KROHNE IFC-020 User Manual

Page 1
Pull-out
Condensed Instructions
KROHNE 12/2002 US size: 7.10003.72.00
GR
DIN A4: 7.10003.32.00
Installation and operating instructions
IFC 020 K IFC 020 F IFC 020 E
Signal converters for electromagnetic flowmeters
Applicable to Software Versions
IFC 020 K and
IFC 020 F No. 3170330200
How to use these Instructions
The flowmeters are supplied ready for operation.
The primary head must be installed in the pipeline as described in the installation instructions inside the packing of the primary head.
– Installation location and connection to power (Section 1) Pages 1/1-1/8 – Electrical connection of outputs and inputs (Section 2) Pages 2/1-2/4 – Factory settings and start-up (Section 3) Pages 3/1-3/2
Power the flowmeter. THAT’S ALL. The system is operative.
IFC 020 E
No. 3175870200
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications technology
Engineering systems & solutions
Switches, counters, displays and recorders
Heat metering
Pressure and temperature
Page 2
Installation and operating instructions IFC 020
0/1
Contents
Versions IFC 020 signal converter 0/3 Items included with supply 0/3 Software history 0/3 System description 0/4 Product liability and warranty 0/4 CE / EMC / Standards / Approvals 0/4
Part A System installation and start-up 1/1-3/2
1 Electrical connection: power supply 1/1-1/8
1.1 Important installation notes – PLEASE NOTE ! 1/1
1.1.1 Location 1/1
1.1.2 Only for separate systems/signal converters (F- and E versions) 1/1
1.1.3 Cable entries (K- and F versions) 1/1
1.2 Connection to power 1/2
1.3 Electrical connection of separate primary head (F- and E versions) 1/3-1/6
1.3.1 General information on signal cable A and B as well as field current cable C 1/3
1.3.2 Grounding of primary head 1/3
1.3.3 Stripping (preparation) of signal cable A and B 1/4
1.3.4 Cable length (max. distance between signal converter and primary head) 1/5
1.3.5 Connection diagrams I and II (IFC 020 F signal converter and primary head) 1/6
1.3.6 Connection diagrams III and IV (IFC 020 E signal converter and primary head) 1/7-1/8
2
Electrical connection of outputs and inputs 2/1-2/4
2.1 Current output I 2/1
2.2 Pulse output P and status output S 2/1
2.3 Control input E (applicable with IFC 020 E only) 2/2
2.4 Connection diagrams for outputs and inputs 2/3-2/4
3.
Start-up 3/1-3/2
3.1 Power-on and measurement 3/1
3.2 Factory settings 3/1
3.3 Setting data 3/2
Part B IFC 020
/ D Signal converter 4/1-5/12
4 Operation of the signal converter 4/1-4/12
4.1 Krohne operator control concept 4/1
4.2 Operating and check elements 4/2
4.3 Function of keys 4/3-4/4
4.4 Table of settable functions 4/5-4/9
4.5 Error messages in measuring mode 4/10
4.6 Reset totalizer and cancel error messages, RESET/QUIT menu 4/11
4.7 Examples of setting the signal converter 4/12
5
Description of functions 5/1-5/12
5.1 Full-scale range Q100% 5/1
5.2 Time constant 5/1
5.3 Low-flow cutoff SMU 5/2
5.4 Display 5/2-5/3
5.5 Internal electronic totalizer 5/3
5.6 Current output I 5/4
5.7 Pulse output P 5/5-5/6
5.8 Status output S 5/7
5.9 Language 5/8
5.10 Entry code 5/8
5.11 Primary head 5/9
5.12 User-defined unit 5/10
5.13 F/R mode, forward/reverse flow measurement 5/11
5.14 Characteristic of outputs 5/11
Page 3
Installation and operating instructions IFC 020
0/2
Part C Special applications, functional checks, service, and order numbers 6/1-9/1
6 Special applications 6/1-6/6
6.1 HART interface 6/1-6/2
6.2 KROHNE
RS 485 interface
6/2
6.3 Stable signal outputs when measuring tube empty 6/3-6/4
6.4 Pulsating flow 6/5
6.5 Rapid changes in flowrate 6/5
6.6 Unsteady display and outputs 6/6
7
Functional checks 7/1-7/8
7.1 Zero check, Fct. 3.03 7/1
7.2 Test of measuring range Q, Fct. 2.01 7/1
7.3 Hardware information and error status, Fct. 2.02 7/2
7.4 Faults and symptoms during start-up and process flow measurement 7/2-7/4
7.5 Test of signal converter using GS 8A simulator (option) 7/5-7/8
8
Service 8/1-8/9
8.1 Illustrations used for service work 8/1-8/2
8.2 Replacement of power fuses 8/3
8.3 Changeover of operating voltage on AC Versions 1 and 2 8/4
8.4 Replacement of electronics unit of signal converter 8/5
8.5 Cleaning the signal converter housing 8/5
8.6 Turning the converter housing of the compact flowmeters 8/6
8.7 IFC 020 K and F: Directions for folding the ribbon cable on the display unit 8/7
8.8 IFC 020 K and F: Illustrations of the PCBs 8/8
8.9 IFC 020 E: Illustrations of the PCBs 8/9
9
Order numbers 9/1
Part D Technical data, measuring principle and block diagram 10/1-12/1
10 Technical data 10/1-10/7
10.1 Full-scale range Q
100%
10/1
10.2 Error limits at reference conditions 10/2
10.3 IFC 020 signal converter 10/3-10/4
10.4 Dimensions and weights 10/5-10/6
10.5 Instrument name plates 10/7
1
1 Measuring principle 11/1
12 Block diagram - signal converter 12/1
Part E Index E1-E2
Printed form to accompany flowmeters returned to Krohne E3
5.15 Applications 5/12
5.16 Setting data 5/12
5.17 Communication interface 5/12
5.18 Control input E (IFC 020 E only) 5/12
Page 4
Installation and operating instructions IFC 020
0/3
IFC 020 signal converter versions
• All signal converter versions include local display and control elements. The operating data are factory-set to your ordered specifications
IFC 020 K Compact flowmeter,
Signal converter is directly mounted on primary head.
IFC 020 F Signal converter in field housing,
Electrical connection to primary head via field power and signal cables.
IFC 020 E Signal converter as 19” plug-in unit (in compliance with DIN 41 494, part 5)
Electrical connection to primary head via field power and signal cables.
Items included with supply
• Signal converter in the version as ordered, see above.
• These installation and operating instructions for the signal converter, including 20-page pull-out condensed instructions for installation, electrical connection, start-up and operator control of the signal converter.
• 2 plug connectors for connection of power supply and outputs/inputs (K- and F- versions only)
• for separate system version only
, F- and E versions:
signal cable in the version and length as ordered (standard: signal cable A, length 10 m / 30 ft)
Software history
Display & control unit Handheld HHT 020 CONFIG user software IFC 020 K and F IFC 020 E ImoCom, RS 485, HART
Software Status Software Status Software Status
3170330100 replaces 3170330200 replaces
3170330200 current 3175870200 current from V 3.15 current
Page 5
Installation and operating instructions IFC 020
0/4
CE / EMC / Standards / Approvals
System description
Electromagnetic flowmeters with the IFC 020 signal converter are precision instruments designed for linear flow measurement of liquid products.
The process liquids must be electrically conductive: ≥ 5 µS/cm
(for cold demineralized water 20 µS/cm).
The full-scale range Q
100%
can be set as a function of the meter size:
Q
100%
= 0.0060 - 86 860 m3/hr = 0.03 - 156.672 US Gal/min
This is equivalent to a flow velocity of 0.3 - 12 m/s or 1 - 40 ft/s.
Product liability and warranty
The electromagnetic flowmeters with the IFC 020 signal converter are designed solely for measuring the volumetric flowrate of electrically conductive, liquid process products.
These flowmeters are not certified for use in hazardous areas. Other flowmeter series are available for such applications.
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests solely with the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty.
In addition, the “General conditions of sale” forming the basis of the purchase contract are applicable.
If flowmeters need to be returned to Krohne, please note the information given on the last-but-one page of these Instructions. Krohne regrets that it cannot repair or check your flowmeter(s) unless accompanied by the completed form sheet.
• Electromagnetic flowmeters with the IFC 020 signal converter meet the protection requirements of Directive 89/336/EEC in conjunction with EN 50081-1 (1992) and EN 50082-2 (1995), as well as Directives 73/23/EEC and 93/68/EEC in conjunction with EN 61010-1, and bear the
CE marking.
Page 6
Installation and operating instructions IFC 020
1/1
Part A System installation and start-up
1 Electrical connection: power supply
1.1 Important installation notes PLEASE NOTE !
1.1.1 Location
Electrical connection in accordance with VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V” or equivalent national regulations.
Do not cross or loop cables inside the terminal compartment.
Use separate cable entries (see below) for power supply, field current cables, signal lines,
outputs and inputs.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunlight. Fit a sunshade if necessary.
When installed in switchgear cabinets, signal converters must be adequately cooled, e.g. use fans or heat exchangers.
Do not expose signal converters to intense vibration.
1.1.2 Onl
y for separate systems/signal converters (F- and E versions)
Keep distance between primary head and signal converter as short as possible.
Refer to Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied Krohne signal cable A (Type DS), standard length 10 m (33 ft).
Always calibrate primary head and signal converter together. Therefore, when installing,
ensure primary constant GK is identical; refer to instrument nameplate for the primary head. If the GK is not identical, set the signal converter to the GK of the primary head. Refer also to Section 4.
Dimensions of signal converter; refer to Section 10.4.
1.1.3 Cable entries (K- and F- versions)
Number of cable entries: 2 for the compact flowmeters
4 for the seperate IFC 020 F signal converter
NOTE: Ensure gaskets are fitted correctly and maintain
the following max. torques!
1 Max. torques for PG 13.5,
1/2“ NPT or 1/2“ PF adapters: 4 Nm / 2.8 ft
x
lbf
2 Max. torques for PG 13.5 only: 3 Nm / 2.1 ft
x
lbf
3 Gasket
A) PG 13.5 cable entries
These cable entries may only be used for flexible electrical cables if the relevant electrical regulations so allow, e.g. National Electric Code (NEC). Do not fix rigid metal conduits (IMC) or flexible plastic conduits to the PG 13.5 cable entries, refer to “Point B/C” below (1/2” NPT or PF adapters).
B) 1/2“ NPT adapters C) 1/2“ PF adapters
For most North American systems the regulations require that electrical conductors be laid in conduits, particularly where power voltages > 100 V AC are concerned. In such cases, use the 1/2” NPT or 1/2” PF adapters to which flexible plastic conduits can be screwed. Do not use rigid metal conduits (IMC)! Lay conduits such that no moisture can penetrate into the converter housing. Should there be risk of any condensation water forming, fill the cross-section of the conduit around the cables at these adapters with a suitable sealing compound.
3
1
2
Page 7
Installation and operating instructions IFC 020
1/2
Connection to power 1.2
PLEASE NOTE !
Rated values:
The flowmeter housings protecting the electronic equipment from dust and moisture must always be kept closed. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage class II.
Safet
y isolation: the flowmeters (signal converters) must be provided with an
isolating facility.
1. AC V
ersion 2. AC Version
230/240 V AC (200 - 260 V AC) 200 V AC (170 - 220 V AC)
switch-selectable to switch-selectable to
115/120 V AC (100 - 130 V AC) 100 V AC (85 - 110 V AC)
Note information on instrument nameplate: supply voltage and frequency
The PE protective ground conductor for the power supply must be connected to the
separate U-clamp terminal in the terminal compartment of the signal converter. For exceptions (compact systems), refer to installation instructions for the primary head.
Connection diagrams for electrical connection between primary head and signal converter: refer to Section 1.3.5 and 1.3.6.
DC V
ersion (in preparation for IFC 020 E)
24 V DC (18 - 32 V DC)
Note information on instrument nameplate: supply voltage and frequency.
For measurement reasons, connect an FE functional ground conductor to the separate
U-clamp terminal in the terminal compartment of the signal converter.
If connected to a functional extra-low voltage source (24 V AC / DC, 48 V AC), provide for protective separation (PELV) in conformity with VDE 0100 / VDE 0106 or IEC 364 / IEC 536, or equivalent national regulations.
Connection diagrams for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.6.
Connection to power (K- and F- versions only)
Power fuse F1
(see Sect. 8.2)
AC: 100 – 240 V DC: 24 V
Power supply
U-clamp terminal
PE protective conductor FE functional ground conductor
L N
1L = 0L =
for
internal
use only
For electrical connection of the IFC 020 E power supply see Section 1.3.6, connection diagrams III to VI.
Page 8
Installation and operating instructions IFC 020
Field current line C (single shielding with IFC 020 F)
Line 2 x 0.75 mm2(18 AWG) Cu, 2 x 1.5 mm2(14 AWG) Cu or 2 x 2.5mm2(12 AWG) Cu single shielding (Cu = copper cross section) The cross section depends on the required cable length, see table in Section 1.3.4.
1/3
1.3
Electrical connection of separate primary heads (F- and E- versions)
1.3.1
General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when Krohne signal lines A and B are used with foil screen and magnetic shield.
• Signal lines must be firmly installed.
• Shields are connected via stranded drain wires.
• Underwater or underground routing is possible.
• Insulating material flame-retardant to IEC 332.1 / VDE 0742.
• Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Si
gnal line A (type DS) with double shielding
1.3.2 Grounding of primary head
• All flowmeters must be properly grounded.
• The grounding conductor should not transmit any interference voltages.
• Do not ground any other electrical device together with this conductor.
• The primary head is connected to ground by means of an FE functional ground conductor.
• Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
• These instructions also contain detailed descriptions on how to use grounding rings and how to install primary heads in metal or plastic pipes or internally coated pipelines.
1 Stranded drain wire, 1st shield, 1.5 mm2 or AWG 14 2 Insulation 3 Stranded wire 0.5 mm
2
or AWG 20 (3.1 red/3.2 white) 4 Special foil, 1st shield 5 Insulation 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG 20
8 Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line), for IFC 020 E only
1 Dummy glider wire 2 Insulation (2.1 red/2.2 white) 3 Special foil, 1st shield (3.1/3.2) 4 Insulation (4.1/4.2) 5 Stranded wire 0.5 mm
2
or AWG 20 (5.1 red/5.2 white)
6 Stranded drain wire, 1st shield, 0.5 mm
2
or AWG 20
(6.1/6.2) 7 Special foil, 2nd shield 8 Stranded drain wire, 2nd shield, 1.5 mm
2
or AWG 14
9 Insulation
10 Mu-metal foil, 3rd shield
11 Stranded drain wire, 3rd shield, 0.5 mm
2
or AWG 20
12 Outer sheath
Page 9
Installation and operating instructions IFC 020
1/4
Stripping (preparation) of signal cable A and B 1.3.3
Please note the different lengths given in the table for signal converter and primary head.
Customer-supplied materials W
Insulation tubing (PVC), Ø 2.0 - 2.5 mm (dia. 1”)
X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
For cable fixation in signal converter housing IFC 020 F
see illustration in Section 10.4
External shielding of signal cable A (Type DS) Wrap stranded drain wire (7) around the mu-metal foil (6) and clamp under the shield terminal in the signal converter terminal box (see also diagram in Sect. 1.3.5).
Signal cable A (type DS) double shielding, for primary head and IFC 020 E
Signal cable A (type DS) double shielding, for IFC 020 F
Signal cable A bending radius 50 mm (2“)
Signal cable A bending radius 50 mm (2“)
Signal line B (type BTS) with triple shielding (bootstrap), for IFC 020 E
Signal line B
bending radius 50 mm (2”)
Length
Converter Primary
mm IFC 020 F + E only IFC 020 E
head
(inch) Signalcable A Signalcable B a 55 (2.17) 70 (2.76) 90 (3.54) b 10 (0.39) 50 (1.97) 98 (0.31) c 15 (0.59) 25 (0.98) 25 (0.98) d 58 (0.31) 78 (0.31) 98 (0.31) e 50 (1.97) 70 (2.76) f 78 (0.31) 98 (0.31)
Page 10
Installation and operating instructions IFC 020
Length
Cross section AF (Cu), minimum
0 - 150 m 5 - 500 ft 2 × 0.75 mm
2
Cu / 2 × 18 AWG
150 - 300 m 500 - 1000 ft 2 × 1.50 mm
2
Cu / 2 × 14 AWG
300 - 600 m 1000 - 1900 ft 2 × 2.50 mm
2
Cu / 2 × 12 AWG
Abbreviations and ex
planatory notes
used in the following tables, diagrams and connection diagrams
A Signal cable A (type DS), with double shielding, see diagram A for max. length B Signal line B (type BTS) with triple shielding, max. length see diagram B (IFC 020 E only)
C Field current cable min. cross-section (AF) and max. length,
(with single shielding for IFC 020 F), see Table
D High-temperature silicone cable, 3 × 1.5 mm
2
(14 AWG) Cu, (with single shielding,
max. length 5 m (16 ft)
E High-temperature silicone cable, 2 × 1.5 mm
2
(14 AWG) Cu, max. length 5 m (16 ft)
AFCross section of field current line C in Cu, see table L Cable length
κκ
Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
Recommended length of signal cable A (Type DS) and B (Type BTS) (Signal cable B, Type BTS, for IFC 020 E only)
1.3.4 Cable lengths (max. distance between signal converter and primary head)
Field current cable C: (for IFC 020 F single shielding!)
