Internal Use Only
http://biz.lgservice.com
Multi Air Conditioner
SVC MANUAL(Exploded View)
MODEL : AMNW09GAF11 [LMAN097HVP] AMNW12GAF11 [LMAN127HVP]
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
1. Specification
|
|
Indoor unit type |
|
ART COOL |
|
|
|
|
|
|
|
|
|
Model |
|
AMNW09GAF11 |
AMNW12GAF11 |
|
|
|
[LMAN097HVP] |
[LMAN127HVP] |
|
|
|
|
|
||
|
|
|
|
|
|
Power supply |
|
Ø, V, Hz |
1, 208/230, 60 |
1, 208/230, 60 |
|
|
|
|
|
|
|
Cooling capacity |
|
kW |
2.64 |
3.28 |
|
|
|
|
|
|
|
|
|
|
Btu/h |
9,000 |
11,200 |
|
|
|
|
|
|
Heating capacity |
|
kW |
3.05 |
3.90 |
|
|
|
|
|
|
|
|
|
|
Btu/h |
10,400 |
13,300 |
|
|
|
|
|
|
Current Nominal running current |
A |
0.2 |
0.2 |
||
|
|
|
|
|
|
Fan |
Motor type |
|
BLDC |
BLDC |
|
|
|
|
|
|
|
|
|
Fan type |
|
Turbo fan |
Turbo fan |
|
|
|
|
|
|
|
|
Motor output x Number of unit |
24 x 1 |
24 x 1 |
|
|
|
|
|
|
|
|
|
Air flow rate |
CMM |
7.7/5.9/4.4 |
8.9/7.3/5.6 |
|
|
|
|
|
|
|
|
(H/M/L) |
l/s |
128/98/73 |
148/122/93 |
|
|
|
|
|
|
|
|
Capacitor |
μF/Vac |
- |
- |
|
|
|
|
|
|
|
|
Drive |
|
Direct Drive |
Direct Drive |
|
|
|
|
|
|
Coil |
Row x column x FPI |
mm |
2R x 20C x 21 |
2R x 20C x 21 |
|
|
|
|
|
|
|
Dimensions (WxHxD) |
Body |
mm(inch) |
600 x 600 x 147(23.6 x 23.6 x 5.8) |
600 x 600 x 147(23.6 x 23.6 x 5.8) |
|
|
|
|
|
|
|
Weight |
Body |
kg(lbs) |
14.5(32.0) |
14.5(32.0) |
|
|
|
|
|
|
|
Sound level (H/M/L) |
|
dB(A)+3 |
39 / 35 / 31 |
42 / 38 / 34 |
|
|
|
|
|
|
|
Piping |
|
Liquid |
mm(inch) |
6.35(1/4) |
6.35(1/4) |
|
|
|
|
|
|
connections |
|
Gas |
mm(inch) |
9.52(3/8) |
9.52(3/8) |
|
|
|
|
|
|
Dehumidification rate |
|
l/h |
1.20 |
1.40 |
|
|
|
|
|
|
|
Safety devices |
|
|
Fuse, Thermal Protector for Fan Motor |
||
|
|
|
|
|
|
Temperature sensor |
|
|
Thermistor |
Thermistor |
|
|
|
|
|
|
|
Referigerant |
|
|
R410A |
R410A |
|
|
|
|
|
|
|
Referigerant control |
|
|
EEV(in Outdoor unit or BD) |
EEV(in Outdoor unit or BD) |
|
|
|
|
|
|
|
Connectable outdoor unit |
|
Multi F / F DX series |
Multi F / F DX series |
||
|
|
|
|
|
|
Power and transmission interunit cable |
No. x AWG |
4 x 18(Including Earth) |
4 x 18(Including Earth) |
Note:
1.All data are based on the following conditions:
-Cooling Temperature : Indoor 26.7 (80 ) DB / 19.4 (67 ) WB Outdoor 35 (95 ) DB / 23.9 (75 ) WB
-Heating Temperature : Indoor 21.1 (70 ) DB / 15.6 (60 ) WB Outdoor 8.33 (47 ) DB / 6.11 (43 ) WB
-Piping Length : Interconnected Pipe Length = 7.5m
-Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2.Wiring cable size must comply with the applicable local and national code.
3.Due to our policy of innovation some specifications may be changed without notification.
4.Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Conversion Formula
kW |
= Btu/h × 0.0002931 |
CFM |
= CMM × 35.3 |
Copyright ©2013 LG Electronics. Inc. All right reserved. |
- 2 - |
Only for training and service purposes |
LGE Internal Use Only |
|
2. Function Table
Category |
Functions |
|
AMNW09GAF11 [LMAN097HVP] |
|
AMNW12GAF11 [LMAN127HVP] |
||
|
|
|
|
|
|
|
|
|
Air supply outlet |
|
3 |
|
Airflow direction control (left & right) |
|
Auto |
|
Airflow direction control (up & down) |
|
Auto |
|
Auto swing (left & right) |
|
O |
Air flow |
Auto swing (up & down) |
|
O |
|
Airflow steps (fan/cool/heat) |
|
4 / 5 / 5 |
|
Chaos wind(auto wind) |
|
O |
|
Jet cool/heat |
|
O / O |
|
Swirl wind |
|
X |
|
Triple filter (Deodorizing) |
|
X |
Air purifying |
Plasma air purifier |
|
X |
Allergy Safe filter |
|
X |
|
|
|
||
|
Long-life prefilter (washable / anti-fungus) |
|
O |
|
Drain pump |
|
X |
|
E.S.P. control |
|
X |
Installation |
Electric heater |
|
X |
|
High ceiling operation |
|
X |
|
Auto Elevation Grille |
|
X |
|
Hot start |
|
O |
Reliability |
Self diagnosis |
|
O |
|
Soft dry operation |
|
O |
|
Auto changeover |
|
X |
|
Auto cleaning |
|
O |
|
Auto operation(artificial intelligence) |
|
O |
|
Auto Restart |
|
O |
|
Child lock* |
|
O |
Convenience |
Forced operation |
|
O |
|
Group control* |
|
O |
|
Sleep mode |
|
O |
|
Timer(on/off) |
|
O |
|
Timer(weekly)* |
|
O |
|
Two thermistor control* |
|
O |
|
Wired remote controller |
|
PREMTB10U |
Individual |
Deluxe wired remote controller |
|
X |
Simple wired remote controller |
|
PQRCVCL0Q / PQRCVCL0QW |
|
controller |
|
||
Simple Wired remote controller(for hotel use) |
|
X |
|
|
|
||
|
Wireless remote controller |
|
O |
|
General central controller (Non LGAP) |
|
X |
Network |
Network Solution(LGAP) |
|
O |
Solution |
Dry contact |
|
PQDSA(1)/PQDSB(1) / PQDSBC / PQDSBNGCM1 |
|
PI 485(for Indoor Unit) |
|
X |
Special |
Zone controller |
|
X |
CTI(Communication transfer interface) |
|
X |
|
function kit |
|
||
Electronic thermostat |
|
X |
|
|
|
||
|
Remote temperature sensor |
|
X |
Others |
Group control wire |
|
PZCWRCG3 |
Telecom shelter controller |
|
X |
|
|
|
||
|
Connector for water level sensor |
|
O |
Note |
|
|
|
1. * : These functions need to connect the wired remote controller. |
|
||
O : Applied |
X : Not applied |
|
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Copyright ©2013 LG Electronics. Inc. All right reserved. |
- 3 - |
Only for training and service purposes |
LGE Internal Use Only |
|