All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of KROHNE Messtechnik GmbH.
Figure 218 Min/max ID setting and resulting variables ............................. 165
10www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
IMPORTANT INFORMATION
KROHNE Oil & Gas pursues a policy of continuous development and product improvement. The
Information contained in this document is, therefore subject to change without notice. Some
display descriptions and menus may not be exactly as described in this handbook. However, due
the straight forward nature of the display this should not cause any problem in use.
To the best of our knowledge, the information contained in this document is deemed accurate
at time of publication. KROHNE Oil & Gas cannot be held responsible for any errors, omissions,
inaccuracies or any losses incurred as a result.
In the design and construction of this equipment and instructions contained in this handbook,
due consideration has been given to safety requirements in respect of statutory industrial regulations.
ABOUT THIS HANDBOOK
01
Users are reminded that these regulations similarly apply to installation, operation and maintenance, safety being mainly dependent upon the skill of the operator and strict supervisory
control.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
11
1. About this book
1.1 Volumes
This is Volume 3 of 3 of the SUMMIT 8800 Handbook:
Volume 1
Volume 1 is targeted to the electrical, instrumentation and maintenance engineer
This is an introduction to the SUMMIT 8800 flow computer, explaining its architect and layout providing the user with familiarity and the basic principles of build. The volume describes the
Installation and hardware details, its connection to field devices and the calibration.
The manual describes the operation via its display, its web site and the configuration software.
Also the operational functional of the Windows software tools are described, including the configurator, the Firmware wizard and the display monitor.
Volume 2
Volume 2 is targeted to the metering software configuration by a metering engineer.
The aim of this volume is to provide information on how to configure a stream and the associated hardware.
The handbook explains the configuration for the different metering technologies, including meters, provers, samplers, valves, redundancy etc.. A step by step handbook using the Configurator
software, on the general and basic setup to successfully implement flow measurement based on
all the applications and meters selections within the flow computer.
SUMMIT 8800ABOUT THIS HANDBOOK01
Volume 3
Volume 3 is targeted to the software configuration of the communication to the outside world.
The manual covers all advance functionality of the SUMMIT 8800 including display configuration,
reports, communication protocols, remote access and many more advance options.
1.2 Content Volume 1
Volume 1 concentrates on the daily use of the flow computer
• Chapter 2: Basic functions of the flow computer
• Chapter 3: General information on the flow computer
• Chapter 4: Installation and replacement of the flow computer
• Chapter 5: Hardware details on the computer, its components and boards
• Chapter 6: Connecting to Field Devices
• Chapter 7: Normal operation via the touch screen
• Chapter 8: How to calibration the unit
• Chapter 9: Operation via the optional web site
• Chapter 10: Operational functions of the configuration software, more details in volume 2
• Chapter 11: How to update the firmware
• Chapter 12: Display monitor software to replicate the SUMMIT 8800 screen on a PC and make
screen shots
1.3 Content Volume 2
Volume 2 concentrates on the software for the flow computer.
• Chapter 2: General information on the software aspects of the flow computer
• Chapter 3: Details on metering principles
• Chapter 4: Basic functions of configurator
• Chapter 5: Configuration of the hardware of the boards
• Chapter 6: Stream configuration
• Chapter 7: Run switching
• Chapter 8: Watchdog
12www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
• Chapter 9: Configure a station
• Chapter 10: Configure a prover or master meter
• Chapter 11: Configure valves
• Chapter 12: Configure a sampler
• Chapter 13: Set-up batching
• Chapter 14: Set two flow computers in redundant configuration
1.4 Content Volume 3
Volume 3 concentrates on the configuration of the SUMMIT 8800
• Chapter 3; Configurator software
• Chapter 4: Date & Time
• Chapter 5: Data Logging
• Chapter 6: Display and web access
• Chapter 7: Reporting
• Chapter 8: Communication
• Chapter 9: General Information
1.5 Information in this handbook
ABOUT THIS HANDBOOK
01
The information in this handbook is intended for the integrator who is responsible to setup and
configure the SUMMIT 8800 flow computer for Liquid and or Gas and or Steam application:
Integrators (hereafter designated user) with information of how to install, configure, operate and
undertake more complicated service tasks.
This handbook does not cover any devices or peripheral components that are to be installed and
connected to the SUMMIT 8800 it is assumed that such devices are installed in accordance with
the operating instructions supplied with them.
Disclaimer
KROHNE Oil & Gas take no responsibility for any loss or damages and disclaims all liability for
any instructions provided in this handbook. All installations including hazardous area installations are the responsibility of the user, or integrator for all field instrumentation connected to
and from the SUMMIT 8800 Flow computer.