Primary head Meter size Signal cable
DN mm inch AB AQUAFLUX F 010 - 10003/8 -40 A1 B1
ECOFLUX IFS 1000 F 010 - 153/8 -1/2 A4 B3
025 - 150 1 - 6 A3 B2
ALTOFLUX IFS 2000 F 150 - 250 6 - 10 A1 B1 ALTOFLUX IFS 4000 F 010 - 1503/8 - 6 A2 B2
200 - 1000 8 - 40 A1 B1 PROFIFLUX IFS 5000 F 002.5 - 151/10 -1/2 A4 B3
025 - 100 1 - 4 A2 B2
VARIFLUX IFS 6000 F 002.5 - 151/10 -1/2 A4 B3
025 - 80 1 - 3 A2 B2
ALTOFLUX M 900 010 - 3003/8 -12 A1 B1
1/5
Diagram A Diagram B (for IFC 020 E only)
Page 11
Installation and operating instructions IFC 020
1/6
Im
portant information on connection diagrams PLEASE NOTE!
The figures in brackets indicate the stranded drain wires for the shields,
see cross-sectional drawing of signal cable in Section 1.3.1.
• Electrical connection to VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V“ or equivalent national regulations.
•PE= protective conductor FE = functional ground conductor
Connection diagrams I and II (IFC 020 F signal converter and primary head) 1.3.5
I II
Process temperature < 150°C (302 °F) Process temperature > 150°C (302 °F)
Primary heads
Primary heads
1 Signal cable A
(Type DS)
2 Shield terminal
for shielded signal cable
3 Field power cable
4 Shield terminal
for shielded field power cable
5 Housing wall,
signal converter
6 Cable entries
Connection of shields at the IFC 020 F
4
5
6
3
1
6
2
IFC 020 F IFC 020 F
Page 12
Installation and operating instructions IFC 020
1/7
III IV
Signal cable A (type DS) Signal cable B (type BTS)
IFC 020 E
IFC 020 E
Process temperature < 150°C (302°F)
Primary head Primary head
Important information on connection diagrams PLEASE NOTE!
The figures in brackets indicate the stranded drain wires for the shields
(see cross-sectional drawing of signal cable in Section 1.3.1).
• Electrical connection to VDE 0100 "Regulations governing heavy-current installations with line voltages up to 1000 V" or equivalent national regulations.
• 24 V DC power supply (in preparation): Functional extra-low voltage with protective separation in conformity with VDE 0100, Part 410 or equivalent national regulations.
For IFC 020 E, please note: The internal bridges marked with *
are needed for power supply > 100 V AC only.
•PE= Protective conductor FE = Functional ground conductor
1.3.6 Connection diagrams III to VI (IFC 020 E signal converter and primary head)
24 V DC FE
0L = 1L =
24 V DC FE
0L = 1L =
Page 13
Installation and operating instructions IFC 020
1/8
V
VI
Signal cable A (type DS) Signal cable B (type BTS)
IFC 020 E IFC 020 E
Process temperature > 150°C (302°F)
Primary head Primary head
24 V DC FE
0L = 1L =
24 V DC FE
0L = 1L =
Page 14
Installation and operating instructions IFC 020
2/1
• All operating data and functions can be set:
Operation
see Section 4 and 5.
7 Function 1.06 and 1.07
.
• The pulse and status outputs can be operated in the active or passive mode.
Active mode: The current output is the internal voltage source,
connection of electronic totalizers (EC)
Passive mode: External DC or AC voltage source required, connection of electronic (EC)
or electromechanical (EMC) totalizers
• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or
cycle counters are connected, allow for minimum counting interval:
gate time, counter
1000
P
100% [ Hz]
Connection diagrams see Sect. 2.4: diagrams - pulse output
 Ã
diagrams - status output Ä Å
2.1 Current output I
The current output is galvanically isolated from all input and output circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
Typical current output
All operating data and functions can be set: Operation see Section 4 and 5.6 Function 1.05.
The current output can also be used as an internal voltage source for the outputs.
U
int
= 15 V DC I = 23 mA when operated without receiver instruments at the current output
I = 3 mA when operated with receiver instruments at the current output
Connection diagrams,
see Sect. 2.4: diagrams À Á Ã Å
For
connection and operation with HART®-interface see Section 6.1.
I+ approx. 15 V DC positive
voltage of current output
I current sink
I
chassis ground, current output
2 Electrical connection of outputs and inputs
2.2 Pulse output P and status output S
The pulse and status outputs are galvanically isolated from the current output and all input circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
• Typical pulse and status outputs
S status output
P⊥chassis ground
P pulse output
Page 15
2/2
Installation and operating instructions IFC 020
Switch open Switch closed
OFF (switched off) without function ON (e.g. operation indicator) Power supply OFF Power supply ON F/R INDICATOR (F/R mode) Forward flow Reverse flow TRIP POINT (Limit switch) Inactive Active ALL ERRORS (all errors) Errors No errors FATAL ERRORS (fatal errors only) Errors No errors
• Characteristics of the status outputs
Control input E (with IFC 020 E only) 2.3
The control inputs are galvanically isolated from the current output and all input circuits.
Setting data and functions can be noted down in Section 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
Typical current input E
All operating data and functions can be set:
Operation see Section 4 and 5.18 Fct. 1.08.
The control inputs must be operated in the passive mode.
• Function of the control inputs
OFF switched off TOTAL.RESET reset totalizer(s) ERROR.RESET delete error messages OUTP. HOLD hold value of outputs
Connection diagram, see Sect. 2.4: diagram
Æ
Z10
Z11
Page 16
Installation and operating instructions IFC 020
2/3
2.4 Input / output connection diagrams
Terminal identification
IFC 020 E
separated, 19” plug-in unit, connection cap X2
IFC 020 F separated, field housing
IFC 020 K compact
For connection and operation of the HART® interface, see Section 6.1. Load at HART® operation ranges between min.
250 and max. 500 .
E: X2
F
K
I Current output C Control input (IFC 020 E only) P Pulse output S Status output RS 485 Interface
1 2
I = 0/4 - 20 mA U
ext
15...20 V DC 20...32 V DC
R
i
0...500 250...750
U
ext
15 V DC
I = 0/4 - 20 mA R
i
500
Current output
I
active
Current output I
passive
Active mode
The current output supplies the power for operation of the outputs and inputs.
Passive mode
External power source required for operation of the outputs and inputs.
3 4
Pulse output P
passive
for electronic (EC) or electromechanical (EMC) totalizers
U
ext
30 V DC/24 V AC
I
max
150 mA
(incl. status output S)
U
int
15 V DC from current output
Operation with current output:
I
max
3 mA
Operation without current output:
I
max
23 mA
R
15 V
I
max
Pulse output P
active (and current output I
active
)
for electronic (EC) totalizers
with and without current output I
Totalizer
- electronic (EC)
- electromechanical (EMC)
Milliammeter
0 or 4-20mA and others
Key, N/O contact
External voltage source (U
ext
),
DC or AC voltage, connection polarity arbitrary
DC voltage,
external power source (U
ext
),
note connection polarity
U
ext
U
ext
I
max
+
Page 17
2/4
Installation and operating instructions IFC 020
U
ext
30 V DC/24 VAC
I
max
6 mA
87
Control input E
passive
(IFC 020 E only)
RS 485 Interface
For connection and operation of the
Krohne RS 485 Interface,
see Section 6.2.
6
5
Status output S
passive
U
ext
30 V DC/24 V AC
I
max
150 mA
(incl. pulse output P)
Status output S
active
with and without current output I
U
int
15 V DC
from current output
I
max
3 mA
Operation with current output
I
max
23 mA
Operation without current output
Load
Load
Page 18
Installation and operating instructions IFC 020
3/1
3 Start-up
Before powering the system, please check that it has been correctly installed according
to Sect. 1 and 2.
The flowmeter is delivered ready for operational use. All operating data have
been factory set in accordance with your specifications.
Please refer to Sect. 3.2 “factory settings”.
Power the unit, and the flowmeter will immediately start process flow measurement.
When powered, the display shows in succession: START UP and READY.
This is followed by display of the current flow rate and/or the current totalizer count on either a continuous or alternating basis, depending on the setting under Fct. 1.04.
Refer to Sect. 4 and 5 for operator control of the “display version”.
3.1 Power-on and measurement
3.2 Factory setting
All operating data are factory set according to your order specifications.
If you have not made any particular specifications at the time of ordering, the instruments will be delivered with the standard parameters and functions listed in the Table below.
To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric flow counted independent of the flow direction. On instruments equipped with a display, measured values may possibly be shown with a “ – ” sign.
This factory setting for the current and pulse outputs may possibly lead to measuring errors, particularly in the case of volume flow counting:
for example, if pumps are switched off and a “backflow” occurs which is not within the range of the low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.
To avoid faulty measurements, therefore, it may be necessary to change the factory setting of some or all of the following functions: – low-flow cutoff SMU, Fct. 1.03, Sect. 5.3 – current output I, Fct. 1.05, Sect. 5.6 – pulse output P, Fct. 1.06, Sect. 5.7 – display (option), Fct. 1.04, Sect. 5.4
Operation see Section 4 and 5.
Standard factory settings
Function Setting
1.01 Full-scale range Q
100%
see nameplate
1.02 Time constant 3 s, for I, S and display
1.03 Low-flow ON: 1 %
cutoff SMU OFF: 2 %
1.04 Display (option)
flow rate m
3
/hr or US Gal/min
totalizer(s) m3 or US Gal
1.05 Current output I
function 2 directions range 4 - 20 mA error message 22 mA
1.06 Pulse output P
function 2 directions pulse value 1 pulse/s pulse width 50 ms
1.07 Status output S flow directions
Function Setting
1.08 Control input off
3.01
Language for display only
English
3.02 Flowmeter diameter see nameplate flow direction (see arrow
+ direction
on primary head)
}
3.04 Entry code no
3.05 User unit
Liter/hror USMGal/day
3.06 Application steady
3.07 Measuring point Altometer
3.08 Communication interface off
Page 19
3/2
Installation and operating instructions IFC 020
Here you can note down the settings of the signal converter !
Fct. No. Function Settings
1.01 Full-scale range
1.02 Time constant
1.03 Low-flow cut-off - ON: - OFF:
1.04 Display Flow
Totalizer
Messages
1.05 Current output I Function
Range I
Error
1.06 Pulse output P Function
Selection
Pulse width
Value
1.07 Status output S
1.08 Control input E (IFC 020 E only)
3.01 Language
3.02 Primary head Meter size
GK value
Field frequency
Power frequency
Flow direction
3.04 Entry code required ? - no - yes
→ → → ↵ ↵ ↵ ↑ ↑ ↑
3.05 User-defined unit
3.06 Application Flow is - steady
- pulsating
3.07 Measuring point
3.08 Communication interface
o
Off
o
HART
o
KROHNE RS 485
Address
Baud rate
Setting data 3.3
Page 20
Installation and operating instructions IFC 020
4/1
4 Operation of the signal converter
Teil B IFC 020 _/ D Signal converter
4.1 Krohne operator control concept
1 3 6. 4 9 m3/hr
Measuring mode
CodE 1
Menu column
Function column
Data column
3.00 INSTALL.
2.00 TEST
1.00 OPERATION
3.05 USER UNIT
3.06 APPLICATION
3.07 MES. POINT
3.08 COM
3.04 ENTRY CODE
3.03 ZERO SET
3.02 FLOWMETER
3.01 LANGUAGE
2.02 HARDW. INFO
2.01 TEST Q
1.07 STATUS S
1.08 CONTROL E
1.06 PULS OUTP. P
1.05 CUR. OUTP. I
1.04 DISPLAY
1.03 L.F. CUTOFF
1.02 TIMECONST.
1.01 FULL SCALE
Direction of movement
see
Sect.
4.4
When this display appears, press following keys:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
Page 21
Installation and operating instructions IFC 020
4/2
Operating and check elements 4.2
The controls are accessible after unscrewing the 4 screws and removing the housing cover.
Display, 1st line
Display, 2nd line
ƒ Display, 3rd line: arrows to identify display
Flowrate current flowrate
Totalizer + totalizer
totalizer
Σ sum totalizer (+ and –)
Overrange I overranging, current output I
P overranging, pulse output P
Keys for operator control of signal converter
Compass field, signals actuation of a key.
IFC 020
Page 22
S T O R E Y E S
F c t . 3. 0 0
INSTALL.
F c t . 1. 5
C U R R E N T I
FUNCT. I
F c t . 1. 5
C U R R E N T I
F c t . 1. 4
D I S P L A Y
F c t . 1. 0 0
O P E R AT I O N
Installation and operating instructions IFC 020
4/3
4.3 Function of keys
The cursor (flashing part of display) has a grey background in the following descriptions.
T
o start operator control
PLEASE NOTE: When “YES” is set under Fct. 3.04 ENTRY CODE, “CodE 1 - - - - - - - - -”
appears in the display after pressing the key. The 9-keystroke Entry Code 1 must now be entered: → → → ↵ ↵ ↵ ↑ ↑ ↑
(each keystroke acknowledged by “
*
”).
To terminate operator control
Press key repeatedly until one of the following menus
Fct. 1.00 OPERATION, Fct. 2.00 TEST or Fct. 3.00 INSTALL. is displayed.
Increase number
T
o select a function
Decrease number
Switch to function
T
o select a sub function
Return to function
Measuring mode
1 3 . 5 7 1
m 3 / h r
Operator control mode
Press key
Store new parameters: acknowledge by
pressing key . Measuring mode continued
with the new parameters.
New parameters not to be stored:
press key to display „STORE.NO“.
Measuring mode continued with the „old“
parameters after pressing key .
Page 23
1 D I R.
9 3. 3 6 5
U S. G a l / m i n
1 3. 5 7 1
m 3/hr
1 3. 5 7 1
m 3 / h r
3 9 7. 3 5
m 3 / h r
3 9 7. 3 5
m 3 / h r
3 9 7. 4 5
m 3 / h r
3 9 7. 3 5
m 3/hr
3. 7 6 9 9
L i t e r / S e c
1 0. 3
Sec
R A N G E I
F c t. 1. 02
T I M E C O N S T.
Installation and operating instructions IFC 020
4/4
increase number
T
o change numbers
decrease number
shift to right
T
o shift cursor (flashing position)
shift to left
select next text
T
o alter texts (units)
For units, the numerical value is converted automatically.
select preceding text
Change to number setting
T
o transfer from text (unit) to number setting
Return to text setting
To transfer to subfunction
Subfunctions do not have a “Fct.No.“ and are identified by a “ ”.
To revert to function display
Page 24
Installation and operating instructions IFC 020
4/5
π
4
π
4
Q actual flowrate Q
100%
100% flow = full scale range
Q
max
= DN2x v
max
/ max. full-scale range (Q
100%
)
at v
max
= 12 m/s / 40 ft/s
Q
min
= DN2x v
min
/ min. full-scale range (Q
100%
)
at v
min
= 0.3 m/s / 1 ft/s
S Status output
SMU Low-flow cutoff for I and P v Flow velocity v
max
Max. flow velocity (12 m/s / 40 ft/s) at Q
100%
v
min
Min. flow velocity (0.3 m/s / 1 ft/s) at Q
100%
F/R Forward/Reverse flow at F/R operation
π
4
4.4 Table of settable functions
Abbreviations used
C Control input (IFC 020 E only) DN Nominal size, meter size F
max
Highest frequency of pulse output
F
min
Lowest frequency of pulse output
F
M
Conversion factor volume for any unit, see Fct. “FACT. VOL.”
