KROHNE OPTISWITCH-6500C User Manual

Page 1
Handbook
Handbook
OPTISWITCH 6500 C
OPTISWITCH 6500 C
OPTISWITCH 6500 COPTISWITCH 6500 C
Switch for level detection and dry-run protection
HandbookHandbook
© KROHNE 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 2
: IMPRINT :::::::::::::::::::::::::::::::::::::::
All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written authorisation of KROHNE Messtechnik GmbH.
Copyright 2013 by KROHNE Messtechnik GmbH - Ludwig-Krohne-Str. 5 - 47058 Duisburg (Germany)
2
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 3
OPTISWITCH 6500 C
CONTENTS
1 Safety instructions 5
1.1 Intended use ..................................................................................................................... 5
1.2 Certifications .................................................................................................................... 5
1.3 Safety instructions from the manufacturer ..................................................................... 6
1.3.1 Copyright and data protection ................................................................................................ 6
1.3.2 Disclaimer ............................................................................................................................... 6
1.3.3 Product liability and warranty ................................................................................................ 7
1.3.4 Information concerning the documentation........................................................................... 7
1.3.5 Warnings and symbols used................................................................................................... 8
1.4 Safety instructions for the operator................................................................................. 8
2 Device description 9
2.1 Scope of delivery............................................................................................................... 9
2.2 System description........................................................................................................... 9
2.3 Nameplate ...................................................................................................................... 10
3 Installation 11
3.1 General notes on installation ......................................................................................... 11
3.2 Installation requirements .............................................................................................. 11
3.3 Process connection ........................................................................................................ 11
3.4 Mounting of 3A marked products................................................................................... 12
3.5 Installation of sliding connection ................................................................................... 13
4 Electrical connections 15
4.1 Safety instructions.......................................................................................................... 15
4.2 Description of electrical connection .............................................................................. 15
4.3 Electrical connection diagramms .................................................................................. 16
4.4 Configuration tool........................................................................................................... 17
4.5 Teach-In function............................................................................................................ 19
5 Operation 21
5.1 Start-up........................................................................................................................... 21
5.2 Fault diagnosis and corrective action ............................................................................ 21
6 Service 22
6.1 Availability of services .................................................................................................... 22
6.2 Returning the device to the manufacturer..................................................................... 22
6.2.1 General information.............................................................................................................. 22
6.2.2 Form (for copying) to accompany a returned device............................................................ 23
6.3 Disposal .......................................................................................................................... 23
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
3
Page 4
CONTENTS
OPTISWITCH 6500 C
7 Technical data 24
7.1 Measuring principle........................................................................................................24
7.2 Technical data................................................................................................................. 25
7.3 Dimensions and weights ................................................................................................ 27
8 Appendix 28
8.1 Order code ...................................................................................................................... 28
8.2 Order code for process connection................................................................................ 29
9 Notes 30
4
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 5
OPTISWITCH 6500 C
1.1 Intended use
The OPTISWITCH 6500 C is a level switch for level detection and dry-run protection for liquids and solids. The device measures liquids such as water and beer and well as viscous and sticky products such as honey or toothpaste. Even dry medias can be measured such as sugar or flour.
The measurement is precise and not affected by the mounting position.
Coating of the sensor or condensate are not detected.
1.2 Certifications
CE marking
The device fulfils the statutory requirements of the following EC directives:
EMC specification acc. to EN 61326-1 (2006)
SAFETY INSTRUCTIONS 1
The manufacturer certifies successful testing of the product by applying the CE marking.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
5
Page 6
1 SAFETY INSTRUCTIONS
1.3 Safety instructions from the manufacturer
1.3.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third parties are identified as such. Reproduction, processing, dissemination and any type of use beyond what is permitted under copyright requires written authorisation from the respective author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the manufacturer's documents is always on a voluntary basis whenever possible. Whenever feasible, it is always possible to make use of the offerings and services without providing any personal data.