Trademarks
SUMMIT 8800 is a trade mark of KROHNE Oil & Gas.
Notifications
KROHNE Oil & Gas reserve the right to modify parts and/or all of the handbook and any other
documentation and/ or material without any notification and will not be held liable for any damages or loss that may result in making any such amendments.
Copyright
This document is copyright protected.
KROHNE Oil & Gas does not permit any use of parts, or this entire document in the creation of
any documentation, material or any other production. Prior written permission must be obtained
directly from KROHNE Oil & Gas for usage of contents. All rights reserved.
Who should use this handbook?
This handbook is intended for the integrator or engineer who is required to configure the flow
computer for a stream including devices connected to it.
Versions covered in this handbook
All Versions
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
13
2. General Information
2.1 Software versions used for this guide
This handbook is based on the software versions as mentioned in Appendix 1: software versions
2.2 Terminology and Abbreviations
AGAAmerican Gas Association
APIAmerican Petroleum Institute
Communication board Single or dual Ethernet network board
Configurator Windows software tool to configure and communicate to the SUMMIT 8800
CPControl Panel
CPU Central Processing Unit
CRC32Cyclic Redundancy Check 32 bits. Checksum to ensure validity of information
FATFactory Acceptance Test
FDS Functional Design Specification
HMIHuman-Machine Interface
HOVHand Operated Valve
I/O Input / Output
ISO International Standards Organization
KOGKROHNE Oil and Gas
KVMKeyboard / Video / Mouse
MOVMotor Operated Valve
MSCMetering Supervisory Computer
MUTMeter Under Test
Navigator360 optical rotary dial
PCPersonal Computer
PRTPlatinum Resistance Thermometers
PSUPower Supply Unit
PTPressure Transmitter
Re-tryMethod to repeat communication a number of times before giving an alarm
RTD:Resistance Temperature Device
Run: Stream/Meter Run
SATSite Acceptance Test
SUMMIT 8800 Flow computer
TimestampTime and date at which data is logged
Time-outCount-down timer to generate an alarm if software stopped running
14www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
2.3 General Controls and Conventions
In the configurator several conventions are being used:
Numeric Data Entry Box
Clear background, black text, used for entering Numeric Data, a value must be entered here
Optional: Coloured background, black text used for entering optional Numeric Data. If no value
is entered then right click mouse key and select Invalidate, box will show and no number will be
entered.
An invalid Number will be shown on the SUMMIT 8800 display as “---------“ and is read serially
as 1E+38
Pull-Down Menu
Select a function or option from a list functions or options
GENERAL INFORMATION
02
Icon
Selects a function or a page.
Tabs
Allows an individual page, sub-page or function to be selected from a series of pages, sub-pages or functions.
Expanded item Fewer items shown.
Non Expanded item +
More items shown.
Option Buttons
Red cross means OFF or No
Green tick means ON or Yes
Data Tree
Items from the Data Tree can be either selected or can be “Dragged and dropped” from the Tree
into a selection box; for example when setting up a logging system or a Modbus list, etc.
Yellow Data circle means Read Only. Red data circle means Read and Write.
Hover over
Hold the cursor arrow over any item, button or menu, etc. Do not click any mouse button, the
item will be lightly highlighted and information relating to the selection will be illustrated.
Grey Text
Indicates that this item has no function or cannot be entered in this particular mode of the system. The data is shown for information purposes only.
Help Index
Display information that assists the user in configuration.
Naming convention of Variables
In the KROHNE SUMMIT 8800 there are variables used with specific naming.
This naming is chosen to identify a variable and relate it to the correct stream.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
15
SUMMIT 8800GENERAL INFORMATION02
The most complex variable is explained below and this explanation can be used to interpret all
the other variable names.
Example: + ph uVN . 1
+Positive (+) or negative (-)
PhPrevious (P) or Current (C) period
Pqh – previous 15 minutes
Ph – previous hour
Pd – previous Day
Pm – previous month
Pq – previous quarter of a year
Cqh – current 15 minutes
Ch – current hour
Cd – current Day
Cm – current month
Cq – current quarter of a year
uType of totals
u – Unhaltable, counts always
m – Maintenance, counts when maintenance is active (optional)
n – Normal, fiscal counters during normal operation
e – Error, fiscal counters with an accountable error
t1 –> t4 – Tarif , fiscal counters based on fiscal thresholds
VNType of flow
VPulses, pulses counted
Vline, gross volume flow
Vmon, monitored grass volume flow
Vbc (p/t) pressure and temperature corrected gross volume flow
Vbc, linearization corrected (Vbc(p/t))gross volume flow
VN, Normalized volume flow
VN(net), Nett normalized flow
VM, Mass flow
VE, Energy flow
VCO2, carbon dioxide flow
1Stream/ Run number
2.4 ID Data Tree
When selecting parameters and options in the Configurator software, the user will be presented
with a tree structure for instance:
16www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
GENERAL INFORMATION
02
Figure 1 Example ID Tree
This is referred to as the ID tree which, depending on its context, includes folders and several
parameters:
2.4.1 Type of data
The rest of this chapter will explain the folders available, the type of selection within the folder
and any other corresponding data.
