All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of KROHNE Messtechnik GmbH.
9.11 Appendix A: HART® menu tree for Basic-DD ............................................................ 112
9.11.1 Overview Basic-DD menu tree (positions in menu tree).................................................. 113
9.11.2 Basic-DD menu tree (details for settings)........................................................................ 114
9.12 Appendix B: HART® menu tree for AMS .................................................................... 117
9.12.1 Overview AMS menu tree (positions in menu tree) .......................................................... 117
9.12.2 AMS menu tree (details for settings)................................................................................ 118
9.13 Appendix C: HART® menu tree for PDM.................................................................... 122
9.13.1 Overview PDM menu tree (positions in menu tree).......................................................... 122
9.13.2 PDM menu tree (details for settings) ............................................................................... 124
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
5
Page 6
1 SAFETY INSTRUCTIONS
1.1 Software history
The "Electronic Revision" (ER) is consulted to document the revision status of electronic
equipment according to NE 53 for all GDC devices. It is easy to see from the ER whether
troubleshooting or larger changes in the electronic equipment have taken place and how that
has affected the compatibility.
Changes and effect on compatibility
1Downwards compatible changes and fault repair with no effect on operation (e.g. spelling
mistakes on display)
2-_Downwards compatible hardware and/or software change of interfaces:
HART
®
H
PPROFIBUS
FFoundation Fieldbus
MModbus
Xall interfaces
3-_Downwards compatible hardware and/or software change of inputs and outputs:
ICurrent output
F, PFrequency / pulse output
SStatus output
CControl input
CICurrent input
Xall inputs and outputs
4Downwards compatible changes with new functions
5Incompatible changes, i.e. electronic equipment must be changed.
IFC 100
INFORMATION!
In the table below, "x" is a placeholder for possible multi-digit alphanumeric combinations,
depending on the available version.
Release dateElectronic RevisionChanges and
Documentation
compatibility
2007-12-11ER 2.0.0
(SW.REV. 2.00 (2.00))
2008-02-29ER 2.0.1
(SW.REV. 2.00 (2.00))
2008-05-07ER 2.0.2
(SW.REV. 2.00 (2.00))
2008-06-27ER 2.0.3
(SW.REV. 2.00 (2.00))
2010-01-04ER 2.0.4
(SW.REV. 2.00 (2.00))
2010-01-04ER 2.1.0
(SW.REV. 2.10 (3.00))
2010-07-08ER 2.1.1
(SW.REV. 2.11 (3.00))
2011-12-12ER 3.0.0
(SW.REV. 3.00 (4.00))
2013-04-26ER 3.0.11MA IFC 100 R05
--
1MA IFC 100 R03
1MA IFC 100 R04
1MA IFC 100 R04
1MA IFC 100 R04
1; 2-HMA IFC 100 R04
1MA IFC 100 R04
1; 2-X; 3-X, 5-S 1MA IFC 100 R05
6
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 7
IFC 100
SAFETY INSTRUCTIONS 1
Release dateElectronic RevisionChanges and
2014-02-14ER 3.0.21MA IFC 100 R05
2014-08-01ER 3.1.01; 2-H; 2-M; 3-F; 3-P;
1 Incompatible change on status output: de-energised status reversed
1.2 Intended use
The electromagnetic flowmeters are designed exclusively to measure the flow and conductivity
of electrically conductive, liquid media.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
If the device is not used according to the operating conditions (refer to chapter "Technical data"),
the intended protection could be affected.
1.3 Certifications
CE marking
Documentation
compatibility
MA IFC 100 R05
3-C
The device fulfils the statutory requirements of the following EC directives:
• Low Voltage Directive 2006/95/EC
• EMC Directive 2004/108/EC
as well as
• EN 61010
• EMC specification acc. to EN 61326/A1
• NAMUR recommendations NE 21 and NE 43
The manufacturer certifies successful testing of the product by applying the CE marking.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
7
Page 8
1 SAFETY INSTRUCTIONS
1.4 Safety instructions from the manufacturer
1.4.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no
guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.
IFC 100
We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.
1.4.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.
8
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 9
IFC 100
1.4.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper
installation and operation of the devices (systems) will cause the warranty to be void. The
respective "Standard Terms and Conditions" which form the basis for the sales contract shall
also apply.
1.4.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the
information in this document and observe applicable national standards, safety requirements
and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of underneath icons.
SAFETY INSTRUCTIONS 1
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
9
Page 10
1 SAFETY INSTRUCTIONS
1.4.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This warning refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to
serious health problems and even death. There is also the risk of seriously damaging the device
or parts of the operator's plant.
IFC 100
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
• HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the
specified sequence.
iRESULT
RESULT
RESULTRESULT
This symbol refers to all important consequences of the previous actions.
1.5 Safety instructions for the operator
10
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and
maintained by properly trained and authorized personnel.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 11
IFC 100
2.1 Scope of delivery
INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
DEVICE DESCRIPTION 2
Figure 2-1: Scope of delivery
1 Device in the version as ordered
2 Documentation (calibration report, Quick Start, CD-ROM with product documentation for measuring sensor and signal
converter)
3 Signal cable (only for remote version)
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
11
Page 12
2 DEVICE DESCRIPTION
2.2 Device description
Electromagnetic flowmeters are designed exclusively to measure the flow and conductivity of
electrically conductive, liquid media.
Your measuring device is supplied ready for operation. The factory settings for the operating
data have been made in accordance with your order specifications.
The following versions are available:
• Compact version (the signal converter is mounted directly on the measuring sensor)
• Remote version (electrical connection to the measuring sensor via field current and signal
cable)
IFC 100
Figure 2-2: Device versions
1 Compact version as 45° version
2 Compact version as 0° version
3 Measuring sensor with connection box
4 Wall version
12
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 13
IFC 100
2.3 Nameplates
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
2.3.1 Nameplate (example)
Figure 2-3: Example of a nameplate
1 Manufacturer
2 Power supply data
3 Software version
4 Tag name
5 Approvals-related pressure and temperature thresholds
6 GK/GKL values (measuring sensor constants); size (mm /inches); field frequency; protection category; materials of
wetted parts
7 Product designation, serial number and manufacturing date
DEVICE DESCRIPTION 2
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
13
Page 14
3 INSTALLATION
3.1 General notes on installation
INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
3.2 Storage
• Store the device in a dry, dust-free location.
• Avoid continuous direct sunlight.
• Store the device in its original packing.
• Storage temperature: -40...+70°C / -40...+158°F
IFC 100
3.3 Transport
Signal converter
• No special requirements.
Compact version
• Do not lift the device by the signal converter housing.
• Do not use lifting chains.
• To transport flange devices, use lifting straps. Wrap these around both process connections.
3.4 Installation specifications
INFORMATION!
The following precautions must be taken to ensure reliable installation.
•
Make sure that there is adequate space to the sides.
•
Protect the signal converter from direct sunlight and install a sun shade if necessary.
•
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat
exchanger.
•
Do not expose the signal converter to intense vibrations. The measuring devices are tested
for a vibration level in accordance with IEC 68-2-64.
14
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 15
IFC 100
3.5 Mounting of the compact version
INFORMATION!
The signal converter is mounted directly on the measuring sensor. For installation of the
flowmeter, please observe the instructions in the supplied product documentation for the
measuring sensor.
3.6 Mounting the wall-mounted housing, remote version
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
3.6.1 Wall mounting
INSTALLATION 3
Figure 3-1: Mounting the wall-mounted housing
1 Prepare the holes with the aid of the mounting plate. For further information refer to
plate, wall-mounted version
2 Fasten the device securely to the wall with the mounting plate.
on page 97.
Mounting
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
15
Page 16
3 INSTALLATION
Mounting multiple devices next to each other
IFC 100
[mm][inch]
aØ6.5Ø0.26
b87.23.4
c2419.5
d31012.2
e25710.1
16
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 17
IFC 100
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
DANGER!
Observe the national regulations for electrical installations!
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
ELECTRICAL CONNECTIONS 4
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
4.2 Important notes on electrical connection
DANGER!
Electrical connection is carried out in conformity with the VDE 0100 directive "Regulations for
electrical power installations with line voltages up to 1000 V" or equivalent national regulations.
CAUTION!
•
Use suitable cable entries for the various electrical cables.
•
The measuring sensor and signal converter have been configured together at the factory. For
this reason, please connect the devices in pairs. Ensure that the measuring sensor constant
GK/GKL (see nameplates) are identically set.
•
If delivered separately or when installing devices that were not configured together, set the
signal converter to the DN size and GK/GKL of the measuring sensor, refer to Function tables
on page 56
.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
17
Page 18
4 ELECTRICAL CONNECTIONS
4.3 Electrical cables for remote device versions, notes
4.3.1 Notes on signal cable A
INFORMATION!
Signal cable A (type DS 300) with double shield ensures proper transmission of measured
values.
Observe the following notes:
• Lay the signal cable with fastening elements.
• It is permissible to lay the signal cable in water or in the ground.
• The insulating material is flame-retardant to EN 50265-2-1: 1997 and IEC 60322-1-2: 2005.
• The signal cable does not contain any halogens and is unplasticized, and remains flexible at
low temperatures.
• The connection of the inner shield (10) is carried out via the stranded drain wire (1).
• The connection of the outer shield (60) is carried out via the stranded drain wire (6).
4.3.2 Notes on field current cable C
IFC 100
DANGER!
A shielded 2-wire copper cable is used for the field current cable. The shielding MUST
MUST be
MUSTMUST
connected in the housing of the measuring sensor and signal converter.
INFORMATION!
The field current cable is not part of the scope of delivery.
18
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 19
IFC 100
ELECTRICAL CONNECTIONS 4
4.3.3 Requirements for signal cables provided by the customer
INFORMATION!
If the signal cable was not ordered, it is to be provided by the customer. The following
requirements regarding the electrical values of the signal cable must be observed:
Electrical safety
• To EN 60811 (Low Voltage Directive) or equivalent national regulations.
• Insulated conductor / insulated conductor 1000 V
• Insulated conductor / outer shield 1000 V
Twisting of the insulated conductors
• At least 10 twists per meter, important for screening magnetic fields.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
19
Page 20
4 ELECTRICAL CONNECTIONS
4.4 Preparing the signal and field current cables
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
4.4.1 Signal cable A (type DS 300), construction
• Signal cable A is a double-shielded cable for signal transmission between the measuring
sensor and signal converter.
• Bending radius: ≥ 50 mm / 2"
IFC 100
Figure 4-1: Construction of signal cable A
1 Stranded drain wire (1) for the inner shield (10), 1.0 mm
2 Insulated wire (2), 0.5 mm
3 Insulated wire (3), 0.5 mm
4 Outer sheath
5 Insulation layers
6 Stranded drain wire (6) for the outer shield (60)
2
Cu / AWG 20
2
Cu / AWG 20
2
Cu / AWG 17 (not insulated, bare)
20
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 21
IFC 100
ELECTRICAL CONNECTIONS 4
4.4.2 Preparing signal cable A, connection to signal converter
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
• Connection of the two shields in the signal converter is carried out via the stranded drain
wires.
