

 

 

 

Fan motor output

 

 

kW

 

 

 

 

 

 

Airflow

 

 

K/min(CFM)

 

Defrost method

 

 

 

 

Noise level

 

 

dB(A)

 

 

 

W

 

mm,(in.)

 

Dimensions

D

 

mm,(in.)

 

 

 

H

 

mm,(in.)

 

Weight

 

 

kg,(lbs)

PIPING

Refrigerant

 

 

 

 

Charge

 

 

kg,(lbs)

 

 

 

 

REEFRIGERANT

Pipe size O.D.

Liquid

 

mm,(in.)

Gas

 

mm,(in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

Between the indoor & outdoor unit

Height difference

 

 

 

Piping length

 

PLH-1.6KKHB.UK

Cooling

 

Heating

 

15,000

 

15,900[20,600]

4,400

 

4,650[6,050]

1.59

 

1.51[2.91]

 

PLH-1.6KKHB.UK

 

Single. 50Hz. 220-240V

0.15

 

0.10[1.50]

0.64

 

0.45[6.28]

0.70

 

0.50[6.63]

Galvanized sheets with gray heat insulation

Plate fin coil

Turbo fan (direct) x 1

0.030

13-16(460-565)

0(direct blow)

[1.4]

Remote controller & built-in

32-37

32(1-1/4)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 253(10)

PANEL : 30(1-1/8)

UNIT : 20(44)

PANEL :3.7(8)

 

PUH-1.6VKA3.UK

 

Single. 50Hz. 220-240V

1.44

 

1.41

6.74

 

6.60

33

Munsell 5Y 7/1

Capillary tube

Hermetic

RH247VFC

1.2

Line start

Inner thermostat, High pressure switch

Plate fin coil

Propeller (direct) x1

0.065

45(1,590)

Reverse cycle

49

870(34-1/4)

295+24 (11-5/8 add 1)

650(25-5/8)

53(117)

R-22

2.2(4.8)

9.52 (3/8)

15.88(5/8)

Flared

Flared

Max. 40m

Max. 40m

6

Mitsubishi PLH-1.6KKHB.UK, PLH-2.5KKHB.UK, PLH-2KKHB.UK Service Manual

Service Ref.

Item

Function

Capacity

 

Btu/h

 

W

 

 

 

Total input

 

kW

 

Service Ref.

 

 

 

Power supply(phase, cycle,voltage)

 

 

Input

 

kW

 

Running current

 

A

 

Starting current

 

A

 

External finish

 

 

UNIT

Heat exchanger

 

kW

Fan motor output

 

 

Fan(drive) x No.

 

 

INDOOR

Booster heater

 

kW

 

Airflow(Low-High)

 

K/min(CFM)

 

External static pressure

mmAq,Pa

 

Operation control & Thermostat

 

 

 

 

 

 

Noise level(Low-High)

 

dB(A)

 

Cond. drain conn. O.D.

 

mm,(in.)

 

 

W

mm,(in.)

 

Dimensions

D

mm,(in.)

 

 

H

mm,(in.)

 

Weight

 

kg,(lbs)

 

Service Ref.

 

 

 

Power supply (phase, cycle, voltage)

 

 

Input

 

kW

 

Running current

 

A

 

Starting current

 

A

 

External finish

 

 

 

Refrigerant control

 

 

 

Compressor

 

 

UNIT

Model

 

 

Motor output

 

kW

OUTDOOR

Fan(drive) x No.

 

 

 

Starter type

 

 

 

Protection devices

 

 

 

Heat exchanger

 

 

 

Fan motor output

 

kW

 

 

 

Airflow

 

K/min(CFM)

 

Defrost method

 

 

 

Noise level

 

dB(A)

 

 

W

mm,(in.)

 

Dimensions

D

mm,(in.)

 

 

H

mm,(in.)

 

Weight

 

kg,(lbs)

PIPING

Refrigerant

 

 

Charge

 

kg,(lbs)

 

 

REEFRIGERANT

Pipe size O.D.

Liquid

mm,(in.)

Gas

mm,(in.)

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

Between the indoor & outdoor unit

Height difference

 

 

Piping length

 

PLH-2KKHB.UK

Cooling

 

Heating

 

18,400

 

19,800[24,600]

5,400

 

5,800[7,200]

2.34

 

2.32[3.72]

 

PLH-2KKHB.UK

 

Single. 50Hz. 220-240V

0.14

 

0.10[1.50]

0.65

 

0.45[6.28]

0.72

 

0.50[6.63]

Galvanized sheets with gray heat insulation

Plate fin coil

Turbo fan (direct) x 1

0.030

13-16(460-565)

0(direct blow)

[1.4]

Remote controller & built-in

32-37

32(1-1/4)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 253(10)

PANEL : 30(1-1/8)

UNIT : 20(44)

PANEL :3.7(8)

 

PUH-2VKA2.UK

 

Single. 50Hz. 220-240V

2.20

 

2.22

9.86

 

9.95

45

Munsell 5Y 7/1

Capillary tube

Hermetic

NH38VMD

1.7

Line start

Inner thermostat, HP switch

Plate fin coil

Propeller (direct) x1

0.065

45(1590)

Reverse cycle

49

870(34-1/4)

295+24 (11-5/8 add 1)

650(25-5/8)

64(141)

R-22

2.2(4.8)

9.52 (3/8)

15.88(5/8)

Flared

Flared

Max. 40m

Max. 40m

7

Service Ref.

Item

Function

Capacity

 

Btu/h

 

W

 

 

 

Total input

 

kW

 

Service Ref.

 

 

 

Power supply(phase, cycle,voltage)

 

 

Input

 

kW

 

Running current

 

A

 

Starting current

 

A

 

External finish

 

 

UNIT

Heat exchanger

 

kW

Fan motor output

 

 

Fan(drive) x No.

 

 

INDOOR

Booster heater

 

kW

 

Airflow(Low-High)

 

K/min(CFM)

 

External static pressure

mmAq,Pa

 

Operation control & Thermostat

 

 

 

 

 

 

Noise level(Low-High)

 

dB(A)

 

Cond. drain conn. O.D.

 

mm,(in.)

 

 

W

mm,(in.)

 

Dimensions

D

mm,(in.)

 

 

H

mm,(in.)

 

Weight

 

kg,(lbs)

 

Service Ref.

 

 

 

Power supply (phase, cycle, voltage)

 

 

Input

 

kW

 

Running current

 

A

 

Starting current

 

A

 

External finish

 

 

 

Refrigerant control

 

 

 

Compressor

 

 

UNIT

Model

 

 

Motor output

 

kW

OUTDOOR

Fan(drive) x No.

