Milton CAT D100-6 Specifications

Page 1
DIESEL GENERATOR SET
FEATURES
Image shown may not reect actual package.
STANDBY 100 ekW 125 kVA
PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
FUEL/EMISSIONS STRATEGY
• EPA Certied for Stationary Emergency Application (EPA Tier 3 emissions levels)
FULL RANGE OF ATTACHMENTS
• Wide range of bolt-on system expansion
attachments, factory designed and tested
• Flexible packaging options for easy and cost effective installation
SINGLE-SOURCE SUPPLIER
• Fully prototype tested with certied torsional vibration analysis available
WORLDWIDE PRODUCT SUPPORT
• Cat dealers provide extensive post sale support including maintenance and repair agreements
• Cat dealers have over 1,800 dealer branch stores operating in 200 countries
• The Cat S•O•SSM program cost effectively detects
internal engine component condition, even the presence of unwanted uids and combustion by-products
Cat® Model D100-6, Three Phase
CAT C4.4 DIESEL ENGINE
Reliable, rugged, durable design
• Field-proven in thousands of applications worldwide
• Four-stroke diesel engine combines consistent performance and excellent fuel economy with minimum weight
• Electronic engine control
GENERATOR SET
• Complete system designed and built at ISO 9001 certied facilities
• Factory tested to design specications at full load conditions
CAT EMCP 4 CONTROL PANELS
• Simple user friendly interface and navigation
• Scalable system to meet a wide range ofcustomer needs
• Integrated Control System and Communications Gateway
SEISMIC CERTIFICATION
• Seismic Certication available
• Anchoring details are site specic, and are dependent on many factors such as generator set size, weight, and concrete strength. IBC Certication requires that the anchoring system used is reviewed and approved by a Professional Engineer
• Seismic Certication per Applicable Building codes:
IBC 2000, IBC 2003, IBC 2006, IBC 2009, IBC 2012 CBC 2007, CBC 2010
• Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
Page 2
STANDBY 100 ekW 125 kVA PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT
System Standard Optional
Air Inlet • Dry replaceable paper element type with restriction indica-
tor
Cooling • Radiator and cooling fan complete with protective guards
• Standard ambient temperatures up to 50°C (122°F)
Exhaust [ ] Industrial
Fuel • Flexible fuel lines to base with NPT connections [ ] Sub-base dual wall UL listed 24 hr fuel tank
Generator • Class H insulation
• Drip proof generator air intake (NEMA 2,IP23)
• Electrical design in accordance with with BS5000 Part 99, EN61000-6, IEC60034-1, NEMA MG-1.33
• IP23 Protection
Power Termination • Circuit breakers, UL/CSA listed, 3 pole (100% rated)
• Power center houses EMCP controller and control termina­tions (CB)
• Segregated low voltage wiring termination panel
• NEMA 1 steel enclosure, vibration isolated
• Electrical stub-up area directly below circuit breaker
Governor • ADEM™A4
Control Panels • EMCP 4.2 digital control panel
• Vibration isolated NEMA 1 enclosure with lockable hinged
door
• DC and AC Wiring harnesses
Lube [ ] Lube oil heater
Mounting • Heavy-duty fabricated steel base with lifting points
• Anti-vibration pads to ensure vibration isolation
• Complete OSHA guarding
• Stub-up pipe ready for connection to silencer pipework
Starting/Charging • 12 volt starting motor
• Batteries with rack and cables
General • High gloss polyurethane paint, Caterpillar Yellow except
rails and radiators gloss black
• Anticorrosive paint protection
• All electroplated hardware
[ ] Radiator stone guard [ ] Radiator transition ange
[ ] Residential [ ] Critical mufers [ ] Overhead silencer mounting kit
[ ] Sub-base dual wall UL listed 48 hr fuel tank [ ] Emergency vent 12 ft extension [ ] 5 gallon spill containment
[ ] Generator upgrade 1 size [ ] Permanent magnet excitation [ ] Internal excitation [ ] Anti-condensation space heater
[ ] Auxiliary contacts [ ] Shunt trip [ ] Overload shutdown via breaker
