Mitsubishi PEHD-3EKA3.UK, PEHD-4EKSA3.UK, PEHD-5EKSA3.UK, PEHD-6EKSA.UK, PEHD-3EKHA3.UK Service Manual

...
4.3 (10)

ADVANCE AND EVER ADVANCING

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

TECHNICAL & SERVICE MANUAL

<indoor unit> Service ref.

Models PEHD-3EKA3.UK PEHD-3EKHA3.UK PEHD-4EKSA3.UK PEHD-4EKHSA3.UK PEHD-5EKSA3.UK PEHD-5EKHSA3.UK PEHD-6EKSA.UK PEHD-6EKHSA.UK

INDOOR UNIT

REMOTE CONTROLLER

This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150A and this manual as a set.

PUH-3YKA2.UK

PUH-3VKA2.UK

PUH-4YKSA2.UK

PUH-4VKSA2.UK

PUH-5YKSA2.UK

PUH-6YKSA2.UK

CONTENTS

1.FEATURES ··································

2.PART NAMES AND FUNCTIONS ············· 2

3.SPECIFICATIONS······························

4.DATA········································

5.REFRIGERANT SYSTEM DIAGRAM ·······14

6.OUTLINES AND DIMENSIONS ················15

7.WIRING DIAGRAM ····························

8.DISASSEMBLY INSTRUCTIONS ············ 17

9.PARTS LIST··································

10.OPTIONAL PARTS·····························

The Slim Line.

From Mitsubishi Electric

TM

1 FEATURES

lndoor unit

Remote controller

 

 

 

 

 

Models

Cooling capacity / Heating capacity

 

 

Btu/h

W

 

PEHD-3EK(H)A3

26,300/30,700(37,900)

7,700/9,000(11,100)

 

PEHD-4EK(H)SA3

33,100/35,500(43,700)

9,700/10,400(12,800)

 

PEHD-5EK(H)SA3

42,300/47,400(57,700)

12,400/13,900(16,900)

 

PEHD-6EK(H)SA

50,000/54,500(64,700)

14,650/16,000(19,000)

1. NEXT GENERATION AIR-CONDITIONING VENTILATION INTERLOCKING SYSTEM "Mr.SLIM"+ "LOSSNAY"

Proper ventilation is important to improve the quality of indoor environments. It eliminates unclean air, which is not only unpleasant, but unhealthy. This "Mr.SLIM" + "LOSSNAY" ventilation interlocking system achieves high air quality with minimum energy consumption.

LOSSNAY's unique total heat exchanger reduces heating and cooling expenses by about 25 percent annually(in comparison with our existing models). In addition, its mechanism of simultaneous forced air supply and exhaust enables it to deliver high quality air.

Together, "Mr.SLIM" + "LOSSNAY" system makes next-generation air conditioning possible. This system is both people and environment friendly.

2. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING

The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for flexible interior design. This new feature is recommended for stores and offices where the user's own imagination is allowed to be incorporated.

3. MOST SUITABLE FOR SIMULTANEOUS TWO ROOM AIR CONDITIONING

Using air ducts for cooling/heating airflow that matches the structure and purpose of the room enables you to provide two air outlets for simultaneous cooling/heating of two rooms.

Air outlet duct

Air intake duct

air intake

4. HIGH EXTERNAL STATIC PRESSURE(OPTION MOTOR)

The exceptional external static pressure of 130Pa allows long ducts to be used more extensively to achieve convenient location of indoor units.(STD:70Pa)

5. DRAIN WATER LIFT-UP MECHANISM(OPTION KIT)

This allows more versatility when selecting drain piping layouts.

1

6.ADVANCED MICROPROCESSOR

(1)Easy to use microprocessor

1)Ultra-thin remote controller

The streamlined, square controller is designed to blend well with any interior. Also, the sophisticated microprocessor allows you to easily carry out a wide range of operations.

2)Attractive liquid crystal display (LCD)

The unit's operation mode, set temperature, room temperature, timer setting, and fan speed are displayed on the remote controller's easy-to-read Liquid Crystal Display (LCD)

3)Convenient 24-hour ON-OFF timer

The timer switches Mr.SLIM on and off automatically at the time you set. Once the timer is set, the remaining time is shown on the LCD.