OPTISWITCH 6500 C
We draw your attention to the fact that data transmission over the Internet (e.g. when communicating by e-mail) may involve gaps in security. It is not possible to protect such data completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish an imprint for the purpose of sending us any advertising or informational materials that we have not expressly requested.
1.3.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including, but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross negligence. In the event any applicable law does not allow such limitations on implied warranties or the exclusion of limitation of certain damages, you may, if such law applies to you, not be subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable in any way for possible consequences of such changes.
6
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 7
OPTISWITCH 6500 C
1.3.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose. The manufacturer accepts no liability for the consequences of misuse by the operator. Improper installation and operation of the devices (systems) will cause the warranty to be void. The respective "Standard Terms and Conditions" which form the basis for the sales contract shall also apply.
1.3.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards, safety requirements and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the text, we advise you to contact your local office for assistance. The manufacturer can not accept responsibility for any damage or injury caused by misunderstanding of the information in this document.
This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. Special considerations and precautions are also described in the document, which appear in the form of underneath icons.
SAFETY INSTRUCTIONS 1
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
7
Page 8
1 SAFETY INSTRUCTIONS
1.3.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This information refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to serious health problems and even death. There is also the risk of seriously damaging the device or parts of the operator's plant.
OPTISWITCH 6500 C
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems. There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the specified sequence.
i RESULT
RESULT
RESULTRESULT This symbol refers to all important consequences of the previous actions.
1.4 Safety instructions for the operator
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and maintained by properly trained and authorized personnel. This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device.
8
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 9
OPTISWITCH 6500 C
2.1 Scope of delivery
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
The following items are supplied with the device:
Measuring device
Hygienic adapter (optional)
Product documentation
DEVICE DESCRIPTION 2
2.2 System description
Inputting physical quantities into an SPC or PLC or other computer and control systems requires accurate and reliably working sensors. The sensor is a detecting element that detects level (liquids/solids), identifies a liquid or a changed characteristics of a liquid and converts it into an electrical on/off signal.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
9
Page 10
2 DEVICE DESCRIPTION
2.3 Nameplate
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
OPTISWITCH 6500 C
Figure 2-1: Example of a nameplate
1 Device type 2 Operating conditions (process pressure, process temperature and ambient temperature) 3 Electrical data 4 Serial number 5 Date of manufacture 6 Approvals and certifications
10
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 11
OPTISWITCH 6500 C
3.1 General notes on installation
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
3.2 Installation requirements
Use only the recommended sleeves or adapters. If other systems are used, no guarantee can be given for proper functionality or leak-tightness.
The connection thread must have direct electrical contact with the threaded sleeve and the metal tank or pipe.
Do not use Teflon or paper gaskets between switch and hygienic adapter. The PEEK sensor together with the stainless steel adapter will perform a hygienic tightening. Assumed that the requirements have been followed.
The tightening torque for the sleeve should be 20...25 Nm (for sliding connection 25...30 Nm).
If the tank or pipe is electrically non-conductive (e.g. plastic), the metal face of a screw-in
sleeve with a diameter of at least 28 mm / 1.1" will suffice as reference ground.
INSTALLATION 3
3.3 Process connection
The hygienic ½" process sleeve is easy to weld into tanks or pipes. The marking points to the
centre of the future position of the cable gland or M12 plug connector. This form of assembly allows installation in conformity with standards of hygiene (to 3A, FDA).
Various hygienic adapter sleeves are available for fitting to other process connections. For more information please refer to chapter "Order code".
The sensor can be installed in any desired position.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
11
Page 12
3 INSTALLATION
3.4 Mounting of 3A marked products
The 3A mark is valid only when the product is mounted in a 3A marked counterpart and installed acc. to the installation manual. Use also a 3A marked O-ring or gasket if relevant.
The 3A marked products conforms to the 3A sanitary standards criteria. Materials and surfaces fulfill the FDA demands.
EPDM O-rings supplied with 3A marked products are conform to sanitary standards class II (8% milk fat).
1 Use only 3A approved counterparts. 2 The inspection hole should be visible and drained. Face it downwards that leaking can be
observed.
