2001
Air-Conditioners For Building Application
TECHNICAL & SERVICE MANUAL
Series PEFY Ceiling Concealed
<Indoor unit>
Models PEFY-P40VMH-A,PEFY-P100VMH-A PEFY-P50VMH-A,PEFY-P125VMH-A PEFY-P63VMH-A,PEFY-P140VMH-A PEFY-P71VMH-A,PEFY-P200VMH-A PEFY-P80VMH-A,PEFY-P250VMH-A
CONTENTS
SAFETY PRECAUTIONS ·························1
1. FEATURES············································3
2. PART NAMES AND FUNCTIONS ········4
3. SPECIFICATION ···································6
4. OUTLINES AND DIMENSIONS············9
5. WIRING DIAGRAM ·····························11
6. REFRIGERANT SYSTEM DIAGRAM····13
7. TROUBLE SHOOTING························14
8. DISASSEMBLY PROCEDURE ···········17
INDOOR UNIT
SAFETY PRECAUTIONS
1.Before installation and electric work
sBefore installing the unit, make sure you read all the “Safety precautions”.
sThe “Safety precautions” provide very important points regarding safety. Make sure you follow them.
sThis equipment may cause the adverse effect on the same supply system.
sPlease report to or take consent by the supply authority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This symbol is displayed on the main unit label.) <Color: Yellow>
: Beware of electric shock (This symbol is displayed on the main unit label.) <Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
•Ask the dealer or an authorized technician to install the air conditioner.
-Improper installation by the user may result in water leakage, electric shock, or fire.
•Install the air unit at a place that can withstand its weight.
-Inadequate strength may cause the unit to fall down, resulting in injuries.
•Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
-Inadequate connection and fastening may generate heat and cause a fire.
•Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.
-Improper installation may cause the unit to topple and result in injury.
•Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
-Ask an authorized technician to install the accessories. Improper installation by the user may result in water leakage, electric shock, or fire.
•Never repair the unit. If the air conditioner must be repaired, consult the dealer.
-If the unit is repaired improperly, water leakage, electric shock, or fire may result.
•Do not touch the heat exchanger fins.
-Improper handling may result in injury.
•If refrigerant gas leaks during installation work, ventilate the room.
-If the refrigerant gas comes into contact with a flame, poisonous gases will be released.
•Install the air conditioner according to this Installation Manual.
-If the unit is installed improperly, water leakage, electric shock, or fire may result.
•Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
-If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
•Securely install the cover of control box and the panel.
-If the cover and panel are not installed properly,dust or water may enter the outdoor unit and fire or electric shock may result.
•When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R22) specified on the unit.
-If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
•If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
-Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
•When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
-If the air conditioner is installed improperly, water leakage, electric shock, or fire may result.
•After completing installation work, make sure that refrigerant gas is not leaking.
-If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may generate noxious gases.
•Do not reconstruct or change the settings of the protection devices.
-If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
1
2.Precautions for devices that use R407C refrigerant
Caution:
•Do not use the existing refrigerant piping.
-The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
•Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as specified in the *JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
-Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
*JIS: Japanese Industrial Standard
•Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
•Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
-The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
•Use liquid refrigerant to fill the system.
-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
•Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.
•Use a vacuum pump with a reverse flow check valve..
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
•Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
-If the conventional refrigerant and refrigerator oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerator oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
•Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
•Be especially careful when managing the tools.