4)Self-diagnostic feature indicates faults instantly

If a problem occurs, the unit will stop operating and the set temperature indicator will change to a self-diagnostic indicator, which shows the location of the trouble.

If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The location of the most recent problem that was stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.

5)Useful memory feature for storing instructions

The previous set value is memorized so that constant temperature control can be achieved. For example, if a power failure occurs, the temperature will not have to be re adjusted afterwards.

(2)Non-polar two-wire remote controller cable

The slim, non-polar, two-wire remote controller cable makes installation simple and trouble free. Also, the remote controller wire can be extended up to 500m.

(3)Automatic cooling/heating changeover operation

An automatic cooling and heating changeover operation system allows you to easily control comfortable year-round air conditioning.

Once the desired temperature is set, unit operation switches automatically between cooling and heating, in accordance with the room temperature. In addition, the use of an outdoor unit fan speed controller allows cooling even when outdoor temperatures are as low as - 5˚C.

7.INNOVATIVE MICROPROCESSOR CONTROL SYSTEM

The most significant feature of PEHD-EK series is the advanced microprocessor control. The development of this system is due to the recent world-wide trend in the air conditioning of larger buildings. They are moving away from centralized duct systems to using individual split type units instead. There are a number of reasons for this change. First of all, the duct's costly and troublesome installation is eliminated. Second, the overall air conditioning balance is excellent in split type units. Lastly, the operation costs are low due to the flexible control of each unit. This system was developed exclusively by Mitsubishi Electric because of high demand. The microprocessor control makes individual control, group control, control using two remote controllers, and remote on/off and individual control possible without troublesome equipment modifications.

2 PART NAMES AND FUNCTIONS

Indoor Unit

Air outlet

Air intake

(sucks the air inside the room into the unit)

2

Remote controller

Operation buttons

button

This switches between continuous operation and the timer operation.

button

Press this button to switch the cool, electronic dry (dehumidify) automatic and heat modes.

TEMP button

This sets the room tempera-

ture.

The temperature

setting

can

be

performed

in 1˚C

units.

 

 

 

 

 

Setting

range :

 

 

Cool

19˚C

to

30˚C

 

Heat

17˚C

to

28˚C

 

The

model name

of the

remote

controller is

indicated.

Once the operation of the unit is set, subsequent operations can be performed only by pressing the ON/OFF button repeatedly.

button

This sets / switches the current time, start time and stop time.

button

This sets the ventilation fan speed.

ON/OFF button

This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.

button

This adjusts the vertical angle

of

the

ventilation.

(This

button dose not operate

in

this model)

FILTER button

This resets the filter service indication display.

(This button dose not operate in this model.)

 

button

This

switches the horizontal

fan motion ON and OFF.

(This

button does not operate

in this model)

CHECK-TEST RUN button

Only press this button to per-

form an

inspection check

or

test operation. Do not use

it

for normal

operation.

 

3

Mitsubishi PEHD-3EKA3.UK, PEHD-4EKSA3.UK, PEHD-5EKSA3.UK, PEHD-6EKSA.UK, PEHD-3EKHA3.UK Service Manual

Display

CENTRALLY

CONTROLLED display

This indicates when the unit is controlled by optinal features such as central control type remote controller.

ON OFF

CLOCK

display

The current

time, start time

and stop time can be displayed in tencecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.

display

This indicates when the con-

tinuous

operation and

time

operation

modes

are

set.

 

It

also

displays

the

time

for

the

timer

operation

at

the

same time

as when

it is

set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

This indicates when the stand by mode is set from the time the sleep operation starts until the heating air discharges.

DEFROST display

This indicates when the defrost operation is performed.

CHECK display

This indicates when a malfunction has occurred in the unit

which should be checked.

˚C display

This displays the selected setting temperature.

display

The selected fan speed is displayed.

˚C display

The temperature of the suction air is displayed during operation. The display range is 8˚C to 39˚C. The display flashes 8˚C when the actual temperature is less then 8˚C and flashes 39˚C when the actual temperature is greater then 39˚C.

Operation lamp

This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.

CHECK MODE

display

TEST RUN

 

This display

lights in the

check mode or when a test operation is perfomed.

Display

This lamp lights when electricity is supplied to the unit.

Caution

• Only the display lights whe the unit is stopped and power is supplied to the unit.

When power is turned ON for the first time, the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.

