All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of KROHNE Messtechnik GmbH.
9.11 Appendix A: HART® menu tree for Basic-DD ............................................................ 158
9.11.1 Overview Basic-DD menu tree (positions in menu tree).................................................. 159
9.11.2 Basic-DD menu tree (details for settings)........................................................................ 160
9.12 Appendix B: HART® menu tree for AMS .................................................................... 164
9.12.1 Overview AMS menu tree (positions in menu tree) .......................................................... 165
9.12.2 AMS menu tree (details for settings)................................................................................ 166
9.13 Appendix C: HART® menu tree for PDM.................................................................... 171
9.13.1 Overview PDM menu tree (positions in menu tree).......................................................... 171
9.13.2 PDM menu tree (details for settings) ............................................................................... 174
6
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 7
MFC 300
1.1 Software History
The "Electronic Revision" (ER) is consulted to document the revision status of electronic
equipment according to NE 53 for all GDC devices. It is easy to see from the ER whether
troubleshooting or larger changes in the electronic equipment have taken place and how that
has affected the compatibility.
Changes and effect on compatibility
1Downwards compatible changes and fault repair with no effect on operation (e.g. spelling
mistakes on display)
2-_Downwards compatible hardware and/or software change of interfaces:
H
HART
PPROFIBUS
FFoundation Fieldbus
MModbus
Xall interfaces
3-_Downwards compatible hardware and/or software change of inputs and outputs:
ICurrent output
F, PFrequency / pulse output
SStatus output
Ccontrol input
CICurrent input
Xall inputs and outputs
4Downwards compatible changes with new functions
5Incompatible changes, i.e. electronic equipment must be changed.
SAFETY INSTRUCTIONS 1
®
INFORMATION!
In the table below, "x" is a placeholder for possible multi-digit alphanumeric combinations,
depending on the available version.
Release dateElectronic RevisionChanges and
Documentation
compatibility
2006-11-06ER 3.1.0x
(SW.REV. 3.10 (2.21))
2006-12-12ER 3.1.1x
(SW.REV. 3.11 (2.21))
2007-02-07ER 3.1.2x
(SW.REV. 3.11 (2.21))
2007-03-12ER 3.1.3x
(SW.REV. 3.11 (2.21))
2007-06-27ER 3.1.4x
(SW.REV. 3.11 (2.22))
2007-04-02ER 3.2.0x
(SW.REV. 3.20 (2.22))
2007-05-04ER 3.2.1x
(SW.REV. 3.20 (2.22))
2007-05-25ER 3.2.2x
(SW.REV. 3.20 (2.22))
--
1; 2-P; 2-MMA MFC 300 R02
1; 2-MMA MFC 300 R02
1; 2-HMA MFC 300 R02
1MA MFC 300 R02
1; 2-X; 2-P; 2-FMA MFC 300 R02
1MA MFC 300 R02
1; 3-IMA MFC 300 R02
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
7
Page 8
1 SAFETY INSTRUCTIONS
MFC 300
Release dateElectronic RevisionChanges and
compatibility
2007-06-27ER 3.2.3x
(SW.REV. 3.20 (2.22))
2007-07-16ER 3.2.4x
(SW.REV. 3.20 (2.22))
2008-08-01ER 3.3.0x
(SW.REV. 3.30 (3.02))
2008-08-25ER 3.3.1x
(SW.REV. 3.30 (3.03))
2008-10-23ER 3.3.2x
(SW.REV. 3.30 (3.03))
2009-05-13ER 3.3.3x
(SW.REV. 3.30 (3.03))
2009-10-29ER 3.3.4x
(SW.REV. 3.30 (3.03))
2009-12-07ER 3.3.5x
(SW.REV. 3.30 (3.03))
2011-03ER 3.3.6x
(SW.REV. 3.40 (3.04))
2011-06ER 3.3.7x
(SW.REV. 3.40 (3.04))
1MA MFC 300 R02
1; 2-FMA MFC 300 R02
1; 2-X; 4MA MFC 300 R02
1MA MFC 300 R02
2-MMA MFC 300 R02
2-FMA MFC 300 R02
1MA MFC 300 R02
2-F; 2-XMA MFC 300 R02
1; 2-FMA MFC 300 R02
1MA MFC 300 R03
Documentation
8
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 9
MFC 300
1.2 Intended Use
The mass flowmeters are designed exclusively to directly measure mass flow rates, product
density and temperature as well to indirectly measure parameters such as the total volume and
concentration of dissolved substances as well as the volume flow rate.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
If the device is not used according to the operating conditions (refer to chapter "Technical data"),
the intended protection could be affected.
1.3 Certifications
CE marking
SAFETY INSTRUCTIONS 1
The device fulfils the statutory requirements of the following EC directives:
• Low Voltage Directive 2006/95/EC
• EMC Directive 2004/108/EC
as well as
• EN 61010
• EMC specification acc. to EN 61326/A1
• NAMUR recommendations NE 21 and NE 43
The manufacturer certifies successful testing of the product by applying the CE marking.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
9
Page 10
1 SAFETY INSTRUCTIONS
1.4 Safety instructions from the manufacturer
1.4.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no
guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.
MFC 300
We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.
1.4.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.
10
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 11
MFC 300
1.4.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper
installation and operation of the devices (systems) will cause the warranty to be void. The
respective "Standard Terms and Conditions" which form the basis for the sales contract shall
also apply.
1.4.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the
information in this document and observe applicable national standards, safety requirements
and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of underneath icons.
SAFETY INSTRUCTIONS 1
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
11
Page 12
1 SAFETY INSTRUCTIONS
1.4.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This information refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to
serious health problems and even death. There is also the risk of seriously damaging the device
or parts of the operator's plant.
MFC 300
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
• HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the
specified sequence.
iRESULT
RESULT
RESULTRESULT
This symbol refers to all important consequences of the previous actions.
1.5 Safety instructions for the operator
12
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and
maintained by properly trained and authorized personnel.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 13
MFC 300
2.1 Scope of delivery
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
DEVICE DESCRIPTION 2
Figure 2-1: Scope of delivery
1 Device in the version as ordered
2 Documentation (calibration report, factory and material certification if ordered, CD-Rom with product documentation
for measuring sensor and signal converter)
3 Signal cable (only for remote version)
Signal converter / measuring sensor combination possibilities
Measuring sensorSignal converter MFC 300
CompactRemote field
housing
OPTIMASS 1000OPTIMASS 1300 COPTIMASS 1300 FOPTIMASS 1300 WOPTIMASS 1300 R
OPTIMASS 2000OPTIMASS 2300 COPTIMASS 2300 FOPTIMASS 2300 WOPTIMASS 2300 R
OPTIMASS 3000OPTIMASS 3300 COPTIMASS 3300 FOPTIMASS 3300 WOPTIMASS 3300 R
OPTIMASS 7000OPTIMASS 7300 COPTIMASS 7300 FOPTIMASS 7300 WOPTIMASS 7300 R
OPTIMASS 8000OPTIMASS 8300 COPTIMASS 8300 FOPTIMASS 8300 WOPTIMASS 8300 R
Remote wallmounted housing
Remote rackmounted housing
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
13
Page 14
2 DEVICE DESCRIPTION
2.2 Device description
The mass flowmeters are designed exclusively to directly measure mass flow rates, product
density and temperature as well to indirectly measure parameters such as the total volume and
concentration of dissolved substances as well as the volume flow rate.
Your measuring device is supplied ready for operation. The factory settings for the operating
data have been made in accordance with your order specifications.
The following versions are available:
• Compact version (the signal converter is mounted directly on the measuring sensor)
• Remote version (electrical connection to the measuring sensor via field current and signal
cable)
MFC 300
Figure 2-2: Device versions
1 Compact version
2 Measuring sensor with connection box
3 Field housing
4 Wall-mounted housing
5 19" rack-mounted housing
14
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 15
MFC 300
2.2.1 Field housing
Figure 2-3: Construction of the field housing
1 Cover for electronics and display
2 Cover for power supply and inputs/outputs terminal compartment
3 Cover for measuring sensor terminal compartment with locking screw
4 Cable entry for measuring sensor signal cable
5 Cable entry for measuring sensor field current cable
6 Cable entry for power supply
7 Cable entry for inputs and outputs
8 Mounting plate for pipe and wall mounting
DEVICE DESCRIPTION 2
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
15
Page 16
2 DEVICE DESCRIPTION
2.2.2 Wall-mounted housing
Figure 2-4: Construction of wall-mounted housing
1 Cover for terminal compartments
2 Terminal compartment for measuring sensor
3 Terminal compartment for inputs and outputs
4 Terminal compartment for power supply with safety cover (shock-hazard protection)
5 Cable entry for measuring sensor cable
6 Cable entry for inputs and outputs
7 Cable entry for inputs and outputs
8 Cable entry for power supply
MFC 300
1 Turn lock to the right and open the cover.
16
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 17
MFC 300
2.3 Nameplates
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
2.3.1 Compact version (example)
DEVICE DESCRIPTION 2
Figure 2-5: Example of nameplate for the compact version
1 Approvals-related information: Ex approval, EC type test certificate, hygienic approvals, etc.
2 Approvals-related thresholds
3 Additional information on documentation, calibration and patents
4 Protection category
5 Approvals-related pressure and temperature thresholds
6 Electrical connection data
7 Software and hardware revision (Electronics Revision), CG number, order number for signal converter and measuring
sensor
8 Manufacturing date, serial number and TAG number
9 Product description
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
17
Page 18
2 DEVICE DESCRIPTION
2.3.2 Remote version (example)
MFC 300
Figure 2-6: Example of a nameplate for the remote version
1 Product designation, manufacturing date, serial number and TAG number
2 Software and hardware revision (Electronics Revision), CG number, order number for signal converter and measuring
sensor
3 Electrical connection data
4 Additional information on documentation, calibration and patents
18
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 19
MFC 300
DEVICE DESCRIPTION 2
2.3.3 Electrical connection data of inputs/outputs (example of basic version)
Figure 2-7: Example of a nameplate for electrical connection data of inputs and outputs
1 Power supply (AC: L and N; DC: L+ and L-; PE for ≥ 24 VAC; FE for ≤ 24 VAC and DC)
2 Connection data of connection terminal D/D-
3 Connection data of connection terminal C/C-
4 Connection data of connection terminal B/B-
5 Connection data of connection terminal A/A-; A+ only operable in the basic version
• A = active mode; the signal converter supplies the power for connection of the subsequent
devices
• P = passive mode; external power supply required for operation of the subsequent devices
• N/C = connection terminals not connected
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
19
Page 20
3 INSTALLATION
3.1 Notes on installation
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
3.2 Storage
• Store the device in a dry, dust-free location.
• Avoid continuous direct sunlight.
• Store the device in its original packing.
• Storage temperature: -50...+70°C / -58...+158°F
MFC 300
3.3 Transport
Signal converter
• No special requirements.
Compact version
• Do not lift the device by the signal converter housing.
• Do not use lifting chains.
• To transport flange devices, use lifting straps. Wrap these around both process connections.
3.4 Installation specifications
INFORMATION!
The following precautions must be taken to ensure reliable installation.
•
Make sure that there is adequate space to the sides.
•
Protect the signal converter from direct sunlight and install a sun shade if necessary.
•
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat
exchanger.
•
Do not expose the signal converter to intense vibration. The flowmeters are tested for a
vibration level in accordance with IEC 68-2-3.
20
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 21
MFC 300
3.5 Mounting of the compact version
INFORMATION!
The signal converter is mounted directly on the measuring sensor. For installation of the
flowmeter, please observe the instructions in the supplied product documentation for the
measuring sensor.
3.6 Mounting the field housing, remote version
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
3.6.1 Pipe mounting
INSTALLATION 3
Figure 3-1: Pipe mounting of the field housing
1 Fix the signal converter to the pipe.
2 Fasten the signal converter using standard U-bolts and washers.
3 Tighten the nuts.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
21
Page 22
3 INSTALLATION
3.6.2 Wall mounting
Figure 3-2: Wall mounting of the field housing
MFC 300
1 Prepare the holes with the aid of the mounting plate. For further information refer to
plate, field housing
on page 146.
