Mitsubishi PKA-P1.6GAL, PKA-P2GAL, PKH-P1.6GALH, PKH-P2GALH, PKA-P1.6GAL1 Service Manual

...
0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

1999

 

 

No.OC176

 

REVISED EDITION-B

TECHNICAL & SERVICE MANUAL

Series PKH/PKA

 

 

 

 

Wall Mounted

R407C

 

 

 

 

 

 

 

Indoor unit

[Service Ref.]

 

[Model names]

 

1999, 2001

1999

 

 

2001

PKH-P1.6GALH

PKH-P1.6GALH

PKH-P1.6GALH1

PKH-P2GALH

PKH-P2GALH

PKH-P2GALH1

2000, 2001

2000

 

 

2001

PKA-P1.6GAL

PKA-P1.6GAL

PKA-P1.6GAL1

PKA-P2GAL

PKA-P2GAL

PKA-P2GAL1

CONTENTS

1. TECHNICAL CHANGES ··············

2. COMBINATION OF INDOOR AND OUTDOOR UNITS ···2

3. SAFETY PRECAUTION ··············

Indoor unit

4. PART NAMES AND FUNCTIONS ··········

5. SPECIFICATIONS ·················

6. DATA ······················

7. OUTLINES AND DIMENSIONS ···········

ON/OFF

8. WIRING DIAGRAM ················

9. REFRIGERANT SYSTEM DIAGRAM··········

 

 

10. TROUBLE SHOOTING ··············

 

 

11. DISASSEMBLY PROCEDURE···········

 

 

12. PARTS LIST ···················

PKH-P1.6, 2GALH

PKH-P1.6, 2GALH1

13. OPTIONAL PARTS ················

 

PKA-P1.6, 2GAL

PKA-P1.6, 2GAL1

 

Remote controller

 

PKH-P1.6GALH1, PKH-P2GALH1, PKA-P1.6GAL1 and PKA-P2GAL1 are added in Revised Edition-B.

Please void OC176 Revised Edition-A.

Refer to the OCT03 Revised Edition-C as regarding control relation. This manual does not cover outdoor units. When servicing them, please refer to the service manual No.OC180 Revised Edition-A, OC261 and this manual in a set.

1 TECHNICAL CHANGES

PKH-P1.6GALH PKH-P1.6GALH1

PKA-P1.6GAL PKA-P1.6GAL1

PKH-P2GALH PKH-P2GALH1

PKA-P2GAL PKA-P2GAL1

Outdoor units which are connected to PKH-P·GALH, PKH-P·GALH1.PKA-P·GAL and PKA-P·GAL1 have been added.

The parts No. of REMOTE CONTROLLER has changed.

(The following parts numbers are interchangeable.)

ON/OFF

[ T7W E02 714 ]

[ T7W E06 714 ]

2 COMBINATION OF INDOOR AND OUTDOOR UNITS

Outdoor unit (OC180 REVISED EDITION-A)

 

Indoor unit

 

 

Heat pump type

 

 

Cooling only type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUH-P

 

 

PU-P

 

 

 

 

 

 

 

 

 

 

 

 

 

1.6VGA

1.6YGA

2VGA

2YGA

1.6VGA

2VGA

 

 

 

Heat pump with

PKH-P1.6GALH

 

 

 

 

 

 

electric heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKH-P2GALH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat pump without

PKA-P1.6GAL

 

 

 

 

 

 

 

 

electric heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling only

PKA-P2GAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit (OC261)

 

 

 

Indoor unit

 

Heat pump type

 

 

Cooling only type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUH-P

 

 

 

 

PU-P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.6VGAA.UK

1.6YGAA.UK

2VGAA.UK

2YGAA.UK

1.6VGAA.UK

1.6YGAA.UK

2VGAA.UK

2YGAA.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat pump with

PKH-P1.6GALH1

 

 

 

 

 

 

 

 

electric heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKH-P2GALH1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat pump without

PKA-P1.6GAL1

 

 

 

 

 

 

 

 

 

 

electric heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling only

PKA-P2GAL1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3 SAFETY PRECAUTION

Cautions for using with the outdoor unit which adopts R407C refrigerant.

· Do not use the existing refrigerant piping.

-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.

· Do not use copper pipes which are broken, deformed or discolour .

In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust / dirt, shaving particles, oils, moisture or any other contamination.

-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will result.

·Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)

-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.

·Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.

-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.

Use liquid refrigerant to fill the system.

-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance may drop.

· Do not use a refrigerant other than R407C.

-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.

· Use a vacuum pump with a reverse flow check valve.

-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.

· Do not use the following tools that are used with conventional refrigerant.

(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)

-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated. -If water is mixed in the R407C, the refrigerant oil may deteriorate.

-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.

· Do not use a charging cylinder.

-Using a charging cylinder may cause the refrigerant to deteriorate.

· Be especially careful when managing the tools.

-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.

· Don’t use the drier which is sold in the field.

-The drier for R407C refrigerant is Per-attached to outdoor unit refrigerant circuit. -Some drier in the field are not in conformity with R407C refrigerant.

[1] Service tools

Use the below service tools as exclusive tools for R407C refrigerant.

No.

Tool name

Specifications

1

Gauge manifold

·Only for R407C.

 

 

 

 

 

·Use the existing fitting SPECIFICATIONS. (UNF7/16)

 

 

 

 

 

·Use high-tension side pressure of 3.43MPa·G or over.

 

 

 

2

Charge hose

·Only for R407C.

 

 

 

 

 

·Use pressure performance of 5.10MPa·G or over.

3Electronic scale

4

Gas leak detector

·Use the detector for R407C.

 

 

 

5

Adapter for reverse flow check

·Attach on vacuum pump.

6Refrigerant charge base

7 Refrigerant cylinder

·For R407C

·Top of cylinder (Brown)

 

 

·Cylinder with syphon

8Refrigerant recovery equipment

3

[2] Notice on repair service

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

[3] Refrigerant recharging

(1) Refrigerant recharging process

1Direct charging from the cylinder.

·R407C cylinder are available on the market has a syphon pipe. ·Leave the syphon pipe cylinder standing and recharge it.

(By liquid refrigerant)

Unit

Gravimeter

(2) Recharge in refrigerant leakage case

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release the refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

4 PART NAMES AND FUNCTIONS

Indoor Unit

Filter

Air intake grille

Air intake

Auto vane

Guide vane

Air outlet

 

4

Wireless remote controller

PKH-P1.6GALH, PKH-P2GALH PKA-P1.6GAL, PKA-P2GAL

● When cover is open.

display

Lights up while transmission to the indoor unit is mode using switches.

display

OPERATION MODE display

Operation mode display indicates which operation mode is in effect.

• FUNCTION display

Lights up when function are set..