3 Mount the device in a self-drained position. 4 Level the inner surface of the pipe with the counterpart. 5 Weld from the inside of the tank, if possible. Welds shall be free from cracks, crevices and
grooves. Weldings should be grinded to R
=0.8µm.
a
OPTISWITCH 6500 C
12
Figure 3-1: Mounting of 3A products in pipe installations (A) or tank installations (B)
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 13
OPTISWITCH 6500 C
3.5 Installation of sliding connection
The following drawing shows how the sliding connection can be used for at least 4 applications:
INSTALLATION 3
Figure 3-2: Possible applications for sliding connection
1 Mounted at the top of a tank to adjust to a certain level.
2 Serving as a cooling neck in high media temperature applications.
3 Adjusted to place the sensor tip deeper inside the tank (for lumpy or sticky media).
4 To reach in through insulation material.
CAUTION!
The OPTISWITCH 6500 C with sliding connection can be mounted with a static pressure up to 16 bar / 232 psi. To prevent personnel injuries, it is essential that the safety chain is mounted correctly and undamaged.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
13
Page 14
3 INSTALLATION
CAUTION!
It is essential that the max. ambient temperature for the electronics is never exceeded.
The operating conditions for the sliding connection in different media temperatures and specified ambient temperatures can be found in the following drawing.
OPTISWITCH 6500 C
Figure 3-3: Media temperature versus external length of sliding connection
a = media temperature in [°C] or [°F] b = external length of sliding connection in [mm] or ["]
= max. 40°C / 104°F
1 T
amb
2 T
= max. 60°C / 140°F
amb
3 T
= max. 75°C / 167°F
amb
4 T
= max. 85°C / 185°F
amb
Example, how to read the drawing:
A 250 mm / 9.9" sliding connection is mounted in a tank with a total insertion length of 150 mm /
5.9". Hence the external length of the sliding connection will be:
250 - 150 = 100 mm or 9.9 - 5.9 = 4".
The media temperature will be max. 160°C / 320°F.
Read the x-axis at 100 mm / 4" an the y-axis at 160°C / 320°F and find that the ambient temperature must be kept below 40°C/ 104°F. In case the radiated heat from the tank will cause
a higher ambient temperature at the housing efficient insulation of the tank must be established.
14
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 15
OPTISWITCH 6500 C
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate!
DANGER!
Observe the national regulations for electrical installations!
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists.
ELECTRICAL CONNECTIONS 4
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
4.2 Description of electrical connection
Terminals 1 and 2 are used for supplying a DC voltage of 12...30 V (M12: terminal 1 and 3). According to polarity, the output will switch to active or inactive when the sensor is immersed (refer to connection diagram). The terminal wired to the negative pole is connected via an internal protective diode to the housing.
The maximum power consumption is 70 mA (excluding load switched). This value should be taken into account in connection with the recommended use of a fuse. An active switching output (PNP) is available at terminal 5 (M12: terminal 4). The switching voltage is a minimum of 1 V below the supply voltage. The maximum output current is 50 mA. At higher loads, the current is limited accordingly. Damage through shorting cannot occur.
CAUTION!
When the top cover is removed, do not look directly at the LED with unshielded eyes or damage to retina may occur!
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
15
Page 16
4 ELECTRICAL CONNECTIONS
4.3 Electrical connection diagramms
Description of normally open (NO) and normally closed (NC)
Normally open Normally closed
OPTISWITCH 6500 C
1 0mA 2 50 mA 3 LED
1 50 mA 2 0mA 3 LED
PNP
Normally open Normally closed
M12 M16 M12 M16
NPN
Normally open Normally closed
M12 M16 M12 M16
16
M12 plug
1: brown; 2: white; 3: blue; 4: black
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 17
OPTISWITCH 6500 C
ELECTRICAL CONNECTIONS 4
Digital output
Normally open Normally closed
M16 M16
1 PLC 2 active high
4.4 Configuration tool
The configuration tool can be ordered optionally to configure the OPTISWITCH 6500 C.
