KROHNE MFC 400 Data sheet

Technical Datasheet
Technical Datasheet
MFC 400
MFC 400
MFC 400MFC 400
Technical DatasheetTechnical Datasheet
Signal converter for mass flowmeters
High performance signal converter for all applications, developed acc. to IEC 61508, SIL 2/3
Smart diagnostics acc. to NAMUR NE 107
The documentation is only complete when used in combination with the relevant documentation for the flow sensor.
© KROHNE 11/2017 - 4002075706 - TD MFC 400 R06 en
CONTENTS
MFC 400
1 Product features 3
1.1 The high performance signal converter for all applications ........................................... 3
1.2 Options and variants......................................................................................................... 5
1.3 Signal converter/flow sensor combination possibilities ................................................. 8
1.4 Measuring principle.......................................................................................................... 8
2 Technical data 9
2.1 Technical data................................................................................................................... 9
2.2 Dimensions and weight .................................................................................................. 20
2.2.1 Housing ................................................................................................................................. 20
2.2.2 Mounting plate of field housing ............................................................................................ 20
3 Installation 21
3.1 Intended use ................................................................................................................... 21
3.2 Installation specifications .............................................................................................. 21
3.3 Mounting of the compact version................................................................................... 21
3.4 Mounting the field housing, remote version .................................................................. 22
3.4.1 Pipe mounting ....................................................................................................................... 22
3.4.2 Wall mounting....................................................................................................................... 23
4 Electrical connections 24
4.1 Safety instructions.......................................................................................................... 24
4.2 Connection diagram ....................................................................................................... 24
4.3 Grounding the flow sensor ............................................................................................. 25
4.4 Connecting power - all housing variants ....................................................................... 26
4.5 Inputs and outputs, overview ......................................................................................... 27
4.5.1 Combinations of the inputs/outputs (I/Os) ........................................................................... 27
4.5.2 Description of the CG number .............................................................................................. 28
4.5.3 Fixed, non-alterable input/output versions.......................................................................... 29
4.5.4 Alterable input/output versions............................................................................................ 30
5 Notes 31
2
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
PRODUCT FEATURES
1.1 The high performance signal converter for all applications
The MFC 400
MFC 400 Coriolis mass flow signal converter will provide the highest performance possible
MFC 400MFC 400 across a wide range of applications. For the measurement of liquids or gases, cryogenic to high temperature fluids, single or multi-phase fluids and advanced digital signal processing techniques is used to give stable and accurate measurements of mass flow, density and temperature.
It is developed according to IEC 61508 and depending on the I/O and flow sensor variant suited for use in safety applications SIL 2/3.
Conforming to the NAMUR standard NE 107 for status and error handling, the MFC 400 features enhanced meter diagnostics. This provides extensive self-checking of internal circuits and information regarding the health of the flow sensor, but just as importantly, vital information about the process and process conditions.
Measuring values and diagnostic information can be transmitted via field bus interfaces including HART
®
, RS485 Modbus, FOUNDATION Fieldbus, PROFIBUS
®
and PROFINET IO.
1
(signal converter in field housing)
1 Supply voltage: 100...230 VAC (standard) and 24 VDC 2 Communication with any third party system possible via HART
PROFINET IO
3 Intuitive navigation and a wide variety of languages integrated as standard for ease of operation
EGM
EGM Entrained Gas Management
Entrained Gas Management
EGMEGM
Entrained Gas Management Entrained Gas Management
EGM was developed for the OPTIMASS Coriolis mass flowmeters to overcome problems caused by air or gas entrainments in a liquid. Powerful control algorithms maintain measurement, even during a complete transition from a pure liquid phase to a gas phase and back. Mass flow and density measurements remain stable and continuous, which has been demonstrated in batch / loading / empty-full-empty applications.
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
®
, Modbus, FOUNDATION Fieldbus, PROFIBUS
®
and
3
1
PRODUCT FEATURES
Highlights
High performance signal converter with multiple output options
Developed according to IEC 61508
Safe configuration via local display or HART
Partial proof test capable
Smart diagnostics, covering entire devices in less than a minute
NE 107 status indicated by display background light
Entrained Gas Management (EGM
Excellent long-term stability
Optical and mechanical keys for ease of use
Redundant data storage in signal converter housing
Real time clock for logging events
Overall, flexible lock concept
®
HART
Communication interfaces for integration into third party systems via HART
Modbus, FOUNDATION Fieldbus, PROFIBUS
7
®
TM
) – the new standard for entrained gas immunity
®
(as standard),
®
and PROFINET IO
MFC 400
Industries
Water & Wastewater
Chemicals
Power plants
Food & Beverage
Machinery
Oil & Gas
Petrochemical
Pulp & Paper
Pharmaceutical
Marine
Applications
Liquids and gases
Liquids with gas entrainment
Slurries and viscous products
Concentration measurement for quality control
Measurement of volume flow
Measurement of density and reference density
Custody transfer loading/unloading
Custody transfer measurements
4
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
1.2 Options and variants
Compact design for standard applications
(Example: OPTIMASS 6400 – compact)
PRODUCT FEATURES
The MFC 400 mass flow signal converter is available in different variants and offers superior performance in any conceivable application. From process control in chemistry, to density and concentration measurements in the food and beverage industry, to custody transfer filling and transport measurements for oil and gas right down to conveyor systems in the pulp and paper industry.