 

 

 

Starter type

 

 

 

Protection devices

 

 

 

Heat exchanger

 

 

 

Fan motor output

 

kW

 

 

 

Airflow

 

K/min(CFM)

 

Defrost method

 

 

 

Noise level

 

dB(A)

 

 

W

mm,(in.)

 

Dimensions

D

mm,(in.)

 

 

H

mm,(in.)

 

Weight

 

kg,(lbs)

PIPING

Refrigerant

 

 

Charge

 

kg,(lbs)

 

 

REEFRIGERANT

Pipe size O.D.

Liquid

mm,(in.)

Gas

mm,(in.)

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

Between the indoor & outdoor unit

Height difference

 

 

Piping length

 

PLH-2.5KKHB.UK

Cooling

 

Heating

 

21,500

 

24,600[31,700]

6,300

 

7,200[9,300]

2.60

 

2.33[4.43]

 

PLH-2.5KKHB.UK

 

Single. 50Hz. 220-240V

0.14

 

0.10[2.20]

0.61

 

0.45[9.20]

0.67

 

0.50[9.55]

Galvanized sheets with gray heat insulation

Plate fin coil

Turbo fan (direct) x 1

0.030

14-17(495-600)

0(direct blow)

[2.1]

Remote controller & built-in

35-39.5

32(1-1/4)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 660(26)

PANEL : 760(30)

UNIT : 253(10)

PANEL : 30(1-1/8)

UNIT : 21(46)

PANEL :3.7(8)

 

PUH-2.5VKA2.UK

 

Single. 50Hz. 220-240V

2.46

 

2.23

10.68

 

9.78

52

Munsell 5Y 7/1

Capillary tube

Hermetic

NH41VMD

2.0

Line start

Inner thermostat, HP switch

Plate fin coil

Propeller (direct) x1

0.085

50(1764)

Reverse cycle

52

870(34-1/4)

295+24 (11-5/8 add 1)

850(34-1/4)

68(150)

R-22

2.8(6.2)

9.52 (3/8)

15.88(5/8)

Flared

Flared

Max. 50m

Max. 50m

8

4

 

 

DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) COOLING CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

Outdoor intake air DB C

 

 

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

intake

20

 

 

 

25

 

30

 

 

 

 

 

35

40

 

 

 

 

 

45

 

 

 

 

air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB C

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4,439

 

1.27

 

4,317

 

 

1.33

4,159

 

1.43

 

3,990

 

1.53

3,812

 

1.64

 

3,624

 

1.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-1.6KKHB.UK

 

18

4,726

 

1.30

 

4,602

 

 

1.36

4,434

 

1.46

 

4,258

 

1.57

4,074

 

1.68

 

3,882

 

1.79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

5,017

 

1.32

 

4,899

 

 

1.38

4,724

 

1.50

 

4,542

 

1.61

4,352

 

1.72

 

4,154

 

1.84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

5,310

 

1.35

 

5,209

 

 

1.41

5,028

 

1.53

 

4,840

 

1.65

4,645

 

1.77

 

4,442

 

1.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5,448

 

1.88

 

5,299

 

 

1.96

5,104

 

2.11

 

4,897

 

2.26

4,678

 

2.41

 

4,447

 

2.56

 

 

PLH-2KKHB.UK

 

18

5,800

 

1.91

 

5,648

 

 

2.00

5,442

 

2.15

 

5,226

 

2.31

5,000

 

2.47

 

4,764

 

2.63

 

 

 

20

6,157

 

1.95

 

6,012

 

 

2.04

5,798

 

2.20

 

5,574

 

2.37

5,341

 

2.54

 

5,099

 

2.71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

6,517

 

1.99

 

6,392

 

 

2.08

6,171

 

2.25

 

5,940

 

2.42

5,700

 

2.61

 

5,451

 

2.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

6,356

 

2.08

 

6,182

 

 

2.17

5,955

 

2.34

 

5,713

 

2.51

5,472

 

2.68

 

5,207

 

2.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2.5KKHB.UK

 

18

6,767

 

2.13

 

6,589

 

 

2.22

6,349

 

2.39

 

6,097

 

2.57

5,841

 

2.74

 

5,571

 

2.92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

7,183

 

2.17

 

7,014

 

 

2.26

6,764

 

2.45

 

6,503

 

2.63

6,232

 

2.82

 

5,954

 

3.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

7,603

 

2.21

 

7,458

 

 

2.31

7,199

 

2.50

 

6,930

 

2.69

6,645

 

2.90

 

6,359

 

3.11

 

Note CA:Capacity (W)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C.:Power consumption (kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity correction factors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

 

 

 

 

 

 

 

 

 

Refrigerant piping length(one way)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5m

 

10m

 

 

15m

 

 

20m

 

25m

 

 

30m

 

 

35m

 

40m

 

 

45m

 

 

50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-1.6KKHB.UK

 

1.00

 

0.993

 

 

0.984

 

 

0.978

 

0.969

 

 

0.961

 

0.956

 

0.948

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2KKHB.UK

 

1.00

 

0.992

 

 

0.983

 

 

0.978

 

0.966

 

 

0.959

 

0.950

 

0.945

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2.5KKHB.UK

 

1.00

 

0.989

 

 

0.980

 

 

0.970

 

0.960

 

 

0.950

 

0.940

 

0.930

 

0.920

 

0.910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling performance curve(50Hz)

TOTAL INPUT (RATIO) CAPACITY (RATIO)

1.4

 

 

 

 

 

1.0

 

 

 

 

22

 

 

 

 

 

20

0.8

 

 

 

 

18

 

 

 

 

16

0.6

 

 

 

 

 

1.4

 

 

 

 

 

1.2

 

 

 

 

22

 

 

 

 

20

 

 

 

 

 

18

1.0

 

 

 

 

16

 

 

 

 

 

0.8

 

 

 

 

 

0.6

 

 

 

 

 

0.4

 

 

 

 

 

-5

5

15

25

35

46

1.2

 

OUTDOOR DB(°C)

INDOOR WB(°C)

INDOOR WB(°C)

9

2) HEATING CAPACITY

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

Outdoor intake air WB C

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-10

 

 

 

-5

 

0

 

 

 

 

5

10

 

 

 

 

 

15

 

 

air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB C

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

CA

 

P.C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

3,184

 

1.03

 

3,650

 

 

1.14

4,160

 

1.25

 

4,714

 

1.38

5,312

 

1.51

 

5,952

 

1.64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-1.6KKHB.UK

 

20

3,049

 