F
T
Conversion factor time for any unit, see Fct. 3.05 “FACT. Time”
GK Primary constant I Current output I
0%
Current at 0% flow
I
100%
Current at 100% flow
P Pulse output P
max
= F
max
/ Q
100%
P
min
= F
min
/ Q
100%
π
4
Fct. Text Description and settings
1.00 OPERATION Operations menu
1.01 FULL SCALE Full-scale range for flowrate Q
100%
Select unit
m3/hr Liter/Sec US.Gal/min
user unit, factory set is “Liter/hr” or “US MGal/day” (see Fct. 3.05)
Press key to transfer to number setting.
Setting ranges The ranges are dependent on the meter size (DN) and the flow
velocity (v): Q
min
= DN2x v
minQmax
= DN2x v
max
Nom. dia./meter size vmin = 0,3 m/s (1 ft/s) vmax = 12 m/s (40 ft/s)
DN 2.5–1000 /
1
/10”–40”: 0.0053 – 033 900 m3/hr
0.0237 – 152 000 US.Gal/min
Press key to return to Fct. 1.01 FULL SCALE.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
) has been changed. With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
min
= F
min
/ Q
100% Pmax
= F
max
/ Q
100%
Check new values!
1.02 TIMECONST. Time constant
Select:
ALL (applies to display and all outputs)
ONLY I+S (only display, current and status outputs)
Press key to transfer to number setting.
Range: 0.2 – 99.9 Sec
Press key to return to Fct. 1.02 TIMECONST.
1.03 L.F.CUTOFF Low-flow cutoff (SMU)
OFF (fixed values: ON = 0.1% / OFF = 0.2%
at 100Hz and 1000Hz, see Fct. 106, 1% resp. 2%)
PERCENT (variable values) ON OFF
1 – 19% 2 – 20%
Press key to transfer to number setting.
Note:
Cutoff “off” value must be greater than cutoff “on” value.
Press key to return to Fct. 1.03 L.F. CUTOFF.
Page 25
Installation and operating instructions IFC 020
4/6
Fct. Text Description and settings
1.04 DISPLAY Display functions
DISP.FLOW Select flow display
NO DISP. •
user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
m3/hr PERCENT
Liter/Sec BARGRAPH (value and bargraph display in %)
US.Gal/min
Press key to transfer to subfunction “DISP. TOTAL.”.
DISP.TOTAL. Select totalizer display
NO DISP. (totalizer switched on but not displayed)
OFF (totalizer switched off)
+TOTAL TOTAL ±TOTAL SUM (Σ)
ALL (single totalizer or all)
Press key to transfer to display unit
m3 Liter US.Gal
user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).
Press key to transfer to format setting.
Format settin
g
• Auto (exponent notation)
# . ####### ##### . ###
## . ###### ###### . ##
### . ##### ####### . #
#### . #### ########
Press key to transfer to subfunction “DISP.MSG”.
DISP.MSG. Additional messages required in measuring mode?
NO YES (cyclic change with displays of measured values)
Press key to return to Fct. 1.04 DISPLAY.
1.05 CURRENT I Current output I
FUNCT. I Select function for current output I
OFF (switched off)
1 DIR. (1 flow direction)
2 DIR. (forward/reverse flow, F/R flow measurement)
Press key , transfer to subfunction “RANGE I”;
RANGE I Select measuring range
0 - 20 mA 4 - 20 mA (fixed ranges)
mA (user-defined range) I
0%
- I
100%
(Value I0%< I
100%
!) 0 - 16 mA 4 - 20 mA
To transfer to number setting, press key →!
Press key to transfer to subfunction “I ERROR“.
I ERROR Select error value
22 mA 0.0 to I0%mA (variable, see above if I0%> 1 mA)
To transfer to number setting, press key →!
Press key to revert to Fct. 1.05 CURRENT. I.
Page 26
Fct. Text Description and settings
1.06 PULS B1 Pulse output P
FUNCT. P Select function for pulse output P
OFF (switched off)
1 DIR. (1 flow direction)
2 DIR. (forward/reverse flow, F/R flow measurement)
Press key to transfer to subfunction “SELECT P”.
SELECT P Select pulse type
100 HZ PULSE/VOL. (pulses per unit volume, flowrate)
1000 HZ PULSE/TIME (pulses per unit time for 100% flowrate)
Press key to transfer to subfunction “PULSWIDTH”. With selection 100 HZ and 1000 HZ, return to Fct.1.06 PULSOUTPUT P (pulswidth 50% cyclic).
PULSWIDTH Select pulse width
50 msec 100 msec 200 msec 500 msec 1 sec
Press key to transfer to subfunction “VALUE P”.
VALUE P Set pulse value per unit volume (appears only when
“PULSE/VOL.” set under “SELECT P” above)
xxxx PulS/m3 xxxx PulS/Liter xxxx PulS/US.Gal
xxxx PulS/
user-defined unit, factory-set is “Liter” or “US M.Gal” (see Fct. 3.05) Setting range “xxxx” is dependent on the pulse width and the full-scale range: P
min
= F
min
/ Q
100%Pmax
= F
max
/ Q
100%
Press key to return to Fct. 1.06
PULS. OUTPUT P”.
VALUE P Set pulse value per unit time (appears only when “PULSE/TIME”
set under “SELECT P” above)
xxxx PulSe/Sec (=Hz) xxxx PulSe/min xxxx PulSe/hr
xxxx PulSe/user-defined unit, factory-set is “hr” (see Fct. 3.05)
Setting range “xxxx” is dependent on the pulse width, see above Press key to return to Fct. 1.06
PULS. OUTPUT P””.
1.07 STATUS. S Status output S
ALL ERROR FATAL ERROR • OFF • ON
F/R INDIC. (F/R indication for forward/reverse measurement)
TRIP. POINT Settin
g range: 002 - 115 PERCENT
Press key to transfer to number setting Press key to return to Fct. 1.07 “STATUS. S“.
1.08 CONTROL E Control input E (IFC 020 E only) (IFC 020 E only) OFF (switched off)
OUTP. ZERO (set outputs to “min.values”)
TOTAL. RESET (reset totalizers)
ERROR. RESET(delete error messages)
Press key to return Fct. 1.08 “Control E”.
Installation and operating instructions IFC 020
Fct. Text Description and settings
2.00 TEST Testmenu
2.01 TEST Q Test measuring range Q
Precautionary query
SURE NO Press key to return to Fct. 2.01 “TEST Q”.
SURE YES Press key, then use or key to
select value: -110 / -100 / -50 / -10 / 0 / +10 / +50 / +100 / +110 PCT.
of set full-scale range Q
100%
.
Displayed value present at outputs I and P.
Press key to return to Fct. 2.01 “TEST Q”.
2.02 HARDW. INFO Hardware information and error status
Before consulting factory, please note down all 6 codes.
MODUL ADC X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press key to transfer to “MODUL IO“.
MODUL IO X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press key to transfer to “MODUL DISP.“.
MODUL DISP. X . X X X X X . X X Press ↵ key to transfer to “MODUL RS
Y Y Y Y Y Y Y Y Y Y
MODUL RS X . X X X X X . X X Press ↵ key to return to Fct. 2.02
Y Y Y Y Y Y Y Y Y Y “HARDW. INFO“.
4/7
Page 27
4/8
Installation and operating instructions IFC 020
3.03 ZERO SET Zero calibration
Note: Carry out only at “0” flow and with completely filled
measuring tube!
Precautionar
y query
CALIB. NO Press key to return to Fct. 3.03 “ZERO SET”.
CALIB. YES Press key to start calibration.
Duration approx. 15-90 seconds, (depends on frequency of magnetic field) current flowrate
displayed in the selected
unit (see Fct. 1.04 “DISP. FLOW”).
A “WARNING” sign appears when flowrate “> 0“; acknowledge by pressing key.
STORE NO (do not store new zero value)
STORE YES (store new zero value)
Press key to return to Fct. 3.03 “ZERO SET”.
3.04 ENTRY CODE Entry code required to enter setting mode?
NO (= entry with only)
YES (= entry with and Code 1: → → → ↵ ↵ ↵ ↑ ↑ ↑ )
Press to return to Fct. 3.04 “ENTRY CODE”.
Fct. Text Description and settings
3.00 INSTALL. Installation menu
3.01 LANGUAGE Select language for display texts
GB / USA (English) F (French)
D (German) others on request
Press key to return to Fct. 3.01 “LANGUAGE”.
3.02 FLOWMETER Set data for primary head
DIAMETER Select size from meter size table
DN 2.5 - 1000 mm equivalent to 1/10- 40 inch
Select with or key. Press key to transfer to subfunction “FULL SCALE ”.
FULL SCALE Full-scale range for flow Q
100%
To set, refer to Fct. 1.01 “FULL SCALE” above.
Press key to transfer to subfunction “GK VALUE”.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
) has been changed. With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
min
= F
min
/ Q
100% Pmax
= F
max
/ Q
100%
Check new values!
GK VALUE Primary head - Set primary constant GK
see primary head nameplate. Ran
ge: 1.0000 - 9.9999
Press key to transfer to subfunction “FIELD. FREQ.”.
FIELD FREQ. Magnetic field frequency
Values: 1/6
and 1/18 of power frequency, see nameplate.
Press key to transfer to subfunction “FLOW DIR.”; DC units only: to transfer to subfunction “LINE FREQ.”.
LINE FREQ. Normal line frequency in your country
Please note: This function is only provided for units with DC power supply 24 V DC to suppress line-frequency interference. Values: 50 Hz and 60 Hz
Press key to transfer to subfunction “FLOW DIR.”.
FLOW DIR. Define flow direction (in F/R mode: forward flow).
Set according to direction of arrow on primary head:
+ DIR. – DIR. Select using or ↓ key. Press key to return to Fct. 3.02 “FLOWMETER ”.
Page 28
Installation and operating instructions IFC 020
4/9
Fct. Text Description and settings
3.05 USER UNIT Set any required unit for flowrate and counting
TEXT VOL. Set text for required flowrate unit (max. 5 characters)
Factory-set: “Liter” or “MGal”. Characters assignable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press key to transfer to subfunction “FACT. VOL.”
FACT. VOL. Set conversion factor (F
M
) for volume
Factory set “1.00000 E+3” for “Liter” or “2.64172E-4” for “US MGal” (exponent notation, here: 1x103or 2.64172x10-4). Factor FM= volume per 1m3. Setting range 1.00000 E-9 to 9.99999 E+9 (= 10-9to 10+9)
Press key to transfer to subfunction “TEXT TIME”.
TEXT TIME Set text for required time unit (max. 3 characters)
Factory-set: “hr” (=hour). Characters assignable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press key to transfer to subfunction “FACT. TIME”
FACT. TIME Set conversion factor (F
T
) for time
Factory-set: “3.60000 E+3” for “hour” or “8.64000 E+4” for “day” (exponent notation, here: 3.6 x103or 8.64 x10-4). Set factor FTin seconds. Setting range
1.00000 E-9 to 9.99999 E+9 (= 10-9to 10+9)
Press key to return to Fct. 3.05 “USER UNIT”.
3.06 APPLICAT. Set overload point for A/D converter
FLOW STEADY (150% of Q
100%
) PULSATING (1000% of Q
100%
)
Press key to return to Fct. 3.06 “APPLICAT.“,
3.07 MEASURING POINT Set measuring point no. Factory setting: ALTOMETER Characters assi
gnable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character). Press key to return to Fct. 3.07 ”MEASURING POINT”
3.08 COM Set comminucation interface
OFF (switched off)
HART (HART-interface switched on)
KROHNE (RS 485 interface switched on)
Address:”HART” 00-15 / “KROHNE” 000-239
BAUD RATE: -1200 -2400 -4800 -9600 -19200
(appears with selection “KROHNE” only)
Press key to return to Fct. 3.08 “COM”.
Page 29
Installation and operating instructions IFC 020
4/10
Error messages in measuring mode 4.5
The following list gives all errors that can occur during process flow measurement. Errors shown in display when “YES“ set in Fct. 1.04 DISPLAY, subfunction “DISP. MSG.“.
Error messages Description of error Error clearance
LINE INT. Power failure Note:
Cancel error in RESET/QUIT. menu
no counting during power failure Reset totalizer if necessary.
CUR. OUTP. I Current output overranged. Check and if necessary correct
(Flow > measuring rage) instrument parameters. After
elimination of cause, error message deleted automatically.
PULSOUTP. P Pulse output overranged. Check and if necessary correct
Note:
instrument parameters. After
totalizer deviation possible. elimination of cause, error message
deleted automatically.
TOTALIZER Totalizer has been reset Cancel error message in
RESET/QUIT. menu, see Section 4.6.
ADC Analog / digital Error message deleted automatically
converter overranged after elimination of cause.
FATAL. ERROR Fatal error, all outputs set Please consult factory.
to “min. values“
Page 30
Installation and operating instructions IFC 020
4/11
4.6 Reset totalizer and cancel error messages, RESET / QUIT menu
Cancel error messages in RESET / QUIT menu
Key Display Description
- - - - - - - - - - - - / - - - Measuring mode
CodE 2 - - Key in entry code 2 for RESET / QUIT
menu: ↑→
↑ → ERROR QUIT. Menu for error acknowledgement QUIT. NO Do not delete error messages,
press twice = return to measuring mode QUIT. YES Delete error messages ERROR QUIT. Error messages deleted - - - - - - - - - - - - / - - - Return to measuring mode
Reset totalizer(s) in RESET / QUIT menu
Key Display Description
- - - - - - - - - - - - / - - - Measuring mode
CodE 2 - - Key in entry code 2 for RESET / QUIT
menu: ↑→
↑ → ERROR QUIT. Menu for error acknowledgement TOTAL. RESET Menu for resetting totalizer RESET NO Do not reset totalizer,
press twice = return to measuring mode RESET. YES Reset totalizer RESET QUIT. Totalizer reset - - - - - - - - - - - - / - - - Return to measuring mode
Page 31
Installation and operating instructions IFC 020
4/12
Examples of setting the signal converter 4.7
As an example the cursor, flashing part of display, is shown below in bold type.
Change measuring range of current output and value for error messages (Fct. 1.05):
Change measuring range from 04-20 mA to 00-20 mA
Change value for error messages from 0 mA to 22 mA
Key Display Description
If “YES” set under Fct. 3.04 ENTRY CODE, key in the
9-keystroke CODE 1 now: → →→ ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00 OPERATION
Fct. 1.01 FULL SCALE 4x Fct. 1.05 CURRENT I
FUNCT. I →↵ RANGE I 04-20 mA Old current range 00-20 mA New current range I ERROR 0 mA Old value for error messages 2x 22 mA New value for error messages Fct. 1.05 CURRENT I Fct. 1.00 OPERATION STORE YES - - - - - - - - - - - - / - - - Measuring range with new data for the current output
Page 32
Installation and operating instructions IFC 020
5/1
5 Description of functions
5.1 Full-scale range Q
100%
π
4
π
4
Fct. 1.01 FULL SCALE
Press key.
Choice of unit for full-scale ran
ge Q
100%
m3/hr (cubic metres per hour)
Liter/Sec (litres per second)
US.Gal/min (US gallons per minute)
User-defined unit, factory-set is „Liter/hr“ (litres per hour) or “US MGal/day”, see Sect. 5.12.
Select with or key. Use key to transfer to numerical setting, 1st number (cursor) flashes.
Set full-scale ran
ge Q
100%
The setting range is dependent on meter size (DN) and flow velocity (v).
Q
min
= DN2x v
minQmax
= DN2x v
max
(refer to flow table in Sect. 10.1)
0.0053 – 33 929 m3/hr
0.00147 – 9 424.5 Liter/Sec
0.00233 – 151 778 US.Gal/min
Change flashing number (cursor) with or key. Use key to shift cursor 1 place to right. Press key to return to Fct. 1.01 FULL SCALE.
Note if “VALUE P” is displayed after pressing key:
PULSE/VOL. is set under Fct. 1.06 PULS B1, subfunction “SELECT P”. Due to the changed full-scale range Q
100%
, the output frequency (F) of the pulse output will be over- or undershot:
P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Change pulse value accordingly, see Sect. 5.7 pulse output P, Fct. 1.06.
5.2 Time constant
Fct. 1.02 TIMECONST.
Press key.
Choice
ALL (applies to display and all outputs)
ONLY I+S (applies only to display, current and status output)
Select with or key.. Transfer to number setting with key. 1st number (cursor) flashes.
Set numerical value
0.2 - 99.9 Sec (seconds)
Change flashing number (cursor) with the or key. Use key to shift cursor 1 place to right. Press key to return to Fct. 1.02 TIMECONST.