Scope of delivery:
Interface unit
CD with software and product drivers (DTM)
USB cable
Cable with 2 alligator clips
M12 connection cable
The configuration tool connects the OPTISWITCH 6500 C with a computer. With the corresponding software, it is possible to get an online communication with the OPTISWITCH 6500 C.
By using this tool, device information like serial number, switching point range and tag numbers are displayed on the computer. Settings as switching point, damping, polarity and output can be changed.
1 PLC 2 active low
Self-learning function for the contact output is possible as well as reset function to the default values of the switching point.
By fine-tuning of the switching point settings, OPTISWITCH 6500 C could differentiate between various products which are covering the sensor. In other words, the device could be set to trigger on a specific product and ignore a second product. Basis for this would be a different ε
these two products.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
value of
r
17
Page 18
4 ELECTRICAL CONNECTIONS
DANGER!
Disconnect the power supply before connecting the configuration tool to the switch!
Figure 4-1: Electrical connection of configuration tool
a = red alligator clip b = black alligator clip
OPTISWITCH 6500 C
INFORMATION!
°
Ambient temperature range is 0...+50
C / +32...+122°F.
DANGER!
The configuration tool cannot be connected to the OPTISWITCH 6500 C within the hazardous area. For programming, remove the device out of this area.
18
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 19
OPTISWITCH 6500 C
4.5 Teach-In function
A Teach-In procedure may be necessary for a medium with a low dielectric constant.
1 12...36 VDC / - or (+) 2 Sensor 3 Output 4 Teach-In 5 Cover 6 12...36 VDC / + or (-)
ELECTRICAL CONNECTIONS 4
Step Action LED Result
1 Connect terminal "Teach-In" to -
VDC (T1 or T2) for 3.5 s.
2 With "no media present" connect
"Teach-In" to -VDC shortly.
3 With "media present" connect
"Teach-In" to -VDC shortly.
Flash 1 time per second. Ready for Teach-In.
Light for 2 seconds and then flash.
Light for 2 seconds. Register "full"state, store and
Register "empty" state. If the media is sticky, foamy, powdery or in other ways leaving parts of the media at the sensor tip this situation has to be established also during the Teach-In process. Otherwise a faulty calibration can be the result.
return to normal operation with the new settings
If the media is sticky, foamy or powdery or in other ways leaving parts of the media at the sensor tip, this situation has to be established also during the Teach-In process.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
19
Page 20
4 ELECTRICAL CONNECTIONS
CAUTION!
Make sure that power is on before Teach-In.
For best Teach-In it is important that the actual process conditions are simulated.
During Teach-In mode the light intensity of the LED will decrease to protect your eyes.
If Teach-In for some reason do not succeed, the device will enter "Error State" and reload factory settings automatically. This state is indicated by a blinking LED (3 short and 1 long blink). The error can normally be fixed by powering off and on. Alternatively remake the "Teach-In" procedure.
The factory settings can always be reloaded by connecting the terminal "Teach-In" to -VDC for more then 6.5 seconds. The reloaded factory settings will be confirmed by pulsing light intensity 3 times.
INFORMATION!
Please observe that the OPTISWITCH 6500 C has been factory adjusted to measure liquids with
> 2, such as oil.
ε
r
In case the media has a lower ε out for the media or alternatively a manual adjustment using the configuration tool can be done.
The adjustment must be made at the medias operating temperature to avoid faulty measurements due to temperature drift.
value (e.g. powder) either a Teach-In procedure must be carried
r
OPTISWITCH 6500 C
20
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 21
OPTISWITCH 6500 C
5.1 Start-up
Before connecting to power, please check that the system has been correctly installed. This includes:
The device must be mechanically safe and mounted in compliance with the regulations.
Check the leak-tightness at the sleeve.
Make sure that the cable gland is tight or, as the case may be, the M12 plug is properly
screwed down.
The power connections must have been made in compliance with the regulations.
Check that the electrical operating data of the power supply are correct.
Switching on the power.
i Check for correct switching function.