Preset Data
Essential to the configuration of the flow computer. Typical data would be keypad values, operating limits, equation selection, calibration data for Turbines and Densitometers and Orifice
plates.
This data would be present in a configuration report, and enables you to see what the flow computer is configured to do.
Used for validation and will form the Data Checksum (visible on the System Information Page).
E.g., if a data checksum changes, the setup of the flow computer has changed and potentially
calculating different results to what is expected.
Typically configured and left alone, only updated after validation e.g. every 6 month / 1 year.
Active Data
These values cover inputs to the flow computer. E.g. from GC, pressure & temperature transmitters, meters etc..
Also Values calculated in the flow computer. E.g. Flow rates, Z, Averages, Density etc..
Local Data
Data that an operator can change locally to perform maintenance tasks. E.g., turn individual
transmitters off without generating alarms. Setting Maintenance mode or Proving Mode.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
17
Totals
Totals for the streams and station.
Contents of this folder are stored in the non-volatile RAM and are protected using the battery.
Custom
User defined variables.
Allows calculations, made in a LUA script, to be used in a configuration.
For details, see volume 3.
2.4.2 Colour codes
With each parameter and option, there are corresponding coloured dots that represent the access and status of the particular selection.
General ID tree
Please note that it might be possible to change the values via the screen
SUMMIT 8800GENERAL INFORMATION02
Red DotData is Read/Write and can be changed over Modbus.
Yellow Dot Data is Read-Only and cannot be changed over Modbus
90% of the data will be Read Only, but items such as Serial Gas Compositions, Time/Date, MF
are commonly written over Modbus.
NOTE: Although the ID may be read/write, the security setting determines whether the ID indeed
can be written.
Alarm Tree
The alarm tree is built of all the registers that hold alarm data. Alarm registers are 32-bit integers, where each bit represents a different alarm.
Red DotRepresents an accountable alarm visible on the alarm list.
Dark Blue DotRepresents a non-accountable alarm visible on the alarm list.
Orange DotRepresents a warning visible on the alarm list.
Light Blue DotRepresents a status alarm, not visible on the alarm list.
Black/Grey DotRepresents a hard- or software fault alarm visible on the alarm list.
An example of typical usage would be the General Alarm Register. This is a 32 bit register that
indicates up to 32 different alarms in the flow computer. This will contain Status Alarms, for example, 1 bit will indicate if there is a Pressure alarm or not. If the Pressure Status bit is set the
user will know that there is a problem with the Pressure.
This should be sufficient information, however if it is not satisfactory, the user can look at the
Pressure alarm, this contains 32 different alarms relating to the Pressure measurement, these
would be Red Dots as they each can create an entry in the alarm list. By reading this register
the user can view exactly what is wrong with the Pressure measurement.
The Light Blue Dots are generally an OR of several other dots. By reading the General register
you can quickly see if the unit is healthy, more information can be provided by reading several
more registers associated with that parameter.
18www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
2.4.3 ID Lookup
When pressing the ID lookup button on top of the screen, a lookup table will be generated:
GENERAL INFORMATION
02
Figure 2 ID lookup
As there are very many ID’s, it is possible to filter for a required ID.
2.5 Specific Requirements for Meters and Volume Convertors
2.5.1 Numbering formats
The number formats used internally in the unit are generally IEEE Double Precision floating
point numbers of 64 bit resolution.
It is accepted that such numbers will yield a resolution of better than 14 significant digits.
In the case of Totalisation of Gas, Volumes, Mass and Energy such numbers are always shown to
a resolution of 8 digits before the decimal point and 4 after, i.e. 12 significant digits.
Depending upon the required significance of the lowest digit, these values can be scaled by a
further multiplier.
2.5.2 Alarms
Each of the various modules that comprise the total operating software, are continuously monitored for correct operation. Depending upon the configuration, the flow computer will complete its allotted tasks within the configured cycle time, 250mS, 500mS or 1 second. Failure to
complete the tasks within the time will force the module to complete, and where appropriate, a
substitute value issued together with an alarm indication.