Coriolis mass flow measuring systems measure the mass and volume flow, the density and the temperature of liquids and gases. In addition, the concentration in mixtures and slurries can also be determined.
Thanks to Entrained Gas Management (EGM MFC 400 systems offer high performance with air entrainment, delivering continuous measurement even with 0...100% gas entrainment.
TM
1
) the
(Example: OPTIMASS 2400 – compact)
Remote field housing version
For standard applications the compact housing is mounted directly on the measuring sensor. In the unlikely event of a failure, the electronics can be easily exchanged and reconfigured using a backup data set that is stored in the housing.
The signal converter in the robust field housing is generally used when it is difficult to access the measuring point or when ambient conditions do not allow the use of the compact version.
(signal converter in field housing)
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
5
1
PRODUCT FEATURES
Communication options
1 Monitoring system 2 Gateway 3 Flowmeter
MFC 400
The basic signal converter variant covers a current
®
output including HART status output, control input and a current input.
The modular input/output variant allows for any combination of up to four inputs and outputs. All inputs and outputs are galvanically isolated from each other and from the rest of the electronic equipment. Inputs and outputs can be passive or active.
In addition, the electronics can be equipped with fieldbus functionality including Foundation Fieldbus, Profibus PA/DP, Modbus or PROFINET IO to enable communication to any third party system.
, pulse/ frequency output,
New: PROFINET IO option
(1. point-to-point or star communication)
With PROFINET IO, real time Ethernet can be connected to IoT scenarios.
The use of existing, legacy, industry-grade devices (e.g. PROFINET flow sensors, actuators and
Programmable Logic Controllers (PLCs)) enables a
new architecture to be used across the Internet.
An unique network topology:
1. Working with point-to-point or star communication using a single Ethernet port and an external switch.
2. Using ring or line communication there are two Ethernet ports available controlled by an internal switch.
(2. ring or line communication)
6
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
Extensive diagnostics of the device and application
PRODUCT FEATURES
The primary focus of a user for a flowmeter is that it delivers reliable and robust measurements. To achieve this all Coriolis mass flowmeters are calibrated before leaving the factory.
In addition, KROHNE was one of the first to introduce extensive diagnostic features.
The MFC 400 provides a wide range diagnostic functions on the flow sensor, signal converter and process integrated in the signal converter.
1
(Measuring principle (Twin tube))
1 Measuring tubes 2 Drive coil 3 Sensor 1 4 Sensor 2
OPTICHECK tool for on-site verification
(Suitcase with OPTICHECK and all cables and
accessories)
Potential problems that may occur in the process including gas bubbles, solids, corrosion, deposits, empty pipe and partial filling of the flow sensor.
Diagnostic info available via local display, status outputs, Fieldbuses, PACTware, xFC toolbox or the OPTICHECK.
The OPTICHECK provides an inline health check of the device under test by an external tool.
A hard copy of the verification report can be printed for every flowmeter. The verification data are digitally stored.
Contact us for more information or for an on-site service visit.
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
7
1
PRODUCT FEATURES
1.3 Signal converter/flow sensor combination possibilities
Flow sensor Flow sensor + signal converter MFC 400
Compact Remote field housing
OPTIMASS 1000 OPTIMASS 1400 C OPTIMASS 1400 F
OPTIMASS 2000 OPTIMASS 2400 C OPTIMASS 2400 F
OPTIMASS 3000 OPTIMASS 3400 C OPTIMASS 3400 F
OPTIMASS 6000 OPTIMASS 6400 C OPTIMASS 6400 F
OPTIMASS 7000 OPTIMASS 7400 C OPTIMASS 7400 F
1.4 Measuring principle
The signal converter has been designed to work with all the measuring tube designs used in the mass flowmeters. For information regarding the measuring principle for a specific measuring tube design, please refer to the technical documentation of the relevant flow sensor.
MFC 400
8
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
TECHNICAL DATA
2.1 Technical data
The following data is provided for general applications. If you require data that is more relevant to your specific application, please contact us or your local sales office.
Additional information (certificates, special tools, software,...) and complete product documentation can be downloaded free of charge from the website (Downloadcenter).
Measuring system
Measuring principle Coriolis principle
Application range Measurement of mass flow, density, temperature, volume flow, flow velocity,
Design
Modular construction The measuring system consists of a flow sensor and a signal converter.
Flow sensor
Flow sensor
Flow sensorFlow sensor OPTIMASS 1000 DN1550 / 1/22" OPTIMASS 2000 DN100400 / 4...12" OPTIMASS 3000 DN0104 / 1/25...4/25" OPTIMASS 6000 DN08250 / 3/8...10" OPTIMASS 7000 DN0680 / 1/43"
Signal converter
Signal converter
Signal converterSignal converter
Compact version (C) OPTIMASS x400 C (x = 1, 2, 3, 6 or 7)
Field housing (F) ­remote version
Options
Options
OptionsOptions
Outputs / inputs
Totaliser 2 (optional 3) internal totalisers with a max. of 8 counter places (e.g. for counting
Verification Integrated verification, diagnostic functions: measuring device, process, measured
Concentration measurement Universal concentration measurement, °Brix, °Baume, °Plato, alcohol
Communication interfaces
concentration
All flow sensors are also available in an Ex version.