[ ] NFPA110 upgrade [ ] Control panel chassis
[ ] IBC Seismic and OSHPD certication per Applicable
Building Codes: IBC2000, IBC20 03, IBC2006, IBC 2009, IBC 2012, CBC 2007, CBC 2010
[ ] Battery charger – UL 10 amp [ ] Battery disconnect switch [ ] Battery removal (does not remove rack and cables) [ ] Coolant Heater
[ ] CSA Certied [ ] Weather protective enclosure Industrial/Critical [ ] Sound attenuated protective enclosure [ ] Caterpillar tool set [ ] Caterpillar White paint
2
Page 3
STANDBY 100 ekW 125 kVA PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
SPECIFICATIONS
STANDARD CAT GENERATOR
Frame size LC3014B
Excitation Self excitation
Pitch 0.6667
Number of poles 4
Number of bearings Single bearing
Number of leads 12
Insulation Class H
IP Rating IP23
Overspeed capability (%) 125
Wave form deviation (%) 2
Voltage regulator Single phase sensing
Voltage regulation +/- 0.5% (steady state)
Additional Voltage Information:
Three Phase Prime Standby
208V Temp Rise 125°C / 225°F 150°C / 270°F
240V Temp Rise 125°C / 225°F 150°C / 270°F
480V Temp Rise 105°C / 189°F 130°C / 234°F
600V Temp Rise 105°C / 189°F 130°C / 234°F
– Consult your Cat dealer for other available voltages
CAT EMCP 4 SERIES CONTROLS
EMCP 4 controls including:
– Run / Auto / Stop Control – Speed and Voltage Adjust – Engine Cycle Crank – 12 volt DC operation – Environmental sealed front face – Text alarm/event descriptions
Digital indication for:
– RPM – DC volts – Operating hours – Oil pressure (psi, kPa or bar) – Coolant temperature – Volts (L-L & L-N), frequency (Hz) – Amps (per phase & average) – ekW, kVA, kVAR, kW-hr, %kW, PF
Warning/shutdown with common LED indication of:
– Low oil pressure – High coolant temperature – Overspeed – Emergency stop – Failure to start (overcrank) – Low coolant temperature – Low coolant level
CAT DIESEL ENGINE
C4.4 In-line 4, 4-cycle diesel
Bore 105.0 mm (4,13 in)
Stroke 127.0 mm (5.0 in)
Displacement 4.4 L (268.5 in3)
Compression ratio 16.2:1
Aspiration T
Fuel system Common rail
Governor type Electronic
EMISSIONS (Nominal
NOx + HC g/kWhr 3.73
CO g/kWhr 1.15
PM g/kWhr 0.21
1
The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engne variations. Emissions data is based on 100% load.
1
)
Programmable protective relaying functions:
– Generator phase sequence – Over/Under voltage (27/59) – Over/Under frequency (81 o/u) – Reverse power (kW) (32) – Reverse reactive power (kVAr) (32RV) – Overcurrent (50/51)
Communications:
– Six digital inputs – Four relay outputs (Form A) – Two relay outputs (Form C) – Two digital outputs – Customer data link (Modbus RTU) – Accessory module data link – Serial annunciator module data link – Emergency stop pushbutton
Compatible with the following:
– Digital I/O module – Local annunciator – Remote CAN annunciator – Remote serial annunciator
3
Page 4
STANDBY 100 ekW 125 kVA PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
TECHNICAL DATA
Open Generator Set – 1800 rpm/60 Hz/480 Volts P3362A
Tier 3 STANDBY PRIME
Generator Set Package Performance
Genset power rating @ 0.8 pf Genset power rating with fan
Fuel Consumption
100% load with fan 75% load with fan 50% load with fan
Cooling System
Air ow restriction (system) Engine coolant capacity with radiator/exp. tank Engine coolant capacity Radiator coolant capacity
Inlet Air
Combustion air inlet ow rate
Exhaust System
Exhaust stack gas temperature Exhaust gas ow rate Exhaust ange size (internal diameter) Exhaust system back pressure (maximum)
Heat Rejection
Heat rejection to coolant (total) Heat rejection to exhaust (total) Heat rejection to aftercooler Heat rejection to atmosphere from engine Heat rejection to atmosphere from generator
Alternator
Motor starting capability @ 30% voltage dip Frame Rotor temperature rise
Lubrication System
Total oil capacity Oil pan
1
For ambient and altitude capabilities consult your Cat dealer. Airow restriction (system) is added to existing restriction from factory.
