Job Name/Location: |
|
|
|
|
Tag #: |
|
|
|
|
|
|
Date: |
|
For: |
File |
Resubmit |
|
PO No.: |
|
|
Approval |
Other |
|
|
|
|
|
|
|
Architect: |
|
GC: |
|
|
|
|
|
|
|
|
|
Engr: |
|
Mech: |
|
|
|
Rep: |
|
|
|
|
|
(Company) |
(Project Manager) |
|
|
LS363HLV |
|
|
|
|
|
Single Zone Wall Mounted Extended Piping |
|
||||
Outdoor Unit (ODU) LSU363HLV |
Indoor Unit (IDU) LSN363HLV |
|
|||
|
|
|
|
|
|
Performance: |
|
|
|
|
|
Cooling: |
|
|
|
|
|
Capacity (Min Rated Max, Btu/h) |
3,070 33,000 34,000 |
|
|||
SEER |
|
|
17.5 |
|
|
EER |
|
|
8.18 |
|
|
|
|
|
|
||
SEER Seasonal Energy Efficiency Ratio EER Energy Efficiency Ratio |
|
|
|
||
Heating: |
|
|
|
|
|
Capacity (Min Rated Max, Btu/h) |
3,070 35,200 38,898 |
|
|||
HSPF |
|
|
10 |
|
|
|
|
|
|
|
|
HSPF Heating Seasonal Performance Factor |
|
|
|
|
|
Cooling Nominal Test Conditions: |
Heating Nominal Test Conditions: |
|
|
|
|
Indoor: 80°F DB/67°F WB |
Indoor: |
70°F DB/60°F WB |
|
|
|
Outdoor: 95°F DB/75°F WB |
Outdoor: 47°F DB/43°F WB |
|
|
|
|
Electrical: |
|
|
|
|
|
Power Supply (V¹/Hz/Ø) |
|
208 230/60/1 |
|
|
|
|
|
|
|
|
|
Outdoor Unit: |
|
|
|
|
|
MOP (A) |
|
|
30 |
|
|
MCA (A) |
|
|
19 |
|
|
Recommended Fuse Size (A) |
|
|
25 |
|
|
Cooling Rated Amps (A) |
|
|
14.85 |
|
|
Heating Rated Amps (A) |
|
|
14.85 |
|
|
Compressor (A) |
|
|
14.6 |
|
|
Fan Motor (A) |
|
|
0.25 |
|
|
MOP Maximum Overcurrent Protection |
MCA Minimum Circuit Ampacity |
|
|
|
|
Total Power Input: |
|
|
|
|
|
Cooling Power Input (kW) |
|
|
4.04 |
|
|
Heating Power Input (kW) |
|
|
3.84 |
|
|
|
|
|
|
|
|
Piping: |
|
|
|
|
|
Liquid Line (in, OD) |
|
|
3/8 |
|
|
Vapor Line (in, OD) |
|
|
5/8 |
|
|
Additional Refrigerant (oz/ft) |
|
0.38 |
|
|
|
Max Pipe Length (ft)² |
|
|
164 |
|
|
Piping Length (no add'l refrigerant, ft) |
24.6 |
|
|
||
Max Elevation (ft) |
|
|
98.4 |
|
|
Controls Features: |
|
|
|
|
|
•24 Hour on/o mer |
•Chaos wind |
•Inverter (variable speed |
|||
•4 Way auto swing |
•Jet cool/Jet heat |
compressor) |
|||
•Auto changeover |
•3M HAF Filter |
•Condensate sensor connec on |
|||
•Auto restart |
•Sleep mode |
•Temp display on indoor unit |
|||
•Built in low ambient standard, |
•Cooling only function |
•Remote control via Wi Fi and |
|||
down to 14°F (cooling mode) |
•Defrost control |
smartphone app |
Optional Accessories (sold separately):
LG Programmable Thermostat PREMTB10U
Low Ambient Wind Baffle (Cooling operation to 0°F) ZLABGP02A
PI 485 PMNFP14A1
Dry contact for 3rd party thermostat PDRYCB300
For a complete list of available accessories, contact your LG representative.
Operating Range:
Outdoor Unit:
Cooling (°F DB) |
|
14 118 |
Heating (°F WB) |
|
4 65 |
|
|
|
Indoor Unit: |
|
|
Cooling (°F WB) |
|
53 75 |
Heating (°F DB) |
|
60 86 |
Unit Data: |
|
|
Refrigerant Type |
|
R410A |
Refrigerant Control |
|
EEV |
Refrigerant Charge (lbs) |
4.85 |
|
ODU Sound Pressure (±3 dB(A))³ |
55 |
|
IDU Sound Pressure (H/M/L/Sleep) (±3 dB(A)) 49/44/40/37 |
||
ODU Net Unit Weight (lbs) |
125 |
|
ODU Shipping Weight (lbs) |
133 |
|
IDU Net Unit Weight (lbs) |
40 |
|
IDU Shipping Weight (lbs) |
46 |
|
Heat Exchanger Coating |
GoldFin™ |
|
|
|
|
Fan: |
|
|
ODU Type |
|
Propeller |
IDU Type |
|
Cross Flow |
Fan Speeds (Fan/Cooling/Heating) |
6/6/6 |
|
Quantity (ODU + IDU) |
|
1 + 1 |
Motor/Drive |
Brushless Digitally Controlled/Direct |
|
ODU Max Air Flow Rate (CFM) |
2,119 |
|
IDU Air Flow Max/H/M/L (CFM) |
953/848/706/530 |
|
Dehumidification (pts/hr) |
6.6 |
|
|
|
|
Notes:
1.Acceptable opera ng voltage: 187V 253V. 2.Piping lengths are equivalent.
3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996. 4.All communica on/power cable to be minimum 18 AWG, 4 conductor, stranded, shielded and must comply with applicable local and national code.
5.See Engineering Manual for sensible and latent capaci es.
6.Power wiring cable size must comply with the applicable local and na onal code. 7.The indoor unit comes with a dry helium charge.
8.This data is rated 0 |
above sea level, with 24.6 of refrigerant line and a 0 level |
difference between outdoor and indoor units. |
|
9.Must follow installa |
on instruc ons in the applicable LG installa on manual. |
For continual product development, LG reserves the right to change specifications without notice. |
|
|
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com |
SB_SZ_WM_Extended_Piping_LS363HLV_12_16 |
Page 1 of 3 |