MFC 400 F
Compact and field housing versions are also available in an Ex version.
Current output (including HART®), pulse output, frequency output, and/or status output, limit switch and/or control input (depending on the I/O version)
volume and/or mass units)
value, stabilisation
concentration, NaOH and API density
HART®, Foundation Fieldbus, Profibus PA and DP, PROFINET IO, Modbus
2
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
9
2
TECHNICAL DATA
Display and user interface
Display and user interface
Display and user interfaceDisplay and user interface
Graphic display LC display, backlit white.
Size: 256 x 128 pixels, corresponds to 59 x 31 mm = 2.32" x 1.22" Display turnable in 90° steps. Ambient temperatures below -25°C/ -13°F may affect the readability of the display.
Operating elements 4 push buttons/optical keys for operator control of the signal converter without
Remote operation
Display functions
Display functions
Display functionsDisplay functions
Operating menu Setting the parameters using 2 measuring pages, 1 status page, 1 graphic page
Language display texts Available languages: English, German, French, Danish, Spanish, Italian, Dutch,
Measurement functions Units:
Diagnostic functions Standards:
opening the housing.
Infrared interface for reading and writing all parameters with IR interface (option) without opening the housing.
PACTwareTM (including Device Type Manager (DTM))
HART® Hand Held Communicator from Emerson Process
AMS® from Emerson Process
PDM® from Siemens
All DTMs and drivers are available free of charge from the manufacturer's website.
(measured values and graphics are freely adjustable)
Polish, Portuguese, Swedish, Turkish
Units: Metric, British and US units selectable as desired from lists for volume/mass
Units:Units: flow and counting, velocity, temperature, pressure
Measured values:
Measured values: Mass flow, total mass, temperature, density, volume flow, total
Measured values:Measured values: volume, velocity, flow direction (not displayed unit – but available via outputs), Brix, Baume, NaOH, Plato, API, mass concentration, volume concentration
Standards: VDI / NAMUR / WIB 2650 and NE 107
Standards:Standards:
Status messages:
Status messages: Output of status messages optional via display, current and/or
Status messages:Status messages: status output, HART
Sensor and sensor electronics diagnosis:
Sensor and sensor electronics diagnosis: Sensor signal integrity, sensor and drive
Sensor and sensor electronics diagnosis:Sensor and sensor electronics diagnosis: coils diagnostics, measurement channels check, comparison of internal signals with references, drive circuit integrity, process temperature, CPU diagnostics, process temperature circuit monitoring, internal data integrity check, redundant calibration
Signal converter and inputs/outputs:
Signal converter and inputs/outputs: Data bus monitoring, current output
Signal converter and inputs/outputs:Signal converter and inputs/outputs: connections, current readback with redundant calibration, factory calibration integrity, electronics temperature, CPU diagnostics, voltage monitoring
®
or bus interface
MFC 400
10
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
TECHNICAL DATA
Measuring accuracy
Reference conditions Medium: water
Temperature: +20°C / +68°F
Pressure: 1 bar / 14.5 psi
Maximum measuring error Refer to technical data for the flow sensor.
Operating conditions
Temperature
Temperature
TemperatureTemperature
Process temperature Refer to technical data for the flow sensor.
Ambient temperature Depending on the version and combination of outputs.
It is a good idea to protect the signal converter from external heat sources such as direct sunlight as higher temperatures reduce the life cycle of all electronic components.
Die-cast aluminium housing:
Die-cast aluminium housing:
Die-cast aluminium housing:Die-cast aluminium housing: SIL device: -40…+55°C/ -40…+131°F Non-SIL device: -40...+60°C / -40...+140°F
Stainless steel housing:
Stainless steel housing:
Stainless steel housing:Stainless steel housing: SIL device: -40…+55°C/ -40…+131°F Non-SIL device: -40...+60°C / -40...+140°F
Ambient temperatures below -25°C/ -13°F may affect the readability of the display.
Storage temperature -40+70°C/ -40…+158°F
Pressure
Pressure
PressurePressure
Medium Refer to technical data for the flow sensor.
Ambient pressure Atmospheric
Chemical properties
Chemical properties
Chemical propertiesChemical properties
State of aggregation Liquids, gases and slurries
Flow rate Refer to technical data for the flow sensor.
Other conditions
Other conditions
Other conditionsOther conditions
Ingress protection according to IEC 60529
IP66/67 (according to NEMA 4/4X)
2
Installation conditions
Installation For detailed information, refer to chapter "Installation".
Dimensions and weight For detailed information refer to chapter "Dimensions and weight".
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
11
2
TECHNICAL DATA
MFC 400
Materials
Signal converter housing Standard: die-cast aluminium (polyurethane coated)
Option: stainless steel 316 / 1.4408
Flow sensor For housing material, process connections, measuring tubes, accessories and
gaskets, refer to technical data for the flow sensor.
Electrical connection
General Electrical connection is carried out in conformity with the VDE 0100 directive
Power supply Standard: 100230 VAC (-15% / +10%), 50/60 Hz
Power consumption AC: 22 VA
Signal cable Only for remote versions.
Cable entries Standard: M20 x 1.5 (8...12 mm)
"Regulations for electrical power installations with line voltages up to 1000 V" or equivalent national specifications.