Mounting
2 Use the mounting material and tools in compliance with the applicable occupational health
and safety directives.
3 Fasten the housing securely to the wall.
Mounting multiple devices next to each other
a ≥ 600 mm / 23.6"
b ≥ 250 mm / 9.8"
22
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 23
MFC 300
3.6.3 Turning the display of the field housing version
INSTALLATION 3
Figure 3-3: Turning the display of the field housing version
The display of the field housing version can be turned in 90° increments.
1 Unscrew the cover from the display and operation control unit.
2 Using a suitable tool, pull out the two metal puller devices to the left and right of the display.
3 Pull out the display between the two metal puller devices and rotate it to the required position.
4 Slide the display and then the metal puller devices back into the housing.
5 Re-fit the cover and tighten it by hand.
CAUTION!
The ribbon cable of the display must not be folded or twisted repeatedly.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
23
Page 24
3 INSTALLATION
3.7 Mounting the wall-mounted housing, remote version
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
3.7.1 Pipe mounting
MFC 300
Figure 3-4: Pipe mounting of the wall-mounted housing
1 Fasten the mounting plate to the pipe with standard U-bolts, washers and fastening nuts.
2 Screw the signal converter to the mounting plate with the nuts and washers.
24
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 25
MFC 300
3.7.2 Wall mounting
Figure 3-5: Wall mounting of the wall-mounted housing
INSTALLATION 3
1 Prepare the holes with the aid of the mounting plate. For further information refer to
plate, wall-mounted housing
2 Fasten the mounting plate securely to the wall.
3 Screw the signal converter to the mounting plate with the nuts and washers.
on page 146.
Mounting multiple devices next to each other
a ≥ 240 mm / 9.4"
Mounting
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
25
Page 26
4 ELECTRICAL CONNECTIONS
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
DANGER!
Observe the national regulations for electrical installations!
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
MFC 300
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
4.2 Important notes on electrical connection
DANGER!
Electrical connection is carried out in conformity with the VDE 0100 directive "Regulations for
electrical power installations with line voltages up to 1000 V" or equivalent national regulations.
CAUTION!
•
Use suitable cable entries for the various electrical cables.
•
The measuring sensor and signal converter have been configured together at the factory. For
this reason, please connect the devices in pairs.
26
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 27
MFC 300
ELECTRICAL CONNECTIONS 4
4.3 Requirements for signal cables provided by the customer
INFORMATION!
If the signal cable was not ordered, it is to be provided by the customer. The following
requirements regarding the electrical values of the signal cable must be observed:
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
27
Page 28
4 ELECTRICAL CONNECTIONS
4.4 Connecting the signal cables
DANGER!
Cables may only be connected when the power is switched off.
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
MFC 300
28
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 29
MFC 300
4.4.1 Connection of signal cable, field housing
Figure 4-1: Electrical connection of the signal cables, field housing
a = white
b = green
c = black
d = red
ELECTRICAL CONNECTIONS 4
1 Remove the locking screw and open the housing cover.
2 Pass the prepared signal cable through the cable entry.
3 Secure the signal cable using the clip.
4 Connect the electrical conductors as shown. The shielding is connected to terminal S.
5 Close the housing cover and secure it with the locking screw.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
29
Page 30
4 ELECTRICAL CONNECTIONS
4.4.2 Connection of signal cable, wall-mounted housing
Figure 4-2: Electrical connection of signal cable, wall-mounted housing
a = white
b = green
c = black
d = red
MFC 300
1 Open the housing cover.
2 Open the cover and guide the prepared signal cable through the cable entry.
3 Connect the twisted shielding to terminal S.
4 Connect the electrical conductors to terminals +, -, A, B.
5 Press the plug into the connector.
6 Close the cover and the housing cover.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
30
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 31
MFC 300
ELECTRICAL CONNECTIONS 4
4.4.3 Connection of signal cable, 19" rack-mounted housing
Figure 4-3: Electrical connection of signal cable, 19" rack-mounted housing
• Connect the conductor to the multipolar plug according to the illustration.
• The shielding of the signal cable can be connected to 22z, 22d, 24z or 24d.
• Press the plug into the connector.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
31
Page 32
4 ELECTRICAL CONNECTIONS
4.4.4 Connection box of measuring sensor
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
MFC 300
Figure 4-4: Electrical connection to connection box of the sensor
a = white
b = green
c = black
d = red
1 Remove the locking screw and open the housing cover.
2 Pass the prepared signal cable through the cable entry.
3 Secure the signal cable using the spring terminal. The shielding MUST
MUST also be connected to
MUSTMUST
the spring terminal.
4 Connect the electrical conductors as shown.
5 Close the housing cover and secure it with the locking screw.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
32
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 33
MFC 300
4.4.5 Connection diagram
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
Wall housing
ELECTRICAL CONNECTIONS 4
Figure 4-5: Connection diagram for remote versions, wall housing
1 Terminal compartment for signal converter
2 Terminal compartment for measuring sensor
3 Connect shielding to spring terminal
4 Connect shielding to terminal S
5 Functional ground
Field housing
Figure 4-6: Connection diagram for remote versions, field housing
1 Terminal compartment for signal converter
2 Terminal compartment for measuring sensor
3 Connect shielding to spring terminal
4 Connect shielding to terminal S
5 Functional ground
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
33
Page 34
4 ELECTRICAL CONNECTIONS
19" rack-mounted housing
Figure 4-7: Connection diagram for remote versions, 19" rack-mounted housing
1 Terminal compartment for signal converter
2 Terminal compartment for measuring sensor
3 Connect shielding to spring terminal
4 Connect shielding to terminal S
(The shielding can be connected to 22z, 22d, 24z or 24d)
5 Functional ground
MFC 300
4.5 Grounding the measuring sensor
DANGER!
There should be no difference in potential between the measuring sensor and the housing or
protective earth of the signal converter!
• The measuring sensor must be properly grounded.
• The grounding cable should not transmit any interference voltages.
• Do not use the grounding cable to connect more than one device to ground.
• The measuring sensors are connected to ground by means of a functional grounding
conductor FE.
• In hazardous areas, grounding is used at the same time for equipotential bonding. Additional
grounding instructions are provided in the separate "Ex documentation", which are only
supplied together with hazardous area equipment.
34
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 35
MFC 300
ELECTRICAL CONNECTIONS 4
4.6 Connecting power, all housing variants
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
• The protection category depends on the housing versions (IP65...67 to IEC 529 / EN 60529 or
NEMA4/4X/6).
• The housings of the devices, which are designed to protect the electronic equipment from
dust and moisture, should be kept well closed at all times. Creepage distances and
clearances are dimensioned to VDE 0110 and IEC 664 for pollution severity 2. Supply circuits
are designed for overvoltage category III and the output circuits for overvoltage category II.
• Fuse protection (I
breaker) to isolate the signal converter must be provided close to the device. The separator
must be marked as the separator for this device.
≤ 16 A) for the infeed power circuit, as well as a separator (switch, circuit
N
100...230 VAC (tolerance range: -15% / +10%)
• Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
• The protective ground terminal PE
clamp terminal in the terminal compartment of the signal converter
For the 19" rack-mounted housing please refer to the connection diagrams.
PE of the power supply must be connected to the separate U-
• For measurement process reasons, a functional ground FE
separate U-clamp terminal in the terminal compartment of the signal converter.
• When connecting to functional extra-low voltages, provide a facility for protective separation
(PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).
FE must be connected to the
FEFE
INFORMATION!
For 24 VDC, 12 VDC-10% is included in the tolerance range.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
35
Page 36
4 ELECTRICAL CONNECTIONS
Power supply connection (excluding 19" rack-mounted housing)
1 100...230 VAC (-15% / +10%), 22 VA
2 24 VDC (-55% / +30%), 12 W
3 24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 22 VA or 12 W
Power supply connection for 19" rack-mounted housing (28 TE)
MFC 300
36
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 37
MFC 300
4.7 Inputs and outputs, overview
4.7.1 Combinations of the inputs/outputs (I/Os)
This signal converter is available with various input/output combinations.
Basic version
• Has 1 current output, 1 pulse output and 2 status outputs / limit switches.
• The pulse output can be set as status output/limit switch and one of the status outputs as a
control input.
Ex i version
• Depending on the task, the device can be configured with various output modules.
• Current outputs can be active or passive.
• Optionally available also with Foundation Fieldbus and Profibus PA
Modular version
• Depending on the task, the device can be configured with various output modules.
ELECTRICAL CONNECTIONS 4
Bus systems
• The device allows intrinsically safe and non intrinsically safe bus interfaces in combination
with additional modules.
• For connection and operation of bus systems, please note the separate documentation.
Ex option
• For hazardous areas, all of the input/output variants for the housing designs C and F with
terminal compartment in the Ex d (pressure-resistant casing) or Ex e (increased safety)
versions can be delivered.
• Please refer to the separate instructions for connection and operation of the Ex-devices.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
37
Page 38
4 ELECTRICAL CONNECTIONS
4.7.2 Description of the CG number
Figure 4-8: Marking (CG number) of the electronics module and input/output variants
1 ID number: 2
2 ID number: 0 = standard; 9 = special
3 Power supply option
4 Display (language versions)
5 Input/output version (I/O)
6 1st optional module for connection terminal A
7 2nd optional module for connection terminal B
The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal
connections. Please refer to the following examples.
Examples for CG number
MFC 300
CG 320 11 100 100...230 VAC & standard display; basic I/O: Ia or Ip & Sp/Cp & Sp & Pp/S
p
CG 320 11 7FK100...230 VAC & standard display; modular I/O: Ia & PN/SN and optional module PN/SN & C
CG 320 81 4EB24 VDC & standard display; modular I/O: Ia & Pa/Sa and optional module Pp/Sp & I
p
Description of abbreviations and CG identifier for possible optional modules
on terminals A and B
AbbreviationIdentifier for CG No.Description
I
a
I
p
Pa / S
a
Pp / S
p
PN / S
N
C
a
C
p
C
N
IIn
a
IIn
p
-8No additional module installed
-0No further module possible
AActive current output
BPassive current output
CActive pulse output, frequency output, status output or limit switch
(changeable)
EPassive pulse output, frequency output, status output or limit switch
(changeable)
FPassive pulse output, frequency output, status output or limit switch acc.
to NAMUR (changeable)
GActive control input
KPassive control input
HActive control input to NAMUR
Signal converter monitors cable breaks and short circuits acc. to
EN 60947-5-6. Errors indicated on LC display. Error messages possible
via status output.
PActive current input
RPassive current input
N
38
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 39
MFC 300
4.7.3 Fixed, non-alterable input/output versions
This signal converter is available with various input/output combinations.
• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Connection terminal A+ is only operable in the basic input/output version.
CG no.Connection terminals
A+AA-BB-CC-DD-
Basic I/Os (standard)
1 0 0
Ia + HART® active 1
Ip + HART® passive 1
Ex i IOs (option)
2 0 0
3 0 0
2 1 0Ia activePN / SNNAMUR
3 1 0Ia activePN / SNNAMUR
2 2 0Ip passivePN / SNNAMUR
3 2 0Ip passivePN / SNNAMUR
Sp / Cp passive 2Sp passivePp / Sp passive 2
passive 2
C
p
Cp passive 2
passive 2
C
p
Cp passive 2
ELECTRICAL CONNECTIONS 4
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SNNAMUR 2
PN / SNNAMUR 2
PROFIBUS PA (Ex i) (option)
D 0 0PA+PA-PA+PA-
FISCO DeviceFISCO Device
D 1 0Ia activePN / SNNAMUR
passive 2
C
p
D 2 0Ip passivePN / SNNAMUR
passive 2
C
p
PA+PA-PA+PA-
FISCO DeviceFISCO Device
PA+PA-PA+PA-
FISCO DeviceFISCO Device
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
39
Page 40
4 ELECTRICAL CONNECTIONS
FOUNDATION Fieldbus (Ex i) (option)
E 0 0V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
E 1 0Ia activePN / SNNAMUR
Cp passive 2
E 2 0Ip passivePN / SNNAMUR
Cp passive 2
1 function changed by reconnecting
2 changeable
V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
MFC 300
40
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 41
MFC 300
4.7.4 Alterable input/output versions
This signal converter is available with various input/output combinations.
• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Term. = (connection) terminal
CG no.Connection terminals
A+AA-BB-CC-DD-
Modular IOs (option)
4 _ _max. 2 optional modules for term. A + B
8 _ _max. 2 optional modules for term. A + B
6 _ _max. 2 optional modules for term. A + B
B _ _max. 2 optional modules for term. A + B
7 _ _max. 2 optional modules for term. A + B
C _ _max. 2 optional modules for term. A + B
ELECTRICAL CONNECTIONS 4
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Pa / Sa active 1
Pa / Sa active 1
Pp / Sp passive 1
Pp / Sp passive 1
PN / SN NAMUR 1
PN / SN NAMUR 1
PROFIBUS PA (option)
D _ _max. 2 optional modules for term. A + BPA+ (2)PA- (2)PA+ (1)PA- (1)
FOUNDATION Fieldbus (option)
E _ _max. 2 optional modules for term. A + BV/D+ (2)V/D- (2)V/D+ (1)V/D- (1)
PROFIBUS DP (option)
F _ 01 optional module for
term. A
Terminati
on P
RxD/TxDP(2)
RxD/TxDN(2)
Terminati
on N
RxD/TxDP(1)
RxD/TxDN(1)
Modbus (option)
G _ _ 2max. 2 optional modules for term. A + BCommonSign. B
(D1)
H _ _ 3max. 2 optional modules for term. A + BCommonSign. B
(D1)
1 changeable
2 not activated bus terminator
3 activated bus terminator
Sign. A
(D0)
Sign. A
(D0)
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
41
Page 42
4 ELECTRICAL CONNECTIONS
4.8 Description of the inputs and outputs
4.8.1 Current output
INFORMATION!
The current outputs must be connected depending on the version! Which I/O versions and
inputs/outputs are installed in your signal converter are indicated on the sticker in the cover of
the terminal compartment.
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power U
• Active mode: load impedance R
R
≤ 450 Ω at I ≤ 22 mA for Ex i outputs
L
• Self-monitoring: interruption or load impedance too high in the current output loop
• Error message possible via status output, error indication on LC display.
• Current value error detection can be adjusted.
• Automatic range conversion via threshold or control input. The setting range for the
threshold is between 5 and 80% of Q
smaller to larger range of 1:20 to 1:1.25).
Signaling of the active range possible via a status output (adjustable).
• Forward / reverse flow measurement (F/R mode) is possible.
≤ 32 VDC at I ≤ 22 mA
ext
≤ 1kΩ at I ≤ 22 mA;
L
100%
MFC 300
, ± 0...5% hysteresis (corresponding ratio from
INFORMATION!
For further information refer to Connection diagrams of inputs and outputs on page 49
Technical data on page 134
to
.
and refer
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
42
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 43
MFC 300
4.8.2 Pulse and frequency output
INFORMATION!
Depending on the version, the pulse and frequency outputs must be connected passively or
actively or according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are
installed in your signal converter are indicated on the sticker in the cover of the terminal
compartment.
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
I ≤ 20 mA at f ≤ 10 kHz (override up to f
I ≤ 100 mA at f ≤ 100 Hz
• Active mode:
Use of the internal power supply: U
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 20 mA at f ≤ 100 Hz
• NAMUR mode: passive in accordance with EN 60947-5-6, f ≤ 10 kHz,
over range up to f
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q
fixed (pulse width adjustable as required from 0.05 ms...2 s)
• Forward / reverse flow measurement (F/R mode) is possible.
• All pulse and frequency outputs can also be used as a status output / limit switch.
max
≤ 12 kHz
≤ 32 VDC
ext
max
=24VDC
nom
ELECTRICAL CONNECTIONS 4
≤ 12 kHz)
≤ 12 kHz)
max
);
100%
) or
100%
CAUTION!
At frequencies above 100 Hz, shielded cables must be used to prevent radio interference.
INFORMATION!
For further information refer to Connection diagrams of inputs and outputs on page 49
Technical data on page 134
to
.
and refer
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
43
Page 44
4 ELECTRICAL CONNECTIONS
4.8.3 Status output and limit switch
INFORMATION!
Depending on the version, the status outputs and limit switches must be connected passively or
actively or according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are
installed in your signal converter are indicated on the sticker in the cover of the terminal
compartment.
• The status outputs / limit switches are electrically isolated from each other and from all
other circuits.
• The output stages of the status outputs/limit switches during simple active or passive
operation behave like relay contacts and can be connected with any polarity.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
≤ 32 VDC; I ≤ 100 mA
U
ext
• Active mode: use of the internal power supply:
=24VDC; I ≤ 20 mA
U
nom
• NAMUR mode: passive in accordance with EN 60947-5-6
• For information on the adjustable operating states refer to
Function tables
MFC 300
on page 79.
INFORMATION!
For further information refer to Connection diagrams of inputs and outputs on page 49
Technical data on page 134
to
.
and refer
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
44
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 45
MFC 300
4.8.4 Control input
INFORMATION!
Depending on the version, the control inputs must be connected passively or actively or
according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are installed in your
signal converter are indicated on the sticker in the cover of the terminal compartment.
• All control inputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
≤ 32 VDC
U
ext
• Active mode: use of the internal power supply:
U
nom
• NAMUR mode: in accordance with EN 60947-5-6
(Active control input to NAMUR EN 60947-5-6: signal converter monitors cable breaks and
short circuits acc. to EN 60947-5-6. Errors indicated on LC display. Error messages possible
via status output.
• For information on the adjustable operating states refer to
=24VDC
ELECTRICAL CONNECTIONS 4
Function tables
on page 79.
INFORMATION!
For further information refer to Connection diagrams of inputs and outputs on page 49
Technical data on page 134
to
.
and refer
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
45
Page 46
4 ELECTRICAL CONNECTIONS
4.9 Electrical connection of the inputs and outputs
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
4.9.1 Field housing, electrical connection of the inputs and outputs
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
INFORMATION!
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
MFC 300
Figure 4-9: Terminal compartment for inputs and outputs in field housing
1 Open the housing cover.
2 Push the prepared cable through the cable entry and connect the necessary conductors.
3 Connect the shield if necessary.
4 Close the touch guard.
5 Close the housing cover.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
46
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 47
MFC 300
ELECTRICAL CONNECTIONS 4
4.9.2 Wall-mounted housing, electrical connection of the inputs and outputs
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
INFORMATION!
Use shielded cables for frequencies above 100 Hz. The electrical connection of the shielding
must take place using 6.3 mm / 0.25" blade receptacles (insulation as per DIN 46 245) in the I/O
terminal compartment.
Figure 4-10: Terminal compartment for inputs and outputs in wall-mounted housing
1 Open the housing cover.
2 Push the cables through the cable entry and connect them to the supplied connector plugs 3.
3 Connect the shield if necessary.
4 Route the connector plugs with the clamped conductors into the sockets provided for that pur-
pose.
5 Close the housing cover.
INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
47
Page 48
4 ELECTRICAL CONNECTIONS
MFC 300
4.9.3 19" rack-mounted housing (28 TE), electrical connection of the inputs and outputs
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
• For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
• Terminal A+ is only operable in the basic version.
Figure 4-11: Terminal compartment for inputs and outputs in rack-mounted housing
1 Shielding
• Connect the conductor to the multipolar plug according to the illustration.
• The signal cable shield is connected to the Pin S.
• Press the plug into the connector.
4.9.4 Laying electrical cables correctly
Figure 4-12: Protect housing from dust and water
1 Lay the cable in a loop just before the housing.
2 Tighten the screw connection of the cable entry securely.
3 Never mount the housing with the cable entries facing upwards.
4 Seal cable entries that are not needed with a plug.
48
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 49
MFC 300
ELECTRICAL CONNECTIONS 4
4.10 Connection diagrams of inputs and outputs
4.10.1 Important notes
INFORMATION!
Depending on the version, the inputs/outputs must be connected passively or actively or acc. to
NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are installed in your signal
converter are indicated on the sticker in the cover of the terminal compartment.
• All groups are electrically isolated from each other and from all other input and output
circuits.
• Passive mode: An external power supply is necessary to operate (activation) the subsequent
devices (U
• Active mode: The signal converter supplies the power for operation (activation) of the
subsequent devices, observe max. operating data.
• Terminals that are not used should not have any conductive connection to other electrically
conductive parts.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
ext
).
Description of the used abbreviations
I
I
a
P
a
P
N
S
a
S
N
C
a
C
N
IInaIInpCurrent input active or passive
Current output active or passive
p
P
Pulse/frequency output active or passive
p
Pulse/frequency output passive acc. to NAMUR EN 60947-5-6
S
Status output/limit switch active or passive
p
Status output/limit switch passive acc. to NAMUR EN 60947-5-6
C
Control input active or passive
p
Control input active acc. to NAMUR EN 60947-5-6:
Signal converter monitors cable breaks and short circuits acc. to EN 60947-5-6. Errors
indicated on LC display. Error messages possible via status output.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
49
Page 50
4 ELECTRICAL CONNECTIONS
4.10.2 Description of the electrical symbols
mA meter
0...20 mA or 4...20 mA and other
RL is the internal resistance of the measuring point including the cable
resistance
DC voltage source (U
), external power supply, any connection polarity
ext
MFC 300
Table 4-1: Description of symbols
DC voltage source (U
connection diagrams
Internal DC voltage source
Controlled internal power source in the device
Electronic or electromagnetic counter
At frequencies above 100 Hz, shielded cables must be used to connect the
counters.
Ri Internal resistance of the counter
Button, NO contact or similar
), observe connection polarity according to
ext
50
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 51
MFC 300
4.10.3 Basic inputs/outputs
CAUTION!
Observe connection polarity.
Current output active (HART®), basic I/Os
• U
• I ≤ 22 mA
• R
= 24 VDC nominal
int, nom
≤ 1kΩ
L
ELECTRICAL CONNECTIONS 4
Figure 4-13: Current output active I
a
Current output passive (HART®), basic I/Os
• U
• U
• I ≤ 22 mA
• U
• R
Figure 4-14: Current output passive I
= 24 VDC nominal
int, nom
≤ 32 VDC
ext
≥ 1.8 V
0
≤ (U
L
ext-U0
)/I
max
p
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
51
Page 52
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
Wall-mounted version: Wall-mounted version:
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Pulse/frequency output passive, basic I/Os
• U
• f
• f
• If the following maximum load resistance R
• The minimum load resistance R
• Can also be set as status output; for the electrical connection refer to status output
≤ 32 VDC
ext
in operating menu set to f
max
max
I ≤ 100 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
= 0.2 V at I ≤ 10 mA
0, max
= 2 V at I ≤ 100 mA
0, max
in the operating menu set to 100 Hz < f
max
I ≤ 20 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
U
= 1.5 V at I ≤ 1 mA
0, max
= 2.5 V at I ≤ 10 mA
0, max
= 5.0 V at I ≤ 20 mA
0, max
reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
L, min
=(U
R
L, max
L, max
L, max
ext-U0
= 47 kΩ
= 10 kΩ
= 1 kΩ
)/I
max
L, min
connection diagram.
≤ 100 Hz:
≤ 10 kHz:
max
is exceeded, the load resistance RL must be
L, max
is calculated as follows:
MFC 300
52
Figure 4-15: Pulse/frequency output passive P
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
p
Page 53
MFC 300
ELECTRICAL CONNECTIONS 4
INFORMATION!
•
Any connection polarity.