When

the central control remote control unit,

which is

sold

separately, is

used

the ON - OFF button,

 

button

and

TEMP button do not operate.

 

 

 

 

 

"NOT

AVAILABLE" is displayed when the

button

and

button are pressed. This indicates that this room

 

unit is

not

equipped with the fan direction

adjustment

function and the

louver

function.

4

 

3

 

 

SPECIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Model

 

 

PEHD-3EK(H)A3.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

Cooling

 

Heating

 

Cooling

 

Heating

 

 

Capacity

4

Btu/h

26,300

 

30,700 (37,900)

 

26,300

 

30,700 (37,900)

 

 

W

7,700

 

9,000 (11,100)

 

7,700

 

9,000 (11,100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total input

4

kW

3.55

 

3.34 (5.44)

 

3.55

 

3.34 (5.44)

 

 

 

 

Model name

 

 

 

 

PEHD-3EK(H)A3.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

~/N,50Hz, 220-240V

 

 

 

 

 

 

Input

 

kW

0.40

 

0.40 (2.50)

 

0.40

 

0.40 (2.50)

 

 

 

 

Running current

 

A

1.70

 

1.70 (10.41)

 

1.70

 

1.70 (10.41)

 

 

 

 

Starting current

 

A

1.90

 

1.90 (10.65)

 

1.90

 

1.90 (10.65)

 

 

 

 

External finish

 

 

 

 

Galvanized sheets

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

 

UNIT

Fan motor output

 

kW

1

0.15

 

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

 

Centrifugal (direct)x2

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

Booster heater

 

kW

 

 

2.1

 

 

 

 

 

 

 

Airflow(Low-High)

 

CMM,(CFM)

 

 

20-25 (700-800)

 

 

 

 

 

 

External static pressure

 

Pa(mmAq)

2

70(7)/130(13) at Hi-notch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation control & Thermostat

 

 

 

 

Remote control & Built-in

 

 

 

 

 

 

Noise level(Low-High)

5

dB(A)

3

37-41

 

 

 

 

 

 

 

Cond.drain conn.O.D.

 

mm,(in)

 

 

32 (1-1/4)

 

 

 

 

 

 

 

 

 

 

W

mm,(in)

 

 

1,175 (46-1/8)

 

 

 

 

 

 

Dimensions

 

D

mm,(in)

 

 

740 (29-1/8)

 

 

 

 

 

 

 

 

 

 

H

mm,(in)

 

 

325 (12-13/16)

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

44 (97) [46 (101)]

 

 

 

 

 

 

Model name

 

 

PUH-3VKA2

 

PUH-3YKA2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

~/N, 220-240V ,50Hz

 

3N~, 380/220-415/240V, 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

kW

3.15

 

2.94

 

3.15

 

2.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

A

13.82

 

12.89

 

5.16

 

4.81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting current

 

A

58

 

58

 

37

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External finish

 

 

 

 

Munsell 5Y7/1

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Capillary tube

 

 

 

 

 

 

Compressor

 

 

 

 

Hermetic

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor output

 

kW

2.2

 

 

 

2.4

 

 

 

 

Model

 

 

NH52VND

 

 

NH52YDA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stater type

 

 

 

 

Line start

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection devices

 

 

V: Inner thermostat,HP switch

 

 

 

 

 

 

 

Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

 

Propeller (direct)x2

 

 

 

 

 

 

Fan motor output

 

kW

 

 

0.085

 

 

 

 

 

 

 

Airflow

 

CMM,(CFM)

 

 

50 (1764)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost method

 

 

 

 

Reverse cycle

 

 

 

 

 

 

Noise level

 

dB(A)

 

 

52

 

 

 

 

 

 

 

 

 

 

 

W

mm,(in)

 

 

870 (34-1/4)

 

 

 

 

 

 

Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

mm,(in)

 

 

295+24 (11-5/8 add 1)

 

 

 

 

 

 

 

 

 

 

H

mm,(in)

 

 

850 (33-7/16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

75 (165)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT PIPING

Charge

 

kg,(lbs)

 

 

3.2 (7.1)

 

 

 

 

Between the indoor

 

Height difference

 

 

Max.50m

 

 

 

 

 

 

Pipe size O.D.

