LG AS-W1264GH0, AS-W0964GH0, AS-W1865DH0, AS-W091264DH0, AS-W1424DH0 Manual

0 (0)

website http://www.lgservice.com

LG

LG

Room Air Conditioner

SERVICE MANUAL

MODELS: AS-W0964DH0

AS-W1264DH0

AS-W1865DH0

AS-W0964GH0

AS-W1264GH0

AS-W1224DH0

AS-W1424DH0

AS-W1825DH0

CAUTION

BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.

ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Air Conditioner Service Manual

TABLE OF CONTENTS

LG Model Name.................................................................................................................................

3

Safety Precautions ...........................................................................................................................

5

Dimensions .....................................................................................................................................

10

Installation.......................................................................................................................................

14

Flaring work and connection of piping.........................................................................................

16

Connecting the cable between indoor unit and outdoor unit.....................................................

21

Checking the drainage and forming the pipings .........................................................................

23

Air purging ......................................................................................................................................

24

Test running ....................................................................................................................................

26

Functions.........................................................................................................................................

27

Operation.........................................................................................................................................

30

Disassembly....................................................................................................................................

41

Troubleshooting Guide ..................................................................................................................

44

Schematic Diagram ........................................................................................................................

65

Product Specifications ..................................................................................................................

73

Exploded View ................................................................................................................................

75

Replacement Parts List ..................................................................................................................

78

2 Room Air Conditioner

LG Model Name

LG Model Name

2003

 

1

 

2

 

-

 

3

4

5

6

7

 

8

 

9

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

 

Type

 

Code of Model

 

 

 

Meaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Producing Center,

 

A~Z

 

 

L: Chang-won R22

 

N: India

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

 

A: Chang-won R410A

 

Z: Brazil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C: Chang-won R407C

 

D: Indonesia

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T: China

 

 

 

M: Mexico

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K: Turkey R22

 

 

 

V: Vietnam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E: Turkey R410A

 

S: Out Sourcing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H: Thailand

 

 

 

 

 

 

 

 

 

 

2

 

 

Product Type

 

A~Z

 

 

S: Split Type Air Conditioner

 

 

 

3

 

Cooling/Heating/Inverter

A~Z

 

 

C: Cooling only

 

V: AC Inverter C/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H: Heat pump

 

 

 

N: AC Inverter H/P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X: C/O + E/Heater

 

Q: DC Inverter C/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z: H/P + E/Heater

 

W: DC Inverter H/P

 

 

 

4, 5

 

 

 

Capacity

 

 

0~9

 

 

Cooling/Heating Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ex. "09" → 9,000 Btu/h

 

 

 

 

 

 

 

 

6

 

 

Electric Range

 

1~9

 

 

1: 115V/60Hz,

 

 

A: 220V, 50Hz, 3Phase

 

 

 

 

 

 

 

 

 

 

 

 

A~Z

 

 

2: 220V/60Hz

 

 

B: 208~230V, 60Hz, 3Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: 208-230V/60Hz

C: 575V, 50Hz, 3Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: 200-220V/50Hz

D: 440~460, 60Hz, 3Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6: 220-240V/50Hz

E: 265V, 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7: 110V, 50/60Hz

F: 200V, 50/60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8: 380-415V/50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9: 380-415V/60Hz

 

 

 

 

 

 

 

 

7

 

 

 

Chassis

 

 

A~Z

 

 

Name of Chassis of Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ex. LSP → SP Chassis

 

 

 

 

 

 

 

 

8

 

 

 

 

Look

 

 

A~Z

 

 

Look,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Color (Artcool Model)

 

 

 

 

 

 

 

 

9

 

 

 

Function

 

 

A~Z

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic+4Way

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Plasma Filter

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

Plasma Filter+4 Way

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

Tele+LCD

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

Tele+LCD+Nano plasma+4Way

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean+Low A

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean+4way+Low A

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

Tele+LED+4way

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

Internet

 

 

 

 

 

 

 

 

J

 

 

 

 

 

 

 

 

 

 

 

 

 

Plasma F+4Way+Oxy generator

 

K

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean+4way

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean+PTC

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+Autoclean+4way+PTC

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

Negative ION+A/Clean

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

(Nano)Plasma+Negative ION+A/Clean

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean

T

 

 

 

 

 

 

 

 

 

 

 

 

 

Nano Plasma F+4Way+(A/changeove)+A/clean+

 

U

 

10

 

 

 

Serial No.