Status output / limit switch passive, basic I/Os
• U
• I ≤ 100 mA
• R
• open:
• The output is open when the device is de-energized.
• X stands for the terminals B, C or D. The functions of the connection terminals depend on the
≤ 32 VDC
ext
= 47 kΩ
L, max
L, min
=(U
ext-U0
R
I ≤ 0.05 mA at U
closed:
U
U
= 0.2 V at I ≤ 10 mA
0, max
= 2 V at I ≤ 100 mA
0, max
settings refer to
)/I
max
= 32 VDC
ext
Function tables
on page 79.
Figure 4-16: Status output / limit switch passive S
p
Control input passive, basic I/Os
• 8V≤ U
• I
max
I
max
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• Can also be set as a status output; for the electrical connection refer to status output
connection diagram.
Figure 4-17: Control input passive C
1 Signal
≤ 32 VDC
ext
= 6.5 mA at U
= 8.2 mA at U
≤ 24 VDC
ext
≤ 32 VDC
ext
≤ 2.5 V with I
0
≥ 8 V with I
0
= 0.4 mA
nom
= 2.8 mA
nom
p
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
53
Page 54
4 ELECTRICAL CONNECTIONS
4.10.4 Modular inputs/outputs and bus systems
CAUTION!
Observe connection polarity.
INFORMATION!
•
For further information on electrical connection refer to Description of the inputs and outputs
on page 42
For the electrical connection of bus systems, please refer to the separate documentation for
•
the respective bus systems.
Current output active (only current output terminals C/C- have HART® capability),
modular I/Os
• U
int, nom
• I ≤ 22 mA
≤ 1kΩ
• R
L
• X designates the connection terminals A, B or C, depending on the version of the signal
converter.
.
= 24 VDC
MFC 300
Figure 4-18: Current output active I
a
Current output passive (only current output terminals C/C- have HART® capability),
modular I/Os
• U
• I ≤ 22 mA
• U
• R
• X designates the connection terminals A, B or C, depending on the version of the signal
Figure 4-19: Current output passive I
≤ 32 VDC
ext
≥ 1.8 V
0
= (U
L, max
converter.
- U0) / I
ext
max
p
54
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 55
MFC 300
ELECTRICAL CONNECTIONS 4
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
Wall-mounted version:Wall-mounted version:
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Pulse/frequency output active, modular I/Os
• U
• f
• f
• If the following maximum load impedance R
• The minimum load impedance R
• X designates the connection terminals A, B or D, depending on the version of the signal
= 24 VDC
nom
in the operating menu set to f
max
≤ 100 Hz:
max
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
= 24 V at I = 20 mA
0, nom
in operating menu set to 100 Hz < f
max
≤ 10 kHz:
max
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
U
U
= 22.5 V at I = 1 mA
0, nom
= 21.5 V at I = 10 mA
0, nom
=19V at I=20mA
0, nom
L, max
be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
L, min
=(U
R
L, max
L, max
L, max
ext-U0
= 47 kΩ
= 10 kΩ
=1kΩ
)/I
max
is calculated as follows:
L, min
converter.
is exceeded, the load impedance RL must
Figure 4-20: Pulse / frequency output active P
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
a
55
Page 56
4 ELECTRICAL CONNECTIONS
INFORMATION!
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
Pulse/frequency output passive, modular I/Os
• U
• f
• f
• If the following maximum load impedance R
• The minimum load impedance R
• Can also be set as status output; refer to status output connection diagram.
• X designates the connection terminals A, B or D, depending on the version of the signal
≤ 32 VDC
ext
in the operating menu set to f
max
I ≤ 100 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
=0.2V at I≤ 10 mA
0, max
=2V at I≤ 100 mA
0, max
in operating menu set to 100 Hz < f
max
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
U
=1.5V at I≤ 1mA
0, max
=2.5 V at I ≤ 10 mA
0, max
=5V at I≤ 20 mA
0, max
be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
R
L, min
=(U
L, max
L, max
L, max
ext-U0
= 47 kΩ
= 10 kΩ
=1kΩ
)/I
max
L, min
converter.
≤ 100 Hz:
max
≤ 10 kHz:
max
is exceeded, the load impedance RL must
L, max
is calculated as follows:
MFC 300
56
Figure 4-21: Pulse frequency output passive P
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
p
Page 57
MFC 300
ELECTRICAL CONNECTIONS 4
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
Wall-mounted version:Wall-mounted version:
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Pulse and frequency output passive PN NAMUR, modular I/O
• Connection in conformity with EN 60947-5-6
• open:
= 0.6 mA
I
nom
closed:
I
= 3.8 mA
nom
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Figure 4-22: Pulse and frequency output passive PN to NAMUR EN 60947-5-6
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
57
Page 58
4 ELECTRICAL CONNECTIONS
Status output / limit switch active, modular I/Os
• Observe connection polarity.
• U
• I ≤ 20 mA
• R
• open:
• X designates the connection terminals A, B or D, depending on the version of the signal
=24VDC
int
≤ 47 kΩ
L
I ≤ 0.05 mA
closed:
U
= 24 V at I = 20 mA
0, nom
converter.
MFC 300
Figure 4-23: Status output / limit switch active S
a
Status output / limit switch passive, modular I/Os
• Any connection polarity.
• U
• I ≤ 100 mA
• R
• open:
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
=32VDC
ext
= 47 kΩ
L, max
L, min
=(U
ext-U0
R
I ≤ 0.05 mA at U
closed:
U
U
=0.2V at I≤ 10 mA
0, max
=2V at I≤ 100 mA
0, max
converter.
)/I
= 32 VDC
ext
max
58
Figure 4-24: Status output / limit switch passive S
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
p
Page 59
MFC 300
ELECTRICAL CONNECTIONS 4
Status output / limit switch SN NAMUR, modular I/Os
• Any connection polarity.
• Connection in conformity with EN 60947-5-6
• open:
= 0.6 mA
I
nom
closed:
= 3.8 mA
I
nom
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Figure 4-25: Status output / limit switch SN to NAMUR EN 60947-5-6
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
59
Page 60
4 ELECTRICAL CONNECTIONS
CAUTION!
Observe connection polarity.
Control input active, modular I/Os
• U
• External contact open:
• Switching point for identifying "contact open or closed":
• X designates the connection terminals A or B, depending on the version of the signal
Control input passive, modular I/Os
• 3V≤ U
• I
• Switching point for identifying "contact open or closed":
• X designates the connection terminals A or B, depending on the version of the signal
=24VDC
int
0, nom
=22V
U
External contact closed:
I
= 4 mA
nom
Contact open (off): U
Contact closed (on): U
0
0
converter.
≤ 32 VDC
ext
=9.5mA at U
max
=9.5mA at U
I
max
Contact open (off): U
ext
ext
≤ 24 V
≤ 32 V
0
Contact closed (on): U
converter.
≤ 10 V with I
≥ 12 V with I
≤ 2.5 V with I
≥ 3V with I
0
nom
nom
nom
nom
MFC 300
= 1.9 mA
= 1.9 mA
=1.9mA
=1.9mA
60
Figure 4-26: Control input passive C
1 Signal
p
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 61
MFC 300
ELECTRICAL CONNECTIONS 4
CAUTION!
Observe connection polarity.
Control input active CN NAMUR, modular I/Os
• Connection acc. to EN 60947-5-6
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
= 6.3 V with I
0, nom
0, nom
= 6.3 V with I
• Detection of cable break:
≥ 8.1 V with I ≤ 0.1 mA
U
0
• Detection of cable short circuit:
≤ 1.2 V with I ≥ 6.7 mA
U
0
• X designates the connection terminals A or B, depending on the version of the signal
converter.
< 1.9 mA
nom
nom
> 1.9 mA
Figure 4-27: Control input active CN to NAMUR EN 60947-5-6
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
61
Page 62
4 ELECTRICAL CONNECTIONS
4.10.5 Ex i inputs/outputs
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
For further information on electrical connection refer to Description of the inputs and outputs on
page 42
Current output active (only current output terminals C/C- have HART® capability), Ex i
I/Os
• Observe connection polarity.
• U
• I ≤ 22 mA
• R
• X designates the connection terminals A or C, depending on the version of the signal
.
= 20 VDC
int, nom
≤ 450 Ω
L
converter.
MFC 300
Figure 4-28: Current output active Ia Exi
Current output passive (only current output terminals C/C- have HART® capability),
Ex i I/Os
• Any connection polarity.
• U
• I ≤ 22 mA
• U
• R
• X designates the connection terminals A or C, depending on the version of the signal
Figure 4-29: Current output passive Ip Exi
≤ 32 VDC
ext
≥ 4 V
0
=(U
L, min
converter.
ext-U0
)/I
max
62
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 63
MFC 300
ELECTRICAL CONNECTIONS 4
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
Wall-mounted version:Wall-mounted version:
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Pulse and frequency output passive PN NAMUR, Ex i I/Os
• Connection acc. to EN 60947-5-6
• open:
= 0.43 mA
I
nom
closed:
I
= 4.5 mA
nom
• X designates the connection terminals B or D, depending on the version of the signal
converter.
Figure 4-30: Pulse and frequency output passive PN as per NAMUR EN 60947-5-6 Exi
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
63
Page 64
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Any connection polarity.
Status output/limit switch SN NAMUR, Ex i I/Os
• Connection acc. to EN 60947-5-6
• open:
= 0,43 mA
I
nom
closed:
I
= 4,5 mA
nom
• The output is closed when the device is de-energized.
• X designates the connection terminals B or D, depending on the version of the signal
converter.
MFC 300
Figure 4-31: Status output/limit switch SN to NAMUR EN 60947-5-6 Exi
64
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 65
MFC 300
ELECTRICAL CONNECTIONS 4
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
•
Any connection polarity.
Control input passive, Ex i I/Os
• 5.5 V ≤ U
• I
= 6 mA at U
max
I
= 6.5 mA at U
max
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• X designates the connection terminals B, if available.
≤ 32 VDC
ext
≤ 24 V
ext
≤ 32 V
ext
≤ 3.5 V with I ≤ 0.5 mA
0
≥ 5.5 V with I ≥ 4 mA
0
Figure 4-32: Control input passive Cp Exi
1 Signal
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
65
Page 66
4 ELECTRICAL CONNECTIONS
4.10.6 HART® connection
INFORMATION!
•
In the basic I/O the current output at connection terminals A+/A-/A always has HART®
capability.
•
For modular I/O and Ex i I/O, only the current output module for the connection terminals
®
C/C- has HART
HART® connection active (point-to-point)
capability.
MFC 300
Figure 4-33: HART® connection active (Ia)
1 Basic I/O: terminals A and A+
2 Modular I/O: terminals C- and C
3 HART
®
communicator
The parallel resistance to the HART® communicator must be R ≥ 230 Ω.
66
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 67
MFC 300
ELECTRICAL CONNECTIONS 4
HART® connection passive (Multi-Drop mode)
• I: I0% ≥ 4mA
• Multi-Drop mode I: I
• U
≤ 32 VDC
ext
• R ≥ 230 Ω
≥ 4mA = I
fix
0%
Figure 4-34: HART® connection passive (Ip)
1 Basic I/O: terminals A- and A
2 Modular I/O: terminals C- and C
3 HART
4 Other devices with HART
®
communicator
®
capability
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
67
Page 68
5 START-UP
5.1 Switching on the power
Before connecting to power, please check that the system has been correctly installed.
This includes:
• The device must be mechanically safe and mounted in compliance with the regulations.
• The power connections must have been made in compliance with the regulations.
• The electrical terminal compartments must be secured and the covers have been screwed
on.
• Check that the electrical operating data of the power supply are correct.
• Switching on the power.
5.2 Starting the signal converter
The measuring device, consisting of the measuring sensor and the signal converter, is supplied
ready for operation. All operating data have been set at the factory in accordance with your order
specifications.
MFC 300
When the power is switched on, a self test is carried out. After that the device immediately
begins measuring, and the current values are displayed.