Option: 24 VDC (-55% / +30%)
DC: 12 W
10 core shielded cable. Detailed specifications are available on request.
Length: max. 20 m / 65.6 ft
Option: 1/2 NPT, PF 1/2
12
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
TECHNICAL DATA
Inputs and outputs
General All outputs are electrically isolated from each other and from all other circuits.
All operating data and output values can be adjusted.
Description of abbreviations U
Current output
Current output
Current outputCurrent output
Output data Volume flow, mass flow, temperature, density, flow velocity, diagnostic values, 2-
Resolution <1 µA Uncertainty ±5 µA Temperature coefficient Typically ±30 ppm/K
Settings
Operating data Modular I/Os
Active U
= external voltage; RL = load + resistance;
ext
= terminal voltage; I
U
0
= nominal current
nom
Safety limit values (Ex i): Ui = max. input voltage; Ii = max. input current;
= max. input power rating;
P
i
Ci = max. input capacity; Li = max. input inductivity
phase signal
Concentration and concentration flow are also possible with available concentration measurement (optional).
Without HART
Without HART
Without HARTWithout HART
®
Q = 0%: 020 mA; Q = 100%: 10…20 mA Alarm signal: selectable 0…22 mA
With HART
With HART
With HARTWith HART
®
Q = 0%: 420 mA; Q = 100%: 10…20 mA Alarm signal: selectable 3…22 mA
Modular I/Os Ex i
Modular I/OsModular I/Os
=24VDC
int, nom
Ex i
Ex iEx i
U
int, nom
=21VDC
2
Passive U
I 22 mA
RL≤ 1kΩ
30 VDC
ext
I 22 mA
U
1.8 V
0
(U
R
L
ext-U0
)/I
max
I 22 mA
RL≤ 400 Ω
I0=90mA
=0.5W
P
0
C0= 90 nF / L0 = 2 mH
= 110 nF / L0=0.5mH
C
0
U
30 VDC
ext
I 22 mA
U
4V
0
(U
R
L
ext-U0
)/I
max
Ui=30V Ii= 100 mA
=1W
P
i
Ci=10nF
~0mH
L
i
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
13
2
TECHNICAL DATA
®
HART
HART
HARTHART
Description
HART® protocol via active and passive current output
HART® version: V7
Universal HART® parameter: completely integrated
Load
230 Ω at HART® test point; Note maximum load for current output!
Multi-Drop operation Disabled loop current mode, output current = 0%, e.g. 4 mA
Multi-Drop address adjustable in operation menu 0...63
Device drivers Available for FC 375/475, AMS, PDM, FDT/DTM
Registration (HART
Yes
Communication Foundation)
Pulse output or frequency output
Pulse output or frequency output
Pulse output or frequency outputPulse output or frequency output
Output data Pulse output: volume flow, mass flow, mass or volume of dissolved substance
during activated concentration measurement
Frequency output: flow velocity, mass flow, temperature, density, diagnostic value Optional: concentration, flow of the dissolved substance
Function Can be set as a pulse output or frequency output
Pulse rate/frequency 0.01...10000 pulses/s or Hz
Settings Mass or volume per pulse or max. frequency for 100% flow
Pulse width: adjustable as automatic, symmetric or fixed (0.05...2000 ms)
Operating data Modular I/Os
Active U
Modular I/Os Ex i
Modular I/OsModular I/Os
=24VDC -
nom
f
in operating menu set to
max
f
100 Hz:
max
Ex i
Ex iEx i
I 20 mA
MFC 400
open: I 0.05 mA
closed:
=24V at I=20mA
U
0, nom
f
in operating menu set to 100 Hz <
max
f
10 kHz:
max
I 20 mA
open: I 0.05 mA
closed:
= 22.5 V at I = 1 mA
U
0, nom
U
= 21.5 V at I = 10 mA
0, nom
=19V at I=20mA
U
0, nom
14
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
TECHNICAL DATA
2
Passive U
32 VDC -
ext
f
in operating menu set to
max
100 Hz:
f
max
I 100 mA
open: I 0.05 mA at U
=32VDC
ext
closed:
= 0.2 V at I ≤ 10 mA
U
0, max
U
= 2 V at I ≤ 100 mA
0, max
f
in operating menu set to 100 Hz <
max
10 kHz:
f
max
I 20 mA
open: I 0.05 mA at U
=32VDC
ext
closed:
= 1.5 V at I ≤ 1mA
U
0, max
U
= 2.5 V at I ≤ 10 mA
0, max
= 5.0 V at I ≤ 20 mA
U
0, max
NAMUR Passive to EN 60947-5-6
U
=8.2V ± 0.1 VDC
ext
R = 1 kΩ ± 10 Ω
open: I
=0.6mA
nom
closed:
=3.8mA
I
nom
Passive to EN 60947-5-6
open: I
=0.43mA
nom
closed: I
=4.5mA
nom
Ui=30V
= 100 mA
I
i
Pi=1W
=10nF
C
i
Li~0mH
Low flow cut off
Low flow cut off
Low flow cut offLow flow cut off
Function Switching point and hysteresis separately adjustable for each output, counter and
the display
Switching point Set in increments of 0.1%.
020% (current output, frequency output)
Hysteresis Set in increments of 0.1%.