 

Liquid

mm,(in)

 

 

9.52 (3/8)

 

 

 

 

 

 

 

 

 

 

Gas

mm,(in)

 

 

15.88 (5/8)

 

 

 

 

 

 

Connection method

 

Indoor side

 

 

Flared

 

 

 

 

 

 

 

 

Outdoor side

 

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping length

 

 

Max.50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. External static pressure at 130Pa

2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)

3. External static pressure at 70Pa

4.

Rating conditions <JIS B 8615, 8616>

 

(INDOOR)

Cooling: 27˚CDB, 19˚CWB

Heating: 20˚CDB

(OUTDOOR)

Cooling: 35˚CDB

Heating: 7˚CDB, 6˚CWB

5.

Noise level: Sound pressure level

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Model

 

 

PEHD-4EK(H)SA3.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

Cooling

 

Heating

 

Cooling

 

Heating

 

Capacity

4

Btu/h

33,100

 

35,500 (43,700)

 

33,100

 

35,500 (43,700)

 

W

9,700

 

10,400 (12,800)

 

9,700

 

10,400 (12,800)

 

 

 

 

 

 

 

 

 

 

Total input

4

kW

4.14

 

4.14 (6.54)

 

3.82

 

3.81 (6.21)

 

 

 

Model name

 

 

 

 

PEHD-4EK(H)SA3.UK

 

 

 

 

 

Power supply

 

 

 

 

~/N, 50Hz, 220-240V

 

 

 

 

 

Input

 

kW

0.62

 

0.62 (3.02)

 

0.62

 

0.62 (3.02)

 

 

 

Running current

 

A

2.64

 

2.64 (12.58)

 

2.64

 

2.64 (12.58)

 

 

 

Starting current

 

A

3.20

 

3.20 (13.2)

 

3.20

 

3.20 (13.2)

 

 

 

External finish

 

 

 

 

Galvanized sheets

 

 

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

UNIT

Fan motor output

 

kW

1

0.27

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

 

Centrifugal (direct)x2

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

 

 

 

Booster heater

 

kW

 

 

2.4

 

 

 

 

 

 

Airflow(Low-High)

 

CMM,(CFM)

 

 

27-34 (950-1200)

 

 

 

 

 

External static pressure

 

Pa(mmAq)

2

70(7) / 130(13) at Hi-notch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation control & Thermostat

 

 

 

 

Remote control & Built-in

 

 

 

 

 

Noise level(Low-High)

5

dB(A)

3

41-46

 

 

 

 

 

 

Cond.drain conn.O.D.

 

mm,(in)

 

 

32 (1-1/4)

 

 

 

 

 

 

 

W

mm,(in)

 

 

1,415 (55-11/16)

 

 

 

 

 

Dimensions

 

D

mm,(in)

 

 

740 (29-1/8)

 

 

 

 

 

 

 

H

mm,(in)

 

 

325 (12-13/16)

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

62 (137) [65(143)]

 

 

 

 

 

Model name

 

 

PUH-4VKSA2

 

PUH-4YKSA2

 

 

 

Power supply

 

 

~/N, 220-240V, 50Hz

 

3N~, 380/220-415/240V, 50Hz

 

 

 

Input

 

kW

3.52

 

3.52

 

3.20

 

3.19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

 

A

16.30

 

16.30

 

5.24

 

5.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting current

 

A

79

 

79

 

40

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External finish

 

 

 

 

Munsell 5Y7/1

 

 

 

 

 

Refrigerant control

 

 

 

 

Capillary tube

 

 

 

 

 

Compressor

 

 

 

 

Hermetic

 

 

 

UNIT

Motor output

 

kW

2.7

 

 

 

.7

 

 

 

 

Model

 

 

NH56VNDT

 

NH56YDA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stater type

 

 

 

 

Line start

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

Protection devices

 

 

V: Inner thermostat, HP switch

 

 

 

 

 

 

Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

 

Propeller (direct) x2

 

 

 

 

 

Fan motor output

 

kW

 

 

0.065+0.065

 

 

 

 

 

Airflow

 

CMM,(CFM)

 

 

95 (3350)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost method

 

 

 

 

Reverse cycle

 

 

 

 

 

Noise level

 

dB(A)

 

 

54

 

 

 

 

 

 

 

 

W

mm,(in)

 

 

870 (34-1/4)

 

 

 

 

 

Dimensions

 

D

mm,(in)

 

 

295+24 (11-5/8 and 1)

 

 

 

 

 

 

 

H

mm,(in)

 

 

1258 (49-1/2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

94 (207)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT PIPING

Charge

 

kg,(lbs)

 

 

4.2 (9.2)

 

 

 

Between the indoor

 

Height difference

 

 

Max.50m

 

 

 

 

 

Pipe size O.D.