Figure 5-1: Displays in measuring mode (examples for 2 or 3 measured values)
x, y and z denote the units of the measured values displayed
It is possible to change between the two measured value windows, the trend display and the list
with the status messages by pressing the keys ↑ and ↓. For information about possible status
messages, their meaning and cause refer to
page 113.
Status messages and diagnostic information
on
68
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 69
MFC 300
6.1 Display and operating elements
Figure 6-1: Display and operating elements (Example: flow indication with 2 measuring values)
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 Indicates when a key has been pressed
4 1st measured variable in large representation
5 Bargraph indication
6 Keys (see table below for function and representation in text)
7 Interface to the GDC bus (not present in all signal converter versions)
8 Infrared sensor (not present in all signal converter versions)
OPERATION 6
CAUTION!
The use of a jumper is only permitted for custody transfer devices to lock the access to custody
transfer relevant parameters. For non custody transfer devices (i.e. process instruments) this
jumper must not be used!
INFORMATION!
•
The switching point for the 4 optical keys is located directly in front of the glass. It is
recommended to activate the keys at right angles to the front. Touching them from the side
can cause incorrect operation.
•
After 5 minutes of inactivity, there is an automatic return to measuring mode. Previously
changed data is not saved.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
69
Page 70
6 OPERATION
MFC 300
KeyMeasuring modeMenu modeSubmenu or function
mode
>Switch from measuring
mode to menu mode;
press key for 2.5 s,
"Quick Start" menu is
then displayed
^Reset of displayReturn to measuring
↓ or ↑Switch between display
pages: measured
value 1 + 2, trend page
and status page(s)
Esc (> + ↑)--Return to menu mode
Table 6-1: Description of key functionality
Access to displayed
menu, then 1st
submenu is displayed
mode but prompt
whether the data should
be saved
Select menuSelect submenu or
Access to displayed
submenu or function
Press 1 to 3 times,
return to menu mode,
data saved
function
without acceptance of
data
Parameter and data
mode
For numerical values,
move cursor
(highlighted in blue) one
position to the right
Return to submenu or
function, data saved
Use cursor highlighted
in blue to change
number, unit, setting
and to move the decimal
point
Return to submenu or
function without
acceptance of data
70
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 71
MFC 300
6.1.1 Display in measuring mode with 2 or 3 measured values
Figure 6-2: Example for display in measuring mode with 2 or 3 measured values
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 1st measured variable in large depiction
4 Bargraph indication
5 Depiction with 3 measured values
6.1.2 Display for selection of sub-menu and functions, 3 lines
OPERATION 6
Figure 6-3: Display for selection of sub-menu and functions, 3 lines
1 Indicates a possible status message in the status list
2 Menu, sub-menu or function name
3 Number relating to 2
4 Indicates position within menu, sub-menu or function list
5 Next menu, sub-menu or function
(_ _ _ signalise in this line the end of the list)
6 Current menu, sub-menu or function
7 Previous menu, sub-menu or function
(_ _ _ signalise in this line the beginning of the list)
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
71
Page 72
6 OPERATION
6.1.3 Display when setting parameters, 4 lines
Figure 6-4: Display when setting parameters, 4 lines
1 Current menu, sub-menu or function
2 Number relating to 1
3 Denotes factory setting
4 Denotes permissible value range
5 Permissible value range for numeric values
6 Currently set value, unit or function (when selected, appears with white text, blue background)
This is where the data is changed.
7 Current parameter (open with >)
8 Factory setting of parameter (non-alterable)
MFC 300
6.1.4 Display when changing parameters, 4 lines
Figure 6-5: Display when changing parameters, 4 lines
1 Current menu, sub-menu or function
2 Number relating to 1
3 Denotes the change of a parameter (simple to check changed data when browsing through lists)
4 Next parameter
5 Currently set data from 6
6 Current parameter (for selection press key >; then see previous chapter)
7 Factory setting of parameter (non-alterable)
72
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 73
MFC 300
6.1.5 Using an IR interface (option)
The optical IR interface serves as an adapter for PC-based communication with the signal
converter without opening the housing.
INFORMATION!
•
This device is not part of the scope of delivery.
•
For more information about activation with the functions A6 or C6.6.6 refer to Function tables
on page 79
.
OPERATION 6
Figure 6-6: IR interface
1 Glass panel in front of the control and display panel
2 IR interface
3 LED lights up when IR interface is activated.
4 Suction cups
Timeout function
Following activation of the IR interface in Fct. A6 or C6.6.6 the interface must be properly
positioned and attached to the housing with the suction cups within 60 seconds. If this does not
happen within the specified time period, the device can be operated using the optical keys again.
Upon activation, the LED 3 lights up and the optical keys no longer function.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
73
Page 74
6 OPERATION
6.2 Zero calibration (menu C1.1.1)
Following installation, perform zero calibration prior to commissioning the device. Finalise the
installation before performing zero calibration. Changes (pipe system or calibration factor) made
after the zero calibration may affect the accuracy, making it necessary to perform zero
calibration again.
Observe the following for reliable zero calibration:
• The measuring sensor should be completely filled with the product at the expected process
pressure and temperature.
• The product may contain no air or gas, especially when it comes to horizontal installations.
Prior to zero calibration, it is recommended that the product be flushed at a high flow rate
(>50%), for 2 minutes.
• After flushing, re-establish zero flow by closing off the corresponding valves.
Set zero calibration automatically or manually using the operating controls. The converter cover
must be installed on the display for automatic calibration.
A) Automatic calibration
MFC 300
KeyDisplayDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release
2 x ↓CSetup
3 x >C1.1.1Zero Calibration
>Calibrate Zero?
Break
↓Calibrate Zero?
Automatic
^Please wait countdown from 40 s
Zero Calibration
+XX.XXX%
5 x ^Save Configuration?
Yes
^Display page
the key.
Display of measured zero calibration
in %.
(Warning, value can be changed!)
74
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 75
MFC 300
OPERATION 6
B) Manual calibration
KeyDisplayDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release
2 x ↓CSetup
3 x >C1.1.1Zero Calibration
>Calibrate Zero?
Break
3 x ↓Calibrate Zero?
Manual
Zero Calibration
+XX.XXX%
5 x ^Save Configuration?
Yes
^Display page
the key.
Display currently stored zero
calibration in %.
(Warning, value can be changed!)
Possible manual entry of zero
calibration.
Storing the displayed zero
calibration.
Under certain conditions, zero calibration is not possible and will be cancelled:
• The product is still flowing. The shut-off valves are not closed tightly enough.
• There are still gas bubbles in the fluid.
Remedy: Flush sensor and repeat calibration
With some media, it may be difficult to perform zero calibration. In such cases, there are various
methods to still achieve good zero calibration:
MediumPossible solutions
Media that tend to evaporate or outgasIncrease pressure.
Two-phase media (slurries), that contain solids that
may fall out.
Two-phase media in which the solids or gasforming components cannot be separated.
Only fill the sensor with the carrier medium.
Fill sensor with another liquid, e.g. water.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
75
Page 76
6 OPERATION
6.3 Menu structure
INFORMATION!
Note the key function within and between the columns.
MFC 300
Measuring modeSelect
menu↓ ↑
^Press
>2.5s
A Quick Setup> ^A1 Language>
↓↑↓↑↓↑↓↑ >
Select menu and/or submenu
↓↑
A2 Tag
A3 Reset> ^3.1 Error Reset
3.2 Reset Totaliser 1
3.3 Reset Totaliser 2
3.4 Reset Totaliser 3
A4 Analogue Outputs4.1 Measurement
4.2 Unit
4.3 Range
4.4 Low Flow Cutoff
4.5 Time Constant
A5 Digital Outputs5.1 Measurement
5.2 Pulse Value Unit
5.3 Value p. Pulse
5.4 Low Flow Cutoff
A6 GDC IR interface
A7 Zero Calibration
A8 Operation Mode
Select
function
and set
data
↓↑ >
^
76
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 77
MFC 300
OPERATION 6
Measuring ModeSelect
menu↓ ↑
^Press
>2.5s
B Test> ^B1 Simulation> ^1.1 Mass Flow>
↓↑↓↑↓↑↓↑ >
Select menu and/or sub-menu
↓↑
1.2 Density
1.3 Temperature
1. Current Output X
1. Status Output X
1. Status Output X
1. Pulse Output X
B2 Actual Values> ^2.1 Operating Hours
2.2 Mass Flow
2.3 Volume Flow
2.4 Velocity
2.5 Density
2.6 Temperature
2.7 Strain MT
2.8 Strain IC
2.9 Tube Frequency
2.10 Drive Level
2.11 Sensor A Level
2.12 Sensor B Level
2.13 2 Phase Signal
2.14 SE PCB Temperature
2.15 BE PCB Temperature
2.16 Act. Operat. Mode
B3 Information> ^3.1 C Number
3.2 Sensor Electronics
3.3 SW.Rev.MS
3.4 SW.Rev.UIS
3.5 Electronic Revision ER
Select
function
and set
data
↓↑ >
^
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
77
Page 78
6 OPERATION
MFC 300
Measuring ModeSelect
menu↓ ↑
^Press
>2.5s
C Setup> ^C1 Process Input> ^1.1 Calibration>
^> ^C3 I/O (Inputs/Outputs)> ^3.1 Hardware>
^> ^C4 I/O Totalisers> ^4.1 Totaliser 1>
^> ^C5 I/O HART> ^5.1 PV is>
^> ^C6 Device> ^6.1 Device Info>
↓ ↑↓ ↑↓ ↑↓ ↑ >
Select menu and/or sub-menu
↓↑
1.2 Density
1.3 Filter
1.4 System Control
1.5 Self Test
1.6 Information
1.7 Factory Calib.
1.8 Simulation
> ^C2 Concentration>
3. Current Output X
3. Frequency Output X
3. Pulse Output X
3. Status Output X
3. Limit Switch X
3. Control Input X
4.2 Totaliser 2
4.3 Totaliser 3
5.2 SV is
5.3 TV is
5.4 4V is
5.5 HART Units
6.2 Display
6.3 1. Meas. Page
6.4 2nd Meas. Page
6.5 Graphic Page
6.6 Special Functions
6.7 Units
6.8 HART
6.9 Quick Setup
Select
function
and set
data
↓↑ >
^
^
^
^
^
^
78
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 79
MFC 300
OPERATION 6
6.4 Function tables
INFORMATION!
Depending on the device version, not all functions are available.
6.4.1 Menu A, Quick Setup
No.FunctionSettings / descriptions
A1 Language
A1LanguageLanguage selection depends on the device version.
A2 Tag
A2Tag
A3 Reset?
A3Reset?
A3.1Error ResetReset Errors? Select: no/yes
A3.2Reset Totaliser 1Reset Totaliser? Select: no / yes (available if activated in C6.9.1)
A3.3Reset Totaliser 2Reset Totaliser? Select: no / yes (available if activated in C6.9.2)
A3.4Reset Totaliser 3Reset Totaliser? Select: no / yes (available if activated in C6.9.3)
Measuring point identifier (Tag no.) (also for HART® operation), appears in
the LC display header (up to 8 digits).
A4 Analogue Outputs (only for HART®)
A4Analogue OutputsApplicable to all current outputs (terminals A, B and C), frequency outputs
A4.1MeasurementSelect measurement: volume flow / mass flow / temperature / density /
A4.2UnitSelection of the unit from a list, depending on the measurement.
A4.3Range1) Setting for main current output (range: 0...100%)
A4.4Low Flow Cutoff1) Setting for main current output (sets output value to "0")
A4.5Time Constant1) Setting for main current output (applicable to all flow measurements)
(terminals A, B and D), limit switch (terminals A, B, C, and / or D) and the 1st
display page / line 1.
velocity /diagnosis 1 / diagnosis 2 /
Depending on the settings for the concentration measurement, the following
measurements are possible:
diagnosis 3 / concentration 1 / concentration 2 / concentration flow 1 /
concentration flow 2
2) Use for all outputs? (also use this setting for Fct. A4.2...A4.5!)