Page 33
Installation and operating instructions IFC 020
5/2
Low-flow cutoff 5.3
Fct. 1.03 L.F.CUTOFF
Press key.
Choice
OFF (fixed tripping point: ON = 0.1 % / OFF = 0.2 %
with 100Hz and 1000Hz, see Fct. 1.06; 1% resp. 2%)
PERCENT (variable tripping points: ON = 1 - 19 % / OFF = 2 - 20 %)
Select with or key. Transfer to number setting using key (only if “PERCENT” selected).
1st number (cursor) flashes.
Settin
g the numerical value when “PERCENT” selected
01 to 19 (cutoff “on” value, left of hyphen)
02 to 20 (cutoff “off” value, right of hyphen)
Change flashing number (cursor) with the or key. Shift cursor 1 place to right using key. Press key to return to Fct. 1.03 L.F.CUTOFF.
Note: The cutoff “off” value must be greater than the cutoff “on” value.
Continuation see next page
Display 5.4
Fct. 1.04 DISPLAY
Press key.
DISP. FLOW = select unit for display of flowrate, press key
NO DISP. (no display)
m3/hr (cubic metres per hour)
Liter/Sec (litres per second)
US.Gal/min (US gallons per minute)
user-defined unit, factory-set: “Liter/hr” (litres per hour) or “US MGal/day”, see Sect. 5.14
PERCENT (percentage display)
BARGRAPH (numerical value and bar graph display in %)
Select with or key. Press key to transfer to subfunction “DISP. TOTAL”.
DISP. TOTAL = select unit for totalizer display, press key
NO DISP. (no display)
OFF (internal totalizer switched off)
• + TOTAL. • – TOTAL. • +/– TOTAL. • SUM (ΣΣ) • ALL (sequential)
Select with or key. Transfer to totalizer unit setting using key.
•m3 (cubic metres)
Liter (litres)
US.Gal (US gallons)
user-defined unit, factory-set: “Liter” or “US MGal”, see Sect. 5.14
Select with or key. Transfer to totalizer format setting using key.
Page 34
Installation and operating instructions IFC 020
5/3
Settin
g of totalizer format
Auto (exponent notation)
# . ####### • ##### . ###
## . ###### • ###### . ##
### . ##### • ####### . #
#### . #### • ########
Select with or key.. Press key to transfer to subfunction “DISP. MSG”.
DISP. MSG. = additional messages required in measuring mode, press key
•NO (no other messages)
YES (display other messages, e.g. errors, in sequence with the measured values)
Select using the or key. Press key to return to Fct. 1.04 DISPLAY.
Note: “BUSY” is displayed in the measuring mode when all displays are set to “NO DISP.” or “NO”. Sequencing of displays is automatic. However, in the measuring mode, manual sequencing
can be carried out with the key. Return to automatic sequencing after approx. 3 minutes.
Please refer to Sect. 3.2 “factory settings”
5.5 Internal electronic totalizer
The internal electronic totalizer counts in m3, regardless of the unit set under Fct. 1.04, subfunction “DISP. FLOW”. The counting range is dependent upon the meter size and has been selected such that the totalizer will count for a minimum of 1 year without overflow:
Only part of the totalizer count is shown in the display because it is not possible to output a 14-digit number. Unit and format of the display are freely selectable, see Fct. 1.04, subfunction “DISP. TOTAL” and Sect. 5.4. This determines which part of the count is to be displayed. Display overflow and totalizer overflow are independent of one another.
Exam
ple
Internal count 0000123 . 7654321 m
3
Format, display unit XXXX . XXXX Liter Internal count in unit 0123765 . 4321000 Liter Displayed 3765 . 4321 Liter
Meter size Counting range
DN mm inch in m
3
US Gal equivalent
2.5 - 50
1
/10- 2 0 - 999 999.99999999 0 - 264 172 052.35800
65 - 200 2
1
/2- 8 0 - 9 999 999.9999999 0 - 2 641 720 523.5800
250 - 600 10 - 24 0 - 99 999 999.999999 0 - 26 417 205 235.800
700 -1000 28 - 40 0 - 999 999 999.99999 0 - 264 172 052 358.00
Page 35
Installation and operating instructions IFC 020
5/4
Current output I 5.6
Fct. 1.05 CURRENT I
Press key.
FUNCT. I = Select function for current output , press key
OFF (switched off, no function)
1 DIR. (1 flow direction)
2 DIR. (2 flow directions, F/R mode, forward/reverse)
Select using or key.
Transfer to subfunction “RANGE I”
with key.
Exceptions: When “OFF” selected, return to Fct. 1.05 CURRENT I.
RANGE I = select measuring range, press key
0 - 20 mA
fixed ranges
4 - 20 mA
mA (user-defined value) I
0%
– I
100%
(value I0%< I
100%
!) 0-16 mA 4-20 mA
Press key to transfer to number setting. Select with or key. Press key to transfer to subfunction “I
ERROR”.
I ERROR = set error value, press key
22 mA (fixed value)
0.0 - I
0%
mA (variable value; only variable when I
0%
1 mA, see ”RANGE I“ above)
Select using or key.. Press key to transfer to number setting. Press key to return to Fct. 1.05 CURRENT I.
Please refer to Sect. 3.2 “Factory settings”.
Refer to Sect. 2.3 for connection diagrams, and to Sect. 5.14 for characteristics.
}
Page 36
Installation and operating instructions IFC 020
5/5
5.7 Pulse output P
Fct. 1.06 PULS.OUTP. P
Press key → . →
FUNCT. P = select function for pulse output, press key
OFF (switched off, no function)
1 DIR. (1 flow direction)
2 DIR. (2 flow directions, F/R mode, forward/reverse)
Select with key or . Press key to transfer to subfunction “SELECT
P”.
Exception: When “OFF” selected, return to Fct. 1.06 PULS P.
SELECT P = select pulse type, press key
100 Hz
1000 Hz
PULSE/VOL. (pulses per unit volume, flow)
PULSE/ZEIT (pulses per unit time for 100% flow)
Select using or key.
Transfer to subfunction ”PULSWIDTH”
with key.
Note: when 100 Hz or 1000 Hz selected, return to Fct. 1.06 PULS.OUTP. P.
PULSWIDTH = set pulse width, press key
50 mSec F
max
= 10 Hz F
min
= 0.0056 Hz (= 20 Pulse / hr)
• 100 mSec = 5 Hz
• 200 mSec = 2.5 Hz
• 500 mSec = 1 Hz
501 mSec = 0,5 Hz
Select using or key.
Transfer to subfunction ”V
ALUE P” with key or return to Fct. 1.06
PULS.OUT. P, depending on choice of pulse type in subfunction ”SELECT P”.
Page 37
Installation and operating instructions IFC 020
5/6
VALUE P = set pulse value per unit volume (appears only when “PULSE/VOL.” set under “SELECT P”, press key.
• XXXX PulS/m3
• XXXX PulS/Liter
• XXXX PulS/US.Gal
• XXXX PulS/ user unit, factory-set: “Liter” or “US MGal”, see Sect. 5.12.
Select using or key. Transfer to number setting with key. 1st digit (cursor) flashes.
Set numerical value
• XXXX (setting range depends on pulse width and full-scale range: P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
)
Change flashing digit (cursor) with or key, shift cursor 1 place to right with key. Press key to return to Fct. 1.06 PULS. P.
or
Please refer to Sect. 3.2 “factory settings”
VALUE P = set pulse value per unit time,
(a
ppears only when ”PULSE/TIME” has been set under “SELECT P”), press key.
• XXXX PulSe/Sec
• XXXX PulSe/min
• XXXX PulSe/hr
• XXXX PulSe/ user unit, factory-set: “hr”, see Sect. 5.12.
Select using or key. Transfer to number setting with key, 1st digit (cursor) flashes.
Set numerical value
• XXXX (setting range depends on pulse width)
Change flashing digit (cursor) with or key, shift cursor 1 place to right with key. Press key to return to Fct. 1.06 PULS. P.
Refer to Sect. 2.4 for connection diagrams, and to Sect. 5.14 for characteristics.
Page 38
Installation and operating instructions IFC 020
5/7
5.8 Status output S
Fct. 1.07 STATUS S
Press key .
Select function of status out
puts, press key
ALL ERROR (indicates all errors)
FATAL.ERROR (indicates fatal errors only)
OFF (switched off, no function)
•ON (indicates that flowmeter is operative)
F/R INDIC. (indicates direction for current and pulse outputs, F/R mode)
TRIP. POINT (setting range: 002 – 115 PERCENT of Q
100%
, full-scale range)
Transfer to number setting with key, 1st digit (cursor) flashes. Change flashing digit (cursor) with and keys. Use and keys to shift cursor 1 place to right or left.
Press key to return to Fct. 1.07 STATUS S.
• Characteristic of status output Switch open Switch closed
OFF (switched off) no function ON (e.g. operation indicator) power OFF power ON F/R INDIC. Forward flow Reverse flow TRIP POINT (limit switch) inactive active ALL ERROR (all errors) errors no error FATAL.ERROR (fatal errors only) errors no error
Please refer to Sect. 3.2 “factory settings”
Refer to Sect. 2.4 for connection diagrams, and to Sect. 5.14 for characteristics.
Page 39
Installation and operating instructions IFC 020
5/8
Language 5.9
Entry code 5.10
Fct. 3.01 LANGUAGE
Press key.
Select lan
guage for texts in display
•D (German)
GB/USA (English)
•F (French)
others on request
Select using or key. Press key to return to Fct. 3.01 LANGUAGE.
Fct. 3.04 ENTRY CODE
Press key.
Choice
•NO (no code, enter setting mode with key)
YES (enter setting mode with key and Code 1: → → → ↵ ↵ ↵ ↑ ↑ ↑)
Select using or key. Press key to return to Fct. 3.04 ENTRY CODE.
Page 40
Installation and operating instructions IFC 020
5/9
5.11 Primary head
Please refer to Sect. 3.2 “factory settings”
Fct. 3.02 FLOW METER
Press key.
DIAMETER = set meter size (see instrument nameplate) press key
Select size from table of meter sizes:
DN 2.5 - 1000 mm equivalent to
1
/10 - 40 inch
Select using or key.
Transfer to subfunction “FULL SCALE”
with key.
FULL SCALE = set full-scale range, press → key.
Set as described in Sect. 5.1.
Transfer to subfunction “GK V
ALUE” with key.
Note: if “VALUE P” is displayed after pressing key.
PULSE/VOL. is set under Fct. 1.06 PULS.OUTP. P, subfunction “SELECT P”. Because the full-scale range Q
100%
has been changed, the output frequency (F) of the pulse output is over- or
undershot: P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Change pulse value accordingly, see Sect. 5.7 pulse output P, Fct. 1.06.
GK VALUE = set primary constant GK, press key.
1.0000 - 9.9999 (note information on instrument nameplate, do not change setting !)
Change flashing digit (cursor) with or key. Shift cursor 1 place to right or left with or key.
Transfer to subfunction “FIELD
FREQ.” with key.
FIELD FREQ. = set magnetic field frequency, press key
1/2 • 1/18 (1/2, 1/6 1/18 or 1/36 of power frequency,
1/6 • 1/36 see instrument nameplate, do not change setting)
Select using or key.
Transfer to subfunction “FLOW DIR.”
with key.
(only for units with DC power supply, transfer to subfunction “LINE FREQ”).
LINE FREQ. = normal line frequency in your country, press → key.
(Please note, applicable for flowmeters equipped with DC in power supply!)
50 Hz Select using the
or key.
60 Hz Transfer to subfunction “FLOW
DIR.” with ↵ key.
FLOW DIR. = set flow direction, press key.
+ DIR. (for identification of flow direction, see “+” arrow on primary head;
- DIR. for F/R mode, identifies the “positive” flow direction)
Select using the or key. Press key to return to Fct. 3.02 FLOW METER.
Zero check
, see Fct. 3.03 and Sect. 7.1.
}
Page 41
Installation and operating instructions IFC 020
5/10
User-defined unit 5.12
Fct. 3.05 USER UNIT
Press key.
TEXT VOL = set text for user-defined unit, press key
• Liter (max. 5 characters, factory-set: “Liter” or “US MGal”)
Characters assi
gnable to each place: A-Z, a-z, 0-9, or “–” (= blank character)
Change flashing place (cursor) using or key. Use or key to shift cursor 1 place to right or left.
Transfer to subfunction “F
ACT. VOL.” with key.
FACT. VOL. = set factor F
M
for volume, press key
• 1.00000 E+3 (factory-set: “1000 or 2.64172 x 10
-4
” / factor FM= volume per 1 m3)
Settin
g range: 1.00000 E-9 to 9.99999 E+9 ( = 10-9to 10+9)
Change flashing place (cursor) using or key.. Use or key to shift cursor 1 place to right or left.
Transfer to subfunction “TEXT TIME”
with key.
TEXT TIME = set text for required time, press key
•hr (max. 3 places, factory-set: “hr = hour”)
Characters assi
gnable to each place: A-Z, a-z, 0-9, or “–” (= blank character)
Change flashing place (cursor) using or key. Use or key to shift cursor 1 place to right or left.
Transfer to subfunction “F
ACT. TIME” with key.
FACT. TIME = set factor F
T
for time, press key
• 3.60000 E+3 (factory-set: “3600” for hour or “8.64 x 104” for day / set factor FT
in seconds) Settin
g range: 1.00000 E-9 to 9.99999 E+9 ( = 10-9to 10+9)
Change flashing place (cursor) using or key. Use or key to shift cursor 1 place to right or left. Press key to return to Fct. 3.05 USER UNIT.
Factors for volume F
M
(factor FM= volume per 1 m3)
Volumetric unit Text examples Factor F
M
Setting
Cubic metres m3 1.0 1.00000 E+0 Litres Liter 1 000 1.00000 E+3 Hectolitres h Lit 10 1.00000 E+1 Decilitres d Lit 10 000 1.00000 E+4 Centilitres c Lit 100 000 1.00000 E+5 Millilitres m Lit 1 000 000 1.00000 E+6 US gallons USGal 264.172 2.64172 E+2 Millions US gallons USMG 0.000264172 2.64172 E -4 Imperial gallons GBGal 219.969 2.19969 E+2 Mega imperial gallons GBMG 0.000219969 2.19969 E -4 Cubic feet Feet3 35.3146 3.53146 E+1 Cubic inches inch3 61 024.0 6.10240 E+4 US barrels liquid US BaL 6.28982 6.28982 E+0 US barrels ounces US BaO 33 813.5 3.38135 E+4
Factors for time FT(factor FTin seconds)
Time unit Text examples Factor FT (seconds) Setting
Seconds Sec 1 1.00000 E+0 Minutes min 60 6.00000 E+1 Hours hr 3 600 3.60000 E+3 Day DAY 86 400 8.64000 E+4 Year (= 365 days) YR 31 536 000 3.15360 E+7
Page 42
Installation and operating instructions IFC 020
5/11
I
I
max
I
100%
I
0%
Q
R
Q
F
%
0
%100 Max
P
115%
P
100%
P= 0 Hz
Q
R
Q
F
%
0
%100 Max
P
max
I
I
max
I
100%
I
0%
Q
R
Q
F
%
0
%100 MaxMax 100
P
115%
P
100%
P= 0 Hz
Q
R
Q
F
%
0
%100 Max
Max 100
P
max
S
Q
R
Q
F
%
0
%100 Max
Max 100
5.13 F/R mode, forward/reverse flow measurement
Refer to Sect. 2.4 for electrical connection of outputs.
Define direction of forward (normal) flow, see Fct. 3.02, subfunction “FLOW DIR.”:
in conjunction with F/R operation, set the direction for the forward flow here. “+” signifies the same direction as shown by the arrow on the primary head, “–” signifies the opposite direction.
Set the status output to ”F/ R INDIC.”, see Fct. 1.07.
Current and/or pulse output must be set to “2 DIR.”, see Fct. 1.05 and 1.06, subfunctions
“FUNCT. I” and “FUNCT. P”.
5.14 Characteristic of outputs
I Current output I
0%
0 or 4 mA
I
100%
20 mA
P Pulse output P
100%
Pulses at Q
100%
, full-scale range
Q
F
1 flow direction, forward flow in F/R operation
Q
R
Reverse flow in F/R operation
Q
100%
Full-scale range
S Status output
switch open switch closed
1 flow direction 2 flow directions, F/R mode
Page 43
Installation and operating instructions IFC 020
5/12
Applications 5.15
Measuring point identification 5.16
Fct. 3.06 APPLICAT.