-If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
2
1 FEATURES
Series PEFY Ceiling Concealed
|
Indoor unit |
|
|
|
|
Models |
|
Cooling capacity/Heating capacity |
|
|
|
|
kW |
|
|
||
|
|
|
|
|
|
PEFY-P40VMH-A |
|
4.5/5.0 |
PEFY-P50VMH-A |
|
5.6/6.3 |
PEFY-P63VMH-A |
|
7.1/8.0 |
PEFY-P71VMH-A |
|
8.0/9.0 |
PEFY-P80VMH-A |
|
9.0/10.0 |
PEFY-P100VMH-A |
|
11.2/12.5 |
PEFY-P125VMH-A |
|
14.0/16.0 |
PEFY-P140VMH-A |
|
16.0/18.0 |
PEFY-P200VMH-A |
|
22.4/25.0 |
PEFY-P250VMH-A |
|
28.0/31.5 |
|
|
|
3
2 PART NAMES AND FUNCTIONS
● Indoor (Main) Unit
Air outlet
Air inlet
● Remote controller [PAR-20MAA]
●Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttons
1
2
3
|
CENTRALLY CONTROLLED |
1Hr. |
|
|
|
|
ON OFF |
|
˚C |
|
CHECK |
CLOCK |
|
|
|
|
|
|
|
|
|
|
|
FILTER |
|
˚C |
|
|
CHECK MODE |
STAND BY |
ERROR CODE |
|
TEST RUN |
|
|
NOT AVAILABLE |
FUNCTION |
||
DEFROST |
|
|||
|
|
|||
|
TEMP. |
|
|
ON/OFF |
FILTER
CHECK TEST
PAR-20MAA |
TIMER SET |
B
A 0
|
|
|
|
|
|
|
|
|
|
|
C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 5 6 8 7 9 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
||||
1 |
[Room temperature adjustment] Button |
7 |
[Up/down airflow direction] Button |
||||||||
2 |
[Timer/continuous] Button |
8 |
[Ventilation] Button |
||||||||
3 |
[Selecting operation] Button |
9 |
[Checking/built-in] Button |
||||||||
4 |
[Time selection] Button |
0 |
[Test run] Button |
||||||||
|
[Time-setting] Button |
A [Filter] Button |
|||||||||
5 |
[Louver] Button |
B [ON/OFF] Button |
|||||||||
6 |
[Fan speed adjustment] Button |
C Position of built-in room temperature |
•Never expose the remote controller to direct sunlight. Doing so can result in the erroneous measurement of room temperature.
•Never place any obstacle around the lower right-hand section of the remote controller. Doing so can result in the erroneous measurement of room temperature.
4
● Display
D C B A U T Q S
|
|
CENTRALLY CONTROLLED |
1Hr. |
|
E |
|
|
ON OFF |
˚C |
|
CHECK |
CLOCK |
|
|
|
|
|
|
|
|
|
|
|
FILTER |
|
|
˚C |
|
CHECK MODE |
F |
STAND BY |
ERROR CODE |
TEST RUN |
|
|
NOT AVAILABLE FUNCTION |
|||
DEFROST |
|
|||
|
|
TEMP. |
|
ON/OFF |
G H I KLJ
(A)Current time/Timer
(B)Centralized control
(C)Timer ON
(D)Abnormality occurs
(E)Operation mode:COOL, DRY,AUTO,FAN,HEAT
(F)Preparing for Heating mode
(G)Defrost mode
(H)Set temperature
(I)Power ON
(J)Louver
(K)Not available function
(L)Ventilation
(M)Function setting mode
(N)Test run mode
(O)Error check mode
(P)Filter sign
(Q)Set effective for 1 hr.