• Bending radius: ≥ 50 mm / 2"
Required materials
• PVC insulating tube, Ø2.5 mm / 0.1"
• Heat-shrinkable tubing
• 2 wire end ferrules to DIN 46 228: E 1.5-8 for the stranded drain wires (1, 6)
• 2 wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)
Figure 4-2: Preparation of signal cable A
a = 80 mm / 3.15"
1 Strip the conductor to dimension a.
2 Cut off the inner shield (10) and the outer shield (60). Make sure not to damage the stranded
drain wires (1, 6).
3 Slide the insulating tubes over the stranded drain wires (1, 6).
4 Crimp the wire end ferrules onto the stranded drain wire.
5 Crimp the wire end ferrules onto the conductors (2, 3).
6 Pull the heat-shrinkable tubing over the prepared signal cable.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
21
Page 22
4 ELECTRICAL CONNECTIONS
4.4.3 Length of signal cable A
INFORMATION!
For temperatures of the medium above 150
intermediate socket are necessary. These are available including the changed electrical
connection diagrams.
°
C / 300°F, a special signal cable and a ZD
IFC 100
Measuring sensorNominal diameterMin. electrical
conductivity
DN [mm][inch]
OPTIFLUX 1000 F10...1503/8...65A1
OPTIFLUX 2000 F25...1501...620A1
200...12008...4820A2
OPTIFLUX 4000 F2.5...1501/10...65A1
200...12008...485A2
OPTIFLUX 5000 F2.5...1001/10...45A1
150...2506...105A2
OPTIFLUX 6000 F2.5...1501/10...65A1
WATERFLUX 3000 F25...6001...2420A1
[µS/cm]
Curve for signal
cable A
22
Figure 4-3: Maximum length of signal cable A
1 Maximum length of signal cable A between the measuring sensor and signal converter [m]
2 Maximum length of signal cable A between the measuring sensor and signal converter [ft]
3 Electrical conductivity of the medium being measured [μS/cm]
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 23
IFC 100
ELECTRICAL CONNECTIONS 4
4.4.4 Preparing field current cable C, connection to signal converter
DANGER!
A shielded 2-wire copper cable is used as the field current cable. The shielding MUST
connected in the housing of the measuring sensor and signal converter.
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
• Field current cable C is not part of the scope of delivery.
• Bending radius: ≥ 50 mm / 2"
Required materials:
• Shielded, at least 2-wire copper cable with suitable heat-shrinkable tubing
• Insulating tube, size according to the cable being used
• Wire end ferrules to DIN 46 228: size according to the cable being used
MUST be
MUSTMUST
Length and cross-section of field current cable C
LengthCross-section AF (Cu)
[m][ft]
0...1500...4922 x 0.75 Cu 12 x 18
150...300492...9842 x 1.5 Cu 12 x 14
300...600984...19682 x 2.5 Cu 12 x 12
1 Cu = copper cross-section
[mm2]
[AWG]
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
23
Page 24
4 ELECTRICAL CONNECTIONS
Figure 4-4: Field current cable C, preparation for the signal converter
a = 80 mm / 3.15"
1 Strip the conductor to dimension a.
2 If a stranded drain wire is present, remove the shield that is present. Make sure not to damage
the stranded drain wire.
3 Slide an insulating tube over the stranded drain wire.
4 Crimp a wire end ferrule onto the stranded drain wire.
5 Crimp the wire end ferrules on the conductors.
6 Pull a shrinkable tube over the prepared cable.
IFC 100
24
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 25
IFC 100
ELECTRICAL CONNECTIONS 4
4.4.5 Preparing signal cable A, connection to measuring sensor
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
• The outer shield (60) is connected in the terminal compartment of the measuring sensor
directly via the shield and a clip.
• Bending radius: ≥ 50 mm / 2"
Required materials
• PVC insulating tube, Ø2.0...2.5 mm / 0.08...0.1"
• Heat-shrinkable tubing
• Wire end ferrule to DIN 46 228: E 1.5-8 for the stranded drain wire (1)
• 2 wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)
Figure 4-5: Preparing signal cable A, connection to measuring sensor
a = 50 mm / 2"
b = 10 mm / 0.39"
1 Strip the conductor to dimension a.
2 Trim the outer shield (60) to dimension b and pull it over the outer sheath.
3 Remove the stranded drain wire (6) of the outer shield and the inner shield. Make sure not to
damage the stranded drain wire (1) of the inner shield.
4 Slide an insulating tube over the stranded drain wire (1).
5 Crimp the wire end ferrules onto conductors 2 and 3 and the stranded drain wire (1).
6 Pull the heat-shrinkable tubing over the prepared signal cable.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
25
Page 26
4 ELECTRICAL CONNECTIONS
4.4.6 Preparing field current cable C, connection to measuring sensor
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
• The field current cable is not included in delivery.
• The shield is connected in the terminal compartment of the measuring sensor directly via the
shield and a clip.
• Bending radius: ≥ 50 mm / 2"
Required materials
• Shielded 2-wire insulated copper cable
• Insulating tube, size according to the cable being used
• Heat-shrinkable tubing
• Wire end ferrules to DIN 46 228: size according to the cable being used
IFC 100
Figure 4-6: Preparation of field current cable C
a = 50 mm / 2"
b = 10 mm / 0.4"
1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp wire end ferrules onto both conductors.
4 Pull a shrinkable tube over the prepared cable.
26
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 27
IFC 100
ELECTRICAL CONNECTIONS 4
4.5 Connecting the signal and field current cables
DANGER!
Cables may only be connected when the power is switched off.
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
27
Page 28
4 ELECTRICAL CONNECTIONS
4.5.1 Connecting the signal and field current cables to the signal converter, remote
version
INFORMATION!
The compact version is supplied preassembled from the factory.
Open housing
Figure 4-7: Open housing
IFC 100
1 Loosen the 4 screws with a suitable tool.
2 Lift the housing at the top and bottom at the same time.
3 Slide the housing cover upward.
4 The housing cover is guided and held by the inside hinge.
28
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 29
IFC 100
ELECTRICAL CONNECTIONS 4
Connecting the signal and field current cables
Figure 4-8: Function of the electrical connection terminal
Connect the electrical conductors as follows:
1 Push the lever downwards with a screwdriver in good condition (blade: 3.5 mm wide and
0.5 mm thick).
2 Insert the electrical conductor into the plug.
3 The conductor will be clamped as soon as the lever is released.
Figure 4-9: Connecting the signal and field current cables
1 Cable entry for field current cable
2 Cable entry for signal cable
3 Connecting the field current cable shield
4 Electrical conductor (7)
5 Electrical conductor (8)
6 Stranded drain wire (1) of the inner shield (10) of the signal cable
7 Electrical conductor (2)
8 Electrical conductor (3)
9 Stranded drain wire (S) of the outer shield (60)
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
29
Page 30
4 ELECTRICAL CONNECTIONS
4.5.2 Connection diagram for signal and field current cable
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
IFC 100
• A shielded 2-wire copper cable is used as the field current cable. The shielding MUST
MUST be
MUSTMUST
connected in the housing of the measuring sensor and signal converter.
• The outer shield (60) is connected in the terminal compartment of the measuring sensor
directly via the shield and a clip.
• Bending radius of signal and field current cable: ≥ 50 mm / 2"
• The following illustration is schematic. The positions of the electrical connection terminals
may vary depending on the housing version.
Figure 4-10: Connection diagram for signal and field current cable
1 Electrical terminal compartment in signal converter
2 Signal cable A
3 Field current cable C
4 Electrical terminal compartment in measuring sensor
5 Functional ground FE
30
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 31
IFC 100
4.6 Grounding the measuring sensor
4.6.1 Classical method
CAUTION!
There should be no difference in potential between the measuring sensor and the housing or
protective earth of the signal converter!
• The measuring sensor must be properly grounded.
• The grounding cable should not transmit any interference voltages.
• Do not use the grounding cable to connect any other electrical devices to ground at the same
time.
• The measuring sensors are connected to ground by means of a functional grounding
conductor FE.
• Special grounding instructions for the various measuring sensors are provided in the
separate documentation for the measuring sensor.
• The documentation for the measuring sensor also contain descriptions on how to use
grounding rings and how to install the measuring sensor in metal or plastic pipes or in pipes
which are coated on the inside.
ELECTRICAL CONNECTIONS 4
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
31
Page 32
4 ELECTRICAL CONNECTIONS
4.7 Connecting the power supply
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
• The housings of the devices, which are designed to protect the electronic equipment from
dust and moisture, should be kept well closed at all times. Creepage distances and
clearances are dimensioned to VDE 0110 and IEC 664 for pollution severity 2. Supply circuits
are designed for overvoltage category III and the output circuits for overvoltage category II.
• Fuse protection (I
breaker) to isolate the signal converter must be provided.
≤ 16 A) for the infeed power circuit, and also a separator (switch, circuit
N
IFC 100
Figure 4-11: Terminal compartment for power supply
1 Retaining band of the cover
2 Cable entry for power supply, remote version
3 Cable entry for power supply, compact version
Version overview
VersionNon-ExEx
100...230 VACStandardOptional
24 VDCStandard-
24 VAC/DCStandardOptional
32
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 33
IFC 100
ELECTRICAL CONNECTIONS 4
• Open the cover of the electrical terminal compartment by pressing down and pulling forwards
at the same time.
Figure 4-12: Power supply connection
1 100...230 VAC (-15% / +10%), 8 VA
2 24 VDC (-55% / +30%), 4 W
3 24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 7 VA or 4 W
• Close the cover after the power has been connected.
• AC: Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
• AC/DC: When connecting to functional extra-low voltages, provide a facility for protective
separation (PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).
INFORMATION!
12 V is not
not included in the tolerance range.
notnot
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
33
Page 34
4 ELECTRICAL CONNECTIONS
4.8 Inputs and outputs, overview
4.8.1 Description of the CG number
Figure 4-13: Marking (CG number) of the electronics module and output variants
1 ID number: 0
2 ID number: 0 = standard; 9 = special
3 Power supply
4 Display (language versions)
5 Output version
4.8.2 Fixed, non-alterable output versions
This signal converter is available with various output combinations.
IFC 100
• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Connection terminal A+ is only operable in the basic output version.
Basic outputs (I/O) (Standard)
CG no.Connection terminals
CC-DD-SA+AA-
1 0 0Sp/ Cp passive 1Pp / Sp passive 1
1 Function change by software
2 Shielding
3 Function changed by reconnecting
Description of the used abbreviations
I
I
a
P
p
S
p
C
p
Current output active or passive
p
Pulse/frequency output passive
Status output / limit switch passive
Control input passive
2
Ia + HART® active 3
Ip + HART® passive 3
34
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 35
IFC 100
ELECTRICAL CONNECTIONS 4
Ex i, Profibus PA + DP, Foundation Fieldbus and Modbus (I/O) (Option)
CG no.Connection terminals
DD-SCC-BB-
Ex i (Option)
3 0 0Pp / Sp passive 1
2
Ip + HART® passive
PROFIBUS PA (Option)
D 0 0PA+ (1)PA+ (2)
2
PA- (1)PA- (2)
FOUNDATION Fieldbus (Option)
E 0 0V/D+ (1)V/D+ (2)
2
V/D- (1)V/D- (2)
PROFIBUS DP (Option)
F 0 0RxD/TxD+ /
P/ +B (1)
RxD/TxD- /
N/ -A (1)
2
Termination
N/ -T
Termination
P/ +T
RxD/TxD+ /
P/ +B (2)
RxD/TxD- /
N/ -A (2)
Modbus (Option)
G 0 0Pp / Sp passive
1 Function change by software
2 Shielding
INFORMATION!