Press key →.
FLOW = Set characterization for the flow, press key
STEADY (flow is steady)
PULSATING (pulsating flow, e.g. due to reciprocating pumps,
see also Sect. 6.4, 6.5 and 6.6 “Special-case applications”)
Press key to return to Fct. 3.06 APPLICAT.
}
select function using
key or
Fct. 3.07 MEAS.PNT
.
Press key →.
Set measuring point identification using max. 10 characters ,
(e.g. TQ1_532197)
You can use any out of A...Z / a...z / 0...9 or _ (underscore)
- Select character by pressing key or ↓.
- Use key to shift one place to the left, back with key.
Press key to return to Fct. 3.07 MEAS.PNT.
Communication interface 5.17
Control input E (IFC 020 E only) 5.18
Fct. 3.08 COM
Press key →.
Specify function
OFF (Switched off)
HART (HART Interface)
KROHNE (RS 485 Interface)
Use key or to set ADDRESS 00-15 after selecting "HART" with key. Press key dto return to Fct. 3.08 COM.
Use key or to set ADDRESS 000-239 after selecting "KROHNE" (RS 485). Press key and set up BAUD RATE: 1200 2400 4800 9600 19200. Use key or to select baud rate. Press key to return to Fct. 3.08 COM.
}
select function using key or
Fct. 1.08 CTRL.INP
. E
Press key .
Select control input function, using key or ↓.
OFF (Switched off, out of function)
ZERO OUTPUT (Set output and display to "Min. values")
RESET COUNT. (Reset counter)
RESET ERROR (Delete / confirm error message)
Press key to return to Fct. 1.08 CTRL.INP. E
For factory-set preferences refer to the start-up protocol and Section 3.2.
Page 44
Installation and operating instructions IFC 020
6/1
Part C Special applications, functional checks,
service, and order numbers
6 Special applications
Power supply unit (and section switch amplifier) must be set up accordingly if in use for HART®operation.
For further information on setting the signal converter refer to chapters 4 and 5.
Settings and operation
Fct. Parameter Point-to-point Multidrop
mode mode
1.05 FUNCT. I 1 CORRECT. or OFF
2 CORRECT.
RANGE I 4-20 mA or Any
I0% m 4 mA
3.09 COM HART HART
ADDRESS 0 01, 02, 03 ..... 15
(use one address at one time only)
Operation Current output Active or passive Passive only
The HART interface is a smart interface, in other words a communication signal superimposed on the current output. All functions and parameters can be accessed via this interface.
The following HART features are supported:
point-to-point connection
multidrop (up to 15 HART devices)
The burst mode is not normally used. Further information about HART is available from the HART Communication Foundation, of which Krohne is a member.
Electrical connection
6
.1 HART
®
interface
HART®- active HART®- passive
active passive
to HART
®
- communicator
or smart-converter
to HART®- communicator or smart converter
R
i
250
power supply unit
to next
HART®-device
Page 45
Installation and operating instructions IFC 020
6/2
HART o
perating tools / Device Description (DD)
The IFC 020 can be operated either via its local operator interface or by means of the HART communicator or the CONFIG program. Both operating tools are available from KROHNE. Operator control by means of the HART communicator requires a device description (DD) which we can load for you into the communicator. We can, of course, also load the DDs of all manufacturers who have filed their DDs with the HART Communication Foundation. If you wish to use the IFC 020 in your operating tool, for example, please ask for the description of the HART command used so that you can address the complete IFC 020 functionality via HART.
Electrical connection
Settings for use in interface operation
It is essential to blank off the final signal converter's electrical bus. To do this, solder up the semicircular circuits of solder points S6 and S7 on the amplifier PCB. For further information refer to sections 8.8 and 8.9.
The RS 485 protocol is available. Please contact your local Krohne supplier / company.
Krohne RS 485 Interface 6.2
For further information on setting the signal converter refer to chapters 4 and 5.
Fct. Parameter Krohne RS 485 Interface
3.08 COM KROHNE
ADRESS 000-239 BAUD RATE 1200 09600
2400 19200
4800
Terminals:
IFC 020 E
IFC 020 K and F
Address, e.g.:
Page 46
Output signals can be stabilized to values as for “zero” flow to prevent random output signals when the measuring tube is empty or when the electrodes are not wetted in the event the measuring tube is partially full.
- Display: 0
- Current output: 0 or 4 mA, see setting in Fct. 1.05
- Pulse output: no pulses (= 0 Hz), see setting in Fct. 1.06
Precondition:
- electrical conductivity of product: 200 µS/cm, 500 µS/cm for meter sizes DN 2.5 - 15 and
1
/10”-1/2
- Signal cable length 10m and vibration free with signal converter
- Homogeneous liquid products, free of solids and gasses an do not tend to electrical or catalytic reactions.
Chan
ges on amplifier PCB, see Fig. in Sect. 8.8.
Switch off power source before opening the housing!
Fig. A, B and D are situated in Section 8.1!
1) Unscrew 4 recessed head screws (Fig. A) and remove transparent cover.
2) Unscrew 4 recessed head screws (Fig. B) and remove black plastic cover.
3) Unscrew 2 recessed head screws (Fig. D) and remove black metal cover.
4) Unscrew 4 recessed head screws and fold display to the side carefully.
5) Join the two “semicircles” of points S1 and S3 on the amplifier board with tin solder,
see illustration in Sect. 8.8.
6) Reassemble in reverse order, points 4) - 2) above.
7) Switch on power.
8) Check setting of the low-flow cutoff SMU, Fct. 1.03, and reset if necessary:
L.F.CUTOFF switched on, range:
O
perator control:
See Sect. 4 and 5.3 Fct. 1.03.
9) After checking and/or resetting, replace the transparent cover and tighten the 4 recessed head screws.
6/3
6.3 Stable signal outputs when measuring tube empty
IFC 020 K and IFC 020 F
Montage- und Betriebsanleitung IFC 020
Full scale range Q
100%
Cutoff ...... values
... OFF ... ... ON ...
> 3 m/s > 10 ft/s >02 % 1 % 1 - 3 m/s 3 -10 ft/s >06 % 4 % < 1 m/s < 03 ft/s >10 % 8 %
Page 47
Installation and operating instructions IFC 020
6/4
IFC 020 E
Changes on amplifier PCB, see Fig. in Sect. 8.9.
Switch off power source before opening the housing!
Illustrations 1 till 3 are situated in Section 8.1
1) Unscrew the 4 recessed head screws (S1) on the front side (Fig. 1).
2) Carefully remove the plug-in unit from the subassembly support.
3) Unscrew the 4 recessed head screws (S2) on the front side (Fig. 1).
4) Remove the ribbon cable from the display unit. For this, first pull up the securing clamp
on the socket (Fig. 3). Note down situation of contact side of the foil plug.
5) Unscrew the 4 recessed head screws on the back side (Fig. 2) and carefully pull the back cover together with the electronic unit out of the plug-in unit.
6) Join the “semicircles” of points S2,S3 and S4 on the amplifier board with tin solder, see illustration in Sect. 8.9.
7) Reassemble in reverse order, points 5) - 1) above.
8) Switch on power.
9) Check setting of the low-flow cutoff SMU, Fct. 1.03, and reset if necessary:
L.F.CUTOFF switched on, range:
Full scale range Q
100%
Cutoff ...... values
... OFF ... ... ON ...
> 3 m/s > 10 ft/s >02 % 1 % 1 - 3 m/s 3 -10 ft/s >06 % 4 % < 1 m/s < 03 ft/s >10 % 8 %
Page 48
Installation and operating instructions IFC 020
6/5
6.4 Pulsating flow
Application
downstream of positive-displacement pumps (reciprocating or diaphragm pumps) without pulsation dampener
Operator control of the signal converter for the new settings, see Sect. 4 and 5
To change settings
Fct. 3.02 FIELD FREQ.
(change magnetic field frequency) – Stroke frequency less than 80 strokes/min (at max. pump lift): do not change setting. – Stroke frequency 80 - 200 strokes/min (at max. pump lift): change setting to 1/2,
only practical with IFM 5020 K and IFS 5000 F (DN 2.5-100 /
1
/10”-4”)
and IFM 4020 K and F IFS 4000 F (DN 10, 15, 50-100 /
1
/10”, 1/2”, 2”-4”),
Please consult factory where other types and meter sizes are concerned.
– Please note: given stroke frequencies close to the tripping point of 80 strokes/min, additional
measuring errors of approx. ± 0.5% of the measured value may occasionally occur.
• Fct. 3.06 APPLICA
T. (adjust overload point of the A/D converter to the application)
Change setting to “PULSATING”.
• Fct. 1.04 DISP
. FLOW (change display presentation of flow)
Change setting to “BARGRAPH” to allow better assessment of display unsteadiness.
• Fct. 1.02 TIMECONST
. (change time constant)
– Set to “ALL” and time (t) in seconds.
– Recommended: t [s] =
– Example: min. number of strokes in operation = 50 strokes/minute
t [s] = = 20 s
With this setting, the residual ripple of the display will amount to approx. ± 2% of the measured value. Doubling the time constant will reduce the residual ripple by a factor of 2.
1000
min. strokes / min
1000
50 / min
6.5 Rapid changes in flowrate
Application
in conjunction with batching processes, fast-response control loops, etc.
Operator control of the signal converter for the new settings
refer to chapters 4 and 5
To change settings
• Fct. 1.02 TIMECONST
. (change time constant)
Setting to “ONLY I” and set time to 0.2 s.
•D
ynamic response with meter sizes DN 2.5-300 / 1/10”-12”
Dead time: approx. 0.06 s at 50 Hz line frequency
approx. 0.05 s at 60 Hz line frequency
Time constant: set as above, current output (mA) additionally plus 0.1 s
• Reducin
g the dead time by a factor of 3 (possible by changing the magnetic field frequency) Fct. 3.02 FLOW METER, subfunction “FIELD FREQ.”, change to “1/2”, only practical with IFM 5020 K and IFS 5000 F (DN 2.5-100 /
1
/10”-4”)
and IFM 4020 K and IFS 4000 F (DN 10, 15, 50-100 /
1
/10”, 1/2”, 2”-4”)
Please consult factory where other types and meter sizes are concerned.
Page 49
Installation and operating instructions IFC 020
6/6
Unsteady display and outputs 6.6
Unsteady display and outputs can occur in connection with – high solids contents, – non-homogeneity, – poor blending, or – chemical reactions still in progress in the process liquid.
If, in addition, flow is also pulsating due to the use of diaphragm or reciprocating pumps, refer to Sect. 6.4.
Operator control of the signal converter for the new settings, see Sect. 4 and 5
To change settings
• Fct. 1.04 DISP
. FLOW (change display presentation of the flow)
Change setting to “BARGRAPH” to allow better assessment of display unsteadiness.
• Fct. 1.02 TIMECONST
. (change time constant) – Setting to “ONLY I”, to “ALL” if pulse output too unsteady. – Set time constant to approx. “20 s”, observe unsteadiness of display and adjust time
constant if necessary.
• Fct. 3.06 APPLICA
T. (adjust overload point of the A/D converter to the application)
Set to “PULSATING” on trial basis, if unsuccessful return to “STEADY”.
• Fct. 3.02 FIELD
FREQ. (change magnetic field frequency) On trial basis, change setting to “1/2”; if unsuccessful return to previous setting, usually “1/6”.
Only practical with IFM 5020 K and IFS 5000 F (DN 2.5-100 /
1
/10”-4”)
and IFM 4020 K and IFS 4000 F (DN 10, 15, 50-100 /
1
/10”, 1/2”, 2”-4”),
Consult factory where other types and meter sizes are concerned.
Page 50
Installation and operating instructions IFC 020
7/1
7. Functional checks
7.1 Zero check Fct. 3.03
Switch off power supply before opening the housing
Set “zero” flow in the pipeline, but make sure that the measuring tube is completely filled with fluid.
Switch on the system and wait 15 minutes.
Press the following keys for zero measurement:
Key Display Description
If “YES” set under Fct. 3.04 ENTRY CODE, key in
9-keystroke CODE 1 now: → → → ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00 OPERATION
2x Fct. 3.00 INSTALL. Fct. 3.01 LANGUAGE
2x Fct. 3.03 ZERO SET
CALIB. NO CALIB. YES 0.00 - - - - - / - - - Flowrate displayed in set unit, see Fct. 1.04 DISPLAY,
subfunction “DISP. FLOW”. Zero measurement in progress, duration approx. 15 - 90 seconds. When flow “> 0” “WARNING” notice appears, confirm with key.
STORE NO If new value not to be stored, press key (3x) 4x = return to
measuring mode.
STORE YES Fct. 3.03 ZERO SET Store new zero value. (2x) 3x - - - - - - - - - - - - / - - - Measuring mode with new zero.
Key Display Description
If “YES” set under Fct. 3.04 ENTRY CODE, key in
9-keystroke CODE 1 now: → → → ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00 OPERATION
Fct. 2.00 TEST Fct. 2.01 TEST Q SURE NO SURE YES
0 PERCENT Current, pulse and status indication outputs indicate the
corresponding values.
± 10 PERCENT
± 50 PERCENT Select using or key
± 100 PERCENT ± 110 PERCENT
Fct. 2.01 TEST Q End of test, actual measured values again present at outputs. (2x) 3x - - - - - - - - - - - - / - - - Measuring mode
7.2 Test of measuring range Q, Fct. 2.01
Switch off power supply before opening the housing !
For this test a measured value can be simulated in the range of -110 to +110 percent
of Q
100%
(full-scale range set, see Fct. 1.01 FULL SCALE).
Switch on the system.
Press the following keys for this test:
Page 51
Installation and operating instructions IFC 020
7/2
Faults and symptons during start-up and process flow measurement 7.4
Before contacting Krohne Service, please read through the
following tables. THANK YOU !
Most faults and symptoms occuring with the flowmeters can be eliminated
with the aid of the following tables.
For greater clarity, faults and symptoms in the tables are divided into various groups.
Groups: D Display
I Current output P Pulse output S Status indication output D / I / P / S LED display, current output, pulse output,
status output and display
Hardware information and error status, Fct. 2.02 7.3
Key Display Description
If “YES” set under Fct. 3.04 ENTRY CODE,
key in the 9-keystroke CODE 1 now: → → → ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00 OPERATION
Fct. 2.00 TEST Fct. 2.01 TEST Q Fct. 2.02 HARDW. INFO
→→MODUL ADC -.- - - - -.- - 1st window
- - - - - - - - - Sam
ple status code
↵→MODUL IO -.- - - - -.- - 2nd window 3.25105.02 ( 8-character code, 1st line)
- - - - - - - - - 3A47F01DB1 (10-character code, 2nd line)
↵→MODUL DISP. -.- - - - -.- - 3rd window
- - - - - - - - -
↵→MODUL RS. -.- - - - -.- - 4rd window
PLEASE NOTE DOWN ALL 6 STATUS CODES !
Fct. 2.02 HARDW. INFO Terminate hardware information (2x) 3x - - - - - - - - - - - - - / - - - Measuring mode
Before consulting factory about errors or flow measurement problems, please invoke Fct. 2.02 HARDW. INFO (hardware information).
An 8-character and a 10-character status code are stored under this function in each of 3 “windows”. These 6 status codes allow rapid and simple diagnosis of your compact flowmeter.
Switch on system.
Press the following keys for display of the status codes:
If you need to return your flowmeter to Krohne, please refer to last
but one page of these Instructions !
Page 52
Group D Display shows . . . Cause Remedial action
D 1 LINE INT. Power failure. Delete error message in
Note:
no counting during RESET/QUIT. menu. Reset
power failure. totalizer(s) if need be.
D 2 CUR.OUTP. I Current output overranged. Check instrument parameters
and correct if necessary. Error message deleted automatically after cause has been eliminated.
D 3 PULS.OUTP. P Pulse output overranged. Check instrument parameters,
Note:
totalizer deviation correct if necessary, and reset
possible totalizer(s). Error message
deleted automatically after cause has been eliminated.
D 4 ADC Analog/digital converter Error message deleted
overranged. automatically after cause
has been eliminated.
D 5 FATAL. ERROR Fatal Error, Replace signal converter
all outputs set to “min.” (see Sect. 8.4) or contact values. Krohne Service, having
first noted down hardware information and error status, see Fct. 2.02.
D 6 TOTALIZER Counts lost Delete error message in
(overflow, data error) RESET/QUIT. menu.
D 7 „STARTUP“ Hardware fault, Replace signal converter
cyclic flashing Watchdog activated. (see Sect. 8.4) or contact
Krohne Service.