1.11

 

3,506

 

 

1.23

4,003

 

1.35

 

4,538

 

1.48

5,112

 

1.62

 

5,724

 

1.77

 

 

25

2,930

 

1.18

 

3,364

 

 

1.31

3,844

 

1.44

 

4,370

 

1.59

4,942

 

1.74

 

5,560

 

1.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

3,972

 

1.58

 

4,552

 

 

1.75

5,188

 

1.93

 

5,880

 

2.11

6,625

 

2.31

 

7,424

 

2.52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2KKHB.UK

 

20

3,803

 

1.71

 

4,373

 

 

1.89

4,993

 

2.08

 

5,661

 

2.28

6,376

 

2.49

 

7,139

 

2.71

 

 

25

3,655

 

1.81

 

4,196

 

 

2.01

4,795

 

2.22

 

5,451

 

2.44

6,165

 

2.67

 

6,935

 

2.91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

4,931

 

1.59

 

5,651

 

 

1.76

6,441

 

1.93

 

7,299

 

2.12

8,225

 

2.32

 

9,216

 

2.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2.5KKHB.UK

 

20

4,721

 

1.71

 

5,429

 

 

1.89

6,198

 

2.09

 

7,027

 

2.29

7,916

 

2.50

 

8,863

 

2.73

 

 

25

4,537

 

1.82

 

5,209

 

 

2.02

5,952

 

2.23

 

6,767

 

2.45

7,653

 

2.68

 

8,609

 

2.92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note CA:Capacity (W)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C.:Power consumption (kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating capacity correction factors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

 

 

 

 

 

 

 

 

 

Refrigerant piping length(one way)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5m

 

10m

 

 

15m

 

 

20m

 

25m

 

 

30m

 

35m

 

40m

 

 

45m

 

 

50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-1.6KKHB.UK

 

1.00

 

1.00

 

 

1.00

 

 

1.00

 

1.00

 

 

1.00

0.998

 

0.995

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2KKHB.UK

 

1.00

 

1.00

 

 

1.00

 

 

1.00

 

1.00

 

 

1.00

0.998

 

0.995

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-2.5KKHB.UK

 

1.00

 

1.00

 

 

1.00

 

 

1.00

 

1.00

 

 

1.00

0.998

 

0.995

 

0.993

 

0.990

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating performance curve(50Hz)

CAPACITY (RATIO)

TOTAL INPUT (RATIO)

1.4

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

1.2

 

 

 

 

 

 

 

 

 

25INDOOR DB ( C)

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

 

 

 

 

 

 

25INDOOR DB ( C)

 

 

 

 

 

 

 

 

 

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5 10 15

 

-12-10 -5

 

OUTDOOR WB( C)

10

2. ELECTRICAL DATA

Indoor unit 220V 50Hz 1phase

Outdoor unit 220V 50Hz 1phase

Service Ref.

Indoor unit

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

 

Outdoor unit

PUH-1.6VKA3.UK

PUH-2VKA2.UK

PUH-2.5VKA2.UK

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

Cool

Heat

Cool

Heat

Cool

Heat

 

 

 

 

 

 

 

 

Capacity (W)

4,300

4,550[5,720]

5,300

5,700[6,870]

6,200

6,900[8,660]

 

 

 

 

 

 

 

 

Total Input (kW)

1.48

1.40[2.57]

2.24

2.22[3.39]

2.53

2.25[4.01]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

0.12

0.08[1.25]

0.12

0.08[1.25]

0.12

0.09[1.85]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Current (A)

0.60

0.41[5.75]

0.61

0.42[5.76]

0.57

0.42[8.44]

 

 

 

 

 

 

 

 

Starting current (A)

0.66

0.45[6.14]

0.67

0.46[6.14]

0.63

0.46[8.79]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

1.36

1.32

2.12

2.14

2.41

2.16

 

Outdoor

 

 

 

 

 

 

 

 

Starting current (A)

30

30

43

43

52

52

 

Current (A)

6.79

6.59

9.83

9.93

11.18

10.02

 

 

 

 

 

 

 

 

 

Indoor unit 230V 50Hz 1phase

Outdoor unit 230V 50Hz 1phase

Service Ref.

Indoor unit

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

 

Outdoor unit

PUH-1.6VKA3.UK

PUH-2VKA2.UK

PUH-2.5VKA2.UK

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

Cool

Heat

Cool

Heat

Cool

Heat

 

 

 

 

 

 

 

 

Capacity (W)

4,350

4,600[5,890]

5,350

5,750[7,040]

6,250

7,050[8,980]

 

 

 

 

 

 

 

 

Total Input (kW)

1.54

1.45[2.74]

2.29

2.27[3.56]

2.57

2.29[4.22]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

0.14

0.09[1.38]

0.13

0.09[1.38]

0.13

0.09[2.02]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Current (A)

0.62

0.43[6.02]

0.63

0.44[6.03]

0.59

0.43[8.82]

 

 

 

 

 

 

 

 

Starting current (A)

0.68

0.47[6.39]

0.69

0.48[6.39]

0.65

0.47[9.19]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

1.40

1.36

2.16

2.18

2.44

2.20

 

Outdoor

 

 

 

 

 

 

 

 

Starting current (A)

32

32

44

44

52

52

 

Current (A)

6.76

6.57

9.78

9.87

10.94

9.86

 

 

 

 

 

 

 

 

 

Indoor unit 240V 50Hz 1phase

Outdoor unit 240V 50Hz 1phase

Service Ref.

Indoor unit

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

 

Outdoor unit

PUH-1.6VKA3.UK

PUH-2VKA2.UK

PUH-2.5VKA2.UK

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

Cool

Heat

Cool

Heat

Cool

Heat

 

 

 

 

 

 

 

 

Capacity (W)

4,400

4,650[6,050]

5,400

5,800[7,200]

6,300

7,200[9,300]

 

 

 

 

 

 

 

 

Total Input (kW)

1.59

1.51[2.91]

2.34

2.32[3.72]

2.60

2.33[4.43]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

0.15

0.10[1.50]

0.14

0.10[1.50]

0.14

0.10[2.20]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Current (A)

0.64

0.45[6.28]

0.65

0.45[6.28]

0.61

0.45[9.20]

 

 

 

 

 

 

 

 

Starting current (A)

0.70

0.50[6.63]

0.72

0.50[6.63]

0.67

0.50[9.55]

 

 

 

 

 

 

 

 

 

unit

Input (kW)

1.44

1.41

2.20

2.22

2.46

2.23

 

Outdoor

 

 

 

 

 

 

 

 

Starting current (A)

33

33

45

45

52

52

 

Current (A)

6.74

6.60

9.86

9.95

10.68

9.78

 

 

 

 

 

 

 

 

 

11

3. STANDARD OPERATION DATA

 

Service Ref.