020% (current output, frequency output)
Damping
Damping
DampingDamping
Function The time constant corresponds to the elapsed time until 63% of the end value has
been reached according to a step function.
Settings Set in increments of 0.1 seconds.
0100 seconds
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
15
2
TECHNICAL DATA
Status output / limit switch
Status output / limit switch
Status output / limit switchStatus output / limit switch
MFC 400
Function and settings Adjustable as automatic measuring range conversion, display of flow direction,
overflow, error or switching point.
Valve control with activated dosing function
Status and/or control: ON or OFF
Operating data Modular I/Os
Active U
Modular I/Os Ex i
Modular I/OsModular I/Os
=24VDC
int
Ex i
Ex iEx i
-
I 20 mA
open: I 0.05 mA
closed:
=24V at I=20mA
U
0, nom
Passive U
32 VDC
ext
-
I 100 mA
R
=47kΩ
L, max
R
L, min
=(U
ext-U0
)/I
max
open: I 0.05 mA at U
=32VDC
ext
closed:
= 0.2 V at I ≤ 10 mA
U
0, max
U
= 2 V at I ≤ 100 mA
0, max
NAMUR Passive to EN 60947-5-6
U
=8.2V ± 0.1 VDC
ext
R = 1 kΩ ± 10 Ω
open:
=0.6mA
I
nom
closed:
I
=3.8mA
nom
Passive to EN 60947-5-6
open: I
=0.43mA
nom
closed:
=4.5mA
I
nom
Ui=30V
= 100 mA
I
i
=1W
P
i
Ci=10nF
=0mH
L
i
16
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
Control input
Control input
Control inputControl input
TECHNICAL DATA
Function Hold value of the outputs (e.g. for cleaning work), set value of the outputs to "zero",
counter and error reset, stop counter, range conversion, zero calibration
Start of dosing when dosing function is activated.
Operating data Modular I/Os
Active U
Modular I/Os Ex i
Modular I/OsModular I/Os
=24VDC
int
Ex i
Ex iEx i
-
External contact open: U
=22V
0, nom
External contact closed:
=4mA
I
nom
Contact open (off):
12 V with I
U
0
nom
=1.9mA
Contact closed (on):
10 V with I
U
0
Passive 3V≤ U
I
=9.5mA at U
max
=9.5mA at U
I
max
32 VDC
ext
nom
ext ext
=1.9mA
24 V32 V
U
32 VDC
ext
I 6mA at U I 6.5 mA at U
ext
=24V
=32V
ext
2
Contact closed (on): U0≥ 3V with I
nom
=1.9mA
Contact open (off):
2.5 V with I
U
0
nom
=1.9mA
NAMUR Active to EN 60947-5-6
Terminals open: U
=8.7V
0, nom
Contact closed (on):
=6.3V with I
U
0, nom
nom
Contact open (off):
=6.3V with I
U
0, nom
nom
Detection of cable break: U0≥ 8.1 V with I ≤ 0.1 mA
Detection of cable short circuit:
1.2 V with I 6.7 mA
U
0
>1.9mA
<1.9mA
On: U0≥ 5.5 V with I ≥ 4mA
Off:
3.5 V with I 0.5 mA
U
0
Ui=30V Ii= 100 mA
=1W
P
i
Ci=10nF
=0mH
L
i
-
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
17
2
TECHNICAL DATA
PROFIBUS DP
PROFIBUS DP
PROFIBUS DPPROFIBUS DP
Description Galvanically isolated according to IEC 61158
Profile version: 3.02
Automatic data transmission rate recognition (max. 12 MBaud)
Bus address adjustable via local display at the measuring device
Function blocks 8 x analogue input (AI), 3 x totaliser
Output data Mass flow, volume flow, mass counter 1 + 2, volume counter, product temperature,
PROFIBUS PA
PROFIBUS PA
PROFIBUS PAPROFIBUS PA
Description Galvanically isolated according to IEC 61158
Function blocks 8 x analogue input (AI), 3 x totaliser
Output data Mass flow, volume flow, mass counter 1 + 2, volume counter, product temperature,
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION FieldbusFOUNDATION Fieldbus
Description Galvanically isolated according to IEC 61158
Function blocks 6 x analogue input (AI), 2 x integrator, 1 x PID
Output data Mass flow, volume flow, density, temperature of tube, several concentration
Modbus
Modbus
ModbusModbus
Description Modbus RTU, Master/Slave, RS485 Address range 1247
Supported function codes 01, 03, 04, 05, 08, 16, 43
Supported Baud rate 1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600, 115200 Baud
PROFINET IO
PROFINET IO
PROFINET IOPROFINET IO
Description PROFINET IO is an Ethernet based communications protocol.
Output data Mass flow, volume flow, flow speed, density, mass or volume counter 1 + 2, product
several concentration measurements and diagnostic data
Profile version: 3.02
Current consumption: 10.5 mA Permissible bus voltage: 932 V; in Ex application: 9...24 V
Bus interface with integrated reverse polarity protection
Typical error current FDE (Fault Disconnection Electronic): 4.3 mA
Bus address adjustable via local display at the measuring device
several concentration measurements and diagnostic data
Current consumption: 10.5 mA Permissible bus voltage: 932 V; in Ex application: 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.01
measurements and diagnostic data
The device features two Ethernet ports with an integrated industrial Ethernet switch.
