Mitsubishi Electronics PAC-SH96SG-E Installation Manual

OPTIONAL
PARTS
E-204
Air Outlet Guide
PAC-SH96SG-E
(to change air blowing direction)
A part to change air direction from outdoor unit. Can also be used to prevent short cycles.
Figure
Specifications
PUHZ-ZRP100/125/140KA
PUHZ-RP200/250KA
2 pieces required
Descriptions
Applicable Models
Air outlet guide
Dimensions
Unit : mm
Air outlet grille: Alloy hot-dip zinc­coated carbon steel sheet
Ivory (3.0Y 7.8/1.1)
Air outlet direction
Washer faced screw (M5x15) x 12 (Iron wire (SWCH18A)/Zinc nickel plated) Washer x 12, Spring washer x 12
Color (Munsell)
Material
Weight
7kg
Changeable between up, down or sideways
Accessory name x Qty. <Material/Surface treatment>
Exterior
* Air Guide prevents reverse rotation of outdoor unit fan when it enters low speed rotation mode with fan controller
being operated. It is also used for protection of fan when strong winds, such as a typhoon, wind blowing through tall buildings, etc., directly strike the air outlet. In addition, installation of this product is necessary when cooling opetation is to be performed in outdoor tempreture of -5or lower (down to -15).
Note the followings when installing this guide:
1) Be sure not to use "upward discharge" in a place where snowing is possible. Snow may accumulate in the guard, which could damage the fan, etc.
2) Attaching this unit will decrease the performance (by 2-3%) and increase noise from outdoor unit (by approx. 1-2 dB).
3) Do not use "upward discharge" when there are any obstacles at the back and on both sides of outdoor unit (air is taken in from top of unit): This could cause a short cycle.
4) To eliminate the influence of external wind, be sure to install the unit with its back facing to wall.
5) Do not install this unit in a place where wind directly blows to the back of the unit.
CAUTION
Air outlet grile Support
598 150
625
638
626
285285
6×85 (=510)
85
45°
OPTIONAL
PARTS
E-205
How to Use / How to Install
Air Outlet Guide to change air blowing directions PAC-SH96SG-E
1
Checking provided parts
Make sure that this package has the following parts as well as the installation sheet:
ԙ
Support
Ԛ
Screw(5%15)
ԛ
Washer
Ԝ
Spring washer
Ԙ
Air Discharge guide
2-fan type outdoor unit
2
Checking Installation Space
3
Installation Method
(Unit: mm)
٨Secure the necessary surrounding space shown below and select a place with less obstacles, to prevent a short cycle.
1) Surrounding space needed when installing one unit
Do not use "upward discharge" in cases of figures (3) and (5) below.
(1) Obstacle at front (open at back, sides and top)
(1) Obstacle at front (open at back, sides and top)
(2) Obstacles at back and front (open at sides and top)
(1) Installing units, one in each row (2) Installing multiple units in multiple rows
(3) Obstacles at back and top (open at front and sides)
(2) Obstacles at back and front (open at sides and top)
(3) Obstacles at back and top (open at front and sides)
(4) Obstacles at back, and sides (open at front and top)
(5) Obstacles at back, sides and top (open at front)
2) Surrounding space needed when installing multiple units
When installing units horizontally in a series, leave at least 10 mm space between units.Do not use "upward discharge" in case of figure (3) below.
4 blowout directions can be selected: Check the orientation of blowout vane, and attach the blowout guide in the direction
that matches the situation at local site.
Limit of 3 units can be installed horizontally in series. When installing a larger number of units, maintain the space between units shown above.
Setting blow-off direction
Upward Downward
Sideways (to left or right)
Discharge vane
Air Discharge guide
500 or more
500 or more
150 or more
500 or less
300 or more
1000 or more
300 or more
200 or more
200 or more
500 or less
500 or more
250 or more
250 or more
1500 or more
1000 or more
1000 or more
500 or more
500 or more
300 or less
1500 or more
1500 or more
Keep at least 2000 when using discharge guide in directions other than "upward discharge".
150 or more
1000 or more
1000 or more
600 or more
Keep at least 3000 when using discharge guide in directions other than "upward discharge".
1500 or more
1500 or more
500 or more
600 or more
1 1 12 12 12
(1)Attach the support to the outdoor unit
using the washers , spring washers
and screws (at the 6 points) on the
existing fan guard
(2)Set the orientation of the blowout vane
of the discharge guide to the desired
direction and install the vane to the
outdoor unit using the washers , spring
washers and screws (at 6 points).