 

Liquid

mm,(in)

 

 

9.52 (3/8)

 

 

 

 

 

 

 

Gas

mm,(in)

 

 

19.05 (3/4)

 

 

 

 

 

Connection method

 

Indoor side

 

 

Flared

 

 

 

 

 

 

Outdoor side

 

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping length

 

 

Max.50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. External static pressure at 130Pa

2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)

3. External static pressure at 70Pa

4.

Rating conditions <JIS B 8615, 8616>

 

(INDOOR)

Cooling: 27˚CDB, 19˚CWB

Heating: 20˚CDB

(OUTDOOR)

Cooling: 35˚CDB

Heating: 7˚CDB, 6˚CWB

5.

Noise level: Sound pressure level

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Model

 

 

PEHD-5EK(H)SA3.UK

 

 

 

 

 

 

Function

 

 

 

Cooling

 

Heating

Capacity

4

Btu/h

 

42,300

 

47,400 (57,700)

 

 

 

 

 

W

 

12,400

 

13,900 (16,900)

 

 

 

 

 

 

Total input

4

kW

 

4.85

 

4.80 (7.80)

 

Model name

 

 

 

 

PEHD-5EK(H)SA3.UK

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

~/N, 50Hz, 220-240V

 

Input

 

kW

 

0.64

 

0.64 (3.64)

 

Running current

 

A

 

2.72

 

2.72 (15.17)

 

Starting current

 

A

 

6.00

 

6.00 (18.50)

 

External finish

 

 

 

 

Galvanized sheets

UNIT

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

Fan motor output

 

kW

1

 

0.30

 

Fan(drive) x No.

 

 

 

 

Centrifugal (direct)x2

INDOOR

 

 

 

 

 

 

 

 

Airflow(Low-High)

 

CMM,(CFM)

 

 

33.5-42 (1180-1480)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static pressure

 

Pa(mmAq)

2

 

70(7) /130(13) at Hi-notch

 

 

 

 

 

 

 

 

 

 

Booster heater

 

kW

 

 

3.0

 

Operation control & Thermostat

 

 

 

 

Remote control & Built-in

 

Noise level(Low-High)

5

dB(A)

3

 

44-50

 

Cond.drain conn.O.D.

 

mm,(in)

 

 

32 (1-1/4)

 

 

 

 

 

 

 

 

 

 

 

 

W

mm,(in)

 

 

1,415 (55-11/16)

 

 

 

 

 

 

 

 

 

 

Dimensions

 

D

mm,(in)

 

 

740 (29-1/8)

 

 

 

 

 

 

 

 

 

 

 

 

H

mm,(in)

 

 

325 (12-13/16)

 

 

 

 

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

65(143) [68(150)]

 

 

 

 

 

 

 

 

 

 

Model name

 

 

 

 

PUH-5YKSA2

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

3N~, 380/220-415/240V, 50Hz

 

Input

 

kW

 

4.21

 

4.16

 

Running current

 

A

 

6.89

 

6.81

 

Starting current

 

A

 

53

 

53

 

External finish

 

 

 

 

Munsell 5Y7/1

 

 

 

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Capillary tube

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

Hermetic

UNIT

 

 

 

 

 

 

 

 

Motor output

 

kW

 

 

3.5

 

Model

 

 

 

 

ZR-61K3-TFD

OUTDOOR

 

 

 

 

 

 

 

 

Stater type

 

 

 

 

Line start

Protection devices

 

 

 

Internal thermostat, Anti-phase protector, Thermal switch, HP switch

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

 

Propeller(direct)x2

 

Fan motor output

 

kW

 

 

0.085+0.085

 

Airflow

 

CMM,(CFM)

 

 

95 (3350)

 

Defrost method

 

 

 

 

Reverse cycle

 

 

 

 

 

 

 

 

 

 

Noise level

 

dB(A)

 

 

55

 

 

 

 

 

 

 

 

 

 

 

 

W

mm,(in)

 

 

970 (38-3/16)

 

Dimensions

 

 

 

 

 

 

 

 

 

D

mm,(in)

 

 

345+24 (13-9/16 add 1)

 

 

 

H

mm,(in)

 

 

1258 (49-1/2)

 

 

 

 

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

 

114 (251)

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

R-22

REFRIGERANT PIPING

Charge

 

kg,(lbs)

 

 

5.4 (11.9)

Between the indoor

 

Height difference

 

 

Max.50m

 

Pipe size O.D.