Supplementary instructions related to the communication busses Foundation Fieldbus, Profibus
PA/DP and Modbus are available on the website (Download Center).
2
+3.3 V; 560 ΩCommonSign. A (D0-)Sign. B (D1+)
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
35
Page 36
4 ELECTRICAL CONNECTIONS
4.9 Description of the inputs and outputs
4.9.1 Current output
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power U
• Active mode:
Load impedance R
• Self-monitoring: interruption or load impedance too high in the current output loop
• Error message possible via status output, error indication on LC display.
• Current value error detection can be adjusted.
• Automatic range conversion via threshold. The setting range for the threshold is between 5
and 80% of Q
1:20 to 1:1.25).
Signaling of the active range possible via a status output (adjustable).
• Forward/reverse flow measurement (F/R mode) is possible.
100%
≤ 32 VDC at I ≤ 22 mA
ext
≤ 750 Ω at I ≤ 22 mA
L
, ± 0...5% hysteresis (corresponding ratio from smaller to larger range of
IFC 100
INFORMATION!
For further information refer to Connection diagrams of outputs on page 41
Technical data on page 85
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
36
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 37
IFC 100
4.9.2 Pulse output and frequency output
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
For the basic I/O signal converter:
For the basic I/O signal converter:
For the basic I/O signal converter:For the basic I/O signal converter:
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 100 mA at f ≤ 100 Hz
For the Ex i I/O signal converter:
For the Ex i I/O signal converter:
For the Ex i I/O signal converter:For the Ex i I/O signal converter:
NAMUR characterictic 4.7 mA / 0.77 mA at f ≤ 10 kHz (over range up to f
For the Modbus I/O signal converter:
For the Modbus I/O signal converter:
For the Modbus I/O signal converter:For the Modbus I/O signal converter:
I ≤ 100 mA at f ≤ 1 kHz (over range up to f
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q
fixed (pulse width adjustable as required from 0.05 ms...2 s)
• Forward/reverse flow measurement (F/R mode) is possible.
• The pulse output and frequency output can also be used as a status output / limit switch.
≤ 32 VDC
ext
ELECTRICAL CONNECTIONS 4
≤ 12 kHz)
max
≤ 12 kHz)
max
≤ 1.2 kHz)
max
);
100%
)
100%
INFORMATION!
For further information refer to Connection diagrams of outputs on page 41
Technical data on page 85
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
37
Page 38
4 ELECTRICAL CONNECTIONS
4.9.3 Status output and limit switch
• The status outputs / limit switches are electrically isolated from each other and from all
other circuits.
• The output stages of the status outputs / limit switches behave like relay contacts.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
For the Ex i I/O signal converter:
For the Ex i I/O signal converter:
For the Ex i I/O signal converter:For the Ex i I/O signal converter:
NAMUR characterictic 4.7 mA / 0.77 mA
• For information on the adjustable operating states refer to
INFORMATION!
For further information refer to Connection diagrams of outputs on page 41
Technical data on page 85
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
.
≤ 32 VDC; I ≤ 100 mA
ext
Function tables
and refer to
IFC 100
on page 56.
38
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 39
IFC 100
4.9.4 Control input
INFORMATION!
Which I/O version and inputs/outputs are installed in your signal converter are indicated on the
sticker in the cover of the terminal compartment.
• All control inputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
• For information on the adjustable operating states refer to
INFORMATION!
For further information refer to Connection diagrams of outputs on page 41
Technical data on page 85
ELECTRICAL CONNECTIONS 4
≤ 32 VDC
ext
Function tables
.
on page 56.
and refer to
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
39
Page 40
4 ELECTRICAL CONNECTIONS
4.10 Electrical connection of the outputs
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
4.10.1 Electrical connection of the outputs
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
IFC 100
Figure 4-14: Connection of outputs
1 Cable entry, remote version
2 Cable entry, compact version
3 Terminal S for shield
• Open the housing cover
• Push the prepared cables through the cable entries and connect the necessary conductors.
• Connect the shield.
• Close the housing cover.
INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.
40
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 41
IFC 100
4.10.2 Laying electrical cables correctly
Figure 4-15: Protect housing from dust and water
1 For compact versions with nearly horizontally-oriented cable entries, lay the necessary elec-
tric cables with a drip loop as shown in the illustration.
2 Tighten the screw connection of the cable entry securely.
3 Seal cable entries that are not needed with a plug.
4.11 Connection diagrams of outputs
ELECTRICAL CONNECTIONS 4
4.11.1 Important notes
• All groups are electrically isolated from each other and from all other output circuits.
• Passive mode: An external power supply is necessary to operate (activation) the subsequent
devices (U
• Active mode: The signal converter supplies the power for operation (activation) of the
subsequent devices, observe max. operating data.
• Terminals that are not used should not have any conductive connection to other electrically
conductive parts.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
Description of the used abbreviations
I
a
P
p
S
p
C
p
ext
I
p
).
Current output active or passive
Pulse/frequency output passive
Status output / limit switch passive
Control input passive
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
41
Page 42
4 ELECTRICAL CONNECTIONS
4.11.2 Description of the electrical symbols
mA meter
0...20 mA or 4...20 mA and other
RL is the internal resistance of the measuring point including the cable
resistance
DC voltage source (U
), external power supply, any connection polarity
ext
IFC 100
Table 4-1: Description of symbols
DC voltage source (U
connection diagrams
Internal DC voltage source
Controlled internal power source in the device
Electronic or electromagnetic counter
At frequencies above 100 Hz, shielded cables must be used to connect the
counters.
Ri Internal resistance of the counter
Button, NO contact or similar
), observe connection polarity according to
ext
42
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 43
IFC 100
4.11.3 Basic outputs
CAUTION!
Observe connection polarity.
Current output active (HART®)
• U
int, nom
• I ≤ 22 mA
≤ 750 Ω
• R
L
®
• HART
at connection terminals A
ELECTRICAL CONNECTIONS 4
= 20 VDC
Figure 4-16: Current output active I
a
Current output passive (HART®)
• U
• U
• I ≤ 22 mA
• U
• R
• HART® at connection terminals A
= 20 VDC
int, nom
≤ 32 VDC
ext
≥ 2 V at I = 22 mA
0
L
≤ (U
ext-U0
)/I
max
Figure 4-17: Current output passive I
p
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
43
Page 44
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Shielding takes place at the electrical connection (S) of the output terminal block.
•
Any connection polarity.
Pulse/frequency output passive (standard)
• U
• f
• f
• The minimum load impedance R
• Can also be set as status output; for the electrical connection refer to status output
• The output is open if the device is de-energised.
≤ 32 VDC
ext
in the operating menu set to f
max
I ≤ 100 mA
R
≤ 47 kΩ
L
closed:
≤ 0.2 V at I = 10 mA
U
0
U
≤ 2 V at I = 100 mA
0
open:
I ≤ 0.05 mA at U
in operating menu set to 100 Hz < f
max
(over range up to f
ext
= 32 V
≤ 12 kHz)
max
I ≤ 20 mA
R
≤ 10 kΩ for f ≤ 1kHz
L
≤ 1kΩ for f ≤ 10 kHz
R
L
closed:
U
≤ 1.5 V at I = 1 mA
0
U
≤ 2.5 V at I = 10 mA
0
≤ 5 V at I = 20 mA
U
0
open:
I ≤ 0.05 mA at U
L, min
=(U
ext-U0
R
ext
= 32 V
)/I
max
connection diagram.
L, min
≤ 100 Hz:
max
≤ 10 kHz:
max
is calculated as follows:
IFC 100
44
Figure 4-18: Pulse/frequency output passive P
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
p
Page 45
IFC 100
ELECTRICAL CONNECTIONS 4
Pulse/frequency output passive (Modbus)
• U
• f
• The minimum load impedance R
• Can also be set as status output; for the electrical connection refer to status output
• The output is open if the device is de-energised.
INFORMATION!
Any connection polarity.
≤ 32 VDC
ext
in the operating menu set to f
max
I ≤ 100 mA
≤ 47 kΩ
R
L
closed:
U
U
=0.2V at I≤ 10 mA
0, max
= 2 V at I ≤ 100 mA
0, max
open:
I ≤ 0.05 mA at U
R
L, min
=(U
ext-U0
= 32 VDC
ext
)/I
max
connection diagram.
≤ 1kHz:
max
is calculated as follows:
L, min
Status output / limit switch passive
• U
• I ≤ 100 mA
• R
• The output is open if the device is de-energised.
Figure 4-19: Status output / limit switch passive S
≤ 32 VDC
ext
= 47 kΩ
L
closed:
U
≤ 0.2 V at I = 10 mA
0
≤ 2 V at I = 100 mA
U
0
open:
I ≤ 0.05 mA at U
ext
= 32 V
p
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
45
Page 46
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Any connection polarity.
Control input passive
• U
• I
• Switching point for identifying "contact open or closed":
• Can also be set as a status output; for the electrical connection refer to status output
≤ 32 VDC
ext
= 6.5 mA at U
nom
= 8.2 mA at U
I
nom
ext
ext
Contact open (off): U
Contact closed (on): U
connection diagram.
= 24 VDC
= 32 VDC
≤ 2.5 V with I
0
≥ 8 V with I
0
= 0.4 mA
nom
= 2.8 mA
nom
IFC 100
Figure 4-20: Control input passive C
1 Signal
p
46
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 47
IFC 100
4.11.4 Ex i outputs
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
CAUTION!
•
Observe connection polarity.
INFORMATION!
•
For further information on electrical connection refer to Description of the inputs and outputs
on page 36
Current output passive (HART®)
• U
• I ≤ 22 mA
• U
• R
• HART® at connection terminals C
≤ 32 VDC
ext
≥ 4 V
0
L, min
=(U
.
ext-U0
)/I
ELECTRICAL CONNECTIONS 4
max
Figure 4-21: Current output passive Ip Exi
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
47
Page 48
4 ELECTRICAL CONNECTIONS
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
CAUTION!
•
Observe connection polarity.
Pulse/frequency output passive to NAMUR
• Connection acc. to EN 60947-5-6
• open:
= 0.77 mA
I
nom
closed:
I
= 4.7 mA
nom
• The output is closed when the device is de-energised.
IFC 100
Figure 4-22: Pulse/frequency output passive PN to NAMUR EN 60947-5-6 Ex i
INFORMATION!
•
Any connection polarity.
Status output / limit switch to NAMUR
• Connection acc. to EN 60947-5-6
• open:
= 0.77 mA
I
nom
closed:
I
= 4.7 mA
nom
• The output is closed when the device is de-energised.
48
Figure 4-23: Status output / limit switch SN to NAMUR EN 60947-5-6 Ex i
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 49
IFC 100
4.11.5 HART® connection
INFORMATION!
The current output always has HART
•
Basic I/O: connection terminals A+/A-/A
•
Ex i I/O: connection terminals C-/C
®
All HART
passively.