TEST RUN CHECK display

CHECK&TEST RUN display indicates that the unit is being checked or test-run.

display

Displays when batteries are dead.

display

The vertical direction of airflow is indicated.

display

FAN SPEED display indicates which fan speed has been selected.

display

The unit is turned ON and OFF alternately each time the button is pressed.

● When cover is open.

MODE SELECT button

Used to switch the operation mode between cooling , drying , blowing , heating and auto mode.

FAN SPEED SELECT button

Used to change the fan speed.

VANE CONTROL button

Used to change the airflow direction.

ADDRESS display

 

 

display

Displays the refrigerant address.

SET TEMP. display indicates desired tempera-

 

 

 

UNIT NO. display

ture set.

 

 

 

 

 

 

 

 

Displays the number of unit..

 

 

 

 

 

FUNCTION NO. display

CLOCK display

 

 

 

 

 

Displays the mode.

 

DIsplays the current time.

 

 

 

SELECTION NO. display

”display

Displays the selection number..

 

 

 

 

 

 

 

 

Flashes when the current time is displayed.

 

 

 

TIMER display

 

ADDRESS

 

Displays when in timer operation or when set-

 

UNIT No.

 

 

FUNCTION No.

˚C

ting timer.

 

 

 

SELECTION No.

 

 

 

 

AM

” “

 

” display

 

 

PM

 

FUNCTION

 

AM

 

 

 

 

TEST RUN

 

 

 

 

 

 

 

PM

 

 

 

 

 

 

 

 

 

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

TEMP.

Displays the order of timer operation.

 

 

 

 

 

 

 

ON/OFF

 

 

 

” “

 

” display

 

 

 

 

 

 

 

START

Displays whether timer is on or off.

 

 

 

MODE

FAN

STOP

 

 

 

 

 

 

VANE

HR.

” “

” display

 

 

 

 

 

 

 

 

 

Displays when the current time and the timer

 

 

MIN.

time can be changed.

RESET

TEMP. button

TEMP.

ON/OFF

 

 

START

MODE

FAN

STOP

VANE HR.

MIN.

RESET

SET TEMPERATURE button sets any desired room temperature.

TIMER CONTROL buttons

STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time.

START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.

HR. and MIN.buttons

Buttons used to set the “hour and minute” of the current time and timer settings.

button

RESET button

5

Wireless remote controller

PKH-P1.6GALH1, PKH-P2GALH1 PKA-P1.6GAL1, PKA-P2GAL1

● When cover is open.

CHECK TESTRUN display

CHECK&TEST RUN display indicates that the unit is being checked or test-run.

display

OPERATION MODE display

Operation mode display indicates which operation mode is in effect.

display

The vertical direction of air flow is indicated.

display

FAN SPEED display indicates which fan speed has been selected.

ON/OFF button

The unit is turned ON and OFF alternately each time the button is pressed.

FAN SPEED SELECT button

Used to change the fan speed.

MODE SELECT button

Used to switch the operation mode between cooling, drying, blowing, heating and auto mode.

wIn case the outdoor unit is cool only type, the heating and auto mode not available.

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation.

Do not use it for normal operation.

VANE CONTROL button

Used to change the air flow direction.

MODEL SELECT display

Blinks when model is selected.

CHECK TESTRUN

MODEL SELECT ˚C

AMPM

AMPM

NOT AVAILABLE

ON/OFF TEMP

 

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

h

TEST RUN

 

min

SET

RESET CLOCK

display

Lights up while transmission to the indoor unit is mode using switches.

display

SET TEMP. display indicates desired temperature set.

CLOCK display

Displays the current time.

TIMER display

Displays when in timer operation or when setting timer.

” “ ” display

Displays the order of timer operation.

” “” display

Displays whether timer is on or off.

button

SET TEMPERATURE button sets any desired room temperature.

TIMER CONTROL buttons

AUTO STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time.

AUTO START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.

h and min buttons

Buttons used to set the “hour and minute” of the current time and timer settings.

LOUVER button

This switch the horizontal fan motion ON and OFF.

(Not available for this model.)

CLOCK button

RESET button

SET button

6

 

5

 

 

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Heat pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Service Ref. With Electric heater

 

PKH-P1.6GALH

 

 

 

 

Without Electric heater

 

PKA-P1.6GAL

 

 

Function

 

 

 

 

Cooling

Heating

 

 

Capacity

w1

 

 

Btu/h

15,000

17,100(19,800)

 

 

 

 

W

4,400

5,000(5,800)

 

 

 

 

 

 

 

 

 

 

 

Total input

w1

 

 

kW

1.78

1.90(2.70)

 

 

 

Service Ref.

 

With Electric heater

 

PKH-P1.6GALH

 

 

 

 

Without Electric heater

 

PKA-P1.6GAL

 

 

 

 

 

 

 

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

Single phase, 50Hz, 220-230-240V

 

 

 

 

 

 

Input

w2

kW

0.07

0.07<0.80>

 

 

 

 

 

 

Running current

w2

A

0.33

0.33<3.33>

 

 

 

 

 

 

Starting current

w2

A

0.40

0.40<3.33>

 

 

 

External finish

 

 

 

 

Munsell 0.70Y8.59/0.97

 

 

UNIT

Heat exchanger

 

 

 

 

Plate fin coil

 

 

Fan

Fan(drive) x No.

 

 

 

 

Line flow (direct) x 1

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

Fan motor output

 

 

kW

 

0.030

 

 

 

 

 

Airflow(Lo-Mi2-Mi1-Hi)

K/min(CFM)

 

9-10-11-12(318-353-388-424)

 

 

 

 

 

 

 

 

 

 

 

 

 

External static pressure

Pa(mmAq)

 

0(direct blow)

 

 

 

Booster heater

w2

kW

 

<0.80>

 

 

 

Operation control & Thermostat

 

Wireless remote controller & built-in

 

 

 

Noise level(Lo-Mi2-Mi1-Hi)

 

 

dB

 

36-38-41-43

 

 

 

Unit drain pipe O.D.

 

 

mm(in.)

 

20(13/16)

 

 

 

Dimensions

 

W

mm(in.)

 

990(39)

 

 

 

 

 

 

 

 

D

mm(in.)

 

235(9-1/4)

 

 

 

 

 

 

 

 

H

mm(in.)