(R)Sensor position
(S)Room temperature
(T)Airflow
(U)Fan speed
R
P
O N M
5
3 SPECIFICATION
3-1. Specification
Model |
|
|
|
PEFY-P40VMH-A |
PEFY-P50VMH-A |
PEFY-P63VMH-A |
PEFY-P71VMH-A |
||||||
Power source |
|
|
|
|
|
~ |
220-240V |
50Hz /60Hz |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling capacity |
1 |
kW |
|
4.5 |
|
5.6 |
|
7.1 |
|
8.0 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating capacity |
1 |
kW |
|
5.0 |
|
6.3 |
|
8.0 |
|
9.0 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
|
Cooling |
kW |
|
0.19/0.23 |
|
0.24/0.30 |
|
0.26/0.33 |
||||
(50/60Hz) |
|
Heating |
kW |
|
0.19/0.23 |
|
0.24/0.30 |
|
0.26/0.33 |
||||
Current |
|
Cooling |
A |
|
0.88/1.06 |
|
1.12/1.38 |
|
1.20/1.51 |
||||
|
Heating |
A |
|
0.88/1.06 |
|
1.12/1.38 |
|
1.20/1.51 |
|||||
|
|
|
|
|
|
|
|||||||
External finish |
|
|
|
|
|
|
Galvanizing |
|
|
|
|||
|
|
|
|
Height |
mm |
|
|
|
380 |
|
|
|
|
Dimension |
|
Width |
mm |
|
|
|
750 |
|
|
|
1000 |
||
|
|
|
|
Depth |
mm |
|
|
|
900 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Net weight |
|
|
kg |
|
44 |
|
|
45 |
|
50 |
|||
Heat exchanger |
|
|
|
|
Cross fin (Aluminum plate fin and copper tube) |
|
|||||||
|
Type |
|
|
|
|
|
|
Sirocco fan 1 |
|
||||
|
Airflow rate |
|
m3/min |
|
10.0-14.0 |
|
13.5-19.0 |
|
15.5-22.0 |
||||
Fan |
(Lo-Hi) |
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
External static |
220V |
Pa |
|
|
|
50/100/200 |
|
|
|
|||
|
pressure 2 |
|
|
|
|
|
|
|
|
|
|
||
|
230, 240V |
Pa |
|
|
|
100/150/200 |
|
|
|
||||
Motor |
Type |
|
|
|
|
|
Single phase induction motor |
|
|||||
Output |
3 |
kW |
|
0.08 |
|
|
0.12 |
|
0.14 |
||||
|
|
|
|
|
|
||||||||
Air filter (option) |
|
|
|
|
Synthethic fiber unwoven cloth filter(long life) |
|
|||||||
|
|
|
|
Gas |
mm |
ø |
12.7 |
|
ø |
15.88 |
|
|
|
Refrigerant |
|
(Flare) |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
||||
pipe dimension |
|
Liquid |
mm |
ø |
6.35 |
|
ø |
9.52 |
|
|
|||
|
|
|
|
(Flare) |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain pipe dimension |
|
|
|
|
32 (1-1/4 inch) |
|
|||||||
Noise level (Lo-Hi) |
|
220V |
dB(A) |
|
27-34 |
|
|
32-38 |
|
32-39 |
|||
|
|
|
|
230, 240V |
dB(A) |
|
31-37 |
|
|
36-41 |
|
35-41 |
Note: 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition. Cooling : Indoor 27˚CDB/19 ˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB (WR2: water 20˚C)
2 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
3 The value are that at 240V.
6
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model |
|
|
|
|
|
|
PEFY-P80VMH-A |
PEFY-P100VMH-A |
PEFY-P125VMH-A |
PEFY-P140VMH-A |
|
||||||
|
Power source |
|
|
|
|
|
|
~ 220-240V |
50Hz /60Hz |
|
|
|
||||||
|
Cooling capacity |
1 |
kW |
9.0 |
|
11.2 |
|
|
14.0 |
|
16.0 |
|
||||||
|
Heating capacity |
1 |
kW |
10.0 |
|
12.5 |
|
|
16.0 |
|
18.0 |
|
||||||
|
Power consumption |
|
|
Cooling |
kW |
0.32/0.40 |
|
|
0.48/0.58 |
|
|
0.48/0.59 |
|
|||||
|
(50/60Hz) |
|
|