 

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

Cooling

 

Heating

Cooling

 

Heating

Cooling

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

Total

Capacity

W

4,400

 

4,650

5,400

 

5,800

6,300

 

7,200

 

 

 

 

 

 

 

 

 

 

 

Input

kW

1.59

 

1.51

2.34

 

2.32

2.60

 

2.33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit Service Ref.

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase,Hz

 

 

1,50

 

1,50

 

1,50

circuit

 

 

 

 

 

 

 

 

 

 

 

Volts

V

 

240

 

240

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

Amperes

A

0.64

 

0.45

0.65

 

0.45

0.61

 

0.45

 

 

 

 

 

 

 

 

 

 

 

Phase,Hz

 

 

1,50

 

1,50

 

1,50

 

Outdoor unit Service Ref.

PUH-1.6VKA3.UK

PUH-2VKA2.UK

PUH-2.5VKA2.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts

V

 

240

 

240

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

A

6.74

 

6.60

9.86

 

9.95

10.68

 

9.78

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge pressure

MPa·G

1.80

 

1.70

1.90

 

1.94

1.95

 

1.71

 

(O/F·G)

(18.3)

 

(17.3)

(19.3)

 

(19.7)

(19.8)

 

(17.4)

circuit

 

 

 

 

Suction pressure

MPa·G

0.54

 

0.40

0.46

 

0.34

0.50

 

0.36

 

(O/F·G)

(5.51)

 

(4.08)

(4.69)

 

(3.47)

(5.1)

 

(3.67)

 

 

 

 

 

Refrigerant

Discharge temperature

C

78.7

 

77.2

84.0

 

86.4

82.8

 

76.0

 

 

 

 

 

 

 

 

 

 

 

Condensing temperature

C

48.5

 

50.7

 

51.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction temperature

C

8.5

 

0.7

4.8

 

–1.8

6.7

 

–1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Ref. pipe length

m

5

 

5

5

 

5

5

 

5

 

 

 

 

 

 

 

 

 

 

 

 

side

Intake air temperature

DB C

27

 

20

27

 

20

27

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

WB C

19

 

15

19

 

15

19

 

15

 

 

 

 

 

 

 

 

 

 

 

Discharge air temperature

DB C

16.1

 

35.2

15.0

 

39.4

13.8

 

41.2

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor side

 

WB C

24

 

6

24

 

6

24

 

6

 

Intake air temperature

DB C

35

 

7

35

 

7

35

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHF

 

0.83

 

0.76

 

0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BF

 

0.21

 

0.21

 

0.14

 

 

 

 

 

 

 

 

 

 

 

 

 

The unit of pressure has been changed to Mpa on the international system of unit (SI unit system.) The converted score against the traditional unit system can be gotten according to the formula below.

1 (Mpa·G)=10.2(O/F·G)

4. OUTLET AIR SPEED AND COVERAGE RANGE

 

Service Ref.

 

PLH-1.6KKHB.UK

PLH-2KKHB.UK

PLH-2.5KKHB.UK

 

 

 

 

 

 

Standard

Air flow

m3/min

16.0

16.0

17.0

Air speed

m/sec.

5.6

5.6

5.9

 

 

 

 

 

 

 

 

Coverage range

m

6.0

6.0

6.4

 

 

 

 

 

 

ceiling

Air flow

m3/min

17.0

17.0

18.0

Air speed

m/sec.

5.9

5.9

6.3

 

High

 

 

 

 

 

Coverage range

m

6.4

6.4

6.8

 

 

 

 

 

 

 

 

Total width of dischsrge outlets

mm

0

0

0

 

 

 

 

 

 

wThe air coverage range is the value up to the position where the air speed is 0.25m/sec. When air is blown out horizontally from the unit at the Hi notch position.

The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.

12

5 OUTLINES AND DIMENSIONS

1.INDOOR UNIT PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK

partselectricalForNOTE1.box may be removed during servicing. When

linepowertheconnectingand the control wire, provide enough length to

wires.electricthe theinstallingWhenNOTE2.optional high-efficiency filter, the dimension

andtransomthebetweenceiling shall be more than 440mm. Also,when

casement,optionaltheinstallingthe dimension between the transom

morebeshallceilingandthan 440m. (The optional highefficiency filter

installed.)bealsocan

 

 

pipeLiquid

 

pipeGas

hilterefficiency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

435

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

135

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional high-

 

 

 

 

 

 

 

 

 

 

 

 

660

 

 

 

 

 

 

Drainhole 25-VPconnection

Feedinghole

(Drainpump)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25~35 690~710 25~35

 

 

 

117

 

 

 

117

 

 

 

 

 

 

Ceiling hole

640

Suspension bolt pitch

 

Terminal block for control

Terminal block for remote controller

Drain hole

Terminal block for

power supply

 

117 117

660

Suspension bolt M10 or

W3/8

41 25

 

 

 

 

 

 

 

Suspensionboltpitch

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

507

 

 

 

54

 

 

 

 

 

 

 

 

 

 

25~35

690~710

 

 

 

25~35

 

 

 

 

 

 

 

 

 

 

Ceilinghole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

loweredge

 

2

Refrigerant pipe {15.88

Flared connection 5/8F

 

 

 

 

 

1

Refrigerant pipe {9.52

Flared connection 3/8F

 

 

 

 

between the

the ceiling slab.

1.6/2/2.5KK

 

 

 

 

 

Leave space of 10~15mm

top surface of the unit and

 

surface

 

panelDecorative

motorVane

vanesAuto-4

 

293

 

 

 

 

30

 

 

 

 

253

 

-2

54

 

 

 

 

 

 

+3

 

 

 

 

243

 

 

 

 

 

 

 

 

 

 

 

 

 

115

 

 

 

 

 

 

 

 

 

Ceiling

 

 

 

 

 

 

 

 

 

466

intake hole

 

 

 

 

 

 

 

Air

 

 

 

 

Controlwire entry Power line entry

side

side

 

 

65~80

Refrigerant piping

electric wire entry

 

Suspensionbolt

 

 

 

 

 

Airoutlethole

466

Airoutlethole

460

760

Unit : mm

 

Intake grill opening/closing side

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

66

 

 

 

 

 

 

 

 

 

 

 

460 outlet hole 760

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

grill

 

 

 

 

66

 

35

 

 

 

 

Airintake

 

 

 

 

13

 

 

 

 

 

 

2. REMOTE CONTROLLER

 

 

Unit : mm (inch)

 

 

 

 

 

 

 

 

 

 

 

 

FILTER

FILTER

CHECK MODE

CHECK MODE

TEST RUN

TEST RUN

120

18

130

Rear side wiring arrangement opening.