Setting: no (applies only to the main current output ) / yes (applies to all
analogue outputs)
Setting: 0…x.xx (format and unit, depending on measurement, see A4.1 and
A4.2 above)
2) Use for all outputs? Make setting, see Fct. A4.1 above!
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A4.1 above!
Setting: xxx.x s (range: 000.1…100 s)
2) Use for all outputs? Make setting, see Fct. A4.1 above!
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
2) Use for all outputs? (also use this setting for Fct. A5.2...A5.5!)
Setting: no (only for pulse output D) / yes (for all digital outputs)
A5.2Pulse Value UnitSelection of the unit from a list, depending on the measurement.
A5.3Value p. Pulse1) Setting for pulse output D (volume or mass value per pulse)
Setting: xxx.xxx in l/s or kg/s
2) Use for all outputs? Make setting, see Fct. A5.1 above!
A5.4Low Flow Cutoff1) Setting for pulse output D (sets output value to "0")
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A5.1 above!
MFC 300
A6 GDC IR interface
A6GDC IR interfaceAfter this function has been activated an optical GDC adapter can be
connected to the LC display. If approximately 60 seconds pass without a
connection being established or after the adapter is removed, then the
function is exited and the optical keys are active once again.
break (exit function without connection)
activate (the IR interface (adapter) and interrupt the optical keys)
A7 Zero Calibration
A7Zero CalibrationZero calibration, calibration sequence as described in Fct. C1.1.1...1.1.4
A8 Operation Mode
A8Operation ModeSet the operating mode.
Setting: measure / stop / standby
For detailed information refer to
Mode (menu A8)
on page 98.
80
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 81
MFC 300
6.4.2 Menu B, Test
No.FunctionSettings / descriptions
B1 Simulation
B1SimulationDisplayed values are simulated.
B1.1Mass FlowSimulation of mass flow
Set value (range and units depend on measurement)
break (exit function without simulation)
Query: start simulation?
Settings: no (exit function without simulation) / yes (start simulation)
B1.2DensitySequence and settings similar to B1.1, see above!
B1.3Temperature
B1.Current Output XSimulation X
B1.Pulse Output X
B1.Frequency Output X
B1.Control Input X
B1.Limit Switch X
B1.Status Output X
X stands for one of the connection terminals A, B, C or D
stands for Fct. B1.4...1.7
X stands for one of the connection terminals A, B, C or D
Sequence and settings similar to B1.1, see above!
For pulse output a set number of pulses are output in 1 s!
OPERATION 6
B2 Actual Values
B2Actual ValuesDisplay of current values;
B2.1Operating HoursDevice operating hours
B2.2Mass FlowCurrent unfiltered mass flow
B2.3Volume flowCurrent unfiltered volume flow
B2.4VelocityCurrent unfiltered flow velocity
B2.5DensityCurrent unfiltered density
B2.6TemperatureCurrent unfiltered temperature
B2.7Strain MTCurrent value for the measuring tube strain
B2.8Strain ICCurrent value for the inner cylinder strain
B2.9Tube FrequencyCurrent vibration frequency of the measuring tube
B2.10Drive LevelCurrent drive level to activate vibration
B2.11Sensor A LevelCurrent vibration amplitude
B2.12Sensor B Level
B2.132 Phase Signal2 phase indicator value
B2.14SE PCB TemperatureTemperature of sensor electronics
B2.15BE PCB TemperatureTemperature of signal converter
B2.16Act. Operat. ModeCurrent operating mode
Exit the displayed function by pressing the ^ key.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
81
Page 82
6 OPERATION
B3 Information
B3Information
B3.1C NumberCG number, cannot be changed (input/output version)
B3.2Sensor Electronics
B3.3SW.REV.MSLC display:
B3.4SW.REV.UIS
B3.5"Bus interface"Only appears with Profibus, Modbus and FF.
B3.6Electronic Revision ERLC display see Fct. B3.3 and B3.4
6.4.3 Menu C, Setup
No.FunctionSettings / descriptions
C1 Process Input
1st line: ID No. of the circuit board
2nd line: software version
3rd line: production date
MFC 300
C1.1 Calibration
C1.1Calibration
C1.1.1Zero CalibrationDisplay of current zero calibration value.
Query: calibrate zero?
Setting: break (return with ^) / standard (factory setting) /
manual (display last value; set new value, range: -10…+10%) /
automatic (shows the current value as the new zero calibration value)
C1.1.2Zero Add. OffsetDirect setting of zero offset
C1.1.3Pipe DiameterSet the pipe diameter in mm to calculate flow velocity
C1.1.4Flow CorrectionDefines additional correction for mass flow;
Range: -100...+100%
C1.2 Density
C1.2.1Density Calib.Start density calibration
For detailed information refer to
99.
C1.2.2DensityDensity mode selection: Actual (back key ^) / fixed (a fixed value is used for
the density (e.g. standard density)) /
Reference (calculates process density based on a reference temperature)
C1.2.3Fixed Density ValueSet the fixed value (e.g. standard density) for the density.
Appears only if density mode "fixed" has been selected in Fct. C1.2.2.
C1.2.3Density Ref. Temp.Set the reference temperature for the reference density option
Appears only if density mode "reference" has been selected in Fct. C1.2.2.
C1.2.4Ref. Density SlopeSet the slope for the reference density option
Appears only if density mode "reference" has been selected in Fct. C1.2.2.
Density calibration (menu C1.2.1)
on page
82
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 83
MFC 300
OPERATION 6
C1.3 Filter
C1.3Filter
C1.3.1Flow DirectionDefine polarity of flow direction.
Forwards (according to the arrow on the measuring sensor) or backwards
(in the opposite direction to the arrow)
C1.3.2Press. Supp. TimeSet the pressure suppression time, range: 0.0...20.0 s
C1.3.3Press. Supp. CutoffCutoff settings for the pressure suppression; range: 0.0...10.0%
C1.3.4Density AveragingSet the time constant for the density measurements; range: 1.0...20.0 s
C1.3.5Low Flow CutoffSet the low flow cutoff; range: 00.0...10.0%
C1.4 System Control
C1.4System Control
C1.4.1FunctionSet the system control.
C1.4.2Sys. Ctrl. ConditionSet the condition for activating the system control.
C1.4.3Sys. Ctrl. Max LimitDefines the upper limit for the condition selected in C1.4.2
C1.4.4Sys. Ctrl. Min LimitDefines the lower limit for the condition selected in C1.4.2
Select: inactive (off) / flow = 0 (flow to zero)
Selection: density or temperature
C1.5 Self Test
C1.5Self Test
C1.5.1Max. Rec. Temp.Display of maximum recorded sensor temperature
C1.5.2Min. Rec. Temp.Display of minimum recorded sensor temperature
C1.5.32 Ph. ThresholdDefines the process-dependent sensitivity for 2 phase signal error message.
C1.5.4Diagnosis 1Defines the parameter for the respective diagnostic value.
C1.5.5Diagnosis 2
C1.5.6Diagnosis 3
Select: off (goes to zero) / sensor average (sensor amplitude A+B) / sensor
deviation / drive level / MT frequency / strain MT / strain IC / 2 phase signal
C1.6 Information
C1.6Information
C1.6.2V No. SensorShows the order number of the measuring sensor.
C1.6.3SE Serial No.Displays the serial number of the sensor electronics
C1.6.4SE VersionDisplays the version of the sensor electronics
C1.6.5SE InterfaceDisplays the interface version of the sensor electronics
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
83
Page 84
6 OPERATION
C1.7 Factory Calib.
C1.7Factory Calib.
C1.7.1Sensor TypeDisplays the sensor type
C1.7.2Sensor SizeDisplays the nominal size of the sensor
C1.7.3Sensor MaterialDisplays the material of the sensor
C1.7.4Max. Allowed Temp.Displays the maximum permitted temperature for the sensor
C1.7.5Min. Allowed Temp.Displays the minimum permitted temperature for the sensor
C1.7.6...
1.7.30
C1.8 Simulation
C1.8Simulation
C1.8.1Mass FlowAs in B1.1
C1.8.2DensityAs in B1.2
C1.8.3TemperatureAs in B1.3
CF1...CF27Displays the sensor calibration coefficients (not CF9 or CF10)
Current range for the selected measurement, e.g. 4...20 mA,
corresponds to 0…100%
Note: with a 0...20 mA current output, HART in Fct. C6.8.1 must be shut off!
xx.x … xx.x mA; range: 0.00…20 mA
(condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA)
xx.x … xx.x mA; range: 03.5…21.5 mA
(condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 21.5 mA)
xx.x mA; range: 3…22 mA (condition: outside of extended range)
Select: error in device (error category [F]) / application error (error category
[F]) / out of specification (error category [S])
Select measurement: Volume Flow / Mass Flow / Temperature / Density /
Velocity / Diagnosis 1 / Diagnosis 2 /
Depending on the settings for the concentration measurement, the following
measurements are possible:
Diagnosis 3 / Concentration 1 / Concentration 2 / Concentration Flow 1 /
Concentration Flow 2
0…xx.xx _ _ _ (format and unit depend on the measurement, see above)
Select: both polarities (plus and minus values are displayed) / positive
polarity (display for negative values = 0) / negative polarity (display for
positive values = 0) / absolute value (use for the output)
±xxx …±xxx%; range: -150…+150%
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
Off (switched off)
Automatic range (range is changed automatically, extended lower range,
only makes sense together with a status output)
External range (change by control input, extended lower range, control input
must also be activated)
OPERATION 6
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
85
Page 86
6 OPERATION
MFC 300
C3..12ThresholdAppears only when Fct. C3..11 threshold is activated between extended
C3..13InformationSerial no. of the I/O board, software version no. and production date of the
C3..14SimulationSequence see B1. Current Output X
C3..154mA TrimmingTrimming of the current at 4 mA
C3..1620mA TrimmingTrimming of the current at 20 mA
and normal range. The automatic range function always changes from the
extended to the normal range when the 100% current is reached.
The upper 100% value of the hysteresis is then = 0. The threshold is then the
hysteresis value, instead of "threshold ± hysteresis" as shown in the display.
Range: 5.0…80%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
circuit board
Reset to 4 mA restores the factory calibration.
Used for HART® setting.
Reset to 20 mA restores the factory calibration.
Used for HART® setting.
C3. Frequency Output X
C3.Frequency Output XX stands for one of the connection terminals A, B or D
C3..1Pulse ShapeSpecify the pulse shape.
C3..2Pulse WidthOnly available if set to "fixed" in Fct. C3..1.
C3..3100% Pulse RatePulse rate for 100% of the measuring range
C3..4MeasurementMeasurements for activating the output.
C3..5Range0…100% of the measurement set in Fct. C3..4
C3..6PolaritySet measured value polarity, please note flow direction in C1.3.2!
C3..7LimitationLimitation before applying the time constant.
Select: symmetric (about 50% on and 50% off) / automatic (constant pulse
with about 50% on and 50% off at 100% pulse rate) / fixed (fixed pulse rate,
setting see below Fct. C3..3 100% pulse rate)
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
Range: 0.0…10000 1/s
Limitation 100% pulse rate ≤ 100/s: I
Limitation 100% pulse rate > 100/s: I
Select measurement: Volume Flow / Mass Flow / Temperature / Density /
Velocity / Diagnosis 1 / Diagnosis 2 /
Depending on the settings for the concentration measurement, the following
measurements are possible:
Diagnosis 3 / Concentration 1 / Concentration 2 / Concentration Flow 1 /
Concentration Flow 2
0…xx.xx _ _ _ (format and unit depend on the measurement, see above)
Select: both polarities (plus and minus values are displayed) / positive
polarity (display for negative values = 0) / negative polarity (display for
positive values = 0) / absolute value (use for the output)
±xxx …±xxx%; range: -150…+150%
max
max
≤ 100 mA
≤ 20 mA
86
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 87
MFC 300
C3..8Low Flow CutoffSets output value to "0":
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C3..9Time ConstantRange: 000.1…100 s
C3..10Invert SignalSelect: Off (activated output generates a high current at the output, switch
closed) /
On (activated output generates a low current at the output, switch open)
C3..11Phase Shift w.r.t. BOnly available when configuring the A or D terminal and only if output B is a
pulse or frequency output. If setting in Fct. C2.5.6 is "Both Polarities", the
phase shift is prefixed by a symbol, e.g. -90° and +90°.