Heating |
kW |
0.32/0.40 |
|
|
0.48/0.58 |
|
|
0.48/0.59 |
|
|||||
|
Current |
|
|
Cooling |
A |
1.47/1.83 |
|
|
2.34/2.66 |
|
|
2.35/2.70 |
|
|||||
|
|
|
Heating |
A |
1.47/1.83 |
|
|
2.34/2.66 |
|
|
2.35/2.70 |
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
External finish |
|
|
|
|
|
|
|
Galvanizing |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
Height |
mm |
|
|
|
380 |
|
|
|
|
|
|
Dimension |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
Width |
mm |
1000 |
|
|
|
|
1200 |
|
|
|
|||||
|
|
|
|
|
|
|
|
Depth |
mm |
|
|
|
900 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Net weight |
|
|
|
kg |
50 |
|
|
|
|
70 |
|
|
|
||||
|
Heat exchanger |
|
|
|
|
Cross fin (Aluminum plate fin and copper tube) |
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
Type |
|
|
|
|
Sirocco fan 1 |
|
|
Sirocco fan 2 |
|
|||||
|
Fan |
|
Airflow rate |
|
|
m3/min |
18.0-25.0 |
|
|
26.5-38.0 |
|
|
28.0-40.0 |
|
||||
|
|
(Lo-Hi) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
External static |
|
220V |
Pa |
|
|
|
50/100/200 |
|
|
|
|
|||
|
|
|
|
|
pressure 2 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
230, 240V |
Pa |
|
|
|
100/150/200 |
|
|
|
|||||
|
Motor |
|
Type |
|
|
|
|
|
|
Single phase induction motor |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
Output |
3 |
kW |
0.18 |
|
|
|
|
0.26 |
|
|
|
||
|
Air filter (option) |
|
|
|
|
|
Synthethic fiber unwoven cloth filter(long life) |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas |
mm |
ø 15.88 |
|
|
ø |
19.05 |
|
|
|
|
|
Refrigerant |
|
|
(Flare) |
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
pipe dimension |
|
|
Liquid |
mm |
|
|
|
ø |
9.52 |
|
|
|
|||||
|
|
|
|
|
|
|
|
(Flare) |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
Drain pipe dimension |
|
|
|
32 (1-1/4 inch) |
|
|
|
||||||||||
|
Noise level (Lo-Hi) |
|
|
220V |
dB(A) |
35-41 |
|
|
|
|
34-42 |
|
|
|
||||
|
|
|
|
|
|
|
|
230, 240V |
dB(A) |
38-43 |
|
|
|
|
38-44 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Model |
|
|
|
|
|
|
PEFY-P200VMH-A |
|
|
PEFY-P250VMH-A |
|
||||||
|
Power source |
|
|
|
|
|
|
3N ~ 380-415V |
50Hz / 60Hz |
|
|
|
||||||
|
Cooling capacity |
1 |
kW |
|
22.4 |
|
|
|
28.0 |
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Heating capacity |
1 |
kW |
|
25.0 |
|
|
|
31.5 |
|
||||||||
|
Power consumption |
|
Cooling |
kW |
0.99/1.14 |
|
|
1.23/1.41 |
|
|||||||||
|
(50/60Hz) |
|
Heating |
kW |
0.99/1.14 |
|
|
1.23/1.41 |
|
|||||||||
|
Current |
|
Cooling |
A |
1.62/1.86 |
|
|
|
2.0/2.3 |
|
||||||||
|
|
Heating |
A |
1.62/1.86 |
|
|
|
2.0/2.3 |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
External finish |
|
|
|
|
|
|
|
Galvanizing |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
mm |
|
|
|
470 |
|
|
|
|
|
|
Dimension |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
Width |
mm |
|
|
|
1250 |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
Depth |
mm |
|
|
|
1120 |
|
|
|
|
|
|
