KROHNE IFC-020 User Manual

KROHNE 12/2002 US: 7.10003.71.00
GR
DIN A4: 7.10003.31.00
Condensed Instructions
IFC 020 K IFC 020 F IFC 020 E
Signal converters for electromagnetic flowmeters
Applicable to Software Versions
IFC 020 K and
IFC 020 F No. 3170330200
Contents
1 Electrical connection: Power 1/1-1/8 2 Electrical connection: Outputs 2/1-2/4 3 Start-up 3/1 4 Operator control of signal converter 4/1-4/4
PLEASE NOTE
These concise instructions do not include the following: device description, technical data, standards, approvals, etc., nor conditions pertaining to product liability and warranty.
The operator is, however, obligated to take note of these sections in the detailed Installation and Operating Instructions.
IFC 020 E
No. 3175870200
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications technology
Engineering systems & solutions
Switches, counters, displays and recorders
Heat metering
Pressure and temperature
Condensed instructions IFC 020
1/1
Part A System installation and start-up
1 Electrical connection: power supply
1.1 Important installation notes PLEASE NOTE !
1.1.1 Location
Electrical connection in accordance with VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V” or equivalent national regulations.
Do not cross or loop cables inside the terminal compartment.
Use separate cable entries (see below) for power supply, field current cables, signal lines,
outputs and inputs.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunlight. Fit a sunshade if necessary.
When installed in switchgear cabinets, signal converters must be adequately cooled, e.g. use fans or heat exchangers.
Do not expose signal converters to intense vibration.
1.1.2 Onl
y for separate systems/signal converters (F- and E versions)
Keep distance between primary head and signal converter as short as possible.
Refer to Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied Krohne signal cable A (Type DS), standard length 10 m (33 ft).
Always calibrate primary head and signal converter together. Therefore, when installing,
ensure primary constant GKL is identical; refer to instrument nameplate for the primary head. If the GKL is not identical, set the signal converter to the GKL of the primary head. Refer also to Sections 4.
Dimensions of signal converter; refer to Section 10.4.
1.1.3 Cable entries (K- and F- versions)
Number of cable entries: 2 for the compact flowmeters
4 for the seperate IFC 020 F signal converter
NOTE: Ensure gaskets are fitted correctly and maintain
the following max. torques!
1 Max. torques for PG 13.5,
1/2“ NPT or 1/2“ PF adapters: 4 Nm / 2.8 ft
x
lbf
2 Max. torques for PG 13.5 only: 3 Nm / 2.1 ft
x
lbf
3 Gasket
A) PG 13.5 cable entries
These cable entries may only be used for flexible electrical cables if the relevant electrical regulations so allow, e.g. National Electric Code (NEC). Do not fix rigid metal conduits (IMC) or flexible plastic conduits to the PG 13.5 cable entries, refer to “Point B, C” below (1/2” NPT or PF adapters).
B) 1/2“ NPT adapters C) 1/2“ PF adapters
For most North American systems the regulations require that electrical conductors be laid in conduits, particularly where power voltages > 100 V AC are concerned. In such cases, use the 1/2” NPT or 1/2” PF adapters to which flexible plastic conduits can be screwed. Do not use rigid metal conduits (IMC)! Lay conduits such that no moisture can penetrate into the converter housing. Should there be risk of any condensation water forming, fill the cross-section of the conduit around the cables at these adapters with a suitable sealing compound.
3
1
2
Condensed instructions IFC 020
1/2
Connection to power 1.2
PLEASE NOTE !
Rated values:
The flowmeter housings protecting the electronic equipment from dust and moisture must always be kept closed. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage class II.
Safet
y isolation: the flowmeters (signal converters) must be provided with an
isolating facility.
1. AC V
ersion
2. AC Version
230/240 V AC (200 - 260 V AC) 200 V AC (170 - 220 V AC)
switch-selectable to switch-selectable to
115/120 V AC (100 - 130 V AC) 100 V AC (85 - 110 V AC)
Note information on instrument nameplate: supply voltage and frequency
The PE protective ground conductor for the power supply must be connected to the
separate U-clamp terminal in the terminal compartment of the signal converter. For exceptions (compact systems), refer to installation instructions for the primary head.
Connection diagrams for electrical connection between primary head and signal converter: refer to Section 1.3.5 and 1.3.6.
DC V
ersion (in preparation for IFC 020 E)
24 V DC (18 - 32 V DC)
Note information on instrument nameplate: supply voltage and frequency.
For measurement reasons, connect an FE functional ground conductor to the separate
U-clamp terminal in the terminal compartment of the signal converter.
If connected to a functional extra-low voltage source (24 V AC / DC, 48 V AC), provide for protective separation (PELV) in conformity with VDE 0100 / VDE 0106 or IEC 364 / IEC 536, or equivalent national regulations.
Connection diagrams for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.6.
Connection to power (K- and F- versions only)
Power fuse F1
(see Sect. 8.2)
AC: 100 – 240 V DC: 24 V
Power supply
U-clamp terminal
PE protective conductor FE functional ground conductor
L N
1L = 0L =
for
internal
use only
For electrical connection of the IFC 020 E power supply see Section 1.3.6, connection diagrams III to VI.
Condensed instructions IFC 020
1/3
Field current line C (single shielding with IFC 020 F)
Line 2 x 0.75 mm2(18 AWG) Cu, 2 x 1.5 mm2(14 AWG) Cu or 2 x 2.5mm2(12 AWG) Cu single shielding (Cu = copper cross section) The cross section depends on the required cable length, see table in Section 1.3.4.