Example for active HART® connection (point-to-point)
connections (point-to-point and multi-drop operation) both work actively and
®
capability.
ELECTRICAL CONNECTIONS 4
Figure 4-24: HART® connection active (Ia)
1 HART
®
communicator
The parallel resistance to the HART® communicator must be R ≥ 230 Ω.
Example for passive HART® connection (multi-drop mode)
• I: I0% ≥ 4mA
• Multi-drop mode I: I
• U
≤ 32 VDC
ext
• R ≥ 230 Ω
≥ 4mA = I
fix
0%
Figure 4-25: HART® connection passive (Ip)
1 HART
2 Other devices with HART
®
communicator
®
capability
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
49
Page 50
5 START-UP
5.1 Switching on the power
Before connecting to power, please check that the system has been correctly installed.
This includes:
• The device must be mechanically safe and mounted in compliance with the regulations.
• The power connections must have been made in compliance with the regulations.
• The electrical terminal compartments must be secured and the covers have been screwed
on.
• Check that the electrical operating data of the power supply are correct.
• Switching on the power.
5.2 Starting the signal converter
The measuring device, consisting of the measuring sensor and the signal converter, is supplied
ready for operation. All operating data have been set at the factory in accordance with your order
specifications.
IFC 100
When the power is switched on, a self test is carried out. After that the device immediately
begins measuring, and the current values are displayed.
Figure 5-1: Displays in measuring mode (examples for 2 or 3 measured values)
x, y and z denote the units of the measured values displayed
It is possible to change between the two measured value windows, the trend display and the list
with the status messages by pressing the keys ↑ and ↓. For information about possible status
messages, their meaning and cause refer to
page 77.
Status messages and diagnostic information
on
50
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 51
IFC 100
6.1 Display and operating elements
Figure 6-1: Display and operating elements (Example: flow indication with 2 measuring values)
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 Indicates when a key has been pressed
4 1st measured variable in large representation
5 Bargraph indication
6 Keys (see table below for function and representation in text)
OPERATION 6
INFORMATION!
•
After 5 minutes of inactivity, there is an automatic return to measuring mode. Previously
changed data is not saved.
KeyMeasuring modeMenu modeSubmenu or function
mode
>Switch from measuring
mode to menu mode;
press key for 2.5 s,
"quick start" menu is
then displayed
^Reset of displayReturn to measuring
↓ or ↑Switch between display
pages: measured
value 1 + 2, trend page
and status page
Esc (> + ↑)--Return to menu mode
Table 6-1: Description of key functionality
Access to displayed
menu, then 1st
submenu is displayed
mode but prompt
whether the data should
be saved
Select menuSelect submenu or
Access to displayed
submenu or function
Press 1 to 3 times,
return to menu mode,
data saved
function
without acceptance of
data
Parameter and data
mode
For numerical values,
move cursor
(highlighted in blue) one
position to the right
Return to submenu or
function, data saved
Use cursor highlighted
in blue to change
number, unit, property
and to move the decimal
point
Return to submenu or
function without
acceptance of data
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
51
Page 52
6 OPERATION
6.1.1 Display in measuring mode with 2 or 3 measured values
Figure 6-2: Example for display in measuring mode with 2 or 3 measured values
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 1st measured variable in large depiction
4 Bargraph indication
5 Depiction with 3 measured values
6.1.2 Display for selection of sub-menu and functions, 3 lines
IFC 100
Figure 6-3: Display for selection of submenu and functions, 3 lines
1 Indicates a possible status message in the status list
2 Menu, submenu or function name
3 Number relating to 6
4 Indicates position within menu, submenu or function list
5 Next menu(s), submenu or function
(_ _ _ signalise in this line the end of the list)
6 Current menu(s), submenu or function
7 Previous menu(s), submenu or function
(_ _ _ signalise in this line the beginning of the list)
52
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 53
IFC 100
6.1.3 Display when setting parameters, 4 lines
Figure 6-4: Display when setting parameters, 4 lines
1 Current menu(s), submenu or function
2 Number relating to 7
3 Denotes factory setting
4 Denotes permissible value range
5 Permissible value range for numeric values
6 Currently set value, unit or function (when selected, appears with white text, blue background)
This is where the data is changed.
7 Current parameter
8 Factory setting of parameter
OPERATION 6
6.1.4 Display when previewing parameters, 4 lines
Figure 6-5: Display when previewing parameters, 4 lines
1 Current menu(s), submenu or function
2 Number relating to 6
3 Denotes a changed parameter (simple check of changed data when browsing through lists)
4 Next parameter
5 Currently set data from 6
6 Current parameter (for selection press key >; then see previous chapter)
7 Factory setting of parameter
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
53
Page 54
6 OPERATION
6.2 Menu structure
INFORMATION!
•
The menu structure for the standard device (HART®) is described. The functions for Modbus,
Foundation Fieldbus and Profibus are described in detail in the corresponding supplementary
instructions.
•
Note the key function within and between the columns.
IFC 100
Measuring modeSelect
menu↓ ↑
^Press
>2.5s
A quick setup> ^A1 language> ^->
^B test> ^B1 simulation> ^Submenus on page 58>
↓↑↓↑↓↑↓↑ >
Select menu and/or submenu
↓↑
A2 tag> ^-
A3 reset> ^A3.1 reset errors
A3.2 counter 1
A3.3 counter 2
A4 analogue outputs> ^A4.1 measurement
A4.2 unit
A4.3 range
A4.4 low flow cutoff
A4.5 time constant
A5 digital outputs> ^A5.1 measurement
A5.2 pulse value unit
A5.3 value p. pulse
A5.4 low flow cutoff
A7 process input> ^A7.1 device serial no.
A7.2 zero calibration
A7.3 size
A7.5 GKL
A7.6 coil resistance Rsp
A7.7 calib. coil temp.
A7.8 target conduct.
A7.9 EF electr. factor
A7.10 field frequency
A7.11 flow direction
B2 actual values
B3 information
Select
function
and set
data
↓↑ >
^
^
54
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 55
IFC 100
OPERATION 6
Measuring modeSelect
menu↓ ↑
^Press
>2.5s
C setup> ^C1 process input> ^C1.1 calibration>
^> ^C2 I/O (Input/Output)> ^C2.1 hardware>
^> ^C3 I/O counter> ^C3.1 counter 1>
^> ^C4 I/O HART> ^C4.1 PV is>
^> ^C5 device> ^C5.1 device info>
↓ ↑↓ ↑↓ ↑↓ ↑ >
Select menu and/or submenu
↓↑
C1.2 filter
C1.3 self test
C1.4 information
C1.5 simulation
C2._ current output X
C2._ frequency out X
C2._ pulse output X
C2._ status output X
C2._ control input X
C2._ limit switch X
C3.2 counter 2
C4.2 SV is
C4.3 TV is
C4.4 4V is
C4.5 HART units
C5.2 display
C5.3 1. meas. page
C5.4 2. meas. page
C5.5 graphic page
C5.6 special functions
C5.7 units
C5.8 HART
C5.9 quick setup
Select
function
and set
data
↓↑ >
^
^
^
^
^
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
55
Page 56
6 OPERATION
6.3 Function tables
INFORMATION!
•
The following tables describe the functions of the standard device with HART® connection.
The functions for Modbus, Foundation Fieldbus and Profibus are described in detail in the
corresponding supplementary instructions.
•
Depending on the device version, not all functions are available.
6.3.1 Menu A, quick setup
No.FunctionSetting / Description
A1 language
A1languageLanguage selection depends on the device version.
A2 tag
A2tag
Measuring point identifier (Tag no.) (also for HART® operation) appears in
the LCD header (max. 8 digits).
IFC 100
A3 reset?
A3reset?Reset error or counter.
A3.1reset errorsreset errors? Select: no / yes
A3.2reset counter 1reset counter? Select: no / yes (available if activated in C5.9.1)
A3.3reset counter 2reset counter? Select: no / yes (available if activated in C5.9.2)
A4 analogue outputs (only for HART®)
A4analogue outputsApplicable to current output (terminal A or C), frequency output (terminal D),
A4.1measurement1) Select: volume flow / mass flow / diagnosis value / flow speed / coil
A4.2unitSelection of the unit from a list, depending on the "measurement"
A4.3range1) Setting for main current output (range: 0...100%)
A4.4low flow cutoff1) Setting for main current output (sets output value to "0")
A4.5time constant1) Setting for main current output (applicable to all flow measurements)
limit switch (terminal C and/or D) and the 1st display page / line 1
temperature / conductivity
2) Use for all outputs? (also use this setting for Fct. A4.2...A4.5!)
Setting: no (applies only to the main current output ) / yes (applies to all
analogue outputs)
Setting: 0…x.xx (format and unit, depending on measurement, see A4.1 and
A4.2 above)
2) Use for all outputs? Make setting, see Fct. A4.1 above!
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A4.1 above!
Setting: xxx.x s (range: 000.1…100 s)
2) Use for all outputs? Make setting, see Fct. A4.1 above!
A4 station address (only for PROFIBUS)
A4station addressSetting of device address.
56
The functions are described in detail in the supplementary instructions.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 57
IFC 100
OPERATION 6
No.FunctionSetting / Description
A4 slave address (only for MODBUS)
A4slave addressSetting of device address.
The functions are described in detail in the supplementary instructions.
A5 digital outputs (only for HART®)
A5digital outputsValid for pulse output (terminal D) and counter 1.
A5.1measurement1) Select the "measurement": volume flow / mass flow
2) Use for all outputs? (also use this setting for Fct. A5.2...A5.4!)
Setting: no (only for pulse output D) / yes (for all digital outputs)
A5.2pulse value unitSelection of the unit from a list, depending on the measurement
A5.3value p. pulse1) Setting for pulse output D (volume or mass value per pulse)
A5.4low flow cutoff1) Setting for pulse output D (sets output value to "0")
Setting: xxx.xxx in l or kg or in the unit selected in A5.2
2) Use for all outputs? Make setting, see Fct. A5.1 above!
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A5.1 above!
A7 process input
A7.1device serial no.Shows the serial no. of the system.
The following process input parameters are only available, if the quick access has been activated in the menu "setup /
device / quick setup".
A7.2zero calibrationDisplay of actual zero calibration value.
Query: calibrate zero?
Settings see Fct. C1.1.1.
A7.3sizeSelect from the size table.
A7.5GKLSet value acc. to information on nameplate; range: 0.5…20
A7.6coil resistance RspField coil resistance at 20°C; range: 10.00...220 Ω
A7.7calib. coil temp.The coil temperature is derived from the coil resistance at the reference
A7.8target conduct.Reference value for on-site calibration; range: 1.000...50000 μS/cm
A7.9EF electr. factorFor calculation of the conductivity based on the electrode impedance.
A7.10field frequencySetting as on the nameplate of the measuring sensor =
A7.11flow directionDefine the polarity of the flow direction.
temperature.
Settings see Fct. C1.1.8.
Settings see Fct. C1.1.11.
line frequency x value (from the following list):
1/2; 1/4; 1/6; 1/8; 1/12; 1/18; 1/36; 1/50
Select:
normal direction (according to the arrow on the measuring sensor) /
reverse direction (in the opposite direction to the arrow)
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
57
Page 58
6 OPERATION
IFC 100
6.3.2 Menu B, test
No.FunctionSetting / Description
B1 simulation
B1simulationThe displayed values are simulated.