 

340(13-3/8)

 

 

 

Weight

With Electric heater

kg(lbs)

 

17(37)

 

 

 

Without Electric heater

kg(lbs)

 

16(35)

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

 

PUH-P1.6VGA / PUH-P1.6YGA

 

 

 

Power supply (phase, cycle, voltage)

 

Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)

 

 

 

 

 

 

Running current

 

 

A

7.66 / 2.67

8.19 / 2.86

 

 

 

 

 

 

Starting current

 

 

A

 

36 / 20

 

 

 

External finish

 

 

 

 

Munsell 5Y 8/1

 

 

 

Refrigerant control

 

 

 

 

Linear Expansion Valve

 

 

 

Compressor

 

 

 

 

Hermetic

 

 

UNIT

 

 

 

Model

 

 

 

 

RE277VHSM / RE277YFKM

 

 

 

 

 

Motor output

 

 

kW

 

1.3

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

Starter type

 

 

 

 

Line start

 

 

 

 

 

Protection devices

 

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase heater

 

 

W

 

30

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

Fan

Fan(drive) x No.

 

 

 

 

Propeller (direct) x 1

 

 

 

 

 

 

Fan motor output

 

 

kW

 

0.070

 

 

 

 

 

 

Airflow

 

 

K/min(CFM)

 

45(1,590)

 

 

 

Defrost method

 

 

 

 

Reverse cycle

 

 

 

Noise level

Cooling

dB

 

46

 

 

 

 

 

 

 

Heating

dB

 

48

 

 

 

Dimensions

 

W

mm(in.)

 

900(35-7/16)

 

 

 

 

 

 

 

 

D

mm(in.)

 

330+20(13+3/4)

 

 

 

 

 

 

 

 

H

mm(in.)

 

650(25-5/8)

 

 

 

Weight

 

 

 

kg(lbs)

 

55(121)

 

 

PIPING

Refrigerant

 

 

 

 

R407C

 

 

 

 

 

Charge

 

 

kg(lbs)

 

2.6(5.7)

 

 

 

 

 

Oil (Model)

Liquid

L

 

0.57 (Ester)MEL56

 

 

REFRIGERANT

Pipe size O.D.

mm(in.)

 

9.52 (3/8)

 

 

 

 

 

 

Gas

mm(in.)

 

15.88 (5/8)

 

 

 

 

 

 

 

 

 

 

 

Connection method

Indoor side

 

Flared

 

 

 

 

 

 

 

Outdoor side

 

Flared

 

 

 

Between the indoor &

Height difference

 

Max. 40m

 

 

 

outdoor unit

Piping length

 

Max. 40m

 

Notes1. Rating Conditions (ISO T1)

 

 

 

 

 

Cooling : Indoor

: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor

: D.B. 35˚C(95˚F),

W.B. 24˚C (75˚F)

Heating : Indoor

: D.B. 20˚C(68˚F)

 

Outdoor

: D.B. 7˚C(45˚F),

W.B. 6˚C (43˚F)

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

2. Guaranteed operating range

 

 

 

w1 : (

) Shows the total rating.

 

 

 

 

Indoor

Outdoor

 

 

 

 

 

 

w2 : < > Shows the only booster heater rating.

 

Cooling

Upper limit

D.B. 35˚C,

W.B. 22.5˚C

D.B. 46˚C

 

 

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

D.B. -5˚C

 

 

 

 

 

 

 

 

 

Heating

Upper limit

D.B. 28˚C

D.B. 24˚C, W.B. 18˚C

 

 

 

Lower limit

D.B. 17˚C

D.B. -11˚C, W.B. -12˚C

 

 

3. Above data based on indicated voltage Indoor Unit Single phase 240V 50Hz

Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Service Ref. With Electric heater

 

 

PKH-P2GALH

 

 

 

 

 

Without Electric heater

 

 

PKA-P2GAL

Function

 

 

 

 

 

 

 

 

 

 

Cooling

Heating

Capacity

 

w1

 

 

 

 

Btu/h

 

 

18,800

22,300(25,100)

 

 

 

 

 

W

 

 

5,500

6,550(7,350)

 

 

 

 

 

 

 

 

 

 

 

Total input

 

w1

 

 

 

 

kW

 

 

2.55

2.64(3.44)

 

Service Ref.

 

 

 

 

With Electric heater

 

 

PKH-P2GALH

 

 

 

 

 

Without Electric heater

 

 

PKA-P2GAL

 

 

 

 

 

 

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

 

 

 

 

Single phase, 50Hz, 220-230-240V

 

 

 

Input

 

 

 

w2

kW

 

 

0.07

0.07<0.80>

 

 

 

Running current

w2

A

 

 

0.33

0.33<3.33>

 

 

 

Starting current

w2

A

 

 

0.40

0.40<3.33>

 

External finish

 

 

 

 

 

 

 

 

 

 

Munsell 0.70Y 8.59/0.97

UNIT

Heat exchanger

 

 

 

 

 

 

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

 

 

 

Line flow (direct) x 1

 

 

Fan motor output

 

 

kW

 

 

 

 

0.030

INDOOR

 

 

 

 

 

 

 

 

 

 

Airflow(Lo-Mi2-Mi1-Hi)

K/min(CFM)

 

9-10-11-12(318-353-388-424)

 

 

External static pressure

Pa(mmAq)

 

 

0(direct blow)

Booster heater

 

 

 

w2

kW

 

 

 

 

<0.80>

 

 

 

 

 

 

 

 

 

Operation control & Thermostat

 

 

 

 

 

Wireless remote controller & built-in

 

Noise level(Lo-Mi2-Mi1-Hi)

 

 

dB

 

 

36-38-41-43

 

Unit drain pipe O.D.

 

 

 

 

mm(in.)

 

 

 

 

20(13/16)

 

Dimensions

 

 

 

 

W

mm(in.)

 

 

 

 

990(39)

 

 

 

 

 

 

 

 

D

mm(in.)

 

 

 

 

235(9-1/4)

 

 

 

 

 

 

 

 

H

mm(in.)

 

 

 

 

340(13-3/8)

 

Weight

With Electric heater

kg(lbs)

 

 

 

 

17(37)

 

Without Electric heater

kg(lbs)

 

 

 

 

16(35)

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

 

 

 

 

 

 

 

 

PUH-P2VGA / PUH-P2YGA

 

Power supply (phase, cycle, voltage)

 

 

 

Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)

 

 

 

Running current

 

 

A

 

 

11.11 / 3.88

11.51 / 4.02

 

 

 

Starting current

 

 

A

 

 

 

 

74 / 30

 

External finish

 

 

 

 

 

 

 

 

 

 

Munsell 5Y 8/1

 

Refrigerant control

 

 

 

 

 

 

 

 

 

Linear Expansion Valve

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

Hermetic

UNIT

 

 

Model

 

 

 

 

 

 

 

 

 

 

NE38VMJM / NE38YEJM

 

 

Motor output

 

 

kW

 

 

 

 

1.7

 

 

Starter type

 

 

 

 

 

 

 

 

 

 

Line start

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection devices

 

 

 

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.