2
Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.m
1
2
29.8 L/hr
23.7 L/hr
17.5 L/hr
0.12 kPa
17.0 L
7.0 L
10.0 L
8.5 m³/min 300.2 cfm 8.4 m³/min 296.6 cfm
506°C
20.0 m³/min
63.5 mm
15.0 kPa
61.0 kW
87.0 kW
18.0 kW
18.0 kW
9.7 kW
206 skV LC3014B 130°C 234°F
8.0 L
7.0 L
125.0 kVA
100.0 ekW
7.9 gal/hr
6.3 gal/hr
4.6 gal/hr
0.48 in. water
4.5 Gal
1.8 Gal
2.6 Gal
943°F
706.3cfm
2.5 in
60.2 in. water
3469 Btu/min 4948 Btu/min 1024 Btu/min
1023.6 Btu/min
551.6 Btu/min
2.1 gal
1.8 gal
27.4 L/hr
21.9 L/hr
16.3 L/hr
0.12 kPa
17.0 L
7.0 L
10.0 L
480°C
19.2 m³/min
63.5 mm
15.0 kPa
57.0 kW
81.0 kW
17.0 kW
15.0 kW
8.4 kW
206 skV LC3014B 105°C 189°F
8.0 L
7.0 L
112.5 kVA
90.0 ekW
7.2 gal/hr
5.8 gal/hr
4.3 gal/hr
0.48 in. water
4.5 Gal
1.8 Gal
2.6 Gal
896°F
678.0 cfm
2.5 in
60.2 in. water
3242 Btu/min 4606 Btu/min 967 Btu/min 853 Btu/min
477.7Btu/min
2.1 gal
1.8 gal
4
Page 5
STANDBY 100 ekW 125 kVA PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
RATING DEFINITIONS AND CONDITIONS
Applicable Codes and Standards: AS1359, CSA C22.2
No 100-04, UL142, UL489, UL601, UL869, UL2200, NFPA 37, NFPA 70, NFPA 99, NFPA 110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, NEMA MG 1-33, 72/23/EEC, 98/37/EC, 2004/108/EC.
Standby – Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
Prime – Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand of 100% of prime-rated eKW with 10% of overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
Fuel rates are based on fuel oil to specication EPA 2D 89.330-96 with a density of 0.845 – 0.850 kg/L (7.052 – 7.094 lbs/U.S. gal.) @ 15°C (59°F) and fuel inlet temperature 40°C (104°F). Additional ratings may be available for specic customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
5
Page 6
STANDBY 100 ekW 125 kVA PRIME 90 ekW 113 kVA
60 Hz 1800 rpm 480 Volts
DIMENSIONS
Package Dimensions
Length
Width
Height
2362 mm 93 in
1110 mm 44 in
1304 mm 51 in
NOTE: For reference only – do not use for installation
design. Please contact your local dealer for exact weight and dimensions. (General Dimension Drawing #4190059).
Performance No.: P3362A
Feature Code: NAC135P
Gen. Arr. Number: 3932540
Source: U.S. Sourced
LEHE0422-01 (04/13)
www.Cat-ElectricPower.com
2013 Caterpillar
All rights reserved.
Materials and specications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the
“Power Edge” trade dress, as well as corporate and product
identity used herein, are trademarks of Caterpillar and may not be
used without permission.
6
Loading...