B1.1flow speedSimulation of the flow speed.
Select:
break (exit function without simulation) /
set value (range: -12…+12 m/s; unit selection in Fct. C5.7.7)
Query: start simulation?
Settings:
no (exit function without simulation) / yes (start simulation)
B1.2volume flowSimulation of volume flow, sequence and settings similar to B1.1, see above!
B1._current out X[_ stands for Fct. B1.3...1.6]
B1._pulse output X
B1._frequency out X
B1._control input X
B1._limit switch X
B1._status output X
simulation X
[X stands for one of the connection terminals A, C or D]
Sequence and settings similar to B1.1, see above!
For the pulse output the set number of pulses are displayed once in a
second!
B2 actual values
B2actual valuesDisplay of actual values;
B2.1operating hoursDisplay the actual operating hours;
B2.2act. flow speedDisplay the actual flow speed;
B2.3act. coil temp.See also Fct. C1.1.7...C1.1.8.
B2.4electr. temperatureDisplay the actual electronics temperature; exit the displayed function with
B2.5act. conductivitySee also Fct. C1.3.1...C1.3.2
B2.6act. electr. noiseSee also Fct. C1.3.13...C1.3.15
B2.8act. coil resistanceDisplay the actual resistance of the field coils.
Exit the displayed function with the ^ key.
Exit the displayed function with the ^ key.
Exit the displayed function with the ^ key.
the ^ key.
58
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 59
IFC 100
OPERATION 6
B3 information
B3informationLC display (this format description is only valid for B3.2....3.5 and B3.8)
B3.1C numberCG number, cannot be changed (input/output version)
B3.2process inputProcess input part of the electronics
B3.3SW.REV.MSInformation about the main software
B3.4SW.REV.UISInformation about the user interface software of the measuring device
B3.5"bus interface"Only appears with Profibus, Modbus and FF and shows the information about
B3.6device serial no.Serial no. of the system
B3.7electronic serial no.Serial number of the electronics assembly
B3.8Electronic Revision ERReference identification number, electronic revision and production date of
1st line: ID no. of the circuit board
2nd line: software version
3rd line: production date
the corresponding interface software.
the device; includes all hardware and software changes
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
59
Page 60
6 OPERATION
IFC 100
6.3.3 Menu C, setup
No.FunctionSettings / descriptions
C1 process input
C1.1 calibration
C1.1calibrationGrouping of all functions related to measuring sensor calibration.
C1.1.1zero calibrationDisplay of actual zero calibration value.
calibrate zero?
Select:
break (return with ^ key)
standard (factory setting) /
manual (display last value, set new value,
range: -1.00…+1 m/s) /
automatic (shows the current value as the new zero calibration value)
C1.1.2sizeSelect from the size table.
C1.1.5GKLSet value acc. to the information on the nameplate.
Range: 0.5…20
C1.1.7coil resistance RspField coil resistance at 20°C.
Range: 10.00...220 Ω
C1.1.8calib. coil temp.The coil temperature is derived from the coil resistance at the reference
C1.1.9densityCalculation of the mass flow with constant product density.
C1.1.10target conduct.Reference value for on-site calibration.
C1.1.11EF electr. factorFactor for the calculation of the conductivity based on the electrode
C1.1.13field frequencySetting as on the nameplate of the measuring sensor.
C1.1.14select settlingMode of the settling time (special function).
C1.1.15settling timeOnly when "manual" selected in Fct. C1.1.14; range: 1.0…250 ms
temperature.
Set coil temperature:
break (return with ^ key) /
standard (= 20°C) /
automatic (set current temperature);
range: -40.0…+200°C
Set coil resistance:
break (return with ^ key) /
standard (= setting of Fct. C1.1.7) /
automatic (= calibration with the current resistance)
Range: 0.1…5kg/l
Range: 1.000...50000 µS/cm
impedance.
Query: calibrate EF?
Select:
break (return with ^ key) /
standard (with factory setting) /
manual (set desired value) /
automatic (determines EF according to the setting in Fct. C1.1.10)
= line frequency x value (from the following list):
1/2; 1/4; 1/6; 1/8; 1/12; 1/18; 1/36; 1/50
Select:
standard (fixed allocation) /
manual (manual time setting for the settling time for the field current)
60
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 61
IFC 100
OPERATION 6
No.FunctionSettings / descriptions
C1.1.16line frequencySetting the line frequency to one value.
Select:
50 Hz / 60 Hz
C1.1.17act. coil resistanceDisplay of the actual resistance of the field coil.
C1.2 filter
C1.2filterGrouping of all functions related to filter of measuring sensor electronics.
C1.2.1limitationLimitation of all flow values, before smoothing by time constant; affects all
C1.2.2flow directionDefine the polarity of the flow direction.
C1.2.3time constantFor all flow measurements and outputs.
C1.2.4pulse filterSuppresses disturbances due to solids, air/gas bubbles and sudden changes
C1.2.5pulse widthLength of interference and delays to be suppressed on sudden changes in
C1.2.6pulse limitationDynamic limitation from one measured value to the next; only if the pulse
C1.2.7noise filterSuppresses noise at low conductivity, high solids content, air and gas
C1.2.8noise levelRange within which changes are evaluated as noise, and outside of which
C1.2.9noise suppressionSet noise suppression (only if the noise filter is set to "on" in Fct. C1.2.7).
outputs.
Settings: -xxx.x / +xxx.x m/s; condition: 1st value < 2nd value
Range 1st value: -100.0 m/s ≤ value ≤ -0.001 m/s
Range 2nd value: +0.001 m/s ≤ value ≤ +100 m/s
Select:
normal direction (according to the arrow on the measuring sensor) /
reverse direction (in the opposite direction to the arrow)
xxx.x s; range: 0.0…100 s
in pH.
Select:
off (without pulse filter) /
on (with pulse filter) /
automatic (with new pulse filter)
Pulse filter "on":
Pulse filter "on": The change from one measurement value to the next one is
Pulse filter "on":Pulse filter "on":
limited to the value "pulse limitation" for the total time "pulse width".
This filter allows a faster signal tracking for slowly changing flow values.
Pulse filter "automatic":
Pulse filter "automatic": The raw flow values are collected into a buffer,
Pulse filter "automatic":Pulse filter "automatic":
covering two times the "pulse width" values. This filter is called "median"
filter.
This filter allows a better suppression of pulse shaped disturbances
(particles or air bubbles in very noisy environment).
flow.
Only available, if the pulse filter is set to "on" or "automatic" in Fct. C1.2.4.
xx.x s; range for "on": 0.01…10 s or for "automatic": 0.1...20 s
filter is set to "on" in Fct. C1.2.4.
xx.x s; range: 0.01...100 m/s
bubbles, and chemically inhomogeneous media.
Select:
off (without noise filter) /
on (with noise filter)
changes are evaluated as flow (only if the noise filter is set to "on" in
Fct. C1.2.7).
C1.3.2limit empty pipeOnly available if "empty pipe [..]" is activated in Fct. C1.3.1.
Range: 0.0…9999 μS (set about 50% of the lowest occurring conductivity in
operation. Conductivity below this value means a signal as "empty pipe".
C1.3.3act. conductivityOnly available if "empty pipe [..]" is activated in Fct. C1.3.1.
Actual conductivity is indicated. Activation takes place only after setting
mode is exited!
C1.3.13electrode noiseSwitch the automatic test off or on.
Select: off / on
C1.3.14limit electr. noiseOnly with activated electrode noise (see Fct. C1.3.13).
Range: 0.000…12 m/s
Noise above this threshold generates an error of category [S].
C1.3.15act. electr. noiseOnly available if the electrode noise is set to "on" in Fct. C1.3.13. Activation
C1.3.16settling of fieldAutomatic test switched off / on.
C1.3.17diagnosis valueSelect diagnosis value for testing the various analogue outputs.
takes place only after setting mode is exited!
Select: off / on
Select:
off (no diagnosis) /
electrode noise (activate in Fct. C1.3.13) /
terminal 2 DC (electrode DC voltage at electrode terminal 2) /
terminal 3 DC (electrode DC voltage at electrode terminal 3)
62
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 63
IFC 100
OPERATION 6
C1.4 information
C1.4informationGrouping of all functions related to information with respect to measuring
C1.4.1linerShows the material of the liner.
C1.4.2electr. materialShows the material of the electrodes.
C1.4.3calibration dateShows the date on which the measuring sensor was calibrated.
C1.4.4serial no. sensorShows the serial no. of the measuring sensor.
C1.4.5V no. sensorShows the order number of the measuring sensor.
C1.4.6sensor electr. infoShows the serial number of the circuit board, the software version number
sensor and sensor electronics.
and the calibration date of the circuit board.
C1.5 simulation
C1.5simulationGrouping of all functions for simulating measuring sensor values.
These simulations have effect on all outputs, including counters and display.
C1.5.1flow speedSequence see Fct. B1.1
C1.5.2volume flowSequence see Fct. B1.2
No.FunctionSettings / descriptions
C2 I/O (Inputs/Outputs)
C2.1 hardware
C2.1hardwareConfiguration of connection terminals.
Selection depends on signal converter version.
C2.1.1terminal ASelect:
C2.1.3terminal CSelect:
C2.1.4terminal DSelect:
off (switched off) / current output
off (switched off) / current output / status output / limit switch / control input
off (switched off) / frequency output / pulse output / status output / limit
switch
C2._ current out X
C2._current out XX stands for connection terminals A
_ stands for Fct. C2.2 (A)
C2._.1range 0%…100%Current range for the selected "measurement", e.g. 4...20 mA, corresponds
C2._.2extended rangeMin. and max. limits of current values. If the current range is exceeded, the
C2._.3error currentSpecify error current.
to 0…100%
xx.x … xx.x mA; range: 0.00…20 mA
Condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA
current is set to these limits.
xx.x … xx.x mA; range: 03.5…21.5 mA
Condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 21.5 mA and out of current range
xx.x mA; range: 3…22 mA
Condition: outside of extended range
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
63
Page 64
6 OPERATION
No.FunctionSettings / descriptions
IFC 100
C2._.4error conditionThe following error conditions can be selected:
C2._.5measurementMeasurements for activating the output.
C2._.6range0…100% of the "measurement" set in Fct. C2._.5.
C2._.7polaritySet polarity; please note flow direction in C1.2.2!
C2._.8limitationLimitation before applying the time constant.
C2._.9low flow cutoffSets the measurement to "0" for low values.
C2._.10time constantRange: 000.1…100 s
C2._.11special functionSelect:
C2._.12thresholdAppears only when Fct. C2._.11 "threshold" is activated between extended
C2._.13informationInformation about serial no. of the I/O board, software version no. and
C2._.14simulationSequence see B1._ current output X
C2._.154mA trimmingTrimming of the current at 4 mA.
error in device (error category [F]) /
application error (error category [F]) /
out of specification (error category [S])
Select:
volume flow / mass flow / diagnosis value /
flow speed / coil temperature / conductivity
x.xx…xx.xx _ _ _ (format and unit depend on the "measurement", see above)
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
±xxx …±xxx%; range: -150…+150%
x.xxx ± x.xxx%; range: 0.0…20%
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
off (switched off) /
automatic range (range is changed automatically, extended lower range; the
magnifying function in the extended lower range, only makes sense in
combination with a status output) /
and normal range.