1.3
Electrical connection of separate primary heads (F- and E- versions)
1.3.1
General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when Krohne signal lines A and B are used with foil screen and magnetic shield.
• Signal lines must be firmly installed.
• Shields are connected via stranded drain wires.
• Underwater or underground routing is possible.
• Insulating material flame-retardant to IEC 332.1 / VDE 0742.
• Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Si
gnal line A (type DS) with double shielding
1.3.2 Grounding of primary head
• All flowmeters must be properly grounded.
• The grounding conductor should not transmit any interference voltages.
• Do not ground any other electrical device together with this conductor.
• The primary head is connected to ground by means of an FE functional ground conductor.
• Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
• These instructions also contain detailed descriptions on how to use grounding rings and how to install primary heads in metal or plastic pipes or internally coated pipelines.
1 Stranded drain wire, 1st shield, 1.5 mm2 or AWG 14 2 Insulation 3 Stranded wire 0.5 mm
2
or AWG 20 (3.1 red/3.2 white) 4 Special foil, 1st shield 5 Insulation 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG 20
8 Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line), for IFC 020 E only
1 Dummy glider wire 2 Insulation (2.1 red/2.2 white) 3 Special foil, 1st shield (3.1/3.2) 4 Insulation (4.1/4.2) 5 Stranded wire 0.5 mm
2
or AWG 20 (5.1 red/5.2 white)
6 Stranded drain wire, 1st shield, 0.5 mm
2
or AWG 20
(6.1/6.2) 7 Special foil, 2nd shield 8 Stranded drain wire, 2nd shield, 1.5 mm
2
or AWG 14
9 Insulation
10 Mu-metal foil, 3rd shield
11 Stranded drain wire, 3rd shield, 0.5 mm
2
or AWG 20
12 Outer sheath
Condensed instructions IFC 020
1/4
Stripping (preparation) of signal cable A and B 1.3.3
Please note the different lengths given in the table for signal converter and primary head.
Customer-supplied materials W
Insulation tubing (PVC), Ø 2.0 - 2.5 mm (dia. 1”)
X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
For cable fixation in signal converter housing IFC 020 F
see illustration in section 10.4
External shielding of signal cable A (Type DS) Wrap stranded drain wire (7) around the mu-metal foil (6) and clamp under the shield terminal in the signal converter terminal box (see also diagram in Sect. 1.3.5).
Signal cable A (type DS) double shielding, for primary head and IFC 020 E
Signal cable A (type DS) double shielding, for IFC 020 F
Signal cable A
bending radius
50 mm (2“)
Signal cable A bending radius 50 mm (2“)
Signal line B (type BTS) with triple shielding (bootstrap), for IFC 020 E
Signal line B
bending radius 50 mm (2”)
Length
Converter Primary
mm IFC 020 F + E only IFC 020 E
head
(inch) Signalcable A Signalcable B a 55 (2.17) 70 (2.76) 90 (3.54) b 10 (0.39) 50 (1.97) 98 (0.31)
c 15 (0.59) 25 (0.98) 25 (0.98) d 58 (0.31) 78 (0.31) 98 (0.31) e 50 (1.97) 70 (2.76) f 78 (0.31) 98 (0.31)
Condensed instructions IFC 020
1/5
Length
Cross section AF (Cu), minimum
0 - 150 m 5 - 500 ft 2 × 0.75 mm2Cu / 2 × 18 AWG 150 - 300 m 500 - 1000 ft 2 × 1.50 mm2Cu / 2 × 14 AWG 300 - 600 m 1000 - 1900 ft 2 × 2.50 mm2Cu / 2 × 12 AWG
Abbreviations and ex
planatory notes
used in the following tables, diagrams and connection diagrams
A Signal cable A (type DS), with double shielding, see diagram A for max. length B Signal line B (type BTS) with triple shielding, max. length see diagram B (IFC 020 E only)
C Field current cable min. cross-section (AF) and max. length,
(with single shielding for IFC 020 F), see Table
D High-temperature silicone cable, 3 × 1.5 mm
2
(14 AWG) Cu, (with single shielding,
max. length 5 m (16 ft)
E High-temperature silicone cable, 2 × 1.5 mm
2
(14 AWG) Cu, max. length 5 m (16 ft)
AFCross section of field current line C in Cu, see table L Cable length
κκ
Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
Recommended length of signal cable A (Type DS) and B (Type BTS) (Signal cable B, Type BTS, for IFC 020 E only)
1.3.4 Cable lengths (max. distance between signal converter and primary head)
Field current cable C: (for IFC 020 F single shielding!)
Primary head Meter size Signal cable
DN mm inch AB
AQUAFLUX F 010 - 10003/
8 -40 A1 B1
ECOFLUX IFS 1000 F 010 - 153/8 -1/2 A4 B3
025 - 150 1 - 6 A3 B2
ALTOFLUX IFS 2000 F 150 - 250 6 - 10 A1 B1 ALTOFLUX IFS 4000 F 010 - 1503/8 - 6 A2 B2
200 - 1000 8 - 40 A1 B1 PROFIFLUX IFS 5000 F 002.5 - 151/10 -1/2 A4 B3
025 - 100 1 - 4 A2 B2
VARIFLUX IFS 6000 F 002.5 - 151/10 -1/2 A4 B3
025 - 80 1 - 3 A2 B2
ALTOFLUX M 900 010 - 3003/8 -12 A1 B1
Diagram A Diagram B (for IFC 020 E only)
Loading...
+ 13 hidden pages