Crankcase heater

 

 

 

 

W

 

 

 

 

38

Heat exchanger

 

 

 

 

 

 

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

 

 

 

Propeller (direct) x 1

 

 

 

 

 

 

 

 

 

 

 

Fan motor output

 

 

kW

 

 

 

 

0.070

 

 

 

Airflow

 

 

 

 

K/min(CFM)

 

 

 

55(1,940)

 

Defrost method

 

 

 

 

 

 

 

 

 

 

Reverse cycle

 

Noise level

 

 

 

Cooling

dB

 

 

 

 

48

 

 

 

 

 

 

 

Heating

dB

 

 

 

 

49

 

Dimensions

 

 

 

 

W

mm(in.)

 

 

900(35-7/16)

 

 

 

 

 

 

 

 

D

mm(in.)

 

 

330+20(13+3/4)

 

 

 

 

 

 

 

 

H

mm(in.)

 

 

 

 

855(33-5/8)

 

Weight

 

 

 

 

 

kg(lbs)

 

 

 

 

71(157)

PIPING

Refrigerant

 

 

 

 

 

 

 

 

 

 

 

R407C

 

 

Charge

 

 

 

 

kg(lbs)

 

 

 

 

3.1(6.8)

 

 

Oil (Model)

 

 

Liquid

L

 

 

 

1.2 (Ester)MEL56

REFRIGERANT

Pipe size O.D.

 

 

 

mm(in.)

 

 

 

 

9.52 (3/8)

 

 

 

 

 

 

Gas

mm(in.)

 

 

 

 

15.88 (5/8)

Connection method

 

 

Indoor side

 

 

 

 

Flared

 

 

 

 

 

 

Outdoor side

 

 

 

 

Flared

Between the indoor &

 

 

Height difference

 

 

 

 

Max. 40m

outdoor unit

 

 

 

Piping length

 

 

 

 

Max. 40m

 

 

 

 

 

 

 

 

Notes1. Rating Conditions (ISO T1)

 

 

 

 

 

 

 

 

Cooling : Indoor

: D.B. 27˚C(80˚F),

W.B. 19˚C (66˚F) Outdoor

: D.B. 35˚C(95˚F),

W.B. 24˚C (75˚F)

 

Heating : Indoor

: D.B. 20˚C(68˚F)

 

 

 

Outdoor

: D.B. 7˚C(45˚F),

W.B. 6˚C (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

 

 

2. Guaranteed operating range

 

 

 

 

 

w1 : (

) Shows the total rating.

 

 

 

 

 

 

 

 

Indoor

 

 

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

w2 : < > Shows the only booster heater rating.

 

 

 

Cooling

Upper limit

 

D.B. 35˚C, W.B. 22.5˚C

 

 

D.B. 46˚C

 

 

 

 

 

 

Lower limit

 

D.B. 19˚C,

W.B. 15˚C

 

 

D.B. -5˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Upper limit

 

 

D.B. 28˚C

 

D.B. 24˚C, W.B. 18˚C

 

 

 

 

 

Lower limit

 

 

D.B. 17˚C

 

D.B. -11˚C, W.B. -12˚C

 

 

3. Above data based on indicated voltage

Indoor Unit Single phase 240V 50Hz

Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz

8

Mitsubishi PKA-P1.6GAL, PKA-P2GAL, PKH-P1.6GALH, PKH-P2GALH, PKA-P1.6GAL1 Service Manual

2. Cooling only type

Item

Service Ref.

PKA-P1.6GAL

PKA-P2GAL

 

 

 

 

 

 

 

 

Function

 

Cooling

Cooling

Capacity

Btu/h

15,000

18,800

W

4,400

5,500

 

Total input

kW

1.78

2.55

 

Service Ref.

 

 

PKA-P1.6GAL

PKA-P2GAL

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

Single phase, 50Hz, 220-230-240V

 

 

Input

 

kW

 

0.07

 

 

Running current

 

A

 

0.33

 

 

Starting current

 

A

 

0.40

 

External finish

 

 

 

Munsell 0.70Y 8.59/0.97

UNIT

Heat exchanger

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

Line flow (direct) x 1

 

Fan motor output

 

kW

 

0.030

INDOOR

 

 

 

 

Airflow(Lo-Mi2-Mi1-Hi)

 

K/min(CFM)

9-10-11-12 (318-353-388-424)

 

External static pressure

Pa(mmAq)

 

0(direct blow)

Booster heater

 

kW

 

 

 

 

 

Operation control & Thermostat

 

 

Wireless remote controller & built-in

 

Noise level(Lo-Mi2-Mi1-Hi)

 

dB

 

36-38-41-43

 

Unit drain pipe O.D.

 

mm(in.)

 

20(13/16)

 

Dimensions

 

W

mm(in.)

 

990(39)

 

 

 

 

D

mm(in.)

 

235(9-1/4)

 

 

 

 

H

mm(in.)

 

340(13-3/8)

 

Weight

 

 

 

kg(lbs)

 

16(35)

 

Service Ref.

 

 

 

 

 

PU-P1.6VGA

PU-P2VGA

 

Power supply (phase, cycle, voltage)

 

 

 

Single phase, 50Hz, 220-230-240V

 

 

Running current

 

 

A

7.66

11.11

 

 

Starting current

 

 

A

36

74

 

External finish

 

 

 

 

 

 

Munsell 5Y 8/1

 

Refrigerant control

 

 

 

 

 

Linear Expansion Valve

 

Compressor

 

 

 

 

 

 

 

Hermetic

UNIT

 

Model

 

 

 

 

RE277VHSM

NE38VMJM

 

Motor output

 

 

kW

1.3

1.7

 

Starter type

 

 

 

 

 

 

Line start

OUTDOOR

 

 

 

 

 

 

 

 

Protection devices

 

 

Internal thermostat, HP switch, Discharge thermo.

Crankcase heater

 

 

W

30

38

Heat exchanger

 

 

 

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

 

Propeller (direct) x 1

 

 

 

 

 

 

 

 

Fan motor output

 

 

kW

 

 

0.070

 

 

Airflow

 

 

K/min(CFM)

45(1,590)

55(1,940)

 

Defrost method

 

 

 

 

 

 

 

Noise level

 

 

Cooling

dB

46

48

 

 

Dimensions

 

W

mm(in.)

 

 

900(35-7/16)

 

 

 

 

 

D

mm(in.)

330+20(13+3/4)

 

 

 

 

 

H

mm(in.)

650(25-5/8)

855(33-5/8)

 

Weight

 

 

 

kg(lbs)

55(121)

71(157)

PIPING

Refrigerant

 

 

 

 

 

 

 

R407C

 

Charge

 

 

kg(lbs)

2.6(5.7)

3.1(6.8)

 

Oil (Model)

 

Liquid

L

0.57 (Ester)MEL56

1.2 (Ester)MEL56

REFRIGERANT

Pipe size O.D.

 

 

mm(in.)