Select: off (no phase shift) / 0° phase shift (between outputs A or D and B,
inversion possible) / 90° phase shift (between outputs A or D and B, inversion
possible) / 180° phase shift (between outputs A or D and B, inversion
possible)
C3.3.11Special FunctionsThis function is only available at the terminal B frequency output. At the
same time, 2 frequency outputs must be available:
1st output at terminal A or D / 2nd output at terminal B
The B output is operated as a slave output, controlled and set using master
output A or D
Selection: off (no phase shift) / phase shift w.r.t. D or A (slave output is B and
master output is D or A)
C3..12InformationSerial no. of the I/O board, software version no. and production date of the
circuit board
C3..13SimulationSequence see B1. Frequency Output X
OPERATION 6
C3. Pulse Output X
C3.Pulse Output XX stands for one of the connection terminals A, B or D
C3..1Pulse ShapeSpecify the pulse shape.
C3..2Pulse WidthOnly available if set to "fixed" in Fct. C3..1
C3..3Max. Pulse RatePulse rate for 100% of the measuring range
C3..4MeasurementMeasurements for activating the output.
C3..5Pulse Value UnitSelection of the unit from a list, depending on the measurement.
C3..6Value p. PulseSet value for volume or mass per pulse.
C3..7PolaritySet polarity, please note Flow Direction in C1.3.2!
Select: Symmetric (about 50% on and 50% off) / Automatic (constant pulse
with about 50% on and 50% off at 100% pulse rate) / Fixed (fixed pulse rate,
setting see below Fct. C3..3 100% pulse rate)
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
Range: 0.0…10000 1/s
Limitation 100% pulse rate ≤ 100/s: I
Limitation 100% pulse rate > 100/s: I
Select: Volume Flow / Mass Flow
xxx.xxx, range in [l] or [kg] (volume or mass for current output C3..6)
At max. pulse rate see above 3..3 Pulse Output.
Select: both polarities (plus and minus values are displayed) / positive
polarity (display for negative values = 0) / negative polarity (display for
positive values = 0) / absolute value (use for the output)
max
max
≤ 100 mA
≤ 20 mA
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
87
Page 88
6 OPERATION
C3..8Low Flow CutoffSets output value to "0"
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C3..9Time ConstantRange: 000.1…100 s
C3..10Invert SignalSelect: Off (activated output generates a high current at the output, switch
closed) /
On (activated output generates a low current at the output, switch open)
C3..11Phase Shift w.r.t. BOnly available when configuring the A or D terminal and only if output B is a
pulse or frequency output. If setting in Fct. C2.5.6 is "Both Polarities", the
phase shift is prefixed by a symbol, e.g. -90° and +90°.
Select: off (no phase shift) / 0° phase shift (between outputs A or D and B,
inversion possible) / 90° phase shift (between outputs A or D and B, inversion
possible) / 180° phase shift (between outputs A or D and B, inversion
possible)
C3.3.11Special FunctionsThis function is only available at the pulse output of terminal B. At the same
time, 2 pulse outputs must be available:
1st output at terminal A or D / 2nd output at terminal B
The B output is operated as a slave output, controlled and set using master
output A or D
Selection: off (no phase shift) / phase shift w.r.t. D or A (slave output is B and
master output is D or A)
C3..12InformationSerial no. of the I/O board, software version no. and production date of the
circuit board
C3..13SimulationSequence see B1. pulse output X
MFC 300
88
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 89
MFC 300
OPERATION 6
C3. Status Output X
C3.Status Output XX (Y) stands for one of the connection terminals A, B, C or D
C3..1ModeThe output shows the following measuring conditions:
C3..2Current Output YOnly appears if output A...C is set under "mode" (see above), and this output
C3..2Frequency Output Y and
Pulse Output Y
C3..2Status Output YOnly appears if output A...D is set under "mode" (see above), and this output
C3..2Limit Switch Y and Control
Input Y
C3..2OffOnly appears if output A...D is set under "mode" (see above) and this output
C3..3Invert SignalOff (activated output supplies a high current, switch closed)
C3..4InformationSerial no. of the I/O board, software version no. and production date of the
out of specification (output activated, signals application error or error in
device refer to
application error (output activated, signals application error or error in
device refer to
polarity flow (polarity of the current flow) /
over range flow (over range of the flow) /
totaliser 1 preset (activates when totaliser X preset value is reached) /
totaliser 2 preset (activates when totaliser X preset value is reached) /
totaliser 3 preset (activates when totaliser X preset value is reached) /
output A (activated by the status of output Y, additional output data see
below) /
output B (activated by the status of output Y, additional output data see
below) /
output C (activated by the status of output Y, additional output data see
below) /
output D (activated by the status of output Y, additional output data see
below) /
off (switched off) /
empty pipe (when pipe empty, output activated) /
Error in device (when error, output activated)
is a "current output".
Polarity (is signalled)
Over Range (is signalled)
Automatic Range signals lower range
Only appears if output A, B or D is set under "mode" (see above), and this
output is a "frequency/pulse output".
Polarity (is signalled)
Over Range (is signalled)
is a "status output".
Same signal (like other connected status output, signal can be inverted, see
below)
Only appears if output A...D / input A or B is set under "mode" (see above),
and this output / input is a "limit switch / control input".
Status off (is always selected here if status output X is connected with a limit
switch / control input Y.
is switched off.
On (activated output supplies a low current, switch open)
circuit board
Status messages and diagnostic information
Status messages and diagnostic information
on page 113 /
on page 113 /
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
89
Page 90
6 OPERATION
MFC 300
C3. Limit Switch X
C3.Limit Switch XX stands for one of the connection terminals A, B, C or D
xxx.x ±x.xxx (format and unit depend on the measurement, see above)
(1st value = threshold / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
Select: both polarities (plus and minus values are displayed) / positive
polarity (display for negative values = 0) / negative polarity (display for
positive values = 0) / absolute value (use for the output)
Off (activated output generates a high current, switch closed)
On (activated output generates a low current, switch open)
circuit board
C3. Control Input X
C3.Control Input X
C3..1ModeX stands for connection terminal A or B
C3..2Invert Signaloff (control input is activated when a current is applied at the input by voltage
C3..3InformationSerial no. of the I/O board, software version no. and production date of the
C3..4SimulationSequence see B 1. control input X
stands for Fct. no. C3.2 (A) / C3.3 (B)
Off (control input switched off) /
hold all outputs (hold current values, not display and totalisers) /
output Y (hold current values) /
all outputs to zero (current values = 0%, not display and totalisers) /
output Y to zero (current value = 0%) /
all totalisers (reset all totalisers to "0") /
totaliser "Z" reset (set totaliser 1, (2 or 3) to "0") /
stop all totalisers /
stop totaliser "Z" (stops totaliser 1, (2 or 3) /
zero outp.+stop Tot. (all outputs 0%, stop all totalisers, not the display) /
external range Y (control input for external range of current output Y) - also
make this setting on current output Y (no check if current output Y is
available) /
Error reset (all resettable errors are deleted)
Zero Calibration
to passive inputs or a low-value resistor to active inputs)
on (control input is activated when no current is applied at the input, low
voltage to passive inputs or a high-value resistor to active inputs)
circuit board
90
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 91
MFC 300
OPERATION 6
No.FunctionSettings / descriptions
C4 I/O Totalisers
C4.1Totaliser 1Set function of totaliser
C4.2Totaliser 2
C4.3Totaliser 3
C4..1Totaliser FunctionSelect: Absolute Total (counts positive and negative values) / +totaliser
C4..2MeasurementSelection of the measurement for totaliser
C4..3Low Flow CutoffSets output value to "0"
C4..4Time ConstantRange: 000.1…100 s
C4..5Preset ValueIf this value is reached, positive or negative, a signal is generated that can be
C4..6Reset TotaliserSequence see Fct. A3.2, A3.3 und A3.4
C4..7Set TotaliserSet totaliser to the desired value.
C4..8Stop TotaliserTotaliser stops and holds the current value.
C4..9Start TotaliserStart totaliser after that totaliser is stopped.
C4..10InformationSerial number of the I/O circuit board, software version number and
stands for 1, 2, 3 (= totaliser 1, 2, 3)
The basic version (standard) has only 2 totaliser!
(counts only the positive values) / -totaliser (counts only the negative values)
/ off (totaliser is switched off)
Select: volume flow / mass flow /
conc. flow 1 (depends on the settings for the concentration measurement)
Range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
used for a status output at which "preset totaliser X" has to be set.
Preset value (max. 8 digits) x.xxxxx in selected unit, see C6.7.10 + 13
Select: break (exit function) / set value (opens the editor to make the entry)
Query: set totaliser?
Select: no (exit function without setting the value) / yes (sets the totaliser and
exits the function)
Select: no (exits the function without stopping the totaliser) / yes (stops the
totaliser and exits the function)
Select: no (exits the function without starting the totaliser) / yes (starts the
totaliser and exits the function)
production date of the circuit board.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
91
Page 92
6 OPERATION
No.FunctionSettings / descriptions
C5 I/O HART
C5I/O HART
C5.1PV isCurrent output (primary variable)
C5.2SV is(secondary variable)
C5.3TV is(tertiary variable)
C5.44V is(4th variable)
C5.5HART UnitsChanges units of DVs (dynamic variables) in the display
Selection / display of the 4 dynamic variables (DV) for HART®.
The HART® current output (terminal A basic I/Os or terminal C modular I/Os)
always has a fixed link to the primary variables (PV). Fixed links of the other
DVs (1-3) are only possible if additional analogue outputs (current and
frequency) are available; if not, the measurement can be freely selected
from the following list: in Fct. A4.1 "measurement".
stands for 1, 2, 3 or 4
X stands for connection terminals A...D
Break: return with ^ key
MFC 300
HART display®: copies the settings for the display units to the settings for
DVs
Standard: sets factory defaults for DVs
C5..1Current Output XShows the current analogue measured value of the linked current output.
C5..1Frequency Output XShows the current analogue measured value of the linked frequency output,
C5..1HART Dynamic Var.
The measurement cannot be changed!
if present. The measurement cannot be changed!
Measurements of the dynamic variables for HART®.
Linear measurements: Volume Flow / Mass Flow / Diagnosis Value /
Fow Velocity
C6.1.3Device Serial No.Serial no. of the system, cannot be changed
C6.1.4BE Serial No.Serial no. of the electronic assembly, cannot be changed.
C6.1.5SW.REV.MSSerial no. of the circuit board, version no. of the main software, production
C6.1.6Electronic Revision ERShows ID no., electronic revision no. and production date;
A…Z; a…z; 0…9; / - , .
date of the circuit board
Contains all hardware and software changes.
92
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 93
MFC 300
OPERATION 6
C6.2 Display
C6.2Display
C6.2.1LanguageLanguage selection depends on the device version.
C6.2.2ContrastAdjust display contrast for extreme temperatures.
C6.2.3Default DisplaySpecification of the default display page that is returned to after a short
C6.2.4Self TestNot available at this time.
C6.2.5SW.REV.UISSerial no. of the circuit board, version no. of user software, production date
Setting: -9…0…+9
This change takes place immediately, not just when setting mode is exited!
delay period.
Select: none (the current page is always active) / 1. meas. page (show this
page) / 2. meas. page (show this page) / status page (show only status
messages) / graphic page (trend display of the 1st measurement)
of the circuit board
C6.3 and C6.4 1st Meas. Page and 2nd Meas. Page
C6.31st Meas. Page stands for 3 = meas. page 1 and 4 = meas. page 2
C6.42nd Meas. Page
C6..1FunctionSpecify number of measured value lines (font size)
Select: one line / two lines / three lines
C6..21st Line VariableSpecify 1st Line Variable.