D 8 BUSY Displays for flow, Change setting in
totalizers and errors disabled. Fct. 1.04.
D 9 Unsteady display – Process product Increase time constant,
conductivity too low, see Fct. 1.02, or switch on.particles/air inclusionstoo large or inhomogeneous
– Pulsating flow – Time constant too low or
switched off.
D 10 No display Power OFF. Switch on power
Check power fuse(s) Replace if defective F1 (F1 and F2 with DC). (see Sect. 8.2).
Group I Fault / Symptom Cause Remedial action
I 1 Receiver instrument Incorrect connection/polarity Connect properly,
indicates “0”. see Sect. 2.4.
Receiver instrument or current Check output (see Sect. 7.2) output defective. with new milliammeter:
T
est ok, check connection cables and receiver instrument, replace if necessary. T
est faulty, current output defective. Replace signal converter (see Sect. 8.4) or contact Krohne Service
Current output disabled, Activate under Fct. 1.05. see Fct. 1.05
Short-circuit between current Check connection and cables, output and pulse output. see Sect. 2.4. Voltage between
I+ and Iapprox. 15 V. Switch off device, eliminate short-circuit, and switch device on again.
I 2 Unsteady display – Process product Increase time constant,
conductivity too low, see Fct. 1.02particles/air inclusionstoo large or inhomogeneous
– Pulsating flow – Time constant too low or
switched off.
Installation and operating instructions IFC 020
7/3
Page 53
Installation and operating instructions IFC 020
7/4
Group P Fault / Symptom Cause Remedial action
P 1 Totalizer connected but does Incorrect connection/polarity Connect properly,
not count any pulses see Sect. 2.4.
Totalizer or external voltage Check output (see Sect. 7.2) source defective. with new totalizer:
T
est ok, check connection cables and previous totalizers and external voltage source, and replace if necessary. T
est faulty, pulse output defective, replace signal converter (see Sect. 8.4) or contact Krohne Service.
Current output is external Check connection and cables, voltage source, short circuit see Sect. 2.4. Voltage between or current / pulse output I
+
and Iapprox. 15 V.
defective Switch off device, eliminate
short circuit, switch device on again. If no function, then current or pulse output defective. Replace signal converter (see Sect.
8.4) or contact Krohne Service.
Pulse output is deactivated, Switch on under Fct. 1.06. see Fct. 1.06.
P 2 Unsteady pulse rate – Process product Increase or switch on
conductivity too low, time constant, under Fct. 1.02particles/air inclusions orswitch on if necessary.too large or inhomogeneous
– Pulsating flow – Time constant too low
or switched off
P 3 Pulse rate too high or Incorrect setting for Change setting under Fct. 1.06.
too low. pulse output.
Group S Fault / Symptom Cause Remedial action
S 1 No function Incorrect connection/polarity Connect properly,
of status display see Sect. 2.4.
Status display or output Set status output under Fct. 1.07 defective or external to “F/R INDIC.“ (flow direction) voltage source not and check (see Sect. 7.2) supplying voltage. with new status display:
T
est ok, check previous status display and external voltage source, and replace if necessary. T
est faulty, status output defective, replace signal converter (see Sect. 8.4) or contact Krohne Service.
Group D/I/P/S Fault / Symptom Cause Remedial action
D/I/P/S1 Unsteady display and – Process product Increase time constant,
outputs conductivity too low, under Fct. 1.02
particles/air inclusionstoo large or inhomogeneous
– Pulsating flow – Time constant too low
D/I/P/S 2 No display and no Power OFF Switch power on.
function of outputs
Check power fuse(s) Replace if defective, F1 (F1 and F2 for DC). see Sect. 8.2.
Page 54
Installation and operating instructions IFC 020
7/5
7.5 Test of signal converter using GS 8 A simulator (option)
7.5.1 IFC 020 K und IFC 020 F signal converter
GS 8 A operating elements and accessories
+ 0 –
B Plug for field power
supply, 2-pin
C5 Plug for signal cable,
5-pin
D Switch,
flow direction
H Socket for H2 plug
on cable Z
H2 Plug of cable Z L Power supply ON P Potentiometer “zero” X3 Socket for plug B
on amplifier PCB
X5 Socket for plug C3
on amplifier PCB
Y Switch,
measuring ranges
Z Cable between GS 8 A
and signal converters IFC 020K and IFC 020 F
Electrical connection
H2
Z
C 5
B
X 5 X 3
amplifier PCB, see Sect. 8.8
Connection of milliammeter and electronic frequency counter, see Sect. 2.4 “Connection of outputs”.
10
Power
Outputs U-clamp terminal
II I+ P PS PE
Milliammeter, accuracy class 0.1, Ri< 500 ohms, range 4-20 mA Electronic frequency counter, input resistance approx. 1 k, range 0-1 kHz, time base min. 1 second, see connection diagrams in Sect. 2.4.
A
a) Switch off power source before
opening the housing !
b) Unscrew the 4 recessed head screws, see
Fig. A in Sect. 8.1, and remove transparent
cover from the signal converter housing.
c) Unscrew recessed head screw, see Fig. B in
Sect. 8.1, and remove black plastic cover.
d) Pull off blue 9-pin plug from the amplifier PCB,
see Sect. 8.9: socket X3 field power supply and socket X5 signal cable.
e) Connect plug B to socket X3 (2-pin) and
plug C (5-pin) to socket X5 (5-pin)
1,25
2,5
5
10
20
320
160
80
40
20
Y
P
D
L
H
Using GS 8 simulator
Additional adapter is required
between GS 8 and IFC 020 K and IFC 020 F signal converter.
Order No. 2.10764.00.
L N
Page 55
Installation and operating instructions IFC 020
IFC 020 E signal converter 7.5.2
GS 8A Operating elements and accessories
+ 0 –
D Switch,
Flow direction
H Socket for H1
plug On cable M
H1 Plug of cable M
L Power supply ON
M Cable between
GS 8A and IFC 020E signal converter
P Potentiometer
"zero point"
Y Switch,
Measuring ranges
Z Leitung zwischen GS 8A
und IFC 020 K und IFC 020 F Meßumformer
Electrical connection
H1
mA meter, accuracy class
0.1, Ri < 500 , range 4-20 mA. Electronic frequency counter, input resistance approx. 1 k, range 0-1 kHz, time basis min. 1 second, see connection diagrams in Sect. 2.4.
A
a) Switch off power supply before starting work !
b) Unscrew the 4 recessed head screws (S1)
on the front plate (see Sect. 8.1, Fig. 1).
c) Carefully pull off plug-in unit from subassembly
support.
d) The electrical connection is on the X1 and X2
connectors at the rear hand side of the IFC 020 E signal converter as shown in connection diagram with cable M.
1,25
2,5
5
10
20
320
160
80
40
20
Y
P
D
L
H
7/6
Power supply
connection
Electrical connection
of mA meter and
electronic frequency
counter (see Sect. 2.4).
Electrical connection of IFC 020 E and GS 8A
Page 56
Installation and operating instructions IFC 020
1) Switch on power supply, allow at least 15 minutes’ warm-up time. .
2) Set switch D (front panel of GS 8A) to “0” position.
3) Adjust zero to 0 or 4 mA with the 10-turn potentiometer P (front panel of GS 8A), depending on setting in Fct. 1.05, deviation <±10 µA.
4) Calculate position of switch Y and displayed setpoints ”I“ and ”f“:
4.1) X =
Q
100%
x
K
GK
x
DN
2
Q
100%
full-scale range (100%) in volumetric unit V per unit time t GK primary constant, see instrument nameplate DN meter size DN im mm, not inches, see instrument nameplate t time in seconds (Sec), minutes (min) or hours (hr) V volumetric unit K constant, according to following table
7/7
7.5.3 Check of setpoint display
t Sec min hr
V
Liter 25 464 424.4 7.074 m3 25 464 800 424 413 7 074 US gallons 96 396 1 607 26.78
4.2) Determine position of switch Y: Use table (front panel GS 8A) to determine value Y
which comes closest to factor X and meets condition Y X.
4.3) Calculate set
point reading ”I“ for current output: I = I0%+ Y(I
100%
- I0%) in mA
X
I
0%
current (0/4mA) at 0% flowrate
I
100%
current (20mA) at 100% flowrate
4.4) Calculate set
point reading ”f“ for pulse output: f =
Y
x
P
100%
in Hz
X
P
100%
pulses per second (Hz) at 100% flowrate
5) Set switch D (front panel GS 8A) to position “+“ or “-“ (forward/ reverse flow).
6) Set switch Y (front panel GS 8A) to the value determined by the method described above.
7) Check setpoint readings I and f, see points 4.3 and 4.4 above.
8) Deviation <1.5% of setpoint. If greater, replace signal converter, see Sect. 8.4.
9) Test of linearity: set lower Y values, readings will drop in proportion to the calculated Y values.
10) Switch off power supply after completing the test.
11) Disconnect the GS 8A.
12) Reassemble in reverse order, see points e) – b) under “electrical connection”, see illustration in Sect. 8.1.
13) The system is ready for operation after the power supply has been switched on.
Exam
ple: see overleaf
Page 57
Installation and operating instructions IFC 020
If you need to return your flowmeter to Krohne,
please refer to last but one page of these Instructions !
Full-scale range Q
100%
= 200 m3/hr (Fct. 1.01) Meter size DN = 80 mm = 3“ (Fct. 3.02) Current at Q
0%
I
0%
= 4 mA
Q
100%
I
100%
= 20 mA
}
(Fct. 1.05)
Pulses at Q
100%
P
100%
= 200 pulses/hr (Fct. 1.06) Primary head constant GK = 3.571 (see nameplate) Constant (V in m3)
(t in hr) K = 7074 (see Table) (DN in mm)
Calculation of “ X ”
and position of “ Y ”
X =
Q
100%
x K
=
200 x 7074
= 61.905
GK x DN
2
3.571 x 80 x 80
Y = 40, position of switch Y, see front panel GS 8A (comes closest to X value and is smaller than X).
Calculation of set
point readings I and f
I = I0%+Y(I
100%
- I0%) = 4 mA +
40
(20mA - 4mA) = 14.3 mA
X 61.905
Deviations are permissible between 14.1 and 14.6 mA
(equivalent to ± 1.5 %).
f = Yx P
100%
=
40
x 200 pulses / hr = 129.2 pulses/hr
X 61.905
Deviations are permissible between 127.3 and 131.1
pulses/hr (equivalent to ± 1.5 %).
7/8
Example 7.5.4
Page 58
Installation and operating instructions IFC 020
8/1
Fig. A
Fig. B
Fig. C
Fig. D
Fig. E
Fig. F
Fig. G
8 Service
IFC 020 K IFC 020 F
8.1 Illustrations used for service work
Switch off power supply before starting service work!
Page 59
Installation and operating instructions IFC 020
8/2
IFC 020 E
Switch off power supply before starting service work!
F
F
B
VB
Front plate / Display
B
VB
B Socket on display PCB F Ribbon cable VB Locking clip of socket B
Fig. 1 Fig. 2
Fig. 3
S1
S2
S2
S1
S3
S3
S4
S4
Page 60
Installation and operating instructions IFC 020
8/3
8.2 Replacement of power supply fuse
Switch off power supply before opening the housing!
Power PCB Power supply Fuse F1
IFC 020 K and IFC 020 F for Section 8.3 Location and position of voltage selector
Rating Order No.
1. AC version 230/240 V AC 125 mA T 5.06627
115/117 V AC 200 mA T 5.05678
2. AC version 200 V AC 125 mA T 5.06627
100 V AC 200 mA T 5.05678
3. AC version 48 V AC 400 mA T 5.05892
24 V AC 800 mA T 5.08085
DC version 24.V DC
F 1
F 1
F 1
F 1
IFC 020 K and IFC 020 F
IFC 020 E
Refer to Sect. 8.1 for Figs. A and B.
1) Unscrew the 4 recessed head screws (Fig. A), and remove transparent cover.
2) Unscrew the recessed head screw (Fig. B) and remove the black plastic
cover.
3) Take out old and insert new power fuse F1, on the left next to the green connecting terminals. Please refer to the following table for fuse rating and order number.
4) Reassemble in reverse order, points 2) – 1) above.
Refer to Sect. 8.1 for Figs. 1 and 2.
1) Unscrew the 4 recessed head screws (S1), on the front (Fig. 1).
2) Carefully remove the plug-in unit from the subassembly support.
3) Replace power fuse F1 back of cassette(Fig. 2). Refer to the following table for fuse rating and order number.
4) Reassemble in reverse order, points 2) - 1) above.
IFC 020 E only
IFC 020 E only
Page 61
Installation and operating instructions IFC 020
8/4
Changeover of operating voltage on AC Versions 1 and 2 8.3.
Switch off power source before opening the housing !
IFC 020 K and IFC 020 F
IFC 020 E
Refer to Sect. 8.1 for Figs. A to F.
1) Unscrew the 4 recessed head screws (Fig. A), and remove transparent cover.
2) Unscrew the recessed head screw (Fig. B) and remove the black plastic
cover.
3) Carefully pull out the green connecting plugs (power supply and outputs)
(Fig. C).
4) Unscrew the 2 recessed head screws (Fig. D) and remove the black metal
cover.
5) Carefully pull out the blue 9-pin plug (connection to the primary head)
(Fig. D).
6) With a screwdriver, carefully remove the 4 metal clips (Fig. E).
7) Remove the electronics unit
from the housing (Fig. F) and detach the ground conductor.
8) Transpose voltage selector on the power supply PCB (illustration in Sect. 8.8) to obtain the required voltage according to the table in Sect. 8.2.
9) Change power fuse F1, see table in Sect. 8.2 for fuse ratings.
10) Reassemble in reverse order, points 7) - 1) above.
Refer to Sect. 8.1 for Figs. 1 to 3.
1) Unscrew the 4 screws (S1), on the front (Fig. 1).
2) Carefully remove the plug-in unit from the subassembly support.
3) Unscrew the 4 recessed head screws (S2) on the front (Fig.1).
4) Remove the ribbon cable from the display unit. For that pull up the securing clamp (Fig. 3). Note down the position of the contact side of the ribbon connector.
5) Unscrew the 4 recessed head screws on the back (Fig.2) and carefully pull the electronic unit out of the cassette, together with the back.
6) Transpose the voltage selector on the power PCB (see Fig. in Sect. 8.9) for the desired voltage according to the decal on the transformer.
7) Exchange power fuse F1. Value see table in Sect. 8.2.
8) Reassemble in reverse order, points 5) - 1) above.
Page 62
Installation and operating instructions IFC 020
8/5
8.4 Replacement of electronics unit of signal converter
8.5 IFC 20 K and IFC 020 F: Cleaning the signal converter housing
Switch off power supply before cleaning the housing!
Clean the signal converter housing (made of polycarbonate, PC) with a cotton cloth dipped in solvent-free mild agent only !
Switch off power source before opening the housing !
IFC 020 K and IFC 020 F
IFC 020 E
Refer to Sect. 8.1 for Figs. A to G.
1) Unscrew the 4 recessed head screws (Fig. A), and remove transparent cover.
2) Unscrew the recessed head screw
(Fig. B) and remove the black plastic
cover.
3) Carefully pull out the green connecting
plugs (power supply and outputs,
Fig. C).
4) Unscrew the 2 recessed head screws
(Fig. D) and remove the black metal
cover.
5) Carefully pull off the blue 9-pin plug
(connection to the primary head)
(Fig. D).
6) With a screwdriver, carefully remove
the 4 metal clips (Fig. E).
7) Remove the electronics unit
from the housing (Fig. F) and detach the ground conductor.
8) Carefully transpose DATAPROM (IC 13)
on the amplifier-PCB (see Fig. in Sect.
8.8) from the “old” and the “new” electronic unit (Fig. G). Watch the position of the IC 13 when putting it on.
9) Check the power supply and fuse F1 on
the new electronic unit and transpose / replace if necessary according to Sect. 8.3 nos. 8) and 9).
10) Reassemble in reverse order,
points 7) - 1) above.
Refer to Sect. 8.1 for Figs. 1 to 3.
1) Unscrew the 4 recessed head screws (S1), on the front (Fig. 1).
2) Carefully remove the plug-in unit from the subassembly support.
3) Unscrew the 4 recessed head screws (S2) on the front (Fig.1).
4) Remove the ribbon cable from the display unit. For that pull up the securing clamp (Fig. 3). Note down the position of the contact side of the ribbun connector.