 

 

9.52 (3/8)

 

 

 

 

Gas

mm(in.)

 

 

15.88 (5/8)

Connection method

 

Indoor side

 

 

Flared

 

 

 

 

Outdoor side

 

 

Flared

Between the indoor &

 

Height difference

 

 

Max. 40m

outdoor unit

 

 

Piping length

 

 

Max. 40m

 

 

 

 

 

Notes1. Rating Conditions (ISO T1)

 

 

 

 

 

 

Cooling : Indoor : D.B. 27˚C(80˚F),

W.B. 19˚C (66˚F)

Outdoor : D.B. 35˚C(95˚F),

W.B. 24˚C (75˚F)

 

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

2. Guaranteed operating range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

Outdoor

 

 

 

 

Cooling

Upper limit

D.B. 35˚C, W.B. 22.5˚C

 

D.B. 46˚C

 

 

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

 

D.B. -5˚C

 

 

 

 

 

 

 

 

3. Above data based on indicated voltage Indoor Unit Single phase 240V 50Hz Outdoor Unit Single phase 240V 50Hz

9

3. Heat pump

Item

Service Ref. With Electric heater

 

PKH-P1.6GALH1

 

 

Without Electric heater

 

PKA-P1.6GAL1

Function

 

 

 

 

Cooling

Heating

Capacity

w1

 

 

Btu/h

15,300

17,100(19,800)

 

 

W

4,500

5,000(5,800)

 

 

 

 

 

Total input

w1

 

 

kW

1.74

1.86(2.66)

 

Service Ref.

 

With Electric heater

 

PKH-P1.6GALH1

 

 

Without Electric heater

 

PKA-P1.6GAL1

 

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

Single phase, 50Hz, 220-230-240V

 

 

Input

w2

kW

0.07

0.07<0.80>

 

 

Running current

w2

A

0.33

0.33<3.33>

 

 

Starting current

w2

A

0.40

0.40<3.33>

 

External finish

 

 

 

 

Munsell 0.70Y8.59/0.97

UNIT

Heat exchanger

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

Line flow (direct) x 1

 

 

 

 

 

INDOOR

 

Fan motor output

 

 

kW

 

0.030

 

Airflow(Lo-Mi2-Mi1-Hi)

K/min(CFM)

 

9-10-11-12(318-353-388-424)

 

 

 

 

 

External static pressure

Pa(mmAq)

 

0(direct blow)

 

Booster heater

w2

kW

 

<0.80>

 

Operation control & Thermostat

 

Wireless remote controller & built-in

 

Noise level(Lo-Mi2-Mi1-Hi)

 

 

dB

 

36-38-41-43

 

Unit drain pipe O.D.

 

 

mm(in.)

 

20(13/16)

 

Dimensions

 

W

mm(in.)

 

990(39)

 

 

 

 

D

mm(in.)

 

235(9-1/4)

 

 

 

 

H

mm(in.)

 

340(13-3/8)

 

Weight

With Electric heater

kg(lbs)

 

17(37)

 

Without Electric heater

kg(lbs)

 

16(35)

 

 

 

 

Service Ref.

 

 

 

PUH-P1.6VGAA.UK / PUH-P1.6YGAA.UK

 

Power supply (phase, cycle, voltage)

 

Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)

 

 

Running current

 

 

A

7.36 / 2.49

7.59 / 2.56

 

 

Starting current

 

 

A

 

36 / 20

 

External finish

 

 

 

 

Munsell 5Y 7/1

 

Refrigerant control

 

 

 

 

Linear Expansion Valve

 

Compressor

 

 

 

 

Hermetic

UNIT

 

Model

 

 

 

 

RE277VHSMT / RE277YFKM

 

Motor output

 

 

kW

 

1.3

 

 

 

 

 

OUTDOOR

 

Starter type

 

 

 

 

Line start

 

Protection devices

 

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch.

 

 

 

 

 

 

Crankcase heater

 

 

W

 

30

 

Heat exchanger

 

 

 

 

Plate fin coil

 

Fan

Fan(drive) x No.

 

 

 

 

Propeller (direct) x 1

 

 

Fan motor output

 

 

kW

 

0.070

 

 

Airflow

 

 

K/min(CFM)

 

45(1,590)

 

Defrost method

 

 

 

 

Reverse cycle

 

Noise level

Cooling

dB

 

47

 

 

 

Heating

dB

 

49

 

Dimensions

 

W

mm(in.)

 

900(35-7/16)

 

 

 

 

D

mm(in.)

 

330+20(13+3/4)

 

 

 

 

H

mm(in.)

 

650(25-5/8)

 

Weight

 

 

 

kg(lbs)

 

55(121)

PIPING

Refrigerant

 

 

 

 

R407C

 

Charge

 

 

kg(lbs)

 

2.5(5.5)

 

Oil (Model)

Liquid

L

 

0.57 (Ester)MEL56

REFRIGERANT

Pipe size O.D.

mm(in.)

 

9.52 (3/8)

 

 

Gas

mm(in.)

 

15.88 (5/8)

 

 

 

 

 

Connection method

Indoor side

 

Flared

 

 

 

Outdoor side

 

Flared

 

Between the indoor &

Height difference

 

Max. 40m

 

outdoor unit

Piping length

 

Max. 40m

Notes1. Rating Conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor

: D.B. 35˚C(95˚F),

W.B. 24˚C (75˚F)

Heating : Indoor

: D.B. 20˚C(68˚F)

Outdoor

: D.B. 7˚C(45˚F),

W.B. 6˚C (43˚F)

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

2. Guaranteed operating range

 

 

w1 : (

) Shows the total rating.

 

 

 

 

Indoor

Outdoor

 

 

 

 

 

 

w2 : < > Shows the only booster heater rating.

 

Cooling

Upper limit

D.B. 35˚C, W.B. 22.5˚C

D.B. 46˚C

 

 

 

 

Lower limit

D.B. 19˚C, W.B. 15˚C

D.B. -5˚C

 

 

 

 

 

 

 

 

 

Heating

Upper limit

D.B. 28˚C

D.B. 24˚C, W.B. 18˚C

 

 

 

Lower limit

D.B. 17˚C

D.B. -11˚C, W.B. -12˚C

 

 

3. Above data based on indicated voltage Indoor Unit Single phase 240V 50Hz

Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Service Ref. With Electric heater

 

PKH-P2GALH1

 

 

Without Electric heater

 

PKA-P2GAL1

Function

 

 

 

 

Cooling

Heating

Capacity

w1

 

 

Btu/h

18,400

21,300(24,000)

 

 

W

5,400

6,250(7,050)

 

 

 

 

 

Total input

w1

 

 

kW

2.37

2.38(3.18)

 

Service Ref.