Select measurement: Volume Flow / Mass Flow / Temperature / Density /
Velocity / Diagnosis 1 / Diagnosis 2 /
Depending on the settings for the concentration measurement, the following
measurements are possible:
Diagnosis 3 / Concentration 1 / Concentration 2 / Concentration Flow 1 /
Concentration Flow 2
C6..3Range0…100% of the measurement set in Fct. C5..2
0…xx.xx _ _ _ (format and unit depend on the measurement)
C6..4LimitationLimitation before applying the time constant.
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C6..6Time ConstantRange: 000.1…100 s
C6..71st Line FormatSpecify decimal places.
Select: automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits) depends on size of font
C6..82nd Line VariableSpecify 2nd Line Variable (only available if this 2nd line is activated)
Select: Bar Graph (for measurement selected in the 1st line ) / Volume
Flow / Mass Flow / Temperature / Density / Velocity / Bar Graph / Totaliser
1 / Totaliser 2 / Totaliser 3 / Operating Hours / Diagnosis 1 / Diagnosis 2
Depending on the settings for the concentration measurement, the following
measurements are possible:
Diagnosis 3 / Concentration 1 / Concentration 2 / Concentration Flow 1 /
Concentration Flow 2
C6..92nd Line FormatSpecify decimal places.
Select: automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits) depends on size of font
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
93
Page 94
6 OPERATION
C6..103rd Line VariableSpecify 3rd Line Variable (only available if this 3rd line is activated)
Select: Volume Flow / Mass Flow / Temperature / Density / Velocity /
Totaliser 1 / Totaliser 2 / Totaliser 3 / Operating Hours / Diagnosis 1 /
Diagnosis 2
Depending on the settings for the concentration measurement, the following
measurements are possible:
Diagnosis 3 / Concentration 1 / Concentration 2 / Concentration Flow 1 /
Concentration Flow 2
C6..113rd Line FormatSpecify decimal places.
Select: automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits) depends on size of font
MFC 300
C6.5 Graphic Page
C6.5Graphic Page
C6.5.1Select RangeGraphic page always shows trend curve of the measurement of the 1st page
C6.5.2RangeSet the scaling for the Y axis. Only available if "manual" is set in C6.5.1.
C6.5.3Time ScaleSet the time scaling for the X axis, trend curve
/ 1st line, see Fct. C6.3.2
Select: Manual (set range in Fct. C6.5.2) /
Automatic (automatic depiction based on the measured values)
Reset only after parameter change or after switching off and on.
+xxx ±xxx%; range: -100…+100%
(1st value = lower limit / 2nd value = upper limit),
condition: 1st value ≤ 2nd value
xxx min; range: 0…100 min
C6.6 Special Functions
C6.6Special Functions
C6.6.1Reset ErrorsReset Errors?
Select: no/yes
C6.6.2Save SettingsSave current settings.
C6.6.3Load SettingsLoad saved settings.
C6.6.4Password Quick SetPassword required to change data in the quick setup menu.
C6.6.5Password SetupPassword required to change data in the setup menu
Select: cancel (exit function without saving) / backup 1 (save in storage
location 1) / backup 2 (save in storage location 2).
Query: continue copy? (cannot be done afterwards)
Select: no (exit function without saving) / yes (copy current settings to
storage backup 1 or backup 2)
Select: break (exit function without loading) / factory settings (load in state
as delivered) / backup 1 (load data from storage location 1) / backup 2 (load
data from storage location 2)
Query: continue copy? (cannot be done afterwards)
Select: no (exit the function without saving) / yes (load data from the selected
storage location)
0000 (= to Quick Setup menu without password)
xxxx (password required); range 4 digits: 0001…9999
0000 (= to Quick Setup menu without password)
xxxx (password required); range 4 digits: 0001…9999
94
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 95
MFC 300
OPERATION 6
C6.6.6GDC IR InterfaceAfter this function has been activated an optical GDC adapter can be
connected to the LC display. If approximately 60 seconds pass without a
connection being established or after the adapter is removed, then the
function is exited and the optical keys are active once again.
Break (exit function without connection)
Activate (the IR interface adapter and interrupt the optical keys)
If approximately 60 seconds pass without a connection being established,
then the function is exited and the optical keys are active once again.
C6.7.11Text free unitFor text to be specified refer to
C6.7.12[m³]*factorSpecification of the conversion factor, based on m³:
C6.7.13Masskg; t; mg; g; lb; ST; LT; oz;
C6.7.14Text free unitFor text to be specified refer to
C6.7.15[kg]*factorSpecification of the conversion factor, based on kg:
C6.7.16Densitykg/l; kg/m³; lb/ft³; lb/gal; SG
C6.7.17Text free unitFor text to be specified refer to
C6.7.18[kg/m³]*factorSpecification of the conversion factor, based on kg/m³:
C6.7.19PressurePa; kPa; bar; mbar; psi (no free units possible);
ft³/h; ft³/min; ft³/s; gal/h; gal/min; gal/s; barrel/h; barrel/day
free unit (set factor and text in the next two functions, sequence see below)
Set free units
xxx.xxx refer to
lb/s; lb/min; lb/h; ST/min; ST/h (ST = Short Ton); LT/h (LT = Long Ton);
free unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 96
Set free units
xxx.xxx refer to
free unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 96
Set free units
xxx.xxx refer to
free unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 96
Set free units
xxx.xxx refer to
free unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 96
Set free units
xxx.xxx refer to
only if current input available.
Set free units
on page 96
on page 96:
on page 96:
on page 96:
on page 96:
on page 96:
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
95
Page 96
6 OPERATION
C6.8 HART
C6.8HART
C6.8.1HART
C6.8.2Address
C6.8.3MessageSet required text:
C6.8.4DescriptionSet required text:
C6.9 Quick Setup
C6.9Quick setupActivate quick access in Quick Setup menu:
C6.9.1Reset Totaliser 1Reset Totaliser 1 in Quick Setup menu?
C6.9.2Reset Totaliser 2Reset Totaliser 2 in Quick Setup menu?
C6.9.3Reset Totaliser 3Reset Totaliser 3 in Quick Setup menu?
Switch HART® communication on/off:
Select: HART on (HART
not activated) current = 0…20 mA
Set address for HART® operation:
Select: 00 (point-to-point operation, current output has normal function,
current = 4…20 mA) / 01...15 (multidrop operation, current output has a
constant setting of 4 mA)
A…Z ; a…z ; 0…9 ; / - + , . *
A…Z ; a…z ; 0…9 ; / - + , . *
Select: yes (switched on) / no (switched off)
Select: yes (activated) / no (switched off)
Select: yes (activated) / no (switched off)
Select: yes (activated) / no (switched off)
®
activated) current = 4…20 mA / HART off (HART
MFC 300
®
6.4.4 Set free units
Free unitsSequences to set texts and factors
Texts
Texts
TextsTexts
Volume flow, mass flow and density:3 digits before and after the slash
6.5.2 Deleting error messages in the menu "quick setup"
INFORMATION!
For the detailed list of the possible error messages refer to Status messages and diagnostic
information on page 113
KeyDisplayDescription and setting
>quick setupPress and hold for 2.5 s, then
>language2 x ↓reset-
>reset errors-
>reset?
no
↓ or ↑reset?
yes
^reset errorsError has been reset.
3 x ^Measuring mode-
.
release the key.
-
-
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
97
Page 98
6 OPERATION
6.5.3 Mode (menu A8)
The device can be switched to "standby". In this mode, all flow values are set to zero and the
counter values are "frozen". The temperature and density values are displayed normally and
output via the outputs. The "standby" indicator on the display shows either the "frozen" counter
value or simply "standby". In this mode, the measuring tubes continue to vibrate and the device
can immediately return to "measuring" mode if necessary.
There is also a "stop" mode. In this mode, the sensor is switched off and is no longer vibrating.
To return to measuring mode from this mode, the measuring device must
complete "start-up" phase again before measurement continues.
The measuring device can be switched into "standby" mode either using the optical keys on the
display or using the control input. You can only switch to "stop" mode using the optical keys.
Setting the mode (from measuring mode):
KeyDisplayDescription and setting
MFC 300
must go through the
mustmust
>AQuick SetupPress and hold for 2.5 s, then release
> ↑A8Mode
Measuring
>Mode
Measuring
↑Mode
Standby
↑Mode
Stop
3 x ^Save Configuration?
Yes
^Display page
the key.
If "standby" or "stop" is selected, the device immediately switches to this operating state. To
return to the measuring mode, go to menu A8 and select "measure".
INFORMATION!
When changing from the "stop" to "standby" mode, the device goes through the entire start-up
phase.
In addition to the "standby" mode, the system control function also allows you to switch to a
comparable "standby" status completely automatically depending on the current operating
temperature or density.
98
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Page 99
MFC 300
6.5.4 Density calibration (menu C1.2.1)
Mass flowmeters are calibrated for density in the factory. Density calibration is based on 2
calibration points. In the factory, air and water are used under reference conditions. The result
of this calibration is saved in the converter electronics and stored in the factory settings.
Regardless, various applications require maximum accuracy which can only be achieved with
on-site calibration.
Available options:
OptionExplanation
OPERATION 6
1 Point CalibrationOne of the 2 saved calibration points is replaced by customer calibration.
2 Point CalibrationThe user recalibrates both calibration points.
DefaultThe signal converter reactivates the factory settings for the density
ManualThe user can read the current density calibration points and enter them if
The signal converter decides which of the 2 calibration points is modified.
calibration.
necessary (according to sensor calibration certificate).
Example of 1 point calibration with town water
KeyDisplayDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release
2 x ↓CSetup
2 x >C1.1Calibration
↓C1.2Density
2 x >C1.2.1Density Calib.
↓C1.2.1Density Calibration?
↓C1.2.1Density Calibration?
↓C1.2.1Density Calibration?
↓C1.2.1Density Calibration?
^C1.2.1DCF1
Press ↓
until
^C1.2.1Single Pt. Calib.
↓C1.2.1Single Pt. Calib.
^C1.2.1Perform Calibration
5 x ^Save Configuration?
^Measuring Mode
C1.2.1DCF1
Break
Default
Manual
2 Point Calibration
1 Point Calibration
XXXXXXXXX
Town Water
Break
OK
Passed
Yes
the key.
Press ^ to exit density calibration
menu.
Press ^ for density calibration.
Factory calibration on OK (6 x ^).
Press ^ to read or change the
current density calibration value.
Press ^ to start 2 point calibration.
Press ^ to start 1 point calibration.
Press ↓ until you reach town water.
Press ^ to start town water
calibration.
Press ^ to start single point
calibration.
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
99
Page 100
6 OPERATION
On-site density calibration:
• Ensure that the device has been properly installed and functions smoothly.
• If air (empty) is used as the medium, the measuring tube must be completely dry and free of
liquids and solids. If possible, blow dry air into the measuring tube to empty it.
• If liquids are used, flush for a few minutes at a high flow rate to remove gas bubbles.
• Set the flow rate to a typical value (50% of the nominal flow is ideal).
• If the process temperature is higher than the ambient temperature, wait until the system has
stabilised.
• When it comes to 1 point and 2 point calibration, you can choose from the options "empty",
"pure water", "town water" and "other". The reference values for the specified products are
stored in the converter.
Density calibration has failed if "calib. error." is displayed. There are several possible reasons
for this:
• The device is not in "measuring" mode.
• The calibration points are too close together.
• One or more calibration points did not pass the plausibility test.
• Flow, pressure, temperature or system are not stable?
• Please check your system and try again.
• If this results in another failed calibration, please contact the manufacturer.
MFC 300
100
www.krohne.com02/2012 - 4000498602 - MA MFC 300 R03 en
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.