The automatic range function always changes from the extended to the
normal range when the 100% current is reached. The upper 100% value of
the hysteresis is then = 0. The threshold is then the hysteresis value, instead
of "threshold ± hysteresis" as shown in the display.
Range: 5.0…80%
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
production date of the circuit board.
Reset to 4 mA restores the factory calibration.
Used for HART® setting.
C2._.1620mA trimmingTrimming of the current at 20 mA.
Reset to 20 mA restores the factory calibration.
Used for HART® setting.
64
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 65
IFC 100
OPERATION 6
C2._ frequency out X
C2._frequency out XX stands for connection terminals D
_ stands for Fct. C2.5 (D)
C2._.1pulse shapeSpecify the pulse shape.
Select:
symmetric (about 50% on and 50% off) /
automatic (constant pulse width about 50% on and 50% off
at 100% pulse rate) /
fixed (fixed pulse rate, setting see below Fct. C2._.3 "100% pulse rate")
C2._.2pulse widthOnly available if "fixed" is set in Fct. C2._.1.
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
C2._.3100% pulse ratePulse rate for 100% of the measuring range.
C2._.4measurementMeasurements for activating the output.
C2._.5range0…100% of the "measurement" set in Fct. C2._.4
C2._.6polaritySet polarity; please note flow direction in C1.2.2!
C2._.7limitationLimitation before applying the time constant.
C2._.8low flow cutoffSets the measurement to "0" for low values.
C2._.9time constantRange: 000.1…100 s
C2._.10invert signalSelect:
C2._.12informationInformation about serial no. of the I/O board, software version no. and
C2._.13simulationSequence see B1._ frequency out X
Limitation is at 120% of this pulse rate or at 1/(1.5 * pulse width) whatever is
lower.
Range: 1…10000 Hz
Select:
volume flow / mass flow / diagnosis value /
flow speed / coil temperature / conductivity
x.xx…xx.xx _ _ _ (format and unit depend on the measurement, see above)
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
±xxx …±xxx%; range: -150…+150%
x.xxx ± x.xxx%; range: 0.0…20%
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
off (activated output: switch closed) /
on (activated output: switch open)
production date of the circuit board.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
65
Page 66
6 OPERATION
C2._ pulse output X
C2._pulse output XX stands for connection terminals D
_ stands for Fct. C2.5 (D)
C2._.1pulse shapeSpecify the pulse shape.
Select:
symmetric (about 50% on and 50% off) /
automatic (constant pulse width of 50% on and 50% off
at max. pulse rate) /
fixed (fixed pulse rate, setting see below Fct. C2._.3 "max. pulse rate")
C2._.2pulse widthOnly available if "fixed" is set in Fct. C2._.1.
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
For pulse widths below 0.5 seconds the max. pulse rate has to be adjusted to
1/(2 * pulse width) to prevent overrange messages.
C2._.3max. pulse rateMaximum pulse rate.
Limitation is at 120% of this pulse rate or at 1/(1.5 * pulse width) whatever is
lower.
Range: 1…10000 Hz
C2._.4measurementMeasurements for activating the output.
Select:
volume flow / mass flow
C2._.5pulse value unitSelection of the unit from a list, depending on the "measurement"
C2._.6value p. pulseSet value for volume or mass per pulse.
xxx.xxx, measured value in [l] or [kg] depending on setting in C2._.5
C2._.7polaritySet polarity; please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2._.8low flow cutoffSets the measurement to "0" for low values.
x.xxx ± x.xxx%; range: 0.0…20%
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
C2._.9time constantRange: 000.1…100 s
C2._.10invert signalSelect:
off (activated output: switch closed) /
on (activated output: switch open)
C2._.12informationInformation about serial no. of the I/O board, software version no. and
production date of the circuit board.
C2._.13simulationSequence see B1._ pulse output X
IFC 100
66
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 67
IFC 100
OPERATION 6
C2._ status output X
C2._status output XX (Y) stands for one of the connection terminals C or D
_ stands for Fct. C2.4 (C) / C2.5 (D)
C2._.1modeThe output shows the following measuring conditions:
C2._.2current output YOnly appears if output A or C is set under "mode" and this output is a
C2._.2frequency out Y and pulse
output Y
C2._.2status output YOnly appears if output C or D is set under "mode" and this output is a "status
C2._.2limit switch YOnly appears if output C or D is set under "mode" and this output is a "limit
C2._.2offOnly appears if output A, C or D is set under "mode" and this output is
C2._.3invert signalSelect:
C2._.4informationSerial no. of the I/O board, software version no. and production date of the
C2._.5simulationSequence see B1._ status output X
out of specification (output set, signals status of category "error in device" or
"application error" or "out of specification" refer to
diagnostic information
application error (output set, signals status of the category "error in device"
or "application error" refer to
on page 77) /
polarity flow (polarity of the current flow) /
over range flow (over range of the flow) /
counter 1 preset (activates when counter X preset value is reached) /
counter 2 preset (activates when counter X preset value is reached) /
output A (activated by the status of output Y, additional output data see
below) /
output C (activated by the status of output Y, additional output data see
below) /
output D (activated by the status of output Y, additional output data see
below) /
off (switched off) /
empty pipe (when pipe empty, output activated) /
error in device (output set, signals status of the category "error in device"
refer to
"current output".
Select:
polarity (is signalled) /
over range (is signalled) /
automatic range (signals lower range)
Only appears if output D is set under "mode and this output is a "frequency
output" or "pulse output".
Select:
polarity (is signalled) /
over range (is signalled)
output".
Select:
same signal (like other connected status output, signal can be inverted, see
below)
switch".
Select:
status off (is always selected here if "status output X" is connected with a
limit switch)
switched off.
off (activated output: switch closed) /
on (activated output: switch open)
circuit board
Status messages and diagnostic information
on page 77) /
Status messages and diagnostic information
Status messages and
on page 77)
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
67
Page 68
6 OPERATION
C2._ limit switch X
C2._limit switch XX stands for one of the connection terminals C or D
_ stands for Fct. C2.4 (C) / C2.5 (D)
C2._.1measurementSelect:
volume flow / mass flow / diagnosis value /
flow speed / coil temperature / conductivity
C2._.2thresholdSwitching level, set threshold with hysteresis.
xxx.x ±x.xxx (format and unit depend on the measurement, see above)
1st value = threshold / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
C2._.3polaritySet polarity; please note flow direction in C1.2.2!
Select:
both polarities (plus and minus values are displayed) /
positive polarity (display for negative values = 0) /
negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive
values)
C2._.4time constantRange: 000.1…100 s
C2._.5invert signalSelect:
off (activated output: switch closed) /
on (activated output: switch open)
C2._.6informationInformation about serial no. of the I/O board, software version no. and
production date of the circuit board.
C2._.7simulationSequence see B1._ limit switch X
IFC 100
C2.4 control input C
C2.4.1modeDefinition of the control input.
off (control input switched off) /
hold all outputs (hold current values, not display and counters) /
output X (hold current values) /
all outputs to zero (current values = 0%, not display and counters) /
output X to zero (current value = 0%) /
reset all counters (reset all counters to "0") /
reset counter X (only counter X (1 or 2) is reset to "0") /
stop all counters /
stop counter X (stop only counter X (1 or 2) /
zero outp.+stop Cnt. (all outputs to "0", stop all counters, not the display) /
error reset (all resettable errors are deleted)
C2.4.2invert signalSelect:
C2.4.3informationSerial no. of the I/O board, software version no. and production date of the
C2.4.4simulationSequence see B 1._ control input X
off (control input is activated when a current is applied at the input (by
voltage to passive inputs or a low-value resistor to active inputs)) /
on (control input is activated when no current is applied at the input (low
voltage to passive inputs or a high-value resistor to active inputs))
circuit board
68
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 69
IFC 100
No.FunctionSettings / descriptions
C3 I/O counter (HART® or Modbus)
C3.1counter 1Set function of counter.
C3.2counter 2
_ stands for 1, 2 (= counter 1, 2)
OPERATION 6
The basic version (standard) has only 2 counters!
These functions are only available for HART
C3._.1functionSelect:
sum counter (counts positive + negative values) /
+ counter (counts only the positive values) /
- counter (counts only the negative values) /
off (counter is switched off)
C3._.2measurementSelection of the "measurement" for counter _.
Select:
volume flow / mass flow
C3._.3low flow cutoffSets low flow values to "0".
Range: 0.0…20%
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
C3._.4time constantRange: 000.1…100 s
C3._.5preset valueIf this value is reached, positive or negative, a signal is generated that can be
used for a status output. For this status output the "preset counter X" has to
be set.
Preset value (max. 8 digits) x.xxxxx in selected unit (see C5.7.10 and C5.7.13).
C3._.6reset counterSequence see Fct. A3.2 and A3.3.
C3._.7set counterSet counter _ to the desired value.
Select:
break (exit function) /
set value (opens the editor to make the entry)
Query: set counter?
®
devices.
Select:
no (exit function without setting the value) /
yes (sets the counter and exits the function)
C3._.8stop counterCounter _ stops and holds the current value.
Select:
no (exit the function without stopping the counter) /
yes (stop the counter and exit the function)
C3._.9start counterStart the counter _, after this counter was stopped.
Select:
no (exit the function without starting the counter) /
yes (start the counter and exit the function)
C3._.10informationSerial no. of the I/O board, software version no. and production date of the
circuit board
C3 I/O counter (Profibus)
For the detailed description of the Profibus functions refer to the corresponding supplementary instructions.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
69
Page 70
6 OPERATION
IFC 100
No.FunctionSettings / descriptions
C4 I/O HART (only for HART® devices)
C4I/O HART
C4.1PV isCurrent output (primary variable)
C4.2SV is(secondary variable)
C4.3TV is (tertiary variable)
C4.44V is(4th variable)
C4.5HART unitsFunction to make the change of the units for the DVs (dynamic variables)
C4._.1current output XShows the current analogue measured value of the linked current output.
C4._.1frequency out XShows the current analog measured value of the linked frequency output, if
C4._.1HART dynamic var.
Selection or display of the 4 dynamic variables (DV) for HART®.
The HART® current output (terminal A for basic I/O or terminal C for Exi I/O)
always has a fixed link to the primary variables (PV).
Fixed links of the other DVs (1-3) are only possible if one additional analogue
output (frequency output) is available. If not, the "measurement" can be
freely selected from the following list:
flow speed / volume flow / mass flow /
diagnosis value / coil temperature / conductivity /
counter 1 / counter 2 / operating hours
X stands for connection terminals A, C and D
_ stands for 1, 2, 3 or 4
possible.
Select:
break (return with ^ key) /
®
display (copies the settings for the display units to the settings for
HART
the DVs) /
load defaults (resets the DVs to the factory defaults)
The "measurement" cannot be changed!
present. The "measurement" cannot be changed!
Measurements of the dynamic variables for HART®.
Select:
flow speed / volume flow / mass flow /
diagnosis value / coil temperature / conductivity /
counter 1 / counter 2 / operating hours
C4 I/O Profibus (only for Profibus devices)
For the detailed description of the Profibus functions refer to the corresponding supplementary instructions.