 

Liquid

mm,(in)

 

 

9.52 (3/8)

 

 

 

Gas

mm,(in)

 

 

19.05 (3/4)

 

Connection method

 

Indoor side

 

 

Flared

 

 

Outdoor side

 

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& outdoor unit

 

 

 

 

 

 

 

 

 

Piping length

 

 

Max.50m

 

 

 

 

 

 

 

 

 

1. External static pressure at 130Pa

2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)

3. External static pressure at 70Pa

4.

Rating conditions < JIS B 8615, 8616>

 

(INDOOR)

Cooling: 27˚CDB, 19˚CWB

Heating: 20˚CDB

(OUTDOOR)

Cooling: 35˚CDB

Heating: 7˚CDB, 6˚CWB

5.

Noise level: Sound pressure level

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Model

 

PEHD-6EK(H)SA.UK

 

 

 

 

 

 

 

Function

 

 

Cooling

 

Heating

 

Capacity

4

Btu/h

50,000

 

54,500 (64,700)

 

W

14,650

 

16,000 (19,000)

 

 

 

 

 

 

 

Total input

4

kW

5.39

 

5.24 (8.24)

 

 

Model name

 

 

 

PEHD-6EK(H)SA.UK

 

 

Power supply

 

 

 

~ /N,50Hz,220-240V

 

 

Input

 

kW

0.66

 

0.66 (3.66)

 

 

Running current

 

A

2.79

 

2.79 (15.24)

 

 

Starting current

 

A

6.25

 

6.25 (18.75)

 

 

External finish

 

 

 

Galvanized sheets

 

UNIT

Heat exchanger

 

 

 

Plate fin coil

 

Fan motor output

 

kW

1

0.30

 

 

Fan(drive) x No.

 

 

 

Centrifugal (direct) x2

 

INDOOR

 

 

 

 

 

 

 

 

Booster heater

 

kW

 

3.0

 

 

Airflow(Low-High)

 

CMM,(CFM)

 

36.5-46 (1,280-1,620)

 

 

External static pressure

 

Pa(mmAq)

2

70(7) / 130(13) at Hi-notch

 

 

 

 

 

 

 

 

 

 

 

Operation control & Thermostat

 

 

 

Remote control & Built-in

 

 

Noise level(Low-High)

5

dB(A)

3

46-51

 

 

Cond.drain conn.O.D.

 

mm,(in)

 

32 (1-1/4)

 

 

 

 

W

mm,(in)

 

1,715 (67-1/2)

 

 

Dimensions

 

D

mm,(in)

 

740 (29-1/8)

 

 

 

 

H

mm,(in)

 

325 (12-13/16)

 

 

Weight

 

kg,(lbs)

 

70(154) [ 73(161)]

 

 

Model name

 

 

 

PUH-6YKSA2.UK

 

 

Power supply

 

 

3N~ , 380/220-415/240V, 50Hz

 

 

Input

 

kW

4.73

 

4.58

 

 

Running current

 

A

7.74

 

7.50

 

 

Starting current

 

A

74

 

74

 

 

External finish

 

 

 

Munsell 5Y7/1

 

 

Refrigerant control

 

 

 

Capillary tube

 

 

Compressor

 

 

 

Hermetic

 

UNIT

Motor output

 

kW

 

4.0

 

 

Model

 

 

 

ZR68KC-TFD

 

OUTDOOR

 

 

 

 

 

 

 

 

Stater type

 

 

 

Line start

 

Protection devices

 

 

Internal thermostat, Anti-phase protector, Thermal switch, HP switch

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

 

Fan(drive) x No.