83.5

46

CAUTION

SW18

SW17

14

6

 

 

WIRING DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLH-1.6KKHB·UK/PLH-2KKHB·UK/PLH-2.5KKHB·UK

 

 

 

 

 

 

 

 

 

 

 

 

 

SYMBOL

 

NAME

SYMBOL

NAME

SYMBOL

NAME

 

 

 

 

 

 

 

 

 

R.B

 

REMOTE CONTROLLER BOARD

CN2L<I.B>

LOSSNAY CONNECTOR

X3<I.B>

VANE MOTOR RELAY

 

 

 

 

 

 

 

 

SW17<R.B>

 

ADDRESS SELECTOR

CN51<I.B>

CENTRALLY CONTROL CONNECTOR

X4<I.B>

FAN MOTOR RELAY

 

 

 

 

 

 

 

 

 

 

SW18<R.B>

 

FUNCTION SELECTOR

FAN2<I.B>

EMERGENCY OPERATION CONNECTOR

F1<I.B>

FUSE (6.3A)

 

 

 

 

 

 

 

 

 

CN1<R.B>

 

PROGRAM TIMER CONNECTOR

F.C<I.B>

FAN PHASE CONTROL

LED1<I.B>

DC 12V POWER LED

 

 

 

 

 

 

 

CN2<R.B>

 

REMOTE SWITCH CONNECTOR

SW1<I.B>

MODE SELECTOR

LED2<I.B>

DC 5V POWER LED

 

 

 

 

 

 

 

MV

 

VANE MOTOR

SW2<I.B>

ADDORESS SELECTOR

CNP<I.B>

DRAIN PUMP CONNECTOR

 

 

 

 

 

 

 

LS

 

LIMIT SWITCH

SW3<I.B>

EMERGENCY OPERATION SWITCH

CN50<I.B>

DRAIN SENSOR CONNECTOR

 

 

 

 

 

 

 

 

 

H2

 

DEW PREVENTION HEATER

SW5, SW7<I.B>

MODEL SELECTOR

DP

DRAIN PUMP

 

 

 

 

 

 

 

 

 

 

RT1

 

ROOM TEMP. THERMISTOR(0°C/15K ,25°C5.4K )

SW6<I.B>

TWIN, TRIPLE SWITCH

DS

DRAIN SENSOR

 

 

 

 

 

 

 

 

 

 

RT2

 

INDOOR COIL THERMISTOR(0°C/15K ,25°C5.4K )

SWA<I.B>

HIGH SEILING, NOISE SAVING SELECTOR

H1

HEATER

 

 

 

 

 

 

 

 

 

 

T

 

TRANSFORMER

SWB<I.B>

NUMBER OF AIR OUTLETS SELECTOR

FS1,2

THERMAL FUSE

 

 

 

 

 

 

 

 

MF

 

INDOOR FAN MOTOR

SWC<I.B>

OPTION SELECTOR

26H

HEATER THERMAL SWITCH

 

 

 

 

 

 

 

C1

 

FAN MOTOR CAPACITOR

ZNR<I.B>

VARISTOR

88H

HEATER CONNECTOR

 

 

 

 

 

 

 

TB2~6

 

TERMINAL BLOCK

X1<I.B>

DRAIN PUMP/D.HEATER RELAY

CNV<I.B>

VANE MOTOR CONNECTOR

 

 

 

 

 

 

 

 

 

I.B

 

INDOOR CONTROLLER BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER 50Hz

 

 

 

 

 

 

 

 

L

~(1PHASE)

 

 

 

 

 

 

 

 

 

-240V

 

 

 

 

 

 

 

 

N

220

60Hz

 

 

 

 

 

 

 

 

 

220V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED ORN YLW

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

YLW

YLW

BRN

BRN

 

RED BLU

 

RED

YLW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

BRN

 

 

 

 

 

 

5

 

 

 

 

 

 

1

3

1 3

 

1

3

1 3

 

 

14.2V AC

11.1V AC

 

 

 

 

MF

C1

BLK

 

 

 

 

 

 

 

 

 

4 3

2 1

 

 

 

 

 

WHT

3

FAN1

 

 

 

 

 

CNV

CNP

 

CND

CNT

 

 

LED2

 

 

 

 

RED

1

 

FAN

 

 

 

 

 

VANE

D.U.M.

F1

POWER

TRANS

 

CN4T

 

5V POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANS

 

 

 

 

 

F.C

 

X4

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

CN22

1

 

 

 

 

 

 

 

 

 

X3

 

X1

 

 

 

 

2

 

 

 

1

TO REMOCON

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

CN40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZNR

 

 

 

4

 

 

 

 

 

 

 

 

X4

SW7

SW3 SWC

X3

X1

 

 

CN50

 

REMOCON

CN30

 

 

 

 

1

3 5

 

 

 

 

5

 

POWER

3

2

 

 

 

 

 

 

Showing

 

OP

 

 

 

 

 

 

 

DRAIN

 

 

 

4

OUTDOOR

3

 

 

 

 

FAN2

 

 

 

STD

 

 

 

 

LED1

 

 

CN51

1

 

CN41

 

 

 

 

 

 

 

 

 

123 fig:1

12

 

 

 

 

 

 

 

 

 

1

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

12V POWER

CONTROLCENTRALLY 2

 

1

CN21

CN23

 

2

 

 

 

 

 

SW2

SW5

SW6

SW1

SWA

SWB

 

 

CN24

 

3

 

2

PIPE

2

VANE

2

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

3

2

 

 

 

4

 

3

 

1

 

1

 

 

 

 

 

 

 

 

 

 

2

3

 

 

HEATER

 

 

CN20

CN2L

 

4

 

 

 

 

OFF

 

 

 

 

 

1

4

 

 

 

 

 

5

 

4

2

2

DS

 

 

 

 

 

123456

1234

1234

12345678910

 

 

 

 

 

 

 

 

INTAKE

LOSSNAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*PLH-1.6,2,2.5KKHB(with heater)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED 3

88H 5

RED FS1

FS2

 

H1

 

 

CN24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

TB2

BLU

 

1 BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

3

 

 

 

 

 

 

 

YLW 6

1

 

 

YLW

26H

 

 

 

 

~(1PHASE)

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

220-240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

88H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YLW

 

 

 

2 YLW

 

 

 

 

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN/YLW

TB2

 

 

1

18

 

 

SW

OFF

 

.