70
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 71
IFC 100
OPERATION 6
No.FunctionSettings / descriptions
C5 device
C5.1 device info
C5.1device infoGrouping of all functions that have no direct effect on the measurement or
C5.1.1TagSettable characters (max. 8 digits):
C5.1.2C numberCG number, cannot be changed; describes the signal converter version
C5.1.3device serial no.Serial no. of the system; cannot be changed.
C5.1.4electronic serial no.Serial no. of the electronic assembly; cannot be changed.
C5.1.5SW.REV.MSSerial no. of the circuit board, version no. of the main software, production
C5.1.6Electronic Revision ERReference identification number, electronic revision and production date of
any output.
A…Z; a…z; 0…9; / - , .
date of the circuit board
the device
Includes all hardware and software changes.
C5.2 display
C5.2display-
C5.2.1languageLanguage selection depends on the device version.
C5.2.2contrastAt extreme temperatures the contrast on the display can be adjusted.
Setting: -9…0…+9
This change takes place immediately, not just when setting mode is exited!
C5.2.3default displaySpecification of the default display page that is returned to after a short
C5.2.5SW.REV.UISSerial no. of the circuit board, version no. of user interface software,
delay period.
Select:
none (current page is always active) /
1. meas. page (shows this page) /
2. meas. page (shows this page) /
status page (shows only status messages) /
graphic page (trend of the 1st measurement)
production date of the circuit board
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
71
Page 72
6 OPERATION
IFC 100
C5.3 1. meas. page & C5.4 2. meas. page
C5.31. meas. page_ stands for 3 = 1. meas. page and 4 = 2. meas. page
C5.42. meas. page
C5._.1functionSpecify the number of measured value lines (font size).
Select:
one line / two lines / three lines
C5._.2measurement 1.lineSpecify the "measurement" for the 1st line.
Select:
volume flow / mass flow / diagnosis value /
flow speed / coil temperature / conductivity
C5._.3range0…100% of the "measurement" set in Fct. C5._.2.
x.xx…xx.xx _ _ _ (format and unit depend on the "measurement")
C5._.4limitationLimitation before applying the time constant
±xxx...±xxx%; range: -120…+120%
C5._.5low flow cutoffSets low flow values to "0".
x.xxx ± x.xxx %; range: 0.0…20 %
1st value = switching point / 2nd value = hysteresis;
condition: 2nd value ≤ 1st value
C5._.6time constantRange: 0.1…100 s
C5._.7format 1.lineSpecify decimal places.
Select:
automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits)
C5._.8measurement 2.lineSpecify measurement 2.line (only available if this 2.line is activated)
Select:
bar graph (for the measurement selected in 1.line) / volume flow / mass flow
/ diagnosis value / flow speed / counter 1 / counter 2 / conductivity / coil
temperature / operating hours
C5._.9format 2.lineSpecify position after decimal point (only available if this 2.line is activated).
Select:
automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits)
C5._.10measurement 3.lineSpecify measurement 3.line (only available if this 3.line is activated).
Select:
volume flow / mass flow / diagnosis value /
flow speed / coil temperature / conductivity /
counter 1 / counter 2 / operating hours
C5._.11format 3.lineSpecify position after decimal point (only available if this 3.line is activated).
Select:
automatic (adaptation is automatic) /
X(=none)…X.XXXXXXXX (max. 8 digits)
72
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 73
IFC 100
OPERATION 6
C5.5 graphic page
C5.5graphic pageThis page always shows trend curve of the "measurement" of the 1. meas.
C5.5.1select rangeSelect:
C5.5.2rangeSet the scaling for the Y axis. Only available if "manual" is set in C5.5.1.
C5.5.3time scaleSet the time scaling for the X axis (trend curve).
page / 1.line (see Fct. C5.3.2).
manual (set range in Fct. C5.5.2) /
automatic (automatic depiction based on the measured values)
Reset only after parameter change or after switching off and on.
±xxx ±xxx%; range: -100…+100%
1st value = lower limit / 2nd value = upper limit;
condition: 1st value ≤ 2nd value
xxx min; range: 0…100 min
C5.6 special functions
C5.6special functions-
C5.6.1reset errorsreset errors?
Select: no / yes
C5.6.2save settingsSave current settings.
Select:
break (exit function without saving) /
backup 1 (saves the settings in the backup 1 storage place) /
backup 2 (saves the settings in the backup 2 storage place)
Query: go on with copy? (cannot be undone)
Select:
no (exit the function without saving /
yes (copy current settings to storage backup 1 or backup 2)
C5.6.3load settingsLoad saved settings.
Select:
break (exit function without loading) /
factory settings (reload factory settings) /
backup 1 (loads the settings from the backup 1 storage place) /
backup 2 (loads the settings from the backup 2 storage place) /
load sensor data (restore factory setting of the values for the measuring
sensor. Display and I/O settings are retained!)
Query: go on with copy? (cannot be undone)
Select:
no (exit the function without saving /
yes (load data from the selected storage place)
C5.6.4password quick setPassword required to change data in the menu "quick setup".
0000 (= to this menu without password)
xxxx (password required); range (4 digits): 0001…9999
C5.6.5password setupPassword required to change data in the menu "setup".
0000 (= to this menu without password)
xxxx (password required); range (4 digits): 0001…9999
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Desired unit= [unit see above] * conversion factor
Conversion factorMax. 9 digits
Shift decimal point:↑ to the left and ↓ to the right
xxx/xxx (max. 6 characters plus a "/")
6.4 Description of functions
6.4.1 Reset counter in the menu "quick setup"
INFORMATION!
It may be necessary to activate resetting of the counter in the menu "quick setup".
IFC 100
KeyDisplayDescription and setting
>quick setupPress and hold for 2.5 s, then release the key.
>language2 x ↓reset-
>reset errors-
↓counter 1Select desired counter.
↓counter 2
>reset counter
no
↓ or ↑reset counter
yes
^counter 1, 2Counter has been reset.
3 x ^Measuring mode-
-
-
76
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 77
IFC 100
6.4.2 Deleting error messages in the menu "quick setup"
INFORMATION!
For the detailed list of the possible error messages refer to Status messages and diagnostic
information on page 77
KeyDisplayDescription and setting
>quick setupPress and hold for 2.5 s, then release the key.
>language2 x ↓reset-
>reset errors-
>reset?
no
↓ or ↑reset?
yes
^reset errorsError has been reset.
3 x ^Measuring mode-
.
-
-
OPERATION 6
6.5 Status messages and diagnostic information
INFORMATION!
As status message always the name of the relevant status group and the status signal is
displayed.
Each status message (= status signal) has a specific symbol, determined by NAMUR, which is
displayed with the message. The length of each message is limited to one line.
SymbolSymbol
background
colour
whiteFFFF
blueFApplication errorNo measurement possible due to
blueSOut of specification Measurements are available but are no
blueCChecks in progress A test function is active. The displayed or
--IInformationNo direct influence on the
LetterStatus signalDescription and consequence
Error in deviceNo measurement possible.
(bold)
process/application conditions.
The device is still OK.
longer sufficiently accurate and should
be checked.
transferred measured value does not
correspond to the actual measured
value.
measurements.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
77
Page 78
6 OPERATION
Operational faults in device
Messages on the display DescriptionActions
IFC 100
Status: F _ _ _ _ _Operational fault in device, mA output ≤
Repair necessary.
3.6 mA or set fault current (depending
on the seriousness of the fault), status
output open, pulse / frequency output:
no pulses
F error in deviceError or failure of device. Parameter or
F IO 1Error, operational fault in IO 1. Parameter
F parameterError, operational fault of data manager,
F configurationInvalid configuration: display software, bus
F displayError, operational fault in display.
F sensor electronicError, operational fault in sensor
F sensor globalData error in the global data of the
F sensor localData error in the local data of the measuring
F field current localData error in the local data of the field
F current output AError, operational fault in current output.
F current output C
F software user interfaceFault revealed by CRC check of operation
F hardware settingsThe set hardware parameters do not match
F hardware detectionExisting hardware cannot be identified.Defective, replace electronic unit.
F RAM/ROM error IO1A RAM or ROM error is detected during the
F FieldbusMalfunction of the Fieldbus interface.-
hardware error. No measurement possible.
or hardware error. No measurement
possible.
electronic unit, parameter or hardware
error. Parameters no longer usable.
parameter or main software do not match
existing configuration.
Parameter or hardware error. No
measurement possible.
electronics. Parameter or hardware error.
No measurement possible.
measuring sensor electronic equipment.
sensor electronic equipment.
current supply.
Parameter or hardware error. No
measurement possible.
software.
the identified hardware. A dialogue appears
in the display.
CRC check.
Group message, when one of the following
or some other severe error occurs.
Load settings (Fct. C4.6.3) (backup 1,
backup 2 or factory settings). If status
message still does not disappear, replace
electronic unit.
If device configuration unchanged:
defective, replace electronic unit.
Defective, replace electronic unit.
Defective, replace electronic unit.
Load settings (Fct. C5.6.3) (backup 1,
backup 2 or factory settings). If status
message still does not disappear, replace
electronic unit.
Defective, replace electronic unit.
Defective, replace electronic unit.
Defective, replace electronic unit.
Replace electronic unit.
Answer queries in dialogue mode, follow
directions.
Defective, replace electronic unit.
Defective, replace electronic unit.
78
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 79
IFC 100
Application error
Messages on the display DescriptionActions
OPERATION 6
Status: F _ _ _ _ _Application-dependent fault, device OK,
but measured values affected.
F application errorApplication-dependent fault, but device is
F empty pipe1 or 2 measuring electrodes are not in
F flow exceeding limitMeasuring range exceeded, filter setting
F field frequency too highField frequency is not reaching steady state,
F DC offsetADC over-ranged by DC offsets. No
F open circuit ALoad on current output A too high, effective
F open circuit C
F over range AThe current or the corresponding measured
F over range C
F over range DThe pulse rate or the corresponding
F active settingsError during the CRC check of the active
F factory settingsError during the CRC check of the factory
F backup 1 settingsError during the CRC check of the backup 1
F backup 2 settings
okay.
contact with the medium; measured value is
set to zero. No measurement possible.
limits measured values. No message if
empty pipe.
If this limit occurs sporadically in processes with air pockets, solid contents or low
conductivity, then either the limit has to be increased or a pulse filter used so as to quell
the error messages and also reduce the measurement errors.
a measured flow value is still being supplied
but may have errors. Measured values are
still supplied, but they are always too low.
No message if coil broken or bridged.
measurement can be performed, the flow is
set to zero. No message if empty pipe.
current too low.
value is limited by a filter setting.
measured value is limited by a filter setting.
Or the demanded pulse rate is too high.
settings.
settings.
or 2 settings.
Application test or operator action
necessary.
Group message, when errors as described
below or other application errors occur.
Measuring pipe not filled, function
dependent on C1.3.2. Check installation. Or
electrodes completely insulated e.g. by oil
film. Clean!
Limitation Fct. C1.2.1, increase values.
If Fct. C1.1.14 settling time is on "manual",
increase the value in Fct. C1.1.15. If it is set
to "standard", set the field frequency in Fct.
C1.1.13 according to the signal converter
nameplate.