For example, if a Calculation fails to complete correctly then a result of 1 or similar will be
returned, which allows the unit to continue functioning whilst an accountable alarm is raised,
indicating an internal problem.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
19
2.5.2.1 Accountable alarm
When the value of any measurement item or communication to an associated device that is providing measurement item to the SUMMIT 8800 goes out of range, the flow computer will issue
an Accountable Alarm.
When any calculation module or other item that in some way affects the ultimate calculation result goes outside its operating band, i.e. above Pressure Maximum or below Pressure minimum,
then the SUMMIT 8800 will issue an Accountable Alarm.
When the SUMMIT 8800 issues an Accountable alarm a number of consequences will occur as
follows:
Front panel accountable alarm will turn on and Flash.
Nature of accountable alarm will be shown on the top line of the alarm log.
Alarm log will wait for user acknowledgement of alarm.
During the period of the alarm, main totalisation will occur on the alarm counters.
2.5.3 Optional consequences
Depending upon the configuration of the SUMMIT 8800 the following optional Consequences will
also occur:
SUMMIT 8800GENERAL INFORMATION02
An Entry will be made in the Audit Log, with Time and Date of occurrence.
The “Used” value of the Parameter in Alarm will be substituted by an alternative value, either
from an alternative measurement source that is in range, or from a pre-set value.
A digital Alarm output will indicate an Alarm condition.
20www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800
3. CONFIGURATOR SOFTWARE
For initial installation of the software refer to Volume 1 of the handbook.
For Hardware and instrumentation, refer to Volume 2 of the handbook
Alter starting the configuration software, the option menu appears:
CONFIGURATOR SOFTWARE
03
Figure 3 Configurator option selections
Select Edit Offline, this function allows the user to create or modify a new configuration without
actually being connected to the flow computer.
Figure 4 Application firmware version
Select the correct software version. The software must be compliant to the connected Summit
8800 firmware version, details of system information can be found in volume 1. We assume that
the version mentioned in append 1 is selected.
The main configuration page of the Configurator software is displayed and will be the starting
point for this manual.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
21
SUMMIT 8800CONFIGURATOR SOFTWARE03
Figure 5 Main Configurator display
22www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800DATE & TIME
4. DATE & TIME
The Summit has a battery backed real-time clock. The clock can be set in several ways:
- Initially a fixed value via the configuration software
- Initially the time of the computer downloading the configuration software..
- Automatically synchronized via an SNTP server
- Manually via the screen
The format of the time can be changed to fit international needs.
The Summit also knows a contract time as often a buyer and seller have different moment of a
day that they like to generate reports, e.g. at 00:00 hours and 06:00 hours. Only required if more
than one report time is needed.
4.1 Initial setting of date and time
04
In the configuration software the initial settings for date and time can be set together with and
the display format and the contract time:
Figure 6 Date & time and contract time selection
Set date fromSelect from
• Don’t sendLeave the Summit clock untouched.
• Set from PC’s date/timeChange the Summit clock to the PC date/time when downloading the
• Set from custom settingsChange the Summit clock to a manual settings when downloading
Date/ timeDate and time for manual setting
Date / time formatSelect the format needed
Contract timeSelect the time as per customer needs.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
software
www.krohne.com
23
4.2 SNTP Time Synchronisation
The SNTP or Simple Network Time Protocol is available to synchronise the internal clock with a
network time server. While the internal clock’s accuracy is limited to about 3 ppm/°C, these time
servers are based on atomic clocks to guarantee the best accuracy. This function also ensures
that all flow computers in a network are using the same time.
The flow computer works with time servers using version 3 or 4 of the SNTP protocol, either
Unicast or Broadcast:
• Unicast is where the flow computer will request the time from a specified time server.
• Broadcast is when the flow computer waits for a broadcast packet from a time server, and
then confirms the results by using a unicast request.
The SNTP can be setup in the hardware section under the Ethernet SNTP:
SUMMIT 8800DATE & TIME04
Figure 7 SNTP Date & time general settings
EnableClick the box to enable SNTP
Operating modeSet the mode as unicast or multicast
PortThe port used for SNTP standard specifies that this should be 123.
Min time adjustmentMinimum amount of time the flow computer clock can be adjusted
Max time adjustment Maximum amount of time the flow computer clock can be adjusted
Max time without adjustment Maximum number of seconds that the flow computer can be expected
to operate without receiving a new time from the time server. If this time
is exceeded without receiving a new time then the flow computer will
give a warning.
Invalid time update limitMaximum number of bad updates that can be received before a warning
is given.
Ignore max adjust on startup Indicates if the maximum time adjustment value should be ignored for
the first valid time received by the flow computer after power up.