 

 

0~9

 

 

LG Model Development Serial No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* ARTCOOL COLOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

Mirror

 

 

 

N

 

Walnut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

White

 

 

 

A

 

Gogh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

Blue

 

 

 

S

 

Sisley

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

Wood

 

 

 

Q

 

Quran

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

Metal

 

 

 

K

 

Mecca

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

Cherry

 

 

 

 

 

 

 

 

Service Manual 3

LG Model Name

2004~

 

1

2

 

-

 

3

4

5

6

 

7

 

8

 

9

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

Type

 

Code of Model

 

 

 

Meaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Producing Center,

 

A~Z

 

L

 

 

Chang_won R22

 

N

India

 

 

 

 

Refrigerant

 

 

 

 

A

 

 

Chang_won R410A

 

Z

Brazil

 

 

 

 

 

 

 

 

 

 

 

C

 

 

Chang_won R407C

 

D

Indonesia

 

 

 

 

 

 

 

 

 

 

 

T

 

 

China

 

 

 

X

Mexico

 

 

 

 

 

 

 

 

 

 

 

K

 

 

Turkey R22

 

 

 

V

Vietnam

 

 

 

 

 

 

 

 

 

 

 

E

 

 

Turkey R410A

 

S

Out sourcing

 

 

 

 

 

 

 

 

 

 

 

H

 

 

Thailand

 

 

 

 

 

 

 

2

Product Type

A~Z

S: Split Type Air Conditioner

 

 

 

 

3

Cooling/Heating/Inverter

A~Z

C: Cooling only

 

V: AC Inverter C/O

 

 

 

 

 

 

H: Heat pump

 

N: AC Inverter H/P

 

 

 

 

 

 

X: C/O + E/Heater

 

Q: DC Inverter C/O

 

 

 

 

 

 

Z: H/P + E/Heater

 

W: DC Inverter H/P

 

 

 

4, 5

Capacity

0~9

Cooling/Heating Capacity

 

 

 

 

 

 

 

Ex. "09" → 9,000 Btu/h

 

 

 

 

 

 

 

 

 

6

Electric Range

1~9

1: 115V/60Hz,

 

A: 220V, 50Hz, 3Phase

 

 

 

 

 

A~Z

2: 220V/60Hz

 

B: 208~230V, 60Hz, 3Phase

 

 

 

 

3: 208-230V/60Hz

 

C: 575V, 50Hz, 3Phase

 

 

 

 

 

 

5: 200-220V/50Hz

 

D: 440~460, 60Hz, 3Phase

 

 

 

 

6: 220-240V/50Hz

 

E: 265V, 60Hz

 

 

 

 

 

 

 

7: 110V, 50/60Hz

 

F: 200V, 50/60Hz

 

 

 

 

 

 

8: 380-415V/50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

9: 380-415V/60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHASSIS

 

Look

Division

 

 

 

 

 

 

 

 

 

 

7

Chassis

A~Z

Name of Chassis of Unit

 

S4/S5

 

D

Panel Type(Deluxe)

 

S6

 

K

Fighting 'Look'

 

 

 

 

Ex. LSP → SP Chassis

 

 

 

 

 

 

 

SQ

 

L

(LG1)

 

8

Look

A~Z

Look,

 

 

 

 

 

 

SR

 

G

(LG2)-SEMI PANEL

 

 

 

Color (Artcool Model)

 

ST

 

M

OEM1

 

 

 

 

 

 

 

 

 

 

 

 

N

OEM2

 

 

 

 

 

 

 

 

 

 

 

 

D

Panel Type(Deluxe)

 

 

 

 

 

 

 

 

 

 

 

P

LG3

 

9

Function

A~Z

 

 

 

 

 

 

 

 

 

 

 

 

Basic

 

 

 

 

 

 

 

 

 

A

 

 

 

Basic+4Way

 

 

 

 

 

 

 

 

 

B

 

 

 

Plasma Filter

 

 

 

 

 

 

 

 

 

C

 

 

 

Plasma Filter+4 Way

 

 

 

 

 

 

 

 

D

 

 

 

Tele+LCD

 

 

 

 

 

 

 

 

 

E

 

 

 

Tele+LCD+Nano plasma+4Way

 

 

 

F

 

 

 

NBF F+(A/changeove)+A/clean+Low A

 