The Ethernet standard 100BASE-TX is supported.
Additionally, the PHYs support the following features:
- Auto negotiation
- Auto crossover
- Auto polarity
temperature, several concentration measurements and diagnostic data
MFC 400
18
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
TECHNICAL DATA
Approvals and certificates
CE This device fulfils the statutory requirements of the relevant EU directives.
Non-Ex Standard
Functional safety according to EN 61508
Hazardous areas
Hazardous areas
Hazardous areasHazardous areas
Option (C version only)
Option (C version only)
Option (C version only)Option (C version only)
ATEX II 1/2 (1) G - Ex d ia [ia Ga] IIC T6 Ga/Gb
Option (F version only)
Option (F version only)
Option (F version only)Option (F version only)
ATEX II 2 (1) G - Ex d [ia Ga] IIC T6 Gb
NEPSI Ex d ia [ia Ga] IIC T6T1 Ga/Gb; Ex de ia [ia Ga] IIC T6T1 Ga/Gb
Option
Option
OptionOption
FM / CSA FM: Class I, Div 1 groups A, B, C, D
IECEx Ex zone 1 + 2
Custody transfer
Custody transfer
Custody transferCustody transfer
Without Standard
Option (in preparation) Liquids other than water 2004/22/EC (MID MI005) according to OIML R117-1
Other standards and approvals
Other standards and approvals
Other standards and approvalsOther standards and approvals
Vibration resistance IEC 60068-2-6
NAMUR NE 21, NE 43, NE 53, NE 107
The manufacturer certifies successful testing of the product by applying the CE mark.
For full information of the EU directives & standards and the approved certifications, please refer to the CE declaration or the manufacturer website.
Depends on I/O variant and flow sensor. For detailed information refer to the "Safety manual".
II 1/2 (1) G - Ex de ia [ia Ga] IIC T6T1 Ga/Gb II 2 (1) G - Ex d ia [ia Ga] IIC T6T1 Gb II 2 (1) G - Ex de ia [ia Ga] IIC T6T1 Gb
II 2 (1) D - Ex t [ia Da] IIIC Txxx Db II 1/2 G - Ex d ia IIC T6T1 Ga/Gb; II 1/2 G - Ex de ia IIC T6T1 Ga/Gb II 2 G - Ex d ia IIC T6T1 Gb; II 2 G - Ex de ia IIC T6T1 Gb II 2 D - Ex t IIIC Txxx°C Db
II 2 (1) G - Ex de [ia Ga] IIC T6 Gb II 2 (1) D - Ex t [ia Da] IIIC T75°C Db
II 2 G - Ex d [ia] IIC T6 Gb; II 2 G - Ex de [ia] IIC T6 Gb
II 2 D - Ex t IIIC T75 Db
CSA: Class I, Div 1 groups C, D
Class II, Div 1 groups E, F, G
Class III, Div 1 hazardous areas
FM: Class I, Div 2 groups A, B, C, D CSA: Class I, Div 2 groups C, D
Class II, Div 2 groups E, F, G
Class III, Div 2 hazardous areas
Gases 2004/22/EC (MID MI002) according to OIML R137
Compliance with API and AGA
10 cycles 10-150-10 Hz with: 0.15 mm for 10-60 Hz and 20 m/s² for 60-150 Hz
2
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
19
2
TECHNICAL DATA
2.2 Dimensions and weight
2.2.1 Housing
Figure 2-1: Dimensions for field housing (F) - remote version
MFC 400
Dimensions [mm / inch] Weight [kg /
a b c g h
202 / 7.75 120 / 4.75 155 / 6.10 295.8 / 11.60 277 / 10.90 5.7 / 12.60
Table 2-1: Dimensions and weight
2.2.2 Mounting plate of field housing
Figure 2-2: Dimensions for mounting plate of field housing
a 72 2.8
b 72 2.8
c Ø9 Ø0.4
Table 2-2: Dimensions in mm and inch
lb]
[mm] [inch]
20
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
3.1 Intended use
The mass flowmeters are designed exclusively to directly measure mass flow rates, product density and temperature as well to indirectly measure parameters such as the total volume and concentration of dissolved substances as well as the volume flow rate.
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
For devices used in SIL applications, additional safety notes apply. For detailed information refer to the "Safety manual".
If the device is not used according to the operating conditions (refer to chapter "Technical data"), the intended protection could be affected.
This device is a Group 1, Class A device as specified within CISPR11:2009. It is intended for use in industrial environment. There may be potential difficulties in ensuring electromagnetic compatibility in other environments, due to conducted as well as radiated disturbances.
INSTALLATION
3
3.2 Installation specifications
The following precautions must be taken to ensure reliable installation.
Make sure that there is adequate space to the sides.
The device must not be heated by radiated heat (e.g. exposure to the sun) to an electronics housing surface temperature above the maximum permissible ambient temperature. If it is necessary to prevent damage from heat sources, a heat protection (e.g. sun shade) has to be installed.
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat exchanger.
Do not expose the signal converter to intense vibrations. The measuring devices are tested for a vibration level as described in the chapter "Technical data".
3.3 Mounting of the compact version
Turning the housing of the compact version is not permitted.