 

With Electric heater

 

PKH-P2GALH1

 

 

Without Electric heater

 

PKA-P2GAL1

 

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

Single phase, 50Hz, 220-230-240V

 

 

Input

w2

kW

0.07

0.07<0.80>

 

 

Running current

w2

A

0.33

0.33<3.33>

 

 

Starting current

w2

A

0.40

0.40<3.33>

 

External finish

 

 

 

 

Munsell 0.70Y 8.59/0.97

UNIT

Heat exchanger

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

Line flow (direct) x 1

 

 

 

 

 

INDOOR

 

Fan motor output

 

 

kW

 

0.030

 

Airflow(Lo-Mi2-Mi1-Hi)

K/min(CFM)

9-10-11-12(318-353-388-424)

 

 

 

 

External static pressure

Pa(mmAq)

 

0(direct blow)

 

Booster heater

w2

kW

 

<0.80>

 

Operation control & Thermostat

 

Wireless remote controller & built-in

 

Noise level(Lo-Mi2-Mi1-Hi)

 

 

dB

 

36-38-41-43

 

Unit drain pipe O.D.

 

 

mm(in.)

 

20(13/16)

 

Dimensions

 

W

mm(in.)

 

990(39)

 

 

 

 

D

mm(in.)

 

235(9-1/4)

 

 

 

 

H

mm(in.)

 

340(13-3/8)

 

Weight

With Electric heater

kg(lbs)

 

17(37)

 

Without Electric heater

kg(lbs)

 

16(35)

 

 

 

 

Service Ref.

 

 

 

PUH-P2VGAA.UK / PUH-P2YGAA.UK

 

Power supply (phase, cycle, voltage)

 

Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)

 

 

Running current

 

 

A

10.26 / 3.70

10.57 / 3.82

 

 

Starting current

 

 

A

 

62 / 31

 

External finish

 

 

 

 

Munsell 5Y 7/1

 

Refrigerant control

 

 

 

 

Linear Expansion Valve

 

Compressor

 

 

 

 

Hermetic

UNIT

 

Model

 

 

 

 

NE36VMJMT / NE36YEKMT

 

Motor output

 

 

kW

 

1.6

 

 

 

 

 

OUTDOOR

 

Starter type

 

 

 

 

Line start

 

Protection devices

 

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch.

 

 

 

 

 

 

Crankcase heater

 

 

W

 

38

 

Heat exchanger

 

 

 

 

Plate fin coil

 

Fan

Fan(drive) x No.

 

 

 

 

Propeller (direct) x 1

 

 

Fan motor output

 

 

kW

 

0.070

 

 

Airflow

 

 

K/min(CFM)

 

55(1,940)

 

Defrost method

 

 

 

 

Reverse cycle

 

Noise level

Cooling

dB

 

48

 

 

 

Heating

dB

 

49

 

Dimensions

 

W

mm(in.)

 

900(35-7/16)

 

 

 

 

D

mm(in.)

 

330+20(13+3/4)

 

 

 

 

H

mm(in.)

 

855(33-5/8)

 

Weight

 

 

 

kg(lbs)

 

71(157)

PIPING

Refrigerant

 

 

 

 

R407C

 

Charge

 

 

kg(lbs)

 

2.6(5.7)

 

Oil (Model)

Liquid

L

 

1.2 (Ester)MEL56

REFRIGERANT

Pipe size O.D.

mm(in.)

 

9.52 (3/8)

 

 

Gas

mm(in.)

 

15.88 (5/8)

 

 

 

 

 

Connection method

Indoor side

 

Flared

 

 

 

Outdoor side

 

Flared

 

Between the indoor &

Height difference

 

Max. 40m

 

outdoor unit

Piping length

 

Max. 40m

Notes1. Rating Conditions (ISO T1)

 

 

 

 

 

Cooling : Indoor

: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor

: D.B. 35˚C(95˚F),

W.B. 24˚C (75˚F)

Heating : Indoor

: D.B. 20˚C(68˚F)

 

Outdoor

: D.B. 7˚C(45˚F),

W.B. 6˚C (43˚F)

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

2. Guaranteed operating range

 

 

 

w1 : (

) Shows the total rating.

 

 

 

 

Indoor

Outdoor

 

 

 

 

 

 

w2 : < > Shows the only booster heater rating.

 

Cooling

Upper limit

D.B. 35˚C,

W.B. 22.5˚C

D.B. 46˚C

 

 

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

D.B. -5˚C

 

 

 

 

 

 

 

 

 

Heating

Upper limit

D.B. 28˚C

D.B. 24˚C, W.B. 18˚C

 

 

 

Lower limit

D.B. 17˚C

D.B. -11˚C, W.B. -12˚C

 

 

3. Above data based on indicated voltage

Indoor Unit Single phase 240V 50Hz

Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz

11

4. Cooling only type

Item

 

 

 

 

Service Ref.

PKA-P1.6GAL1

 

PKA-P2GAL1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

 

 

 

 

Cooling

 

Cooling

Capacity

 

 

 

 

Btu/h

15,300

 

18,400

 

 

 

 

W

4,500

 

5,400

 

 

 

 

 

 

 

 

Total input

 

 

 

 

kW

1.74

 

2.37

 

Service Ref.

 

 

 

 

PKA-P1.6GAL1

 

PKA-P2GAL1

 

 

 

 

 

 

 

 

 

 

 

Power supply(phase, cycle,voltage)

 

 

 

Single phase, 50Hz, 220-230-240V

 

 

 

Input

 

 

kW

0.07

 

 

 

 

Running current

 

 

A

0.33

 

 

 

 

Starting current

 

 

A

0.40

 

 

External finish

 

 

 

 

 

Munsell 0.70Y 8.59/0.97

UNIT

Heat exchanger

 

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

 

Line flow (direct) x 1

 

 

Fan motor output

 

 

kW

0.030

INDOOR

 

 

 

 

 

 

Airflow(Lo-Mi2-Mi1-Hi)

K/min(CFM)

9-10-11-12 (318-353-388-424)

 

 

External static pressure

Pa(mmAq)

 

0(direct blow)

Booster heater

 

 

kW

 

 

 

 

 

 

 

 

Operation control & Thermostat

 

 

 

Wireless remote controller & built-in

 

Noise level(Lo-Mi2-Mi1-Hi)

 

 

dB

36-38-41-43

 

Unit drain pipe O.D.

 

 

mm(in.)

20(13/16)

 

Dimensions

 

W

mm(in.)

990(39)

 

 

 

 

 

 

D

mm(in.)

235(9-1/4)

 

 

 

 

 

 

H

mm(in.)

340(13-3/8)

 

Weight

 

 

 

 

kg(lbs)

16(35)

 

Service Ref.