 

 

G

 

 

 

NBF F+(A/changeove)+A/clean+4way+Low A

 

 

 

H

 

 

 

Tele+LED+4way

 

 

 

 

 

 

 

 

 

I

 

 

 

Internet

 

 

 

 

 

 

 

 

 

J

 

 

 

Plasma F+4Way+Oxy generator

 

 

 

K

 

 

 

NBF F+(A/changeove)+A/clean

 

 

 

L

 

 

 

NBF F+(A/changeove)+A/clean+4way

 

 

 

M

 

 

 

NBF F+(A/changeove)+A/clean+PTC

 

 

 

N

 

 

 

NBF F+(A/changeove)+Autoclean+4way+PTC

 

 

 

P

 

 

 

NBF F+(A/changeove)+A/clean+4way+Low A+PTC

 

 

Q

 

 

 

(Nano)Plasma+ION+A/Clean

 

 

 

S

 

 

 

4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean

 

T

 

 

 

Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator

 

U

 

 

 

4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator

 

V

 

 

 

Dry contact

 

 

 

 

 

 

 

 

 

W

 

 

 

Wire remocon

 

 

 

 

 

 

 

 

 

8

10

Serial No.

0~9

LG Model Development Serial No.

 

 

 

 

 

 

 

* ARTCOOL COLOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

Mirror

 

 

 

 

 

 

 

 

 

 

 

 

W

 

White

 

 

 

 

 

 

 

 

 

 

 

 

B

 

Blue

 

 

 

 

 

 

 

 

 

 

 

 

D

 

Wood

 

 

 

 

 

 

 

 

 

 

 

 

M

 

Metal

 

 

 

 

 

 

 

 

 

 

 

 

C

 

Cherry

 

 

 

 

 

 

 

 

 

4 Room Air Conditioner

Safety Precautions

Safety Precautions

To prevent injury to the user or other people and property damage, the following instructions must be followed.

Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

This symbol indicates the possibility of death or serious injury.

This symbol indicates the possibility of injury or damage to properties only.

■ Meanings of symbols used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

Installation

Do not use damaged power cords, plugs, or a loose socket.

• There is risk of fire of electric shock.

Always use the power plug and socket with the ground terminal.

• There is risk of electric shock.

Install the panel and the cover of control box securely.

• There is risk of fire of electric shock.

Do not modify or extend the power cord.

• No grounding may cause electric shock.

Service Manual 5

LG AS-W1264GH0, AS-W0964GH0, AS-W1865DH0, AS-W091264DH0, AS-W1424DH0 Manual

Safety Precautions

For re-installation of the installed product, always contact a dealer or an authorized service center.

There is risk of fire, electric shock, explosion, or injury.

ful of the case edges and the fins on the condenser and evaporator.

Do not install, remove, or re-install the unit by yourself.

There is risk of fire, electric shock, explosion, or injury.

For installation, always contact the dealer or an Authorized service center

• There is risk of fire, electric shock, explosion, or injury.

Do not install the product on a defective installation stand.

Be sure the installation area does not deteriorate with age.

It may cause injury, accident, or damage to the product.

If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.

6 Room Air Conditioner

Safety Precautions

Operation

Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.

• There is risk of fire or electrical shock.

Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.

• There is risk of fire or electrical shock.

Do not allow water to run into electrical parts.

Use a dedicated outlet for this appliance.

• There is risk of fire or electrical shock.

Do not place a heater or other appliances near the power cable.

• There is risk of fire and electric shock.

Do not store or use flammable gas or combustibles near the air conditioner.

• There is risk of fire, failure of the product, or electric • There is risk of fire or failure of product. shock.

Wax

Thinner

Service Manual 7

Safety Precautions

Unplug the unit if strange sounds, odors, or smoke comes from it.

• There is risk of electric shock or fire.

Be cautious that water could not enter the product.

There is risk of fire, electric shock, or product damage.

Always check for gas (refrigerant) leakage after installation or repair of product.

Install the drain hose to ensure that water is drained away properly.

• Low refrigerant levels may cause failure of product.

• A bad connection may cause water leakage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep level even when installing the product.

• To avoid vibration or water leakage.

Use two or more people to lift and transport the air conditioner.

• Avoid personal injury.

90˚

8 Room Air Conditioner

Safety Precautions

Operation

Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.

Wax

Do not touch the metal parts of the product when removing the air filter. They are very sharp!