The signal converter is mounted directly on the flow sensor. For installation of the flowmeter, please observe the instructions in the supplied product documentation for the flow sensor.
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
21
3
INSTALLATION
3.4 Mounting the field housing, remote version
Remarks for sanitary applications
To prevent contamination and dirt deposits behind the mounting plate, a cover plug must be installed between the wall and the mounting plate.
Pipe mounting is not suitable for sanitary applications!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools in compliance with the applicable occupational health and safety directives.
3.4.1 Pipe mounting
MFC 400
Figure 3-1: Pipe mounting of the field housing
1 Fix the signal converter to the pipe. 2 Fasten the signal converter using standard U-bolts and washers. 3 Tighten the nuts.
22
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
3.4.2 Wall mounting
Figure 3-2: Wall mounting of the field housing
INSTALLATION
3
1 Prepare the holes with the aid of the mounting plate. For further information refer to
plate of field housing
on page 20.
2 Fasten the mounting plate securely to the wall. 3 Screw the signal converter to the mounting plate with the nuts and washers.
Figure 3-3: Mounting multiple devices next to each other
a 600 mm / 23.6" b 250 mm / 9.8"
Mounting
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
23
4
ELECTRICAL CONNECTIONS
4.1 Safety instructions
All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate!
Observe the national regulations for electrical installations!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
Observe without fail the local occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists.
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
4.2 Connection diagram
MFC 400
The device must be grounded in accordance with regulations in order to protect personnel against electric shocks.
Figure 4-1: Connection diagram
1 Terminal compartment for signal converter 2 Terminal compartment for flow sensor 3 Connect shielding to spring terminal (drain wire and overall shield)
24
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
Cable Connection terminal
Cable pair Colour
1 yellow X1 SA+
1 black X1 SA-
2 green X1 SB+
2 black X1 SB-
3 blue X2 T1
3 black X2 T2
4 red X2 T3
4 black X2 T4
5 white X3 DR+
5 black X3 DR-
Table 4-1: Colour coding of cables
4.3 Grounding the flow sensor
ELECTRICAL CONNECTIONS
4
There should be no difference in potential between the flow sensor and the housing or protective earth of the signal converter!
The flow sensor must be properly grounded.
The grounding cable should not transmit any interference voltages.
Do not use the grounding cable to connect more than one device to ground.
The flow sensors are connected to ground by means of a functional grounding conductor FE.
In hazardous areas, grounding is used at the same time for equipotential bonding. Additional
grounding instructions are provided in the supplementary "Ex documentation", which are only supplied together with hazardous area equipment.
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
25
4
ELECTRICAL CONNECTIONS
4.4 Connecting power - all housing variants
The device must be grounded in accordance with regulations in order to protect personnel against electric shocks.
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
The protection category depends on the housing versions (IP65...67 or NEMA4/4X/6).
The housings of the devices, which are designed to protect the electronic equipment from
dust and moisture, should be kept well closed at all times. Creepage distances and clearances are dimensioned to VDE 0110 and IEC 60664 for pollution severity 2. Supply circuits are designed for overvoltage category III and the output circuits for overvoltage category II.
Fuse protection (I
breaker) to isolate the signal converter must be provided close to the device. The separator must be marked as the separator for this device.
100...230 VAC (tolerance range: -15% / +10%)
Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
The protective ground terminal PE
clamp terminal in the terminal compartment of the signal converter
16 A) for the infeed power circuit, as well as a separator (switch, circuit
N
PE of the power supply must be connected to the separate U-
PEPE
MFC 400
240 VAC + 5% is included in the tolerance range.
24 VDC (tolerance range: -55% / +30%)
Note the data on the nameplate!
For measurement process reasons, a functional ground FE
separate U-clamp terminal in the terminal compartment of the signal converter.
When connecting to functional extra-low voltages, provide a facility for protective separation
(PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 60364 / IEC 61140 or relevant national regulations).
FE must be connected to the
FEFE
For 24 VDC, 12 VDC - 10% is included in the tolerance range.
Figure 4-2: Power supply connection
1 100...230 VAC (-15% / +10%), 22 VA 2 24 VDC (-55% / +30%), 12 W
26
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
4.5 Inputs and outputs, overview
4.5.1 Combinations of the inputs/outputs (I/Os)
This signal converter is available with various input/output combinations.
Modular version
Depending on the task, the device can be configured with various output modules.
Ex i version
Depending on the task, the device can be configured with various output modules.
Current outputs can be active or passive.
Optionally available also with Foundation Fieldbus and Profibus PA.
Bus systems
The device allows intrinsically safe and non intrinsically safe bus interfaces in combination
with additional modules.
For connection and operation of bus systems, note the supplementary instructions.
ELECTRICAL CONNECTIONS
4
Ex option
For hazardous areas, all of the input/output variants for the housing designs C and F can be
delivered with terminal compartment in Ex d (pressure-resistant casing) or Ex e (increased safety).
For connection and operation of Ex devices, note the supplementary instructions.
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
27
4
ELECTRICAL CONNECTIONS
4.5.2 Description of the CG number
Figure 4-3: Marking (CG number) of the electronics module and input/output variants
1 ID number: 3 2 ID number: 0 = standard 3 Power supply option 4 Display 5 Input/output version (I/O) 6 1st optional module for connection terminal A 7 2nd optional module for connection terminal B
The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal connections. Please refer to the following examples.