 

 

 

Propeller(direct)x 2

 

 

Fan motor output

 

kW

 

0.10+ 0.10

 

 

Airflow

 

CMM,(CFM)

 

100 (3530)

 

 

 

 

 

 

 

 

 

 

 

Defrost method

 

 

 

Reverse cycle

 

 

Noise level

 

dB(A)

 

56

 

 

 

 

W

mm,(in)

 

970 (38-3/16)

 

 

Dimensions

 

 

 

 

 

 

 

 

 

D

mm,(in)

 

345+ 24 (13-9/16 and 1)

 

 

 

 

H

mm,(in)

 

1,258 (49-1/2)

 

 

 

 

 

 

 

 

 

 

 

Weight

 

kg,(lbs)

 

117 (258)

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

REFRIGERANT PIPING

Charge

 

kg,(lbs)

 

5.0 (11.0)

 

Between the indoor

 

Height difference

 

Max.50m

 

 

Pipe size O.D.

 

Liquid

mm,(in)

 

9.52 (3/8)

 

 

 

 

Gas

mm,(in)

 

19.05 (3/4)

 

 

Connection method

 

Indoor side

 

Flared

 

 

 

Outdoor side

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& outdoor unit

 

 

 

 

 

 

 

 

 

Piping length

 

Max.50m

 

 

 

 

 

 

 

 

 

 

1. External static pressure at 130Pa

2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)

3. External static pressure at 70Pa

4.

Rating conditions < JIS B 8615, 8616>

 

(INDOOR)

Cooling: 27˚CDB, 19˚CWB

Heating: 20˚CDB

(OUTDOOR)

Cooling: 35˚CDB

Heating: 7˚CDB, 6˚CWB

5.

Noise level: Sound pressure level

 

8

4 DATA

1. PERFORMANCE DATA

1) COOLING CAPACITY

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Ref.

intake air

20

 

25

 

30

 

35

 

40

 

45

 

 

WB˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

 

16

7,839

 

2.87

7,623

 

3.00

7,315

 

3.21

6,984

 

3.43

6,637

 

3.64

6,283

 

2.90

PEHD-3EK(H)A3.UK

18

8,339

 

2.94

8,124

 

3.06

7,792

 

3.29

7,454

 

3.51

7,099

 

3.74

6,738

 

3.10

20

8,847

 

2.98

8,639

 

3.11

8,301

 

3.35

7,946

 

3.60

7,585

 

3.83

7,215

 

3.33

 

 

 

 

 

 

 

 

22

9,363

 

3.04

9,186

 

3.18

8,832

 

3.43

8,470

 

3.68

8,100

 

3.94

7,715

 

3.56

 

16

9,875

 

3.09

9,603

 

3.23

9,215

 

3.46

8,798

 

3.69

8,361

 

3.92

7,915

 

3.11

PEHD-4EK(H)SA3.UK

18

10,505

 

3.16

10,234

 

3.29

9,816

 

3.54

9,390

 

3.78

8,943

 

4.02

8,488

 

3.34

20

11,145

 

3.20

10,883

 

3.34

10,457

 

3.61

10,010

 

3.87

9,555

 

4.12

9,089

 

3.58

 

 

 

 

 

 

 

 

22

11,795

 

3.26

11,572

 

3.41

11,126

 

3.69

10,670

 

3.96

10,204

 

4.24

9,719

 

3.83

 

16

12,623

 

3.92

12,276

 

4.10

11,780

 

4.39

11,247

 

4.68

10,689

 

4.98

10,118

 

3.96

PEHD-5EK(H)SA3.UK

18

13,429

 

4.01

13,083

 

4.18

12,549

 

4.49

12,003

 

4.80

11,433

 

5.11

10,851

 

4.25

20

14,247

 

4.07

13,913

 

4.25

13,367

 

4.58

12,797

 

4.91

12,215

 

5.24

11,619

 

4.54

 

 

 

 

 

 

 

 

22

15,078

 

4.15

14,793

 

4.34

14,223

 

4.68

13,640

 

5.03

13,045

 

5.38

12,425

 

4.86

 

16

14,782

 

4.32

14,372

 

4.50

13,844

 

4.86

13,273

 

5.20

12,731

 

5.55

12,116

 

5.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PEHD-6EK(H)SA.UK

18

15,734

 

4.40

15,324

 

4.60

14,767

 

4.96

14,177

 

5.33

13,581

 

5.69

12,951

 

6.05

20

16,701

 

4.49

16,305

 

4.68

15,734

 

5.07

15,119

 

5.45

14,489

 

5.84

13,844

 

6.24

 

 

 

 

 

 

 

 

22

17,683

 

4.58

17,346

 

4.78

16,745

 

5.17

16,115

 

5.58

15,456

 

6.00

14,782

 

6.44

Note C A: Capacity(W)

P.C.: Power consumption(kW)

Cooling capacity correction factors

Service Ref.