• There is risk of personal injury.

Do not step on or put anyting on the product. (outdoor units)

Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.

• There is risk of personal injury and failure of product.

• There are sharp and moving parts that could cause

 

personal injury.

Service Manual 9

Dimensions

Dimensions

SymbolsUsedin this Manual

This symbol alerts you to the risk of electric shock.

This symbol alerts you to hazards that could cause harm to the air conditioner.

NOTICE This symbol indicates special notes.

IndoorUnit

H

D

W

Installation plate

Model

Dimension

 

7k, 9k, 12k, 14k Btu Series

 

 

W

mm

840

H

mm

270

D

mm

153

10 Room Air Conditioner

Dimensions

H

D

W

Installation plate

Model

Dimension

 

18k, 24k Btu Series

 

 

W

mm

1090

H

mm

300

D

mm

178

Service Manual 11

Dimensions

OutdoorUnit

 

W

L2

L1

D

 

 

L3

 

H

L4

Gas side (3-way valve)

L5

Liquid side (2-way valve)

 

MODEL

9k, 12k, 14k Btu Series

DIM

7k,

unit

 

W

mm

770

H

mm

540

D

mm

245

L1

mm

285

L2

mm

65

L3

mm

518

L4

mm

10

L5

mm

100

 

 

 

12 Room Air Conditioner

H L4

L5

DIM

W

H

D

L1

L2

L3

L4

L5

L6

L7

L8

L9

L10

L11

Dimensions

W

D

L2

L1

 

 

 

L3

 

 

 

L10

 

 

 

Gas side

 

 

 

L11

 

 

 

Liquid side

L7

L6

L8

L9

 

MODEL

 

18k, 24k Btu Series

 

 

 

 

mm

 

870

 

mm

 

655

 

mm

 

320

 

mm

 

370

 

mm

 

340

 

mm

 

25

 

mm

 

630

 

mm

 

25

 

mm

 

546

 

mm

 

162

 

mm

 

162

 

mm

 

54

 

mm

 

74.5

 

mm

 

79

Service Manual 13

More
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 5cm

Installation

Installation

SelectionoftheBestLocation

Indoor unit

Do not have any heat or steam near the unit.

Select a place where there are no obstacles in front of the unit.

Make sure that condensation drainage can be conveniently routed away.

Do not install near a doorway.

Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.

Use a stud finder to locate studs to prevent unnecessary

damage to the wall.

10cm

More than 5cm

Rooftop Installations:

If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.

Consult local codes regarding rooftop mounting.

PipingLengthandElevation

Capacity

Pipe Size

Standard

Max.

Max.

Additional

 

 

Length

Elevation

Length

Refrigerant

(Btu/h)

GAS

LIQUID

(m)

B (m)

A (m)

(g/m)

 

 

 

 

 

 

 

5k~14k

3/8"(Ø9.52)

1/4"(Ø6.35)

4 or 7.5

7

15

20

 

 

 

 

 

 

1/2"(Ø12.7)

1/4"(Ø6.35)

4 or 7.5

7

15

20

 

 

 

 

 

 

 

 

 

1/2"(Ø12.7)

1/4"(Ø6.35)

4 or 7.5

15

30

20

18k~28k

5/8"(Ø15.88)

1/4"(Ø6.35)

4 or 7.5

15

30

20

 

 

 

 

 

 

 

 

5/8"(Ø15.88)

3/8"(Ø9.52)

4 or 7.5

15

30

30

 

 

 

 

 

 

 

30k~38k

5/8"(Ø15.88)

3/8"(Ø9.52)

7.5

15

30

30

 

 

 

 

 

 

3/4"(Ø19.05)

3/8"(Ø9.52)

7.5

15

30

50

 

 

 

 

 

 

 

 

Indoor unit

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

Grade

 

Clearance(cm)

 

 

A

 

B

 

 

 

 

5K~28K

10

 

5

 

 

 

 

 

30K~38K

30

 

12

Outdoor unit

If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.

Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.

Do not place animals and plants in the path of the warm air.

Take the air conditioner weight into account and select a place where noise and vibration are minimum.

Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

More than 60cm

More than 10cm

More than 10cm

 

A

 

A

B

Outdoor unit

Indoor unit

B

 

Outdoor unit

I

 

Oil trap

Indoor

B

If case more than 5m

Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Oil trap should be installed every 5~7 meters.

