1
Checking provided parts
Make sure that this package has the following parts as well as the installation sheet:
ԙ
Support
Ԛ
Screw(5%15)
ԛ
Washer
Ԝ
Spring washer
Ԙ
Air Discharge guide
2-fan type outdoor unit
2
Checking Installation Space
3
Installation Method
(Unit: mm)
٨Secure the necessary surrounding space shown below and select a place with less obstacles, to prevent a short cycle.
1) Surrounding space needed when installing one unit
Do not use "upward discharge" in cases of figures (3) and (5) below.
(1) Obstacle at front
(open at back, sides and top)
(1) Obstacle at front
(open at back, sides and top)
(2) Obstacles at back and front
(open at sides and top)
(1) Installing units, one in each row (2) Installing multiple units in multiple rows
(3) Obstacles at back and top
(open at front and sides)
(2) Obstacles at back and front
(open at sides and top)
(3) Obstacles at back and top
(open at front and sides)
(4) Obstacles at back, and sides
(open at front and top)
(5) Obstacles at back, sides
and top (open at front)
2) Surrounding space needed when installing multiple units
When installing units horizontally in a series, leave at least 10 mm space between units.
Do not use "upward discharge" in case of figure (3) below.
4 blowout directions can be selected: Check the orientation of blowout vane, and attach the blowout guide in the direction
that matches the situation at local site.
Limit of 3 units can be installed horizontally
in series. When installing a larger number
of units, maintain the space between units
shown above.
㧨Setting blow-off direction㧪
Upward Downward
Sideways (to left or right)
Discharge vane
Air Discharge guide
500 or more
500 or more
150 or more
500 or less
300 or more
1000 or more
300 or more
200 or more
200 or more
500 or less
500 or more
250 or more
250 or more
1500 or more
1000 or more
1000 or more
500 or more
500 or more
300 or less
1500 or more
1500 or more
Keep at least 2000 when using
discharge guide in directions other than
"upward discharge".
150 or more
1000 or more
1000 or more
600 or more
Keep at least 3000 when using
discharge guide in directions other
than "upward discharge".
1500 or more
1500 or more
500 or more
600 or more
1 1 12 12 12
(1)Attach the support to the outdoor unit
using the washers , spring washers
and screws (at the 6 points) on the
existing fan guard
(2)Set the orientation of the blowout vane
of the discharge guide to the desired
direction and install the vane to the
outdoor unit using the washers , spring
washers and screws (at 6 points).