Net weight |
|
|
|
kg |
|
|
|
100 |
|
|
|
|
|||||
|
Heat exchanger |
|
|
|
|
Cross fin (Aluminum plate fin and copper tube) |
|
|||||||||||
|
|
|
|
Type |
|
|
|
|
|
|
Sirocco fan 2 |
|
|
|
||||
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
Airflow rate |
|
|
m3/min |
|
58.0 |
|
|
|
72.0 |
|
||||||
|
|
|
|
External static |
|
380V |
Pa |
|
|
|
110/220 |
|
|
|
|
|||
|
|
|
|
pressure 4 |
|
400, 415V |
Pa |
|
|
|
130/260 |
|
|
|
|
|||
|
Motor |
|
Type |
|
|
|
|
|
|
phase induction motor |
|
|
|
|||||
|
|
Output |
5 |
kW |
|
0.76 |
|
|
|
1.08 |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|||||||||
|
Air filter (option) |
|
|
|
|
Synthethic fiber unwoven cloth filter(long life) |
|
|||||||||||
|
|
|
|
|
|
|
|
Gas |
mm |
ø |
25.4 |
|
|
ø |
28.58 |
|
||
|
Refrigerant |
|
(Brazing) |
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
pipe dimension |
|
|
Liquid |
mm |
|
|
|
ø 12.7 |
|
|
|
|
|||||
|
|
|
|
|
|
|
(Brazing) |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Drain pipe dimension |
|
|
|
32 (1-1/4 inch) |
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
Noise level |
|
|
380V |
dB(A) |
42(110Pa)/45(220Pa) |
|
|
50(110Pa)/52(220Pa) |
|
||||||||
|
|
|
400, 415V |
dB(A) |
44(130Pa)/47(260Pa) |
|
|
52(130Pa)/54(260Pa) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
Note: 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19 ˚CWB,Outdoor 35˚CDB |
(WR2: water 30˚C) |
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB |
(WR2: water 20˚C) |
2 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
3 The value are that at 240V.
4 The external static pressure is set to 110Pa (at 380V) /130Pa (at 400, 415V) at factory shipment.
5 The value are that at 415V.
7
3-2. Electrical parts specifications
Model
Parts
name
Tranrsformer
Room temperature thermistor
Liquid pipe thermistor
Gas pipe thermistor
Fuse
(Indoor controller board)
Fan motor (with Inner-
thermostat)
Innerthermostat
(Fan motor)
Fan motor capacitor
Linear expansion valve
Power supply terminal bed
Transmission
terminal bed
Symbol
T
TH21
TH22
TH23
FUSE
MF1,2
C1
LEV
TB2
TB5
TB15
PEFY- |
PEFY- |
PEFY- |
PEFY- |
|
PEFY- |
PEFY- |
PEFY- |
PEFY- |
PEFY- |
PEFY- |
P40VMH-A |
P50VMH-A |
P63VMH-A |
P71VMH-A |
P80VMH-A |
P100VMH-A |
P125VMH-A |
P140VMH-A |
P200VMH-A |
P250VMH-A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Primary) 50/60Hz |
220-240V (Secondry) (23.5V 0.9A) |
|
|
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
Resistance 0˚C/15kΩ,10˚C/9.6kΩ,20˚C/6.3kΩ,25˚C/5.4kΩ,30˚C/4.3kΩ,40˚C/3.0kΩ
|
|
|
250V |
6.3A |
|
|
|
|
|
|
|
4-pole OUTPUT |
4-pole |
4-pole |
4-pole |
|
4-pole OUTPUT 400W |
130W |
Output |
Output |
Output |
|
|
180W |
220W |
230W |
|
NS-112VMH |
|
NC-45VMH |
|
||||
NC-71VMH |
NC-80VMH |
NC-90VMH |
|
|
|
|
|
|
|
|
|
OFF 135˚C±5˚C
ON 95˚C±20˚C
4-pole 4-pole Output Output 550W 800W NS-200VMH NS-250VMH
3.0µF 440V |
|
4.0µF |
5.0µF 440V |
|
7.0µF 440V |
- |
|
|