More than 70cm

More

than 60cm

 

14 Room Air Conditioner

Installation

HowtoFixInstallationPlate

The wall you select should be strong and solid enough to prevent vibration

1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.

Mount the installation plate horizontally by aligning the centerline using a level.

Installation Plate

Chassis

Hook

Type "A" screw

2.Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

 

 

Installation plate

 

 

D

 

 

 

 

B

Ø70mm

C

 

 

A

Ø70mm

 

 

 

 

 

Left rear piping

 

 

Right rear piping

 

 

CHASSIS

 

Distance (mm)

 

 

(Grade)

A

B

C

D

 

 

7k, 9k, 12k, 14k

75

65

105

65

 

18k, 24k

105

65

260

65

DrillaHoleintheWall

Drill the piping hole with a ø 70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.

 

WALL

Indoor

Outdoor

 

 

 

 

 

 

 

5-7mm

(3/16"~5/16")

 

 

Open the Front Grille.

Pass Telephone Control Cord Wire through the hole which the power cord goes through.

Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.

Fix Telephone Control Cord Wire inside Control box so as not to disconnect.

Close the Front Grille.

Drainhosejunction

Remove the rubber stopple in the desired drain direction.

Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.

Adhesive

Only the desired direction

Connecting

part

Drain

hose

Service Manual 15

Flaring work and connection of piping

Flaring work and connection of piping

Flaringwork

Flaring work

Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.

Cut the pipes and the cable.

Use the piping kit accessory or pipes purchased locally.

Measure the distance between the indoor and the outdoor unit.

Cut the pipes a little longer than the measured distance.

Cut the cable 1.5m longer than the pipe length.

Copper

 

Slanted Uneven Rough

pipe

90°

Burr removal

Completely remove all burrs from the cut cross section of pipe/tube.

Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.

Pipe

Reamer

Point down

Putting nut on

Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)

Flare nut

Copper tube

• Carry out flaring work using flaring tool as shown below.

Outside diameter

A

 

 

 

mm

inch

mm

 

 

 

Ø6.35

1/4

0~0.5

 

 

 

Ø9.52

3/8

0~0.5

 

 

 

Ø12.7

1/2

0~0.5

 

 

 

Ø15.88

5/8

0~1.0

 

 

 

Ø19.05

3/4

1.0~1.3

Check

Compare the flared work with figure below.

If flare is noted to be defective, cut off the flared section and re-flare it.

Smooth all round

Inside is shiny without scratches

= Improper flaring =

Inclined Surface Cracked Uneven

damaged thickness

Even length all round

Connectionofpiping--Indoor

Preparing the indoor unit's piping and drain hose for installation through the wall.

Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.

Replace the plastic tubing holder in the original position.(Optional)

Drain hose

Flaring work

Firmly hold copper pipe in a die in the dimension shown in the table above.

 

"A"

 

Handle

Bar

Bar

 

 

Yoke

 

 

 

 

 

 

Cone

 

Copper pipe

 

 

 

Clamp handle

Red arrow mark

 

 

 

When install, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.

16 Room Air Conditioner

Flaring work and connection of piping

For right rear piping

Route the indoor tubing and the drain hose in the direction of rear right.

Connecting the pipings to the indoor unit and drain hose to drain pipe.

Align the center of the pipes and sufficiently tighten the flare nut by hand.

Drain hose

Indoor unit tubing

Flare nut Pipes

• Tighten the flare nut with a wrench.

Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.

Do not connect the cable to the indoor unit.

Make a small loop with the cable for easy connection later.

Open-end wrench (fixed)

Flare nut

Wrench

Connection pipe

Indoor unit tubing

Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Tape

Connecting pipe

Drain hose

Connecting cable

NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.

*Foamed polyethylene or equivalent is recommended.

Indoor unit installation

Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting

cable

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Outside diameter

Torque

 

 

 

mm

inch

kg.m

Ø6.35

1/4

1.8

Ø9.52

3/8

4.2

Ø12.7

1/2

5.5

Ø15.88

5/8

6.6

Ø19.05

3/4

6.6

When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Indoor unit drain hose

Adhesive Vinyl tape(narrow)

Wrap the insulation material around the connecting portion.

•Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Connection

Indoor

unit pipe

pipe

 

Vinyl tape

Wrap with vinyl tape

(wide)

 

Service Manual 17

Flaring work and connection of piping

Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.