2

 

ON

.B

 

 

 

R

 

 

 

 

 

2

 

7

LU

B

1

 

LU

B 6

 

GRILL

 

 

LS

MV

 

 

H2

5

10

 

N

N R

 

R B

N

B

 

 

 

BR

 

 

DP

 

 

N

 

 

BR

 

 

DC12V

 

 

CN2

 

 

 

TB6

 

 

 

 

 

 

1

2

 

 

 

 

 

SW

 

ON

 

 

 

 

 

 

 

3

 

 

 

17

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRES

 

 

 

 

CN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

5

 

 

 

 

 

 

 

 

 

 

 

 

3

4

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

TRNSMISSION

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

DC12V

 

1

 

1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

WIRES

 

 

BLU

2

 

 

 

 

 

TRNSMISSION

 

 

3

 

 

 

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

TB3

 

 

BRN

 

2

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

BG79Y408H0

 

 

YLW

 

 

 

 

 

 

 

 

ORN

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB4

 

 

 

 

 

 

 

fig:1

MODELS

1.6KK

2KK

2.5KK

SW7

ON

ON

ON

OFF

OFF

OFF

 

1 2 3

1 2 3

1 2 3

NOTES :

1. Since the indoor transformer (T)is connected with 240Vpower. If 220, 230v power is used. change the wiring connection showing fig: w2

 

 

 

 

 

 

 

240V

YELLOW

 

fig:w2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230V

ORANGE

 

 

 

 

 

 

 

When power supply is

230V

 

 

 

220V

RED

 

 

 

 

 

 

220V

 

 

 

 

 

 

 

2.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.

3.Indoor and outdoor connecting wires are made with polarities. make wiring matching terminal numbers.

4.Symbols used in wiring diagram above are. / : Terminal block, : Connector.

5.Emergency operation

If remote controller or microcomputer fails but there is no other truble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.

[Check items]

(1)Make sure that no other trouble exists the outdoor unit. Trouble with the outdoor unit prevents emergency operation.

(If any trouble exists the outdoor unit error code “P8”will be displayed on the remote controller and the trouble position will be shown on the outdoor controller board LED. See electric wiring diagram of the outdoor unit for details.)

(2)Make sure that there is no trouble with the indoor fan.

Emergency operation will be continuous run with the power ON/OFF (ON/OFF with the remote controller is not possible). [Emergency operation procedure]

(1)Switch the fan connector on the indoor controller board from FAN 1 to FAN 2.

(2)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating. (3)Turn on the outdoor unit side circuit breaker, then the indoor unit side circuit breaker.

(4)During emergency operation indoor fan runs at High speed but auto-vane does not work.

(5)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for a long time. (6)Emergency cooling should be limited to 10 hours maximum. (the indoor unit heat exchanger may freeze).

(7)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.

NOTE: If the drain water lift up mechanism is identified to be defective with the microcomputer doctor during cooling, do not use emergency operation (it causes drain overflow)

15

7 REFRIGERANT SYSTEM DIAGRAM

PLH-1.6KKHB·UK/PUH-1.6VKA3·UK PLH-2KKHB·UK/PUH-2VKA2·UK PLH-2.5KKHB·UK/PUH-2.5VKA2·UK

Unit : mm

Flow of refrigerant (cooling)

Flow of refrigerant (heating)

High pressure

control switch

Oil separator

 

 

Refrigerant pipe

4-way valve

Service

Outdoor unit

 

Indoor unit

 

(option)

 

port

Outdoor heat exchanger

 

 

15.88mm(

5/8")

Ball valve

 

 

 

 

 

 

 

 

(with heat insulator)

Strainer

 

 

 

 

 

 

 

 

 

 

 

 

Flexible tube

 

 

 

 

Indoor

 

 

 

Service

 

 

Outdoor coil

heat

 

 

 

port

 

 

 

 

 

 

 

thermistor

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

(TH)

 

 

 

 

 

 

 

 

Strainer

Flared

 

 

 

Bypass

 

 

connection

 

 

 

 

 

 

 

valve

w

 

 

 

 

 

 

 

 

 

 

Accumulator

 

 

 

 

 

 

 

Restrictor

Capillary

Indoor coil

Restrictor

 

 

 

 

valve

tube

 

 

 

Compressor

 

 

thermistor

valve

 

 

 

 

 

(RT2)

 

 

 

 

 

 

 

Distributor

 

Refrigerant pipe

Ball valve

with

 

 

(option)

 

(with service port)

strainer

 

 

Capillary

9.52mm(

3.8")

 

 

 

 

(with heat insulator)

 

 

tube

 

 

 

 

 

PLH-1.6 (O.D.3.2 I.D.1.6 –R630) PLH-2.5 (O.D.3.2 I.D.1.8 –R430) PLH-2 (O.D.3.2 I.D.1.8 –R630)

Strainer

wPLH-1.6 (O.D.3.2 I.D.1.8 –R400) PLH-2 (O.D.4.0 I.D.2.0 –R430) PLH-2.5 (O.D.4.2 I.D.2.4 –R1550)

High pressure protect switch

Refrigerant flow in cooling

R.V.coil

Heating ON

Refrigerant flow in heating

Cooling OFF

 

16

8 OPERATION FLOW-CHART

MAIN OPERATION

START

 

Power circuit

NO

 

breaker

 

1 YES

YES Check SW

 

 

 

 

 

 

 

 

 

 

ON twice

 

 

 

 

 

 

 

 

 

 

 

NO

w1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

SW

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

“OFF” timer

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

NO

Set

time

NO

 

 

 

“ON” timer

 

 

 

 

 

 

 

 

 

 

complete

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set time

YES

 

 

 

 

 

 

 

complete

 

 

 

 

 

w2

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trouble

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Remote controller

 

 

 

operation display

 

STOP

Trouble STOP

Operating mode

YES

 

 

 

(COOL)

 

PROTECTION DEVICE

PROTECTION DEVICE

NO

COOL operation

SELF HOLD RELEASE

SELF HOLD

 

YES

 

 

Operating mode

 

w3

 

Remote controller

(DRY)

 

Remote controller

 

 

indicator lamp OFF

 

DRY operation

trouble display

NO

 

 

 

 

Operating mode

YES

 

 

 

 

 

(HEAT)

 

Indoor side

 

NO

HEAT operation

 

w4

 

 

 

w6

YES

Fan STOP

 

 

Operating mode

 

 

(FAN)

w7

Auxiliary heater OFF

 

NO

FAN operation

 

 

 

 

 

 

 

Auto COOL/HEAT

 

 

 

operation

 

Outdoor side

w5

Compressor OFF

Fan STOP

Four-way valve OFF

w1 In addition, the centralized control and remote control can be operated. w2 The modes which indicate the sources of trouble are listed below.