 

 

 

Refrigerant piping length(one way)

 

 

 

5m

10m

15m

20m

25m

30m

35m

40m

45m

50m

 

PEHD-3EK(H)A3.UK

1.00

0.981

0.968

0.952

0.940

0.925

0.913

0.900

0.886

0.874

PEHD-4EK(H)SA3.UK

1.00

0.989

0.980

0.970

0.960

0.950

0.940

0.930

0.920

0.910

PEHD-5EK(H)SA3.UK

1.00

0.981

0.968

0.952

0.940

0.925

0.913

0.900

0.886

0.874

PEHD-6EK(H)SA.UK

1.00

0.975

0.955

0.935

0.918

0.900

0.884

0.869

0.855

0.840

2) HEATING CAPACITY

 

Indoor

 

 

 

 

 

 

Outdoor intake air DB˚C

 

 

 

 

 

 

Service Ref.

intake air

-10

 

-5

 

 

0

 

5

10

 

15

 

 

WB˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

CA

 

P.C.

 

15

6,245

 

2.35

7,128

 

2.59

8,091

 

2.84

9,136

 

3.10

10,251

 

3.38

11,439

 

4.37

PEHD-3EK(H)A3.UK

20

5,975

 

2.53

6,849

 

2.78

7,786

 

3.05

8,793

 

3.34

9,865

 

3.64

11,007

 

4.20

 

25

5,751

 

2.69

6,570

 

2.97

7,479

 

3.27

8,469

 

3.57

9,540

 

3.90

10,683

 

4.09

 

15

7,217

 

2.60

8,237

 

2.86

9,350

 

3.14

10,557

 

3.43

11,846

 

3.74

13,218

 

4.84

PEHD-4EK(H)SA3.UK

20

6,905

 

2.81

7,914

 

3.08

8,997

 

3.38

10,161

 

3.70

11,399

 

4.03

12,719

 

4.66

 

25

6,646

 

2.98

7,592

 

3.29

8,642

 

3.62

9,786

 

3.96

11,024

 

4.32

12,345

 

4.52

 

15

9,646

 

3.28

11,009

 

3.60

12,497

 

3.96

14,110

 

4.32

15,833

 

4.72

17,666

 

6.10

PEHD-5EK(H)SA3.UK

20

9,229

 

3.53

10,577

 

3.88

12,025

 

4.26

13,581

 

4.66

15,235

 

5.08

16,999

 

5.87

 

25

8,883

 

3.76

10,147

 

4.15

11,550

 

4.56

13,079

 

4.99

14,734

 

5.44

16,500

 

5.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

10,957

 

3.58

12,557

 

3.95

14,313

 

4.35

16,220

 

4.78

18,277

 

5.22

20,480

 

5.69

PEHD-6EK(H)SA.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

10,492

 

3.85

12,064

 

4.26

13,773

 

4.69

15,616

 

5.14

17,590

 

5.63

19,695

 

6.13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

10,083

 

4.09

11,574

 

4.54

13,227

 

5.01

15,037

 

5.51

17,006

 

6.03

19,131

 

6.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note C A : Capacity(W)

P.C.: Power consumption(kW)

Heating capacity correction factors

Service Ref.

 

 

 

Refrigerant piping length(one way)

 

 

 

5m

10m

15m

20m

25m

30m

35m

40m

45m

50m

 

 

 

 

 

 

 

 

 

 

 

 

PEHD-3EK(H)A3.UK

1.00

1.00

1.00

1.00

1.00

1.00

0.998

0.995

0.993

0.990

PEHD-4EK(H)SA3.UK

1.00

1.00

1.00

1.00

1.00

1.00

0.998

0.995

0.993

0.990

PEHD-5EK(H)SA3.UK

1.00

1.00

1.00

1.00

1.00

1.00

0.998

0.995

0.993

0.990

PEHD-6EK(H)SA.UK

1.00

1.00

1.00

1.00

1.00

1.00

0.998

0.995

0.993

0.990

9

Loading...