5.2 Fault diagnosis and corrective action
OPERATION 5
Fault Cause Action / elimination
LED not "on" Sensor cap not in contact with
liquid product
Supply voltage < 12 V, permittivity too low
No switching output Cable break Check continuity of cables
Incorrect polarity of supply Reverse terminals 1 and 2 (M12:
Short-circuit Check wiring
-
Measure voltage at Pin 1 and 2 (M12: pin 1 and 3)
terminal 1 and 3)
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
21
Page 22
6 SERVICE
6.1 Availability of services
The manufacturer offers a range of services to support the customer after expiration of the warranty. These include repair, maintenance, technical support and training.
INFORMATION!
For more precise information, please contact your local sales office.
6.2 Returning the device to the manufacturer
6.2.1 General information
This device has been carefully manufactured and tested. If installed and operated in accordance with these operating instructions, it will rarely present any problems.
CAUTION!
Should you nevertheless need to return a device for inspection or repair, please pay strict attention to the following points:
Due to statutory regulations on environmental protection and safeguarding the health and safety of our personnel, manufacturer may only handle, test and repair returned devices that have been in contact with products without risk to personnel and environment.
This means that the manufacturer can only service this device if it is accompanied by the following certificate (see next section) confirming that the device is safe to handle.
OPTISWITCH 6500 C
CAUTION!
If the device has been operated with toxic, caustic, flammable or water-endangering products, you are kindly requested:
to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from such dangerous substances,
to enclose a certificate with the device confirming that is safe to handle and stating the product used.
22
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 23
OPTISWITCH 6500 C
6.2.2 Form (for copying) to accompany a returned device
Company: Address:
Department: Name:
Tel. no.: Fax no.:
Manufacturer's order no. or serial no.:
The device has been operated with the following medium:
SERVICE 6
This medium is: water-hazardous
toxic
caustic
flammable
We checked that all cavities in the device are free from such substances.
We have flushed out and neutralized all cavities in the device.
We hereby confirm that there is no risk to persons or the environment through any residual media contained in the device when it is returned.
Date: Signature:
Stamp:
6.3 Disposal
CAUTION!
Disposal must be carried out in accordance with legislation applicable in your country.
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
23
Page 24
7 TECHNICAL DATA
7.1 Measuring principle
A high frequency signal sweep is radiated from the sensor tip into the tank / pipe. The medium will act as a virtual capacitor, which together with a coil in the sensor head, will form a circuit creating the switching point signal. This virtual capacity will depend of the dielectric value of the medium and it is well defined for most media.
The measurement is precise and unaffected by the mounting position.
OPTISWITCH 6500 C
1 Tank wall / pipe wall 2 Medium 3 Line of electric flux
24
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 25
OPTISWITCH 6500 C
TECHNICAL DATA 7
7.2 Technical data
INFORMATION!
The following data is provided for general applications. If you require data that is more relevant to your specific application, please contact us or your local sales office.
Additional information (certificates, special tools, software,...) and complete product documentation can be downloaded free of charge from the website (Download Center).
Measuring system
Measuring principle Electromagnetic wave, 100..180 MHz
Application range Level detection, dry-run protection and media separation of liquids and
Design
Construction The measurement system consists of a measuring sensor and the electronic
Options Sliding connection / extension for high-temperature applications
Accessories Comprehensive range of adapters and process connections for hygienic
solids.
unit which is available in a compact version. The switching point is signalled by a blue LED indication through the housing cover.
Teach-In function for applications where the medium is hard to detect.
installation. Please refer to the specific data sheet "Accessories".