5) Unscrew the 4 recessed head screws on the back (Fig.2) and carefully pull the electronic unit out of the cassette, together with the back.
6) Carefully transpose DATAPROM (IC 13) on the amplifier-PCB (see Fig. in Sect. 8.9) from the “old” and the “new” electronic unit . Watch the position of the IC 13 when putting it on.
7) Check the power supply and fuse F1 on the new electronic unit and transpose / replace if necessary according to Sect. 8.3 nos. 6) and 7).
8) Reassemble in reverse order, points 5) - 1) above.
Page 63
Installation and operating instructions IFC 020
8/6
IFC 020 K and IFC 020 F: Turning the display PCB 8.6
Switch off power supply before opening the housing!
For the illustrations A, B and D refer to Section 8.1.
1) Unscrew the 4 recessed head screws (Fig. A), and remove transparent cover from signal converter housing
2) Unscrew recessed head screw (Fig. B), and remove black plastic cover.
3) Unscrew the 2 recessed head screws (Fig. D), and remove black metal cover.
4) Unscrew the 4 recessed head screws of display PCB.
5) Carefully turn display PCB.
6) Fold the ribbon cable as shown in the illustrations found under Section 8.7. PLEASE NOTE! The ribbon cable must lie flat between display PCB and
amplifier PCB and must not exert any pressure on electronic components.
7) Reassemble in reverse order using point 1) to 4) referenced above.
Page 64
Installation and operating instructions IFC 020
8/7
8.7 IFC 020 K and IFC 020 F: Directions for folding the ribbon cable on the display unit
A Socket X7 on amplifier PCB,
see Sect. 8.8
B Socket on display PCB C Contact side D Display F Ribbon cable I Insulated side K 5 keys for operator control R Reference point, power terminals 90° Bend cables 90° as shown
in drawing
Version 1 / Standard IFC 020 K/D
Compact flowmeter
Version 3/ Standard IFC 020 F/D
Separate version
Version 4
R
R
R
K
K
K
A
A
A
B
B
B
F
F
F
D
D
D
Version 2
R
K
A
B
F
D
R
A
F
C
F
Version 2 only
90°
90°
I
F
B
Display board
Amplifier board
Page 65
Installation and operating instructions IFC 020
B) Power supply PCB,
AC versions
F1 Power fuse. Ratings
see Section 8.2 or Chapter 9
SW Voltage selector for
changing the voltage see Section 8.3
Tr Transformer
8/8
IFC 020 K and IFC 020 F: Illustrations of the PCBs 8.8
A) Amplifier PCB
IC 13 DATAPROM (sensor),
see Sect. 8.4.
S1, S3 for “empty tube”
cut-out, see Sect. 6.3.
S2, S4 not used S6, S7 for blanking off the bus
lead, KROHNE RS 485 interface, Sect.6.2.
X3 2-pin plug connector,
pin 7 and 8, field power supply, see Sect. 7.5.
X5 5-pin plug connector,
pin 1-5, signal cable, see Sect. 7.5.
Tr
F1
SW
IC 13
X5
X3
7 8
1 2
3
S2
S1
S4
S3
4 5
S6
S7
Page 66
Installation and operating instructions IFC 020
8/9
8.9 IFC 020 E: PCB illustrations
A) Amplifier PCB
IC 13 DATAPROM (Sensor)
See Section 8.4
S2, S3 For use of empty tube
cut-off
S4 See Section 6.3 S1 Not used S6, S7 Used to blank off
electrical bus of Krohne RS 485 Interface See Section 6.2
B) Power supply PCB,
AC Versions
SW Voltage selector
For changing the voltage see Section
8.3
Tr Transformer
Tr
X4
SW
S6X3S7
S3 S2
S4 S1
IC 13
Page 67
Installation and operating instructions IFC 020
9/1
Order-numbers 9
Electronic unit
Power fuse F1
Power supply
Rating Order No. Fuse type
200 and 230 / 240 V AC 125 mA T 5.06627 100 and 115 / 117 V AC 200 mA T 5.05678 5 x20 G-fuse 48 V AC 400 mA T 5.05892 switching capacity 1500 A 24 V AC 800 mA T 5.08085 24 V DC in preperation
Power supply unit Power supply Order No.
IFC 020 K IFC 020 E IFC 020 F
AC V
ersion 1 230 / 240 V AC 2.10989.01 2.11502.02
115 / 117 V AC
AC Version 2 200 V AC
100 V AC 2.10989.02 2.11502.01
Page 68
Installation and operating instructions IFC 020
10.1
Full-scale range Q
100%
Part D Technical Data, Measuring Principle and
Block Diagram
10 Technical data
Full-scale ranges Q
100%
Flow rate Q = 100% 6 liter/h to 33 900 m3/h (0.03 - 156 000 US Gal/min), adjustable as
required, equivalent flow velocity 0.3 - 12 m/s (1 - 40 ft/s)
Unit m
3
/hr, Liter/Sec, US gallons/min. or user-defined unit,
e.g. Liter/day or US MGal/day
10/1
Meter size
DN
mm
inch
v = 0.3 m/s
(minimum)
v = 12 m/s
(maximum)
Full-scale range
Q
100%
in m3/h
v = 1 m/s
Flow tables
v = flow velocity in m/s
Meter size
DN
mm
inch
v = 1 ft/s
(minimum)
v = 40 ft/s
(maximum)
Q
100%
in US Gal/min
0002.5 0004 0006 0010 0015 0020 0025 0032 0040 0050 0065 0080 0100 0125 0150 0200 0250 0300 0400 0500 0600 0700 0800 0900
1000
00
1
/
10
001/
8
001/
4
003/
8
001/
2
003/
4
01 01
1
/
4
011/
2
02 02
1
/
2
03 04 05 06 08
10 12 16 20 24 28 32 36 40
0000.0245
0000.0383
0000.1530
0000.3735
0000.8405
0001.494
0002.334
0003.824
0005.979
0009.339
0015.78
0023.90
0037.35
0058.38
0084.05
0149.43
0233.4
0336.2
0597.9
0933.9
1345 1919 2507 3173 3917
000000.979
000001.530
000006.120
000014.93
000033.61
000059.75
000093.34
000153.0
000239.0
000373.5
000630.9
000955.6 001493 002334 003361 005975 009334 013442 023899 037345 053781 076760
100272 126904 156672
v = flow velocity in ft/s
0002.5 0004 0006 0010 0015 0020 0025 0032 0040 0050 0065 0080 0100 0125 0150 0200 0250 0300 0400 0500 0600 0700 0800 0900
1000 1200 1400 1600
00
1
/
10
001/
8
001/
4
003/
8
001/
2
003/
4
01 0- 01
1
/
2
02 0- 03 04 0- 06 08
10 12 16 20 24 28 32 36 40 48 56 64
000.0053
000.0136
000.0306
000.0849
000.1909
000.3393
000.5302
000.8686
001.358
002.121
003.584
005.429
008.483
013.26
019.09
033.93
053.02
076.35
0135.8
0212.1
0305.4
0415.6
0542.9
0662.8
0848.2
1221 1663 2171
00000.2121
00000.5429
00001.222
00003.392
00007.634
00013.57
00021.20
00034.74
00054.28
00084.82
00143.3
00217.1
00339.2
00530.1
00763.4 01357 02120 03053 05428 08482
12215 16625 21714 26510 33929 48858 66501 86859
0000.0177
0000.4520
0000.1018
0000.2827
0000.6362
0001.131
0001.767
0002.895
0004.524
0007.069
0011.95
0018.10
0028.27
0044.18
0063.62
0113.1
0176.7
0254.5
0452.4
0706.9
1018 1385 1810 2290 2827 4072 5542 7238
Page 69
Installation and operating instructions IFC 020
Current output same error limits as above, additionally ± 10 µA
Reproducibility and repeatability 0.1% of MV, minimum 1 mm/s / 0.04 inch/s at constant flow
External influences t
ypical values maximum values
Ambient temperature Pulse output < 0.003% of MV (1) 0.015% of MV (1) Current output < 0.013% of MV (1) 0.025% of MV (1)1 Power su
pply < 0.023% of MV 0.055% of MV at 10% variation
Load
< 0.013% of MV 0.025% of MV at max. permissible load,
see pages 6 and 7
(1) All Krohne signal converters undergo burn-in tests, duration minimum 20 hours at varying ambient temperatures
– 20 to + 60°C/– 4 to + 140°F. The tests are controlled by computers.
Error limits at reference conditions 10.2
Display, digital values, pulse output F maximum error in % of measured value (not typical values) v Flow velocity in m/s and ft/s
Reference conditions similar to EN 2
9104
Product water at 10 – 30°C/50 – 86°F
Electrical conductivity > 300 µS/cm
Power supply (rated voltage) U
N
(± 2%) Ambient temperature 20 – 22°C/68 – 71.6°F Warm-up time 60 min Max. calibration equipment error
10x smaller than F
Inlet/outlet runs 10
x
DN/2 xDN (DN = meter size)
Primary head properly grounded and centered
Calibrated on EN 17025 accredited calibration equipment in direct volumetric comparsion.
10/2
Type/Meter size Maximum error in % of measured value (MV) ...
Curve
DN mm DN 2.5 – 6
DN 2.5 – 6(1)
DN 10
DN 10
inch
1
/10” – 1/4
DN 2.5 – 6(1)
3
/8
DN 10
v 1 m/s / 3 ft/s ± 0.5% of MV
DN 2.5 – 6(1)
± 0.3% of MV
DN 10
v < 1 m/s / < 3 ft/s± (0.4% of MV + 1 mm/s)± (0.4% of MV + 0.04 inch/s
± (0.2% of MV + 1 mm/s)± (0.2% of MV + 0.04 inch/s)
B
D
A
E
per 1 K / 1.8°F temperature variation
}
* IFS 6000 F (DN 2.5-4 and 1/10”-1/6”) additional error ±0.3% of MV
Page 70
Installation and operating instructions IFC 020
10.3 IFC 020 signal converter
10/3
Versions with display / control elements HART®and RS 485 interfaces IFC 020 K Compact version,converter directly mounted on the signal
converter version
IFC 020 F Seperate housing fieldversion IFC 020 E Seperate housing, 19” Plug-in unit
Current output
Function – all operating data settable, galvanically isolated
Current: ranges 0 – 20 mA and 4 – 20 mA Active mode max. 500 load
Passive mode external voltage: 15 ... 20 V DC 20 ... 32 V DC
load: min. ... max. 0 ... 500 250 ... 750
Error identification 0 / 3.6 / 22 mA and variable
Forward/reverse flow measurment direction identified via status output
Pulse output
Function – all operating data settable, galvanically isolated
– digital pulse division, interpulse period non-uniform,
therefore if frequency and cycle meters connected allow for minimum counting interval:
gate time, totalizer
Pulse rate for Q=100% 10, 100 or 1000 pulses/sec.(=Hz), blocked or to your choice
per m3, Litre US Gallons or freely selectable unit.
Activ mode connection: electronic totalizers
voltage: approx. 15 V DC, from current output load: I
max
< 23 mA, operation without current output
load: I
max
< 23 mA, operation with current output
Passive mode connection: electronic or electromechanical totalizers
voltage: external, U
ext
32 V DC/24 V AC
load: I
max
150 mA
Pulse width – 50, 100, 200 or 500 msec.,selectable at frequencies < 10Hz
symetric at
frequencies < 10Hz
Forward/reverse flow measurement flow direction identified via status output Status output (passive)
Function settable as indicator for flow direction, errors or trip point
Connection voltage: external, U
ext
32 V DC/24 V AC
load current: I
max
150 mA
Control input (passive) IFC 020 E only Function – adjustable for totalizer reset, or reset setting
outputs to min. values
– initiate function by “low” or “high” control signals
Control signals U
max
: 24 V AC 32 V DC (any polarity)
low: 1,4 V 2 V high: 3 V 4 V
Time constant 0.2 – 99.9 s, adjustable in increments of 0.1 second Low-flow cutoff Cutoff “on” value: 1 – 19% of Q
100%
, adjustable
Cutoff “off” value: 2 – 20% in 1% increments
1000
P
100%
[Hz]
}
Page 71
Installation and operating instructions IFC 020
10/4
Local display (D version) 3-field LCD Display function actual flowrate, forward, reverse and sum totalizers
(7-digit), or 25-character bar graph with percentage indication and status messages
Units: Actual flowrate m3/h, liter/s., US gallons/min or user-defined unit,
e. g. liters/day
Totalizer m3, liters, US gallons or user-defined unit,
e. g. hecto-liters or US gallons/day (adjustable count duration up to overflow)
Language of plain texts English, German, French, others on request
Display: Top field 8-character, 7-segment numeral and sign display,
and symbols for key acknowledgement Middle field 10-character, 14-segment text display Bottom field 6 markers to identify display in measuring mode
Power supply
1. Rated voltage Tolerance band
2. Rated voltage Tolerance band
Frequency
Power consumption (incl. primary head)
Housing
IFC 020 K / IFC 020 F Materials Polyamid (PA) and die-cast aluminium Protection category (IEC 529/EN 60 529) IP 67 equivalent to NEMA 6
Housing
IFC 020 E 19” plug-in unit acc. DIN 41494, 21TE wide,3HE high Materials aluminium profile, galvanised sheet metal Protection category (IEC 529/EN 60 529) IP 20
1. AC Version 2. AC Version DC Version
Standard Option Option
(not IFC 020 E) (for IFC 020 E in preparation)
230 / 240 V 200 V 24 V
200 – 260 V 170 – 220 V 18 – 32 V
115 / 120 V 100 V
100 – 130 V 85 – 110 V
48 – 63 Hz 48 – 63 Hz
approx. 8 VA approx. 8 VA approx. 8 W
When connected to functional extra-low voltage, galvanic, safety separation (PELV)
is essential (to VDE 0100/VDE 0106 and IEC 364/IEC 536 or equivalent
national standard).
Page 72
Installation and operating instructions IFC 020
10.4
IFC 020 and ZD dimensions and weights
IFC 020 F
weight approx. 3.8 kg / 8.4 lb
10/5
dia. 9
(0.35”)
27.5
(1.08”)
1 output cable (see Sect. 2.4) 2 signal cable of primary head
(see Sect. 1.3)
3 field power cable of primary head
(see Sect. 1.3)
4 power supply cable (see Sect. 1.2) 5 internal connection
(see Fig. in Sect. 8.8, plug connectors X3 and X5)
116 (4.57”)
160 (6.30”) 144 (5.67”)
9 (0.35”)
dia. 9
(0.35”)
4
5
258 (10.16”)
220 (8.66”)
1
2
3
4
34 (1.34”)
120 (4.72”)
1
1
ZD Intermediate connection box
Weight approx.
0.5 kg/1.1 lbs
dimensions in mm
(--) dimensions in inch
PG 16
1
/2” NPT
57 (4.02”)
22 (4.02”)
80
125 (4.92”)
68 (2.68”)
(3.15”)
Page 73
Installation and operating instructions IFC 020
10/6
IFC 020 E
Dimensions (in mm)
Weight approx. 1.4 kg
Subassembly support 3 HE, assembly dimensions in compliance with DIN 41491, Part 5
Guiding rails
F-shaped multipole
connector, DIN 41612
X1 X2
Front plate thread bore hole (M 2.5)
1 TE = 05.08 mm 1 HE = 44.17 mm
Multipole connector attachment holes
Attachment plane Multipole connectors
Attachment plane
Front plates
19” Subassembly support purchase order numbers
– Subassembly support
including guiding rails, pre-installed 2.07230
– Subassembly support fully installed including IFC 020 E, 1.01643.01.00 (230 V)
multipole connectors plus solder points
1.01643.02.00 (115 V)
– Blind plates 2 TE 3.06660.00
3 TE 3.06738.00 5 TE 3.06739.00
8 TE 3.06740.00 14 TE 3.06741.00 21 TE 3.07590.00
– Special design of
multipole connectors X1 and X2: Threaded terminal end 5.08400 Wire-Wrap (1 x 1) mm 5.08402 Termi-Point (0.8 x 1.6) mm 5.08403
Page 74
Installation and operating instructions IFC 020
10.5 Instrument nameplates
Separate signal converter in rotatable field housing
10/7
Measuring range Current output Tag No.
Primary head constant Pulse output
ALTOFLUX IFM 4080K /D/ /6 A94 9872 ISO Kl. E IP 67 DN50/2”-PFA- HC4 PN 40 Bar
Altometer
Q: 0-21.2 m
3
/h GK: 5.123
I: 0-20 mA R
i
0.5 kOhm P: 1000 p/s
Tag:
Holland
Insulation class
of field coils
Protection category
to IEC 529 / EN 60529
Flange pressure rating or flange class
Electrode material
(see table)
Liner
(see table)
Meter size
DN in mm and inch equivalent
Type designation
Serial No.