 

 

 

 

PU-P1.6VGAA.UK / PU-P1.6YGAA.UK

PU-P2VGAA.UK / PU-P2YGAA.UK

 

Power supply (phase, cycle, voltage)

 

 

Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V(4wires)

 

 

 

Running current

 

 

A

7.36 / 2.49

 

10.26 / 3.70

 

 

 

Starting current

 

 

A

36 / 20

 

62 / 31

 

External finish

 

 

 

 

 

Munsell 5Y 7/1

 

Refrigerant control

 

 

 

 

 

Linear Expansion Valve

 

Compressor

 

 

 

 

 

Hermetic

UNIT

 

 

Model

 

 

 

 

RE277VHSMT / RE277YFKM

NE36VMJMT / NE36YEKMT

 

 

Motor output

 

 

kW

1.3

 

1.6

 

 

Starter type

 

 

 

 

 

Line start

OUTDOOR

 

 

 

 

 

 

 

 

 

Protection devices

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch.

Crankcase heater

 

 

W

30

 

38

Heat exchanger

 

 

 

 

 

Plate fin coil

Fan

Fan(drive) x No.

 

 

 

 

 

Propeller (direct) x 1

 

 

 

 

 

 

 

 

 

Fan motor output

 

 

kW

0.070

 

 

 

Airflow

 

 

K/min(CFM)

45(1,590)

 

55(1,940)

 

Defrost method

 

 

 

 

 

 

Noise level

 

Cooling

dB

47

 

48

 

 

 

Dimensions

 

W

mm(in.)

900(35-7/16)

 

 

 

 

 

 

D

mm(in.)

330+20(13+3/4)

 

 

 

 

 

 

H

mm(in.)

650(25-5/8)

 

855(33-5/8)

 

Weight

 

 

 

 

kg(lbs)

55(121)

 

71(157)

PIPING

Refrigerant

 

 

 

 

 

R407C

 

 

Charge

 

 

kg(lbs)

2.5(5.5)

 

2.6(5.7)

 

 

Oil (Model)

 

Liquid

L

0.57 (Ester)MEL56

1.2 (Ester)MEL56

REFRIGERANT

Pipe size O.D.

 

mm(in.)

9.52 (3/8)

 

 

 

 

 

Gas

mm(in.)

15.88 (5/8)

Connection method

 

Indoor side

 

Flared

 

 

 

 

 

Outdoor side

 

Flared

Between the indoor &

 

Height difference

 

Max. 40m

outdoor unit

 

Piping length

 

Max. 40m

 

 

 

Notes1. Rating Conditions (ISO T1)

 

 

 

 

 

 

 

Cooling : Indoor : D.B. 27˚C(80˚F),

W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)

 

Refrigerant piping length (one way) : 5m (16ft)

 

 

 

 

 

2. Guaranteed operating range

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

Outdoor

 

 

 

 

 

Cooling

Upper limit

D.B. 35˚C, W.B. 22.5˚C

 

D.B. 46˚C

 

 

 

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

 

D.B. -5˚C

 

 

 

 

 

 

 

 

 

 

3. Above data based on indicated voltage Indoor Unit Single phase 240V 50Hz

Outdoor Unit Single phase 240V 50Hz / 3 pahses 415V 50Hz

12

6 DATA

1.PERFORMANCE DATA

1)COOLING CAPACITY<1> PKH-P1.6GALH PKA-P1.6GAL

Indoor

Indoor

 

 

 

 

 

 

Outdoor intake air D.B.(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

25

 

 

 

30

 

 

Intake air

Intake air

 

 

 

 

 

 

 

 

 

 

D.B.(°C)

W.B.(°C)

 

CA

SHC(W)

 

SHF

P.C.

CA

SHC(W)

 

SHF

P.C.

CA

SHC(W)

 

SHF

P.C.

20

16

 

4,356

2,919

 

0.67

1.42

4,224

2,830

 

0.67

1.50

4,092

2,742

 

0.67

1.59

20

18

 

4,664

2,565

 

0.55

1.45

4,532

2,493

 

0.55

1.53

4,378

2,408

 

0.55

1.64

20

20

 

5,016

2,157

 

0.43

1.50

4,906

2,110

 

0.43

1.57

4,774

2,053

 

0.43

1.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

16

 

4,356

3,267

 

0.75

1.42

4,224

3,168

 

0.75

1.50

4,092

3,069

 

0.75

1.59

22

18

 

4,664

2,938

 

0.63

1.45

4,532

2,855

 

0.63

1.53

4,378

2,758

 

0.63

1.64

22

20

 

5,016

2,558

 

0.51

1.50

4,906

2,502

 

0.51

1.57

4,774

2,435

 

0.51

1.67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

16

 

4,356

3,615

 

0.83

1.42

4,224

3,506

 

0.83

1.50

4,092

3,396

 

0.83

1.59

24

18

 

4,664

3,311

 

0.71

1.45

4,532

3,218

 

0.71

1.53

4,378

3,108

 

0.71

1.64

24

20

 

5,016

2,959

 

0.59

1.50

4,906

2,895

 

0.59

1.57

4,774

2,817

 

0.59

1.67

24

22

 

5,346

2,513

 

0.47

1.53

5,236

2,461

 

0.47

1.62

5,104

2,399

 

0.47

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

16

 

4,356

3,964

 

0.91

1.42

4,224

3,844

 

0.91

1.50

4,092

3,724

 

0.91

1.59

26

18

 

4,664

3,685

 

0.79

1.45

4,532

3,580

 

0.79

1.53

4,378

3,459

 

0.79

1.64

26

20

 

5,016

3,361

 

0.67

1.50

4,906

3,287

 

0.67

1.57

4,774

3,199

 

0.67

1.67

26

22

 

5,346

2,940

 

0.55

1.53

5,236

2,880

 

0.55

1.62

5,104

2,807

 

0.55

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

16

 

4,356

4,312

 

0.99

1.42

4,224

4,182

 

0.99

1.50

4,092

4,051

 

0.99

1.59

28

18

 

4,664

4,058

 

0.87

1.45

4,532

3,943

 

0.87

1.53

4,378

3,809

 

0.87

1.64

28

20

 

5,016

3,762

 

0.75

1.50

4,906

3,680

 

0.75

1.57

4,774

3,581

 

0.75

1.67

28

22

 

5,346

3,368

 

0.63

1.53

5,236

3,299

 

0.63

1.62

5,104

3,216

 

0.63

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

16

 

4,356

4,356

 

1.00

1.42

4,224

4,224

 

1.00

1.50

4,092

4,092

 

1.00

1.59

30

18

 

4,664

4,431

 

0.95

1.45

4,532

4,305

 

0.95

1.53

4,378

4,159

 

0.95

1.64

30

20

 

5,016

4,163

 

0.83

1.50

4,906

4,072

 

0.83

1.57

4,774

3,962

 