EO-Signal transmitting/receiving error

P1-Room temperature thermistor malfunction

P2-Indoor coil thermistor malfunction

P4-Drain sensor malfunction

P5-Drain overflow

P6-Coil frost/overheat protection

P7-System error

P8-Outdoor unit trouble

w3 The CHECK swich will show if an error has occurred in the past. w4 Fan runs on low speed for 1 minute in order to remove overheat air.

w5 The 3-minute (6 minutes heating mode) time-delay functions after compressor stops. w6 FAN or AUTO mode is selected by the indoor dipswitch setting.

w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)

17

COOLING OPERATION

COOL operation

Four-way valve/OFF

NO

 

Initial

 

 

 

 

COOLING

 

 

w8

 

YES

 

 

Vane initial

 

 

 

setting

 

NO

 

Vane

 

 

55 deg downward angle

 

 

70 deg downward angle

 

NO

 

 

YES

 

 

Fan speed

 

 

 

 

 

 

 

 

LOW

 

 

 

 

 

YES

 

NO

Downward discharge

 

 

 

 

 

1 hour

 

 

 

 

 

YES

 

Vane setting notch

Vane horizontal

 

 

airflow

 

 

 

 

 

 

 

w9

Compressor

NO

YES

 

 

 

 

 

thermostat

 

 

 

 

ON

NO

 

 

 

 

 

 

Allowance

 

 

 

cancel

 

NO YES

3-minute

 

 

 

time delay

 

 

 

NO

 

 

YES

6-minute

Allowance

YES

 

time delay

period

 

 

 

 

 

NO

 

 

NO

 

 

 

 

 

6 minute

 

 

 

 

 

 

 

 

NO

3-minute

 

 

time delay

 

 

 

compressor operation

 

 

 

 

 

 

YES

 

 

Allowance set

 

Coil frost protection

 

 

 

 

 

 

 

w10

YES

 

 

 

 

 

Coil frost

 

 

 

 

 

prevention

 

 

 

 

 

 

NO

 

 

 

 

 

w11

 

NO

 

 

 

 

 

Cooling area

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

NO

10-minute

 

 

NO

 

 

 

compressor operation

 

 

1 min continue

 

 

 

 

 

 

 

 

YES

 

 

 

YES

 

 

Allowance cancel

 

 

 

 

 

 

 

 

FAN speed

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

 

Coil frost

YES

 

 

 

 

 

protection

 

 

 

 

YES

 

NO

 

 

 

FAN speed

 

 

 

 

LOW 5 min

 

NO

16-minute

 

Indoor coil

NO

elapse

 

 

tempreature is

 

NO

 

 

compressor operation

 

 

 

 

 

 

10 C or higher

 

 

Outdoor unit

 

YES

 

YES

 

 

trouble

 

 

 

 

 

 

Indoor pipe

YES

3-minute

 

 

 

 

temperature is

 

time delay

 

 

 

 

1 C or lower

 

 

 

 

 

NO

Coil frost

 

Coil frost

 

prevention

 

prevention release

 

 

 

 

 

 

 

 

 

 

 

 

Compressor ON Compressor OFF

1

w8 When operation stops or changes to cooling or dry mode, the auto vane tums to a horizontal angle. If operation changes during auto vane SWING, the auto vane will continue to swing.

w9 When operating TEST RUN, the thermostat will be continuously ON.

w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will stop for 6 minutes.

w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature. Heating area : Indoor coil temperature is more than 5 degrees below the room temperature. FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.

18

HEATING OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat operation

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w15

 

 

 

 

w11

YES

 

 

 

 

 

PLH-KKHB

NO

NO

 

 

 

 

 

 

 

 

 

 

Initial

 

 

 

 

 

Heating area

 

 

 

 

 

Type

 

 

HEATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

NO

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

Defrost release

 

 

 

 

3-minute

NO

Vane setting notch

Vane initial setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost

NO

 

 

 

 

 

Auxiliary heater

 

 

 

 

 

 

 

 

30 min. elapse

 

 

 

 

 

 

OFF

 

 

 

YES

 

 

 

 

YES

 

2

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrosting

 

 

 

 

 

 

 

 

 

 

 

Indoor coil

NO

 

 

 

 

 

 

Outdoor unit trouble

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermstor is 60 C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

or higher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Four-way valve ON

 

 

 

 

 

1

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Low notti

 

 

Hor adjust

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in process

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

Airflow 10% up

FAN setting notch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor ON

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Indoor piping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

35 C or higher

 

 

 

NO

 

10-minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

YES

 

 

compressor

 

 

 

 

 

 

 

NO

 

 

w9

 

 

operation

 

 

 

 

 

 

 

 

 

thermostat ON

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

YES

 

 

 

 

 

 

 

HOT adjust

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

3 min.restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 min. elapse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prevention

Allowance cancel

 

 

 

 

 

 

 

YES

 

 

 

Allowance cancel

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

NO

 

 

 

 

 

Indoor piping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN SPEED

 

 

 

 

YES

6 min. restart

 

 

 

 

 

55 C or lower

 

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prevention

 

Heating

YES

 

 

NO

 

 

 

 

NO

 

 

 

 

NO

 

A

 

 

 

 

 

FAN SPEED

 

 

 

2

 

 

NO

 

 

 

 

 

 

 

 

 

 

area

 

 

Auxiliary heater

NO

Auxiliary heater

 

Low 2 min.