Magnetic field frequency
(here: 1/6 of power frequency)
Abbreviations
Liner
AL Fused aluminium
oxide (99.7% Al2O3) H Hard rubber NE Neoprene PFA Teflon®-PFA PP Polypropylene PUI Irethane T Teflon®-PTFE W Soft rubber
Electrode material
C conductive rubber compound HB 2 Hastelloy B2 HC 4 Hastelloy C4 IN Incoloy M4 Monel 400 Ni Nickel PT Platinum TA Tantalum TI Titanium V4A Stainless steel 1.4571 (SS 316 Ti) xx /TC xx with conductive PTFE compound
(xx = base material, e.g. HC4)
Teflon®is a registered trademark of Du Pont
Compact flowmeters
ALTOFLUX IFC 090F /D/ /6 A96 6008
Altometer
Q: 0-150 m
3
/h GK: 2.706
I: 0-20 mA R
i
0.5 kOhm P: 1000 p/s
Tag: 98-FT-096
Holland
Measuring range Current output Tag No.
Primary head constant Pulse output
Type designation
Serial No.
Magnetic field frequency
(here: 1/6 of power supply frequency)
Page 75
Installation and operating instructions IFC 020
11/1
Measuring principle
11
The flowmeter is designed for electrically conductive fluids.
Measurement is based on Faraday’s law of induction, according to which a voltage is induced in an electrically conductive body which passes through a magnetic field. The following expression is applicable to the voltage.:
U = K xB xv xD
where: U = induced voltage K = an instrument constant B = magnetic field strength v = mean velocity D = pipe diameter
Thus the induced voltage is proportional to the mean flow velocity, when the field strength is constant.
Inside the electromagnetic flowmeter, the fluid passes through a magnetic field applied perpendicular to the direction of flow. An electric voltage is induced by the movement of the fluid (which must have a minimum electrical conductivity). This is proportional to the mean flow velocity and thus to the volume of flow. The induced voltage signal is picked up by two electrodes which are in conductive contact with the fluid and is transmitted to a signal converter for a standardized output signal.
This method of measurement offers the following advantages:
1. No pressure loss through pipe constriction or protruding parts.
2. Since the magnetic field passes through the entire flow area, the signal represents a mean value over the pipe cross-section; therefore, only relatively short straight inlet pipes 5
x
DN from the electrode axis are required upstream of the primary head.
3. Only the pipe liner and the electrodes are in contact with the fluid.
4. Already the original signal produced is an electrical voltage which is an exact linear function of the mean flow velocity.
5. Measurement is independent of the flow profile and other properties of the fluid.
The magnetic field of the primary head is generated by a square wave current fed from signal converter to the field coils.
This field current alternates between positive and negative values. Alternate positive and negative flowrate-proportional signal voltages are generated at the same frequency by the effect of the magnetic field, which is proportional to the current. The positive and negative voltages at the primary head electrodes are subtracted from one another in the signal converter. Subtraction always takes place when the field current has reached its stationary value, so that constant interference voltages or external or fault voltages changing slowly in relation to the measuring cycle are suppressed. Power line interference voltages coupled in the primary head or in the connecting cables are similarly suppressed.
U
U
D
v
B
Page 76
Installation and operating instructions IFC 020
12/1
12
Block diagram – signal converter
1 Input amplifier
n
overdrive-proof signal processing, rapid and accurate
n
digital signal processing and sequence control
n
patented, high-resolution A/D converter, digitally controlled and monitored
n
high signal-to-noise ratio through low­loss field power supply
2 Field power supply
n
the low-loss field power supply generates the pulsed, electronically controlled DC current for the magnetic coils of the primary head
n
the low-loss regulator reduces the power take-off
n
high field current causes a high signal level.
3 Current output
n
galvanically isolated from all other groups
n
converts the digital output signal from the
µP 3 microprocessor into a proportional
current
n
HART
®
and RS 485-interfaces,
switchable
4 Binary outputs
n
galvanically isolated from other groups
n
selectable input/output combinations
n
pulse output, passive FET optocouplers allow connection of electronic and electromechanical totalizers
n
status output, for limit value, error identification, or flow direction in forward/reverse flow mode (F/R)
5 Display/operator control unit
n
large-size illuminated LC display
n
3 keys for operator control of the signal converter
n
connection to the internal IMoCom bus
6 IMoCom bus plug connector
n
for connection of external control and test devices
7 External control input (IFC 020 E only)
n
reset of internal totalizer
n
zero setting of all outputs
The standard
n
high accuracy
n
practice oriented standard equipment
n
current and pule output (galvanically isolated)
n
status output, adjustable for many tasks: indicators for trip point, flow direction and errors.
n
IMoCom-Bus suitable for many in- and external tasks
n
simple, uniform KROHNE control outline
n
very lowpower consumption
n
HART
®
and RS 485-interfaces
Page 77
Installation and operating instructions IFC 020
E1
Keyword Section No. Fct. No.
F
F = forward flow 4.4, 5.3, 5.14 1.04-1.07 F1, F2 = fuses 8.1, 8.5 Factory settings 3.2 Fatal error 4.5 FE = functional ground 1.2, 1.3.3, 1.3.5 Field power supply 5.12, 10.4, 12 3.02 Flow
– pulsating 6.4 3.06
– rapid changes 6.5 Flow direction 4.4, 5.1, 5.14 3.02 Flowrate, rapid changes 6.5 Flow rate (Q) 4.4, 5.1 3.02 Flow velocity v 4.4, 5.1 3.02 Frequency (pulse output)
– F
max
5.7 1.06, 3.07
– F
min
5.7 1.06, 3.07
Frequency output,
see pulse output P 2.3, 5.7 1.06, 3.07 Full-scale range Q
100%
4.4, 5.1, 5.14 1.01, 3.02 Function(s) 4.4 Function of keys 4.1-4.3 Functional checks 7.1 et seq.
– primary head 7.5 – setpoint display values 7.6 – system 7.4 – test full scale range 7.2 2.01
– zero 7.1 3.03 Functional ground FE 1.2, 1.3.3, 1.3.5 Functions column 4.1-4.3 Fuses (F . . . ) 8.1, 8.5
G
GK = primary (head) constant 4.4, 5.11 3.02 Grounding primary head 1.3.3 GS 8A = primary (head) simulator 7.6
H
Hand held bar magnet 4.2 Hand held terminal 6.2 Hardware information 7.3 2.02 HART 6.7 Hazardous duty areas (Ex) 6.1, page 0/4
I
I = current (analog) output 2.3, 5.6 1.05 IEC technical standards page 0/4 IMoCom bus (plug) 6.2, 8.9, 12 Initial start-up 3 Input (programming) 4.1 et seq. Instrument nameplates 10.5 Interface RS 232 6.2, 10.4 Intermediate connection box (ZD) 1.3.5, 10.2 Internal electronic totalizer 2.4, 5.5, 5.7 1.04
K
Keys 4.1-4.3 Keystroke combinations for
– entry into setting level 4.1-4.3 3.04
– error cancellation 4.6
– quitting setting level 4.1-4.3
– totalizer reset 4.6
L
Language of display texts 5.10 3.01 LCD display, see display 4.2, 4.4, 5.4 1.04 Limit message 4.4, 5.8 1.07 Line voltage, see power supply Low-flow cutoff (SMU) 4.4, 5.3 1.03
Keyword Section No. Fct. No.
A
Abbreviations 1.3.2, 1.3.4,
2.1, 4.4 Accuracies 10.3 ADC = analog-digital converter 4.5, 12 Ambient temperature 10.4 Application 5.19 3.06 Automatic range change (BA) 4.4, 5.18 1.06, 1.07
B
B1/B2 output/input terminals 2.1, 2.6, 5.16
3.07 (1.06, 1.07) BA = automatic range change 4.4, 5.18 1.06, 1.07 Block diagram IFC 020 12 B version (basic) 4, 6.2, 8.4,10.4
C
C = control input 2.5, 2.6, 5.9 1.06, 1.07, 3.07 Cable length 1.3.4 Changeover, power supply 8.1 Characteristics of outputs 5.15 Clearing error messages 4.6 Coding for entry into
setting level 5.11 3.04 CONFIG software 6.2 Connecting & operating points
– front panel power supply 4.2
– PCB amplifier 8.9
– PCB power supply 8.9 Connection diagrams
– GS8A simulator 7.6
– Outputs/inputs 2.6
– Power supply 1.2, 1.3.5 Control input C
– connection 2.6 1.06, 1.07, 3.07
– description 2.5, 2.6, 5.9 1.06, 1.07, 3.07 Conversion factor
– Quantity (volume) 4.4 + 5.12 3.05
– Time 4.4 + 5.12 3.05 Current output I 2.2, 5.6 1.05 Cut-off “off” value (SMU OFF) 5.3 1.03 Cut-off “on” value (SMU ON) 5.3 1.03
D
Data 4.4 Data column 4.1-4-3 Data errors 4.5 Dimensions
– IFC 020 F 10.2
– ZD 10.2 Display 4.2, 5.4, 8.4 1.04 DN = meter size in mm 4.4 3.02 DS, signal cable A 1.3.1
E
EC = electronic totalizer 2.3, 2.6, 5.8 1.06 Electrical connection
– GS8A simulator 7.6
– outputs and inputs 2.6
– power supply 1.1, 1.3.5 Electromagnetic compatibility page 0/4 EMC = electromechanical totalizer 2.3, 2.6, 5.8 1.06 EN technical standards page 0/4 Error 4.5 Error list 4.5 Error (messages) 4.5
– cancel 4.5
– limits 10.3
– reset / delete 4.6 External range change 4.4, 5.18 1.06, 1.07 External totalizers 2.3, 2.6, 5.7 1.06
Index Part E
Page 78
Installation and operating instructions IFC 020
E2
Keyword Section No. Fct. No.
S
S = Status output 2.4, 4.4, 5.8 1.06, 1.07, 3.07 Safety isolation 2.1 Setting level 4.1- 4.4 1.00 et seq.,
2.00 et seq.,
3.00 et seq.
Signal converter IFC 020
– accuracies 10.3 – cable A 1.3.1 – changeover, power supply 8.2 – connecting & operating points 4.2, 8.9 – connection to power 1.2 – functional checks 7.1-7.6, – fuses, power 8.5 – mounting location 1.1 – nameplates 10.5 – operator control 4.1-4.3 – power consumption 10.4 – printed circuit boards 8.9 – spare parts 9
– technical data 10.1-10.4 Simulator GS 8A 7.6 SMU = low-flow cutoff 4.4, 5.3 1.03 Software 6.2 Spare parts, see order numbers 9 Status output S 2.4, 4.4, 5.8 1.06, 1.07, 3.07
T
T = time constant 5.2 1.02 Technical data
– accuracies 10.3
– dimensions & weights 10.2
– signal converter IFC 020 10.1-10.4 Terminals B1/B2 2.1, 2.6, 5.16
3.07 (1.06, 1.07) Tests, see functional checks 7.1 et seq. Time constant (T) 5.2 1.02 Totalizer (internal electronic) 2.3, 5.7 1.06, 3.07 Trip point 2.4, 2.6, 5.8 1.06, 1.07 Troubleshooting, see
functional checks 7.1 et seq.
U
Units for
– display 4.4, 5.4 1.04 – flow 4.4, 5.1 1.01 – P 4.4, 5.7 1.06
User-defined unit 4.4, 5.13 3.05
V
v = flow velocity 4.4, 5.1 3.02 VDE standards page 0/4
W
Weights, see dimensions 10.2
Z
Zero check (adjustment) 7.1 3.03 ZD, intermediate connection box 1.3.5, 10.2
Keyword Section No. Fct. No.
M
Magnetic field frequency 4.4 + 5.11 3.02 Magnetic sensors 4.2 Main menu column 4.1 Main menus 4.1 to 4.3 1.00, 2.00, 3.00 Mass flow measurement,
see user defined unit 4.4, 5.13 Measuring principle 11 Menu 4.1, 4.4 Meter size (DN) 4.4, 5.12 3.02
N
Numerical format, display 5.4, 5.5 1.04
O
Option = optional equipment 6.2, 10.4 Order numbers 9 Outputs
– characteristics 5.15
– connection diagrams 2.6
– setting 4.4
– – I 5.6 1.05
– – P 5.7, 5.16 1.06, 3.07
– – S 5.8, 5.16 1.06, 1.07, 3.07
– voltage stable when
measuring tube empty 6.3 Overflow, display 5.5 1.04 Overranged
– I (current output) 2.2, 2.6, 5.6, 5.8 1.06, 1.07 – P (pulse output) 2.3, 2.6, 5.7, 5.8 1.06, 1.07
Overvoltage class 2.1
P
P = pulse output 2.4, 4.4, 5.7 1.06 PCB = printed circuit boards 8.9 PC software 6.2 PE = protective conductor 1.2 Power supply (= line voltage)
– changeover 8.2 – connection 2.1, 10.4 – consumption 10.4 – failure 4.5, 7.4 – frequency 1.2, 10.4
– voltage 1.2, 10.4 Primary constant, see GK 4.4, 5.12 3.02 Primary head
– constant, see GK 4.4, 5.12 3.02
– simulator GS 8A 7.6
– testing 7.5 Primary simulator, see GS 8A 7.6 Printed circuit boards, see PCB 8.9 Program organization 4.1 Programming = input 4.1-4.3 Programming mode, entry into 4.1-4-3 Protective conductor PE 1.2 Pulsating flow 6.4, 6.5, 6.6 3.06 Pulse output P 2.3, 4.4, 5.7 1.06 Pulse width 4.4, 5.7 1.06 Pulses per unit time 4.4, 5.7 1.06 Pulses per unit volume 4.4, 5.7 1.06
Q
Q = flow rate 4.4, 5.1 1.01, 3.02 Q
100%
= full-scale range 4.4, 5.1 1.01, 3.02
R
R = reverse flow 4.4, 5.14 1.04-1.07 Range change
– automatic 2.5, 2.6, 1.06, 1.07
5.8, 5.18
– external 2.5, 2.6, 1.06, 1.07
5.9, 5.18 Range setting 4.4, 5.1, 5.12 1.01, 3.02 Replacement
– electronic unit 8.7
– power fuses 8.1 Reset totalizers 4.6 Reverse flow (R) 4.4, 5.14 1.04-1.07 Revert to
– functions column 4.1-4.3
– main menu column 4.1-4.3
– measuring mode 4.1-4.3
– submenu column 4.1-4.3 RS 232 interface 6.2
Page 79
Installation and operating instructions IFC 020
E3
If you need to return flowmeters for testing
or repair to Krohne
SPECIMEN certificate
Your electromagnetic flowmeter
• has been carefully manufactured and tested by a company with ISO 9001 certification
• and volumetrically calibrated in one of the world’s most accurate test rigs.
If installed and operated in accordance with these operating instructions, your flowmeter will rarely present any problems.
Should you nevertheless need to return a flowmeter for checkout or repair, please pay strict attention to the following points
:
Due to statutory regulations concerning protection of the envi­ronment and the health and safety of our personnel, Krohne may only handle, test and repair returned flowmeters that have been in contact with liquids if it is possible to do so with­out risk to personnel and environment. This means that Krohne can only service your flowmeter if it is accompanied
by a certificate in line with the following model confirming that the flowmeter is safe to handle.
If the flowmeter has been operated with toxic, caustic, flammable or water-endangering liquids, you are kindly requested
• to check and ensure, if necessary by rinsing or neutraliz­ing, that all cavities in the flowmeter are free from such dangerous substances. (Directions on how you can find out whether the primary head has to be opened and then flushed out or neutralized are obtainable from Krohne on request.)
• to enclose a certificate with the flowmeter confirming that the flowmeter is safe to handle and stating the liquid used.
Krohne regret that they cannot service your flowmeter unless accompanied by such a certificate.
Company: Address:
Department: Name:
Tel. No.:
The enclosed electromagnetic flowmeter
Type: Krohne Order No. or Series No.:
has been operated with the following liquid:
Because this liquid is
water-endangering * / toxic * / caustic * / flammable *
we have
– checked that all cavities in the flowmeter are free from such substances *
– flushed out and neutralized all cavities in the flowmeter *
(* delete if not applicable)
We confirm that there is no risk to man or environment through any residual liquid contained in this flowmeter.
Date: Signature:
Company stamp:
Loading...