0.83

1.67

30

22

 

5,346

3,796

 

0.71

1.53

5,236

3,718

 

0.71

1.62

5,104

3,624

 

0.71

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

16

 

4,356

4,356

 

1.00

1.42

4,224

4,224

 

1.00

1.50

4,092

4,092

 

1.00

1.59

32

18

 

4,664

4,664

 

1.00

1.45

4,532

4,532

 

1.00

1.53

4,378

4,378

 

1.00

1.64

32

20

 

5,016

4,565

 

0.91

1.50

4,906

4,464

 

0.91

1.57

4,774

4,344

 

0.91

1.67

32

22

 

5,346

4,223

 

0.79

1.53

5,236

4,136

 

0.79

1.62

5,104

4,032

 

0.79

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

16

 

4,356

4,356

 

1.00

1.42

4,224

4,224

 

1.00

1.50

4,092

4,092

 

1.00

1.59

34

18

 

4,664

4,664

 

1.00

1.45

4,532

4,532

 

1.00

1.53

4,378

4,378

 

1.00

1.64

34

20

 

5,016

4,966

 

0.99

1.50

4,906

4,857

 

0.99

1.57

4,774

4,726

 

0.99

1.67

34

22

 

5,346

4,651

 

0.87

1.53

5,236

4,555

 

0.87

1.62

5,104

4,440

 

0.87

1.73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CA : Capacity (W)

 

 

 

SHC(W) : Sensible heat capacity

 

 

 

 

 

 

P.C. : Power consumption (kW)

SHF : Sensible heat factor

 

 

 

 

 

 

 

13

COOLING CAPACITY<2>

PKH-P1.6GALH

PKA-P1.6GAL

Indoor

Indoor

 

 

 

 

 

 

Outdoor intake air D.B.(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

 

 

40

 

 

 

45

 

 

Intake air

Intake air

 

 

 

 

 

 

 

 

 

 

D.B.(°C)

W.B.(°C)

 

CA

SHC(W)

 

SHF

P.C.

CA

SHC(W)

 

SHF

P.C.

CA

SHC(W)

 

SHF

P.C.

20

16

 

3,916

2,624

 

0.67

1.71

3,740

2,506

 

0.67

1.83

3,564

2,388

 

0.67

1.98

20

18

 

4,224

2,323

 

0.55

1.75

4,092

2,251

 

0.55

1.89

3,828

2,105

 

0.55

2.03

20

20

 

4,576

1,968

 

0.43

1.80

4,400

1,892

 

0.43

1.92

4,136

1,778

 

0.43

2.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

16

 

3,916

2,937

 

0.75

1.71

3,740

2,805

 

0.75

1.83

3,564

2,673

 

0.75

1.98

22

18

 

4,224

2,661

 

0.63

1.75

4,092

2,578

 

0.63

1.89

3,828

2,412

 

0.63

2.03

22

20

 

4,576

2,334

 

0.51

1.80

4,400

2,244

 

0.51

1.92

4,136

2,109

 

0.51

2.06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

16

 

3,916

3,250

 

0.83

1.71

3,740

3,104

 

0.83

1.83

3,564

2,958

 

0.83

1.98

24

18

 

4,224

2,999

 

0.71

1.75

4,092

2,905

 

0.71

1.89

3,828

2,718

 

0.71

2.03

24

20

 

4,576

2,700

 

0.59

1.80

4,400

2,596

 

0.59

1.92

4,136

2,440

 

0.59

2.06

24

22

 

4,928

2,316

 

0.47

1.83

4,752

2,233

 

0.47

1.98

4,488

2,109

 

0.47

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

16

 

3,916

3,564

 

0.91

1.71

3,740

3,403

 

0.91

1.83

3,564

3,243

 

0.91

1.98

26

18

 

4,224

3,337

 

0.79

1.75

4,092

3,233

 

0.79

1.89

3,828

3,024

 

0.79

2.03

26

20

 

4,576

3,066

 

0.67

1.80

4,400

2,948

 

0.67

1.92

4,136

2,771

 

0.67

2.06

26

22

 

4,928

2,710

 

0.55

1.83

4,752

2,614

 

0.55

1.98

4,488

2,468

 

0.55

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

16

 

3,916

3,877

 

0.99

1.71

3,740

3,703

 

0.99

1.83

3,564

3,528

 

0.99

1.98

28

18

 

4,224

3,675

 

0.87

1.75

4,092

3,560

 

0.87

1.89

3,828

3,330

 

0.87

2.03

28

20

 

4,576

3,432

 

0.75

1.80

4,400

3,300

 

0.75

1.92

4,136

3,102

 

0.75

2.06

28

22

 

4,928

3,105

 

0.63

1.83

4,752

2,994

 

0.63

1.98

4,488

2,827

 

0.63

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

16

 

3,916

3,916

 

1.00

1.71

3,740

3,740

 

1.00

1.83

3,564

3,564

 

1.00

1.98

30

18

 

4,224

4,013

 

0.95

1.75

4,092

3,887

 

0.95

1.89

3,828

3,637

 

0.95

2.03

30

20

 

4,576

3,798

 

0.83

1.80

4,400

3,652

 

0.83

1.92

4,136

3,433

 

0.83

2.06

30

22

 

4,928

3,499

 

0.71

1.83

4,752

3,374

 

0.71

1.98

4,488

3,186

 

0.71

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

16

 

3,916

3,916

 

1.00

1.71

3,740

3,740

 

1.00

1.83

3,564

3,564

 

1.00

1.98

32

18

 

4,224

4,224

 

1.00

1.75

4,092

4,092

 

1.00

1.89

3,828

3,828

 

1.00

2.03

32

20

 

4,576

4,164

 

0.91

1.80

4,400

4,004

 

0.91

1.92

4,136

3,764

 

0.91

2.06

32

22

 

4,928

3,893

 

0.79

1.83

4,752

3,754

 

0.79

1.98

4,488

3,546

 

0.79

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

16

 

3,916

3,916

 

1.00

1.71

3,740

3,740

 

1.00

1.83

3,564

3,564

 

1.00

1.98

34

18

 

4,224

4,224

 

1.00

1.75

4,092

4,092

 

1.00

1.89

3,828

3,828

 

1.00

2.03

34

20

 

4,576

4,530

 

0.99

1.80

4,400

4,356

 

0.99

1.92

4,136

4,095

 

0.99

2.06

34

22

 

4,928

4,287

 

0.87

1.83

4,752

4,134

 

0.87

1.98

4,488

3,905

 

0.87

2.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CA : Capacity (W)

 

 

 

SHC(W) : Sensible heat capacity

 

 

 

 

 

 

P.C. : Power consumption (kW)

SHF : Sensible heat factor

 

 

 

 

 

 

 

14

Loading...