For remote signal converters, check the
connection of the signal cable.
Current not correct, mA output cable has
open circuit or load too high. Check cable,
reduce load (set < 750 ohm).
Check with Fct. C2.1 hardware or sticker in
terminal compartment, which output is
connected to the terminal.
If current output: extend Fct. C2.x.6 range
and Fct. C2.x.8 limitation.
If frequency output: extend values in
Fct. C2.x.5 and Fct. C2.x.7.
Upload backup 1 or backup 2 settings, check
and adjust if necessary.
-
Save active settings in backup 1 or 2.
Measurements out of specification
Messages on the display DescriptionActions
Status: S _ _ _ _ _Out of specification, measurement
continues, accuracy possibly less.
S uncertain measurement Device maintenance necessary; measured
values only conditionally usable.
S empty pipe1 or 2 measuring electrodes are not in
contact with the medium; measured value is
set to zero. No measurement possible.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Maintenance required.
Group message, when errors as described
below or other influences occur.
Measuring pipe not filled, function
dependent on C1.3.2. Check installation. Or
electrodes completely insulated e.g. by oil
film. Clean!
79
Page 80
6 OPERATION
Messages on the display DescriptionActions
IFC 100
Status: S _ _ _ _ _Out of specification, measurement
Maintenance required.
continues, accuracy possibly less.
S electrode noiseNoise on the electrodes too high. Measured
values are still supplied. No message if
empty pipe.
S field coil brokenField coil resistance too high.Check field coil connections to the
S field coil bridgedField coil resistance too low.
S electronic temperatureUpper limit for the permissible electronic
temperature has been exceeded.
S coil temperatureUpper limit for the permissible coil
temperature has been exceeded. No
message if coil broken/bridged.
S overflow counter 1This is counter 1 or FB2 (with Profibus).
Counter has overrun and started again at
zero.
S overflow counter 2This is counter 2 or FB3 (with Profibus).
Counter has overrun and started again at
zero.
S backplane invalidThe data record on the backplane is invalid.
The CRC check has revealed a fault.
S field frequency too highThe field frequency is set so high that the
field current cannot settle. The measured
values displayed are too low.
a) Electrodes extremely soiled;
b) Conductivity too low: activate noise or
pulse filter Fct. C1.2.4, C1.2.7;
c) Gas bubbles, solids or chem. reactions in
medium: activate noise or pulse filter
Fct. C1.2.4, C1.2.7;
d) Electrode corrosion (if message also
appears when flow is zero): use sensor with
suitable electrode material.
electronic module (for remote versions:
field current cable) for open circuit / short
circuit
Ambient temperature too high, direct solar
radiation or, for C version, process
temperature too high.
Process and ambient temperature too high.
-
-
No data can be loaded from the backplane
when replacing electronics. Save the data to
the backplane again (Service).
Set field frequencey lower, see Fct. C1.1.13.
Simulation of the measured values
Messages on the display DescriptionActions
Status: C _ _ _ _ _Output values partially simulated or
Maintenance required.
fixed
C checks in progressTest mode of the device. Measured values
are possibly simulated values or values with
fixed settings.
C test sensorTest function of the measuring sensor
electronics is active.
C simulation fieldbusValues on the Foundation Fieldbus interface
are simulated.
Message depending on the situation via
HART
-
-
Information
Messages on the display DescriptionActions
Status: I _ _ _ _ _Information (current measurement OK)
I counter 1 stoppedThis is counter 1 or FB2 (with Profibus). The
counter has stopped.
I counter 2 stoppedThis is counter 2 or FB3 (with Profibus). The
counter has stopped.
If counter to continue counting, activate
"yes" in Fct. C2.y.9 (start counter).
®
or FDT.
80
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 81
IFC 100
Messages on the display DescriptionActions
Status: I _ _ _ _ _Information (current measurement OK)
OPERATION 6
I power failThe device was not in operation for an
I over range display 11st line on page 1 (2) of display limited by
I over range display 2
I over range conductivityThe limits for the conductivity measurement
I control input C act.This message appears when the control
I backplane sensorThe data on the backplane are not usable
I backplane settingsThe global settings on the backplane are not
I backplane differenceThe data on the backplane differ from the
I write cycles overfl.The maximum number of write cycles of the
I baudrate searchThe baudrate of the Profibus DP interface is
I no data exchangeThere is no data exchange between the
I conductivity offConductivity measurement switched off.Change the settings in Fct. C1.3.1.
I empty pipe1 or 2 measuring electrodes are not in
I diagnosis channel offDiagnosis value switched off.Change the settings in Fct. C1.3.17.
unknown period of time, because the power
was switched off. This message is for
information only.
filter setting.
have been exceeded (>10000 µS/cm) or are
lower than permitted (<0.1 µS/cm).
input is active.
because they have been generated with an
incompatible version.
usable because they have been generated
with an incompatible version.
data in the display. If the data are usable, a
dialogue is indicated in the display.
EEPROM or FRAMS on the Profibus DP PCB
has been exceeded.
searched for.
signal converter and the Profibus.
contact with the medium; measured value is
set to zero. No measurement possible.
Temporary power failure. Counters did not
run during it.
Select in menu "display" Fct. C4.3 and/or
C4.4 the 1st or 2nd meas. page and increase
values in functions C4.z.3 range and/or
C4.z.4 limitation.
If the measuring sensor has been properly
connected and filled with medium, this does
not affect the flow measurement. The
conductivity measured values cannot be
used.
-
-
-
-
-
-
-
Measuring pipe not filled, function
dependent on C1.3.2. Check installation. Or
electrodes completely insulated e.g. by oil
film. Clean!
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
81
Page 82
7 SERVICE
7.1 Spare parts availability
The manufacturer adheres to the basic principle that functionally adequate spare parts for each
device or each important accessory part will be kept available for a period of 3 years after
delivery of the last production run for the device.
This regulation only applies to spare parts which are subject to wear and tear under normal
operating conditions.
7.2 Availability of services
The manufacturer offers a range of services to support the customer after expiration of the
warranty. These include repair, maintenance, technical support and training.
INFORMATION!
For more precise information, please contact your local sales office.
7.3 Returning the device to the manufacturer
IFC 100
7.3.1 General information
This device has been carefully manufactured and tested. If installed and operated in accordance
with these operating instructions, it will rarely present any problems.
CAUTION!
Should you nevertheless need to return a device for inspection or repair, please pay strict
attention to the following points:
•
Due to statutory regulations on environmental protection and safeguarding the health and
safety of our personnel, manufacturer may only handle, test and repair returned devices that
have been in contact with products without risk to personnel and environment.
•
This means that the manufacturer can only service this device if it is accompanied by the
following certificate (see next section) confirming that the device is safe to handle.
CAUTION!
If the device has been operated with toxic, caustic, flammable or water-endangering products,
you are kindly requested:
•
to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from
such dangerous substances,
•
to enclose a certificate with the device confirming that is safe to handle and stating the
product used.
82
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 83
IFC 100
7.3.2 Form (for copying) to accompany a returned device
Company:Address:
Department:Name:
Tel. no.:Fax no.:
Manufacturer's order no. or serial no.:
The device has been operated with the following medium:
SERVICE 7
This medium is:radioactive
water-hazardous
toxic
caustic
flammable
We checked that all cavities in the device are free from such
substances.
We have flushed out and neutralized all cavities in the
device.
We hereby confirm that there is no risk to persons or the environment through any residual media
contained in the device when it is returned.
Date:Signature:
Stamp:
7.4 Disposal
CAUTION!
Disposal must be carried out in accordance with legislation applicable in your country.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
83
Page 84
8 TECHNICAL DATA
8.1 Measuring principle
An electrically conductive fluid flows inside an electrically insulated pipe through a magnetic
field. This magnetic field is generated by a current, flowing through a pair of field coils.
Inside of the fluid, a voltage U is generated:
U = v * k * B * D
U = v * k * B * D
U = v * k * B * DU = v * k * B * D
in which:
v = mean flow velocity
k = factor correcting for geometry
B = magnetic field strength
D = inner diameter of flow meter
The signal voltage U is picked off by electrodes and is proportional to the mean flow velocity v
and thus the flow rate q. A signal converter is used to amplify the signal voltage, filter it and
convert it into signals for totalising, recording and output processing.
IFC 100
Figure 8-1: Measuring principle
1 Induced voltage (proportional to flow velocity)
2 Electrodes
3 Magnetic field
4 Field coils
84
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 85
IFC 100
TECHNICAL DATA 8
8.2 Technical data
INFORMATION!
•
The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
•
Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).
Measuring system
Measuring principleFaraday's law of induction
Application rangeContinuous measurement of current volume flow, flow velocity, conductivity, mass
Design
Modular constructionThe measuring system consists of a measuring sensor and a signal converter.
and counting, flow velocity, electrical conductivity, temperature
IFC 100
Measuring accuracy
Reference conditionsMedium: water
Temperature: +20°C / +68°F
Pressure: 1 bar / 14.5 psi
Inlet section: ≥ 5 DN
Maximum measuring errorStandard calibration: +0.3% of the measured value +1 mm/s, depending on the
Repeatability±0.1%
measuring sensor
Extended calibration is selectable and special calibrations are available on request.
For detailed information and accuracy curves, refer to chapter "Accuracy".
Current output electronics: ±10 µA; ±100 ppm/°C (typically: ±30 ppm/°C)
86
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
Page 87
IFC 100
TECHNICAL DATA 8
Operating conditions
Temperature
Temperature
TemperatureTemperature
Process temperatureRefer to technical data for the measuring sensor.
Ambient temperatureDepending on the version and combination of outputs.
It is a good idea to protect the converter from external heat sources such as direct
sunlight as higher temperatures reduce the life cycle of all electronic components.
Ambient temperatures below -25°C / -13°F may affect the readability of the display.
Storage temperature-40…+70°C / -40…+158°F
Pressure
Pressure
PressurePressure
MediumRefer to technical data for the measuring sensor.
Ambient pressureAtmospheric
Chemical properties
Chemical properties
Chemical propertiesChemical properties
Electrical conductivityAll media except for water: ≥ 5 µS/cm
State of aggregationConductive, liquid media
Solid content (volume)≤ 10% for OPTIFLUX measuring sensors
Gas content (volume)≤ 3% for OPTIFLUX measuring sensors
Flow rateFor detailed information, refer to chapter "Flow tables".
Other conditions
Other conditions
Other conditionsOther conditions
Protection category acc. to
IEC 529 / EN 60529
(also refer to the technical data for the measuring sensor)
Water: ≥ 20 µS/cm
IP66/67 (acc. to NEMA 4/4X)
Installation conditions
InstallationFor detailed information, refer to chapter "Installation conditions".
Inlet / outlet sectionsRefer to technical data for the measuring sensor.
Dimensions and weightsFor detailed information refer to chapter "Dimensions and weights".
Materials
Signal converter housingAluminium with a polyester topcoat
Measuring sensorFor housing materials, process connections, liners, grounding electrodes and
gaskets, refer to technical data for the measuring sensor.
www.krohne.com07/2014 - 4000041005 - MA IFC 100 R05 en
87
Page 88
8 TECHNICAL DATA
Electrical connection
GeneralElectrical connection is carried out in conformity with the VDE 0100 directive