 

 

NO

Indoor piping

 

 

 

 

 

 

 

ON

 

 

elapse

 

 

 

 

 

NO

 

 

 

 

thermostat ON

 

 

 

 

-15 C or lower

 

Hot adjust start

 

 

 

 

 

YES

 

YES

 

YES

 

 

 

YES

 

 

FAN STOP

 

 

 

 

 

FAN SPEED

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor piping

 

Auxiliary heater ON

 

setting nitch

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN SPEED very low

w11

 

 

 

60 C or higher

 

 

 

 

 

 

trouble

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow area

 

 

YES

 

 

 

Hot adjust

 

 

 

 

 

 

 

20 min.elaspe

 

 

 

 

 

 

release

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor ON

 

 

 

 

 

Auxiliary heater OFF

 

 

 

 

 

 

 

FAN SPEED

 

YES

w10

 

 

 

 

 

 

 

 

 

 

 

Airflow area

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Very low airflow

 

 

 

Heating area

 

trouble

 

Overheat remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START

 

 

 

 

 

 

 

Compressor OFF

 

 

w11

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow area

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

Cooling area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70 C or higher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Defrost operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START

 

 

 

Allowance

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

period

 

 

 

 

 

 

 

 

 

 

Four-way valve

 

 

 

YES

 

6-minute restart

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload protect

 

prevention

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allowance set

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor OFF

 

 

 

 

 

AUTOMATIC COOLING/HEATING OPERATION

 

 

 

 

 

 

 

 

 

 

Auto COOL/HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w16

 

 

 

 

 

 

1

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Initial mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w17

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1 =T0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL mode

 

HEAT mode

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL mode

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

T1 < (T0 - 2)

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1>(T0 + 2)

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

After 15min.

YES

 

 

After 15min.

YES

 

 

 

 

 

 

 

 

 

 

 

 

T1>(T0 + 2)

 

 

 

 

 

 

 

 

 

 

T1<(T0-2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL operation

 

HEAT operation

 

HEAT operation

Cool mode

 

 

 

 

 

 

 

 

 

 

set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

1

 

 

 

 

 

 

 

 

w15 ( i ) Until Low airflow is set while hot adjustment (ii)While defrosting (FAN STOP)

(iii)When thermostat is OFF

In the case of( i ), (ii) and (iii) above, airflow is horizontal regardless the VANE setting. w16 When AUTO operation is started, COOL or HEAT mode is selected automatically.

w17 T1 : Room temperature. To : Set temperature

19

DRY OPERATION

DRY operation

Four-way valve / OFF

NO

Initial dry

 

 

operation

 

 

YES

w8

Vane

Vane initial setting

setting notch

 

YES

w12

 

 

 

 

Room tempereature is

 

 

 

 

 

 

 

 

 

 

18°C or lower

 

 

 

 

 

NO

 

 

 

 

 

During

NO

 

 

 

 

compressor ON

 

 

 

 

 

YES

 

 

 

 

 

3-minute

NO

 

 

YES

 

compressor

 

 

delay

 

 

operation

 

 

 

 

 

 

 

 

 

YES

 

 

NO

 

NO

w9

 

YES

Compressor &

w9

 

 

 

 

 

 

 

thermostat

 

 

 

 

 

ON

 

 

YES

 

 

NO

 

 

Compressor ON

NO

 

 

NO

 

 

 

 

 

 

time completes

 

 

 

 

 

YES

 

 

YES

w13

 

 

 

 

 

 

10-minute compressor

 

 

 

 

 

OFF timer start

 

 

 

 

 

Compressor OFF

 

 

 

 

 

w14

 

 

 

w14

 

Fan STOP

 

 

 

 

 

1

 

 

 

 

w8—9 Refer to page 26~27.

w12 When room temperature is 18°C or below, the compressor cannot operate.

When room temperature rises over 18°C, the compressor starts after a 3-minute time delay. w13 Compressor ON time is decided by room temperature. Refer to page 26~27 .

w14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan. It is not possible to set the fan speed with the remote controller

20

9 MICROPROCESSOR CONTROL

1.OUTLINE OF MICROPROCESSOR CONTROL

INPUT to remote controller

OFF-ON switching.

COOL/DRY-AUTO-HEAT selector switching.

Thermostat setting.

TIMER mode selector-switching and Timer setting.

HIGH-LOW fan speed switching.

AUTO Vane selector (AIR DISCHARGE) switching.

TEST RUN switching.

CHECK mode switching.

(Self diagnostic trouble shooting)

Indoor unit

Remote controller board

OUTPUT to remote controller

 

● Processes and transmits

Remote controller

orders.

 

● LCD indicator

 

FILTER

 

CHECK MODE

 

TEST RUN

240KA

 

Non-polar, two-wire cable

12VDC

maxinmum length 500 meters

Signal

 

INPUT from indoor unit

Room temperature thermistor (RT1)

Indoor coil thermistor (RT2)

Drain sensor

OUTPUT to indoor unit

Indoor controller board

Receives orders from remote controller and temperature data from indoor unit.

Processes orders and data.

Controls indoor and outdoor operation.

Self diagnostic function.

wSystem control operation.

wEmergency operation.

wSet by dipswitch on indoor controller board.

● Transmits the power to remote controller.

1 2 3

● Autovane’s angle setting.

 

 

● Booster heater ON-OFF Control.

 

unit

● Drain pump : ON-OFF.

 

● Emergency stop.

Polar three-wire cable

outdoor

 

 

 

Independent Control of

Outdoor unit

to

Outdoor Unit

 

12VDC

OUTPUT

● Compressor

 

 

protectiondevice working

 

 

● Defrosting

 

 

START-STOP

 

 

● Fan speed control.

1

 

● Crankcase heater control

2

 

ON-OFF.

3

 

● Self diagnostic function

 

 

Compressor and outdoor fan : ONOFF

Operation mode change :COOLHEAT.

21

2. INDOOR UNIT CONTROL

2-1COOL operation

FILTER

CHECK MODE

TEST RUN

240KA

<How to operate>

1 Press POWER ON/OFF button.

2 Press the button to display “

3 Press the TEMP button to set the desired temperature.

NOTE: Set temperature changes 1°C when the or button is pressed one time.

Cooling 19 to 30°C

<COOL operation time chart>

 

 

 

Operation starts by

 

 

Room temperature

 

Room temperature

 

Operation stops by

 

 

 

P O W E R b u t t o n

 

 

becomes equal to

 

rises above set

 

P O W E R b u t t o n

 

 

 

ON.

 

 

set temperature.

 

temperature.

 

OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW or HIGH

 

 

 

LOW or HIGH

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

OFF

 

 

Initally 30

degrees

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

(Changeable by remote controller setting)

 

 

 

 

 

 

 

 

 

 

discharge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto vane

air flow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

position

position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 minutes

Drain pump

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Booster heater

OFF

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum 3 minutes w1

 

 

 

 

 

 

w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.

(1) Compressor control

1 3-minute time delay

To prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when room temperature is higher than set temperature.

The compressor stops when room temperature is equal to or lower than the set temperature. 3 The compressor stops in check mode or during protective functions.

4 Coil frost prevention

To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1: or below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to 10: or above, the compressor will start after a 3-minute time delay.

NOTE : By turning OFF the dipswitch SW1-5 on indoor controller board, the start temperature of coil frost prevention changes from 1: to -3:.

22

Loading...
+ 50 hidden pages