Measuring accuracy
Resolution ±1 mm / ±0.04" Hysteresis ±1 mm / ±0.04"
Reference conditions acc. to EN 60770
Reference conditions acc. to EN 60770
Reference conditions acc. to EN 60770Reference conditions acc. to EN 60770 Temperature +20°C ±5°C / +70°F ±10°F Pressure 1013 mbar abs. ±20 mbar / 14.69 psig ±0.29 psig Relative air humidity 60% ±15%
Operating conditions
Temperature
Temperature
TemperatureTemperature
Ambient temperature (T Process temperature -40+85°C / -40+185°F (short version and DN38 connection)
Pressure
Pressure
PressurePressure
Ambient pressure Atmospheric
Process pressure Standard and DN38 connection: max. 40 bar / 580 psi
Other conditions
Other conditions
Other conditionsOther conditions
Protection category (acc. to EN 60529)
) -40+85°C / -40+185°F
amb
< 1 hour, T
-40 +200°C / -40...+392°F (with sliding connection)
Sliding connection: max. 16 bar / 232 psi
IP67 equivalent to NEMA 4X
< 60°C / 140°F: -40…+140°C / -40+284°F
amb
Installation conditions
Installation In any position. For detailed information refer to chapter "Installation".
Dimensions and weights For detailed information refer to chapter "Dimensions and weights".
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
25
Page 26
7 TECHNICAL DATA
OPTISWITCH 6500 C
Materials
Sensor housing Stainless Steel 1.4301 / 304
Process connection Stainless Steel 1.4404 / 316L
Sensor insulation Virgin PEEK, FDA conform
Electrical connection Cable gland M16: Plast or Nickel-plated brass
Plug M12: Nickel-plated brass
Process connections
Standard Hygienic G½; DN38
Other For other hygienic process connections, e. g. Tri-clamp, 11851, Varivent
please refer to the chapter "Order code".
Electrical connections
Power supply 1236 VDC, 70 mA max.
Power consumption 1.7 W
Power-up time <2s
Reaction time Max. 0.1 s
Damping 0...10 s
Cable entry M16 cable gland or M12 (4 pole Lumberg)
Output
Output (active) Max. 50 mA, short-circuit and high-temperature protected
Output type PNP or NPN
Output polarity See drawing in chapter "Electrical connection". Active "Low" NPN and digital output; (-VDC + 2.5 V) ± 0.5 V; R
Active "High" PNP and digital output; (VDC - 2.5 V) ± 0.5 V; R
Factory settings Measure: εr>2; damping: 0.1s
load
load
=1kOhm
=1kOhm
Approvals and certifications
CE This device fulfils the statutory requirements of the EC directives.
Other standards and approvals
Other standards and approvals
Other standards and approvalsOther standards and approvals
Electromagnetic compatibility (EMC) EN 61326-1 (2006)
Vibration resistance IEC 68-2-6, GL test 2 (standard and DN38 connection) Hygiene 3A for G½ and DN38, FDA conform materials
The manufacturer certifies successful testing of the product by applying the CE marking.
26
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 27
OPTISWITCH 6500 C
7.3 Dimensions and weights
G½" hygienic connection, DN38 hygienic connection and G½" hygienic sliding
connection (from left to right)
TECHNICAL DATA 7
1 M12x1 plug 2 M16x1.5 cable gland 3 WS 22 4 G½" 5 PEEK tip 6 Sliding connection length (refer to ordering data) 7 Safety chain 8 G½" hygienic sliding nipple
Dimensions Approx. weight
[mm] [inches] [kg] [lb]
G
G½" hygienic connection
" hygienic connection
GG
" hygienic connection" hygienic connection
a Ø55 Ø2.17 0.4 0.9
b 18 0.71
c 44 1.73
d 58 2.28
DN38 hygienic connection
DN38 hygienic connection
DN38 hygienic connectionDN38 hygienic connection
a Ø55 Ø2.17 0.4 0.9
b 31.5 1.20
c 19 0.70
d 58 2.28
The weight for devices with sliding connection depends on the ordered length of the sliding connection (max. 0.5 kg / 1.1 lb).
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
27
Page 28
8 APPENDIX
8.1 Order code
VGP9
VGP9 4 1 0 0 0 Order code
VGP9VGP9
OPTISWITCH 6500 C
1 OPTISWITCH 6500 C, with IP67 (equivalent to NEMA4X), stainless steel housing -
FDA compliant materials The use of a VGP7 process connections is required for 3A approved switches.