440V |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
DC12VSteppingmotor |
DC12V Stepping motor drive |
||
DC12V Stepping motor drive |
DC12V Stepping motor drive |
||||||
port dimension ø3.2(0~2000pulse ) |
port dimension ø5.2(0~2000pulse) |
driveportdimension |
port dimension ø5.2(0~2000pulse) |
||||
EDM-402MD |
|
EDM-804MD |
ø6.4(0~2000pulse) |
EDM-804MD 2 |
|||
|
EDM-1004MD |
||||||
|
|
|
(L,N, |
) 330V 30A |
|
(L1,L2,L3,N, ) |
|
|
|
|
|
660V 40A |
|||
|
|
|
|
|
|
|
|
|
|
|
(1,2),(M1,M2,S) 300V 10A |
|
|
||
|
|
|
|
|
8
9
G-ø3
D |
C |
50x(G-1)=H |
Air inlet |
|
41 F |
10 |
|
70 |
|
340 |
|
3 |
Lifting bolt |
383 |
814 (Lifting bolt pitch)
904
Model:40-80(Note 3)
|
|
|
900 |
|
|
|
24 |
|
847 |
|
|
|
10 |
|
|
|
|
|
|
|
|
Drain hole |
|
|
Control box |
|
(option) |
||
|
|
|
|
|
2 |
340 |
50x5= 250 |
|
|
|
|
|
50 |
|
|
|
|
|
45 |
|
|
|
|
17 |
Terminal bed |
|
30 |
|
1 |
|
(Power source) |
|
|
92 |
200 |
|
Terminal box |
Terminal bed |
|||
|
|
|
|
(Transmission) |
343 |
|
Keep duct-work length 850mm or more. |
387 |
||
|
|||
Drain hole |
|
||
|
|
J-ø3
|
50x(J-1)=K bolt pitch) A |
|
(LiftingB |
Air outlet |
|
|
50 |
|
50 |
15 |
80 |
|
|
|
23 |
60
29
15 |
|
|
|
|
5050 50 50 |
77 |
328 |
250 |
380 |
41 25 |
130 |
|
94 |
|
|
Indoor |
Reguired space for service and maintenance |
Unit |
|
|
|
|
625 |
|
P40·-PEFY |
|
|
|
|
|
|
|
|
700 |
|
|
Note 2 |
|
|
100~200 |
150~200 |
|
L |
|
||
|
|
|
|
|
|
|
|
450 |
50 |
50 |
|
|
|
Access door |
450 |
|
|
|
50· |
|
|
|
|
|
|
|
|
E |
|
Ceiling surface |
|
Higherthan 20mm |
Higher than 20mm |
100·80· 71· 63· |
Access door |
|
|
|
|
||
Make the access door at the appointed position |
|
|
|
|||
properly for service maintenance. |
|
|
|
|||
|
|
|
Lower than 300mm |
|
|
125· |
|
|
550mmthanLower |
3 |
|
|
A-140VMH |
250 |
|
|
|
|
|
|
When installing the drain water lifting-up mech(option).
Model |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
L |
M |
N |
PEFY-P40VMH-A |
800 |
754 |
680 |
600 |
550 |
50 |
11 |
500 |
10 |
450 |
780 |
ø12.7 |
ø6.35 |
PEFY-P50·63VMH-A |
800 |
754 |
680 |
600 |
550 |
50 |
11 |
500 |
10 |
450 |
780 |
ø15.88 |
ø9.52 |
PEFY-P71·80VMH-A |
1050 1004 |
930 |
850 |
800 |
25 17 |
800 |
15 |
700 1030 |
ø15.88 |
ø9.52 |
|||
PEFY-P100 ·125·140VMH-A1250 |
1204 1130 |
1050 |
1000 |
25 |
21 1000 |
19 |
900 |
1230 |
ø19.05 |
ø9.52 |
Note1.Use M10 screw for the lifting bolt (field supply).
2.Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned. 3.This chart indicates for PEFY-P100·125·140 models, which has 2 fans.
PEFY-P40·50·63·71·80 models have 1 fan.
4.Make sure to install the air filter(field supply) on the air intake side.
In case field supplied air filter is used, attach it where the filter service is easily done.
Refrigerant piping flare connection(gas M copper tube):HP··············1
Refrigerant piping flare connection(liquid N copper tube):LP············2
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory)·····3
mm : Unit
DIMENSIONS AND OUTLINES 4