MFC 400
CG430114AC 100...230 VAC & standard display; modular I/O: Ia & PN/SN and optional module Ia/SN & Pa/S
CG43081200 24 VDC & standard display; Ex i I/O: Ia & Pa/Sa and optional module Ia & PN/SN/C
Table 4-2: Examples for CG number
N
Abbreviation Identifier for CG number Description
I
a
I
p
Pa / S
a
Pp / S
p
PN / S
N
C
a
C
p
C
N
- 8 No additional module installed
- 0 No further module possible
Table 4-3: Description of abbreviations and CG identifier for possible optional modules on terminals A and B
A Active current output
B Passive current output
C Active pulse output, frequency output, status output or limit
switch (changeable)
E Passive pulse output, frequency output, status output or limit
switch (changeable)
F Passive pulse output, frequency output, status output or limit
switch according to NAMUR (changeable)
G Active control input
K Passive control input
H Active control input acc. to NAMUR
Signal converter monitors cable breaks and short circuits according to EN 60947-5-6. Errors indicated on LC display. Error messages possible via status output.
a
28
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
4.5.3 Fixed, non-alterable input/output versions
This signal converter is available with various input/output combinations.
The grey boxes in the tables denote unassigned or unused connection terminals.
In the table, only the final digits of the CG no. are depicted.
CG no. Connection terminals
A+ A A- B B- C C- D D-
Ex i I/Os (option)
2 0 0
3 0 0
2 1 0 Ia active PN / SNNAMUR
Cp passive 1
3 1 0 Ia active PN / SNNAMUR
passive 1
C
p
2 2 0 Ip passive PN / SNNAMUR
Cp passive 1
3 2 0 Ip passive PN / SNNAMUR
passive 1
C
p
ELECTRICAL CONNECTIONS
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
PN / SN NAMUR 1
PN / SN NAMUR 1
PN / SN NAMUR 1
PN / SN NAMUR 1
PN / SNNAMUR 1
PN / SNNAMUR 1
4
PROFIBUS PA (Ex i) (option)
D 0 0 PA+ PA- PA+ PA-
FISCO Device FISCO Device
D 1 0 Ia active PN / SNNAMUR
passive 1
C
p
D 2 0 Ip passive PN / SNNAMUR
passive 1
C
p
PA+ PA- PA+ PA-
FISCO Device FISCO Device
PA+ PA- PA+ PA-
FISCO Device FISCO Device
FOUNDATION Fieldbus (Ex i) (option)
E 0 0 V/D+ V/D- V/D+ V/D-
FISCO Device FISCO Device
E 1 0 Ia active PN / SNNAMUR
passive 1
C
p
E 2 0 Ip passive PN / SNNAMUR
Cp passive 1
V/D+ V/D- V/D+ V/D-
FISCO Device FISCO Device
V/D+ V/D- V/D+ V/D-
FISCO Device FISCO Device
PROFINET IO (option)
N 0 0 RX+ RX- TX+ TX- TX+ TX- RX+ RX-
Port 2 Port 1
Table 4-4: Electrical connection of fixed, non-alterable input/output versions
1 Changeable
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
29
4
ELECTRICAL CONNECTIONS
MFC 400
4.5.4 Alterable input/output versions
This signal converter is available with various input/output combinations.
The grey boxes in the tables denote unassigned or unused connection terminals.
In the table, only the final digits of the CG no. are depicted.
Term. = (connection) terminal
CG no. Connection terminals
A+ A A- B B- C C- D D-
Modular I/Os (option)
4 _ _ max. 2 optional modules for term. A + B
I + HART® active/passive 1
PROFIBUS PA (option)
D _ _ max. 2 optional modules for term. A + B PA+ (2) PA- (2) PA+ (1) PA- (1)
P/S active/passive/ NAMUR 1
FOUNDATION Fieldbus (option)
E _ _ max. 2 optional modules for term. A + B V/D+ (2) V/D- (2) V/D+ (1) V/D- (1)
PROFIBUS DP (option)
F _ 0 1 optional module for
term. A
Termina­tion P
RxD/TxD­P(2)
RxD/TxD­N(2)
Termina­tion N
RxD/TxD­P(1)
RxD/TxD­N(1)
Modbus (option)
G _ _ 2 max. 2 optional modules for term. A + B Common Sign. B
(D1)
H _ _ 3 max. 2 optional modules for term. A + B Common Sign. B
(D1)
Table 4-5: Electrical connection of alterable input/output versions
1 Software configurable 2 Not activated bus terminator 3 Activated bus terminator
Sign. A (D0)
Sign. A (D0)
30
www.krohne.com 11/2017 - 4002075706 - TD MFC 400 R06 en
MFC 400
NOTES
5
www.krohne.com11/2017 - 4002075706 - TD MFC 400 R06 en
31
K
K
K
KROHNE – Process instrumentation and measurement solutions
Flow
Level
Temperature
Pressure
Process Analysis
Services
© KROHNE 11/2017 - 4002075706 - TD MFC 400 R06 en - Subject to change without notice.
Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.: +49 203 301 0 Fax: +49 203 301 10389 info@krohne.com
The current list of all KROHNE contacts and addresses can be found at: www.krohne.com
Loading...