Process connection
Process connection
Process connectionProcess connection
For hygienic use in combination with VGP7 process connections
For hygienic use in combination with VGP7 process connections
For hygienic use in combination with VGP7 process connectionsFor hygienic use in combination with VGP7 process connections 1 G½ - standard sensor length 18 mm / 0.7" (for use with hygienic process
connections)
2 DN38 hygienic connection incl. EPDM "O"-ring, 3A certified - insertion length
of 18 mm
For non-hygienic use
For non-hygienic use
For non-hygienic useFor non-hygienic use 3 G½ - with rigid extended sensor 100 mm / 3.9" (sliding connection) 4 G½ - with rigid extended sensor 250 mm / 9.8" (sliding connection)
Electrical connection
Electrical connection
Electrical connectionElectrical connection
1 M16 - polyamid cable gland included
2 M16 - brass cable gland included
3 M12 - 4-pin connector plug
Approvals
Approvals
ApprovalsApprovals
0 Without 1 Certified acc. to 3A, G½, DN 38 in combination with hygienic adapter
VGP7
Output configuration
Output configuration
Output configurationOutput configuration
0 Standard
1 Customer settings - based on data from an installed device.
"% of triggering, damping, hysteresis, output mode" to be specified separately.
28
Order code for configuration tool (incl. interface unit + USB cable + CD with driver + alligator clips + M12 connection cable)
XGP9
XGP9 0 0 0 0 1 0 Order code
XGP9XGP9
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 29
OPTISWITCH 6500 C
8.2 Order code for process connection
APPENDIX 8
VGP7 4 Process connection type
VGP7
VGP7 4 0 0 Order code
VGP7VGP7
Process connection type
Process connection typeProcess connection type
0 Without
1 Weld-in sleeve; HWN 200
2 Collared weld-in sleeve; HWN 210 3 Weld-in sleeve with shoulder for pipes DN2550; HWN 220
4 Hygienic adapter for G1 process connection; HGA 200
7 Spherical weld-in sleeve for angled sensor mounting; HWN 250
8 DRD - DN50 sanitary connection; HMM 250
A DIN 11851 - DN25 conical nozzle incl. rotating union nut and gasket; HMT 225
B DIN 11851 - DN50 conical nozzle, incl. rotating union nut and gasket; HMT 250
C Varivent flange type N - DN40/50, incl. "O"-ring; HVF 250
D Tri Clamp 2", DN50 - DIN 32676, ISO 51/40 mm, incl. EPDM seal; HTC 250
U DIN 11851 - DN40 conical nozzle incl. rotating union nut and gasket; HMT 240 V Tri Clamp 1½", DN25/40 DIN 32676, ISO 25/33, 7/38 mm; HTC 240
W SMS adapter 1145 / 51 mm, incl. union nut; HSM 251
Z Allen screw blanking plug; HST 200
Surface
Surface
SurfaceSurface
0 Standard
1 Inside electro-polished
Material test / certification
Material test / certification
Material test / certificationMaterial test / certification
0 Without
1 Material certificate 3.1 (EN 10204)
2 Declaration of conformity 2.1 (EN 10204)
Surface test
Surface test
Surface testSurface test
0 Without
2 Surface roughness test report EN 10204 2-1
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
29
Page 30
9 NOTES
OPTISWITCH 6500 C
30
www.krohne.com 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
Page 31
OPTISWITCH 6500 C
NOTES 9
www.krohne.com01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en
31
Page 32
KROHNE product overview
Electromagnetic flowmeters
Variable area flowmeters
Ultrasonic flowmeters
Mass flowmeters
Vortex flowmeters
Flow controllers
Level meters
Temperature meters
Pressure meters
Analysis products
Products and systems for the oil & gas industry
Measuring systems for the marine industry
Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Straße 5 47058 Duisburg (Germany) Tel.:+49 203 301 0 Fax:+49 203 301 103 89 info@krohne.com
© KROHNE 01/2014 - 4000649104 - MA OPTISWITCH 6500 R04 en - Subject to change without notice.
The current list of all KROHNE contacts and addresses can be found at: www.krohne.com
Loading...