Offset from GMT The time zone of the local time as an offset from the atom clock +/-
GMT minutes
24www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800DATE & TIME
Figure 8 SNTP Date & time unicast settings
Server timeoutThe timeout that applies to each server, after which the next available server in
the list is tried. It is recommended that this value is a factor of the maximum
time without adjustment.
Poll interval Frequency of the flow computer polling the time server. It is recommended that
this value is not divisible by 60.
Number of servers The number of time servers the flow computer can connect to.
Time server IP address of each server.
04
Figure 9 SNTP Date & time broadcast settings
Broadcast timeout The flow computer the waits for a broadcast before giving an alarm. It is
recommended that this value is a factor of the maximum time without
adjustment.
Broadcast domain.IP address on the client subnet for the client operating in broadcast mode to
listen for time updates from broadcast servers.
4.3 Manually change date and time
To be able to set the date and time manually, a display item has to be created under “Security”
with the time in it. (see also next chapter).
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
25
SUMMIT 8800DATE & TIME04
Figure 10 Manual Date & time settings
If the operator then goes into Edit mode, he can change the time as follows:
Figure 11 Manual Date & time adjustment
26www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800DATA LOGGING
5. DATA LOGGING
To store historical data is one of the major functions of a flow computer. The Summit 8800 is has
3 types of log’s:
Alarm logStorage of current and historical alarms.
Audit trail logStorage of any change made to the unit that has metrological significance.
Data logStorage of user defined data, either periodically or event diven.
The first two are system logs and cannot be changed, however an audit log can be extended with
user defined data.
5.1 Alarm and audit log security
It is possible to define what to do with alarm acknowledgment and clearing alarm and audit logs
depending on the 4 hardware security switches on the back of the Summit. Two of them determine the security mode of the Summit:
OpenAny changes can be made (using user passwords) and applications can be loaded.
PartialChanges can be made except calibration data. No new application can be loaded.
FullNo changes in parameters, values or any other data is not possible.
05
The different security mode also effects the alarm/ audit clearing and acknowledgment and can
be set under “display, alarm/audit security configuration“
Figure 12 Display security window
Clear Alarm LogDetermines if the alarm log may be cleared in open/ partial/ full mode.
Acknowledge Alarms Determines if the alarms may be acknowledged in open/ partial/ full mode.
Clear Audit Log Determines if the audit log may be cleared in open/ partial/ full mode.
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
27
5.2 Alarm log
Every time an alarm or warning occurs, it will be stored in the alarm log. The log contains a
maximum of 200 entries consisting of time and date when the alarm occurred and vanished plus
a description of the alarm or warning.
SUMMIT 8800DATA LOGGING05
Figure 13 Alarm log
As the alarm log is a system functions, it does not need any configuration, exept for the alarm
acknowledge and clear, which is depending on the security configuration (see previous chapter)
All alarm information stored in the Summit’s internal data flash memory. Each record contains
a CRC 32 check which is generated when the log record is created and checked for validity each
time data is read from the Unit.
5.3 Audit trail log
Any change made in the Summit which influences the flow measurement in any way is stored in
an audit trail to be able to track back what went wrong and possibly recalculate the results.This
log contains a maximum of 200 kbyte of internal memory, typically good at least 2000 entries.
Each entry consists of time and date when the event occurred, the operator name, the description of the event and the value before and after change:
28www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
SUMMIT 8800DATA LOGGING
Figure 14 Audit trail log
05
Each record contains a CRC 32 check which is generated when the log record is created and
checked for validity each time data is read from the unit.
As the audit trail log is a system functions, it does not need any configuration. However, configuration of the audit acknowledge, which is depending on the security configuration, is possible
(see chapter Alarm and audit log security).
5.3.1 Audit log extension
For diagnostic purposes, the user can extend the audit trail with alarms and with up to 10 additional data items per event. These data will be stored on an external SD card only. Configuration
can be done under “general” :
08/2013 - MA SUMMIT 8800 Vol3 R02 en
www.krohne.com
29
SUMMIT 8800DATA LOGGING05
Figure 15 Audit log extension
The user can select which alarm types are to be included in the audit log:
Figure 16 Audit log select alarms
Accountable alarmsAlarms (min or max exceeded) which influence the flow measurements
Non-accountable alarmsAlarms which do not influence the flow measurements
WarningsWarnings (hi or low exceeded) which do not influence the flow
measurements
FaultsHardware faults, such as wrong hardware cards inserted for this
application
Select which additional data is to be recorded for each audit event, often these are the flow
totals at time of event:
30www.krohne.com08/2013 - MA SUMMIT 8800 Vol3 R02 en
Loading...
+ 141 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.