Wrap with vinyl tape

Pipe

Vinyl tape(wide)

Drain hose

For left rear piping

Route the indoor tubing and the drain hose to the required piping hole position.

Insert the piping, drain hose, and the connecting cable into the piping hole.

Connecting cable

Drain pipe

Connecting the pipings to the indoor unit and the drain hose to drain pipe.

Align the center of the pipes and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut Pipes

• Tighten the flare nut with a wrench.

 

Open-end wrench (fixed)

 

Flare nut

Wrench

 

Connection pipe

Indoor unit tubing

 

 

Outside diameter

Torque

mm

inch

kg.m

Ø6.35

1/4

1.8

Ø9.52

3/8

4.2

Ø12.7

1/2

5.5

Ø15.88

5/8

6.6

Ø19.05

3/4

6.6

When extending the drain hose at the indoor unit, install the drain pipe.

Insert the connecting cable into the indoor unit.

 

• Don't connect the cable to the indoor unit.

Drain hose

 

• Make a small loop with the cable for easy connection later.

 

Tape the drain hose and the connecting cable.

• Connecting cable

Indoor unit installation

Hang the indoor unit from the hooks at the top of the installation plate.

Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Indoor unit

Spacer

Installation plate 8cm

Indoor unit drain hose

Adhesive Vinyl tape (narrow)

Wrap the insulation material around the connecting portion.

Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material

18 Room Air Conditioner

Flaring work and connection of piping

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Connection

Indoor

unit piping

pipe

 

Vinyl tape

Wrap with vinyl tape

(wide)

 

 

Pipe

 

Vinyl tape(narrow)

Connecting cable

 

• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

Pipe

Drain hose

Vinyl tape(narrow)

Wrap with

vinyl tape(wide)

Reroute the pipings and the drain hose across the back of the chassis.

Piping passage piping hole

Set the pipings and the drain hose to the back of the chassis with the tubing holder.

Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Tubing holder

Indoor unit installation

Remove the spacer.

Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting

cable

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Installation Information (For left piping)

Good case

For left piping. Follow the instruction below.

Press on the upper side of clamp. ()

• Unfold the tubing to downward slowly. ()

• Bend the tubing to the left side of chassis.

Service Manual 19

Flaring work and connection of piping

Bad case

Following bending type from right to left could cause problem of pipe damage.

Connectionofthepipes-Outdoor

Align the center of the pipings and sufficiently tighten the flare nut by hand.

Finally, tighten the flare nut with torque wrench until the wrench clicks.

When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.

Outside diameter

Torque

 

 

 

mm

inch

kg.m

Ø6.35

1/4

1.8

Ø9.52

3/8

4.2

Ø12.7

1/2

5.5

Ø15.88

5/8

6.6

Ø19.05

3/4

6.6

 

 

 

Outdoor unit

Gas side piping (Bigger diameter)

Liquid side piping (Smaller diameter)

Torque wrench

20 Room Air Conditioner

Connecting the cable between indoor unit and outdoor unit

Connecting the cable between indoor unit and outdoor unit

Connectthe cabletotheIndoor unit.

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)

The above circuit diagram is subject to change without notice.

The earth wire should be longer than the common wires.

When installing, refer to the circuit diagram behind the panel front of the indoor unit.

Connect the wires firmly so that they may not be pulled out easily.

Connect the wires according to color codes, referring to the wiring diagram.

If a power plug is not used, provide a circuit breaker between power source and the unit as shown by.

Main power source

Air

Circuit Breaker

Conditioner

Use a circuit

 

breaker or time

 

delay fuse.

The power cord connected to the "A" unit should be selected according to the following specifications(Type "B" approved by HAR or SAA).

 

 

 

 

(mm2)

NORMAL CROSS

 

Grade

 

 

 

 

 

7k

9k~14k

18k

24k

-SECTIONAL AREA

 

 

 

 

0.75

1.0

1.5

2.5

 

 

 

 

 

 

Unit(A)

Indoor

Indoor

Indoor

Indoor

 

 

 

 

 

Cable Type(B)

H05VV-F

H05VV-F

H05VV-F

H05VV-F

 

 

 

 

 

The power connecting cable connecting the indoor and outdoor unit should be selected according to the following specifications (Type "B" approved by HAR or SAA).

 

 

 

 

(mm2)

NORMAL CROSS

 

Grade

 

 

 

 

 

7k

9k~14k

18k

24k

-SECTIONAL AREA

 

 

 

 

0.75

1.0

1.5

2.5

 

 

 

 

 

 

Cable Type(B)

H07RN-F

H07RN-F

H07RN-F

H07RN-F

 

 

 

 

 

Service Manual 21

Connecting the cable between indoor unit and outdoor unit

Connectthecabletotheoutdoorunit

Remove the control cover from the unit by loosening the screw.

Connect the wires to the terminals on the control board individually.

Secure the cable onto the control board with the cord clamp.

Refix the control cover to the original position with the screw.

Use a recognized circuit breaker "A" between the power source and the unit.

A disconnecting device to adequately disconnect all supply lines must be fitted.

Circuit

 

 

 

Grade

 

 

Breaker

5k~14k

18k

24k~28k

30k, 32k

36k, 38k

(A)

 

 

 

 

 

 

15

20

30

30

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

Terminal block

Over 5mm

Connecting cable

Connecting cable

Cover control

After the confirmation of the above conditions, prepare the wiring as follows:

1)Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.

2)The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)

3)Specification of power source.

4)Confirm that electrical capacity is sufficient.

5)See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.

6)Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 21))

7)Always install an earth leakage circuit breaker in a wet or moist area.

8)The following would be caused by voltage drop.

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.

9)The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.

22 Room Air Conditioner

Checking the drainage and forming the pipings

Checking the drainage and forming the pipings

Checkingthedrainage

To remove the front panel from the indoor unit.

Set the air direction louvers up-and-down to the position(horizontally) by hand.

Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.

Formthepiping

Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.

If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.

Pull the right and the left side.

To check the drainage.

Pour a glass of water on the evaporator.

Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Drain piping

• The drain hose should point downward for easy drain flow.

Downward slope

• Do not make drain piping.

 

Do not raise

 

Accumulated

 

 

 

 

 

drain water

 

 

 

 

 

 

 

Tip of drain hose

 

 

 

 

Air

 

Less than

 

 

 

 

 

dipped in water

 

 

 

 

 

50mm gap

 

 

 

 

 

 

Water

 

Water

Waving

Water

 

 

leakage

 

leakage

leakage

Ditch

 

 

 

 

 

 

 

 

 

 

In cases where the outdoor unit is installed below the indoor unit perform the following.

Tape the piping, drain hose and connecting cable from down to up.

Secure the tapped piping along the exterior wall using saddle or equivalent.

Seal small openings around pipings with a gum type sealer.

Taping

Drain hose

Pipings

Connecting cable

Trap is required to prevent water from entering into electrical parts.

In cases where the Outdoor unit is installed above the Indoor unit perform the following.

Tape the piping and connecting cable from down to up.

Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.

Fix the piping onto the wall by saddle or equivalent.

Seal a small opening around the pipings with gum type sealer.

Trap

Trap

Service Manual 23

Air purging

Air Purging

Airpurging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.

Pressure in the system rises.

Operating current rises.

Cooling(or heating) efficiency drops.

Moisture in the refrigerant circuit may freeze and block capillary tubing.

Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.

Airpurgingwithvacuumpump

Preparation

Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

Leak test

Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.

Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.

Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves.

Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.

Outdoor unit

Manifold valve

Pressure gauge Lo Hi

Charge hose

To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.

Nitrogen gas cylinder(in vertical standing position)

24 Room Air Conditioner

Air purging

Soap water method

(1)Remove the caps from the 2-way and 3-way valves.

(2)Remove the service-port cap from the 3-way valve.

(3)To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it.

(4)Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.

(5)If bubbles come out, the pipes have leakage.

Evacuation

Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit.

Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump.

The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.

Required time for evacuation when 30 gal/h vacuum pump is used

If tubing length is less than 10m (33 ft)

if tubing length is longer than 10m (33 ft)

 

 

10 min. or more

15 min. or more

 

 

When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.

Finishing the job

With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.

Turn the valve stem of gas side valve counter-clockwise to fully open the valve.

Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.

Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.

Replace the valve caps at both gas and liquid side service valves and fasten them tight.

This completes air purging with a vacuum pump. The air conditioner is now ready to test run.

Gas side

Liquid side

3-way valve (Close)

2-way valve (Open)

Cap

Hexagonal wrench

Outdoor unit

Manifold

Pressure gauge

Open Close

Vacuum pump

Service Manual 25

Loading...
+ 57 hidden pages