KROHNE IFC-020 User Manual

Page 1
KROHNE 12/2002 US: 7.10003.71.00
GR
DIN A4: 7.10003.31.00
Condensed Instructions
IFC 020 K IFC 020 F IFC 020 E
Signal converters for electromagnetic flowmeters
Applicable to Software Versions
IFC 020 K and
IFC 020 F No. 3170330200
Contents
1 Electrical connection: Power 1/1-1/8 2 Electrical connection: Outputs 2/1-2/4 3 Start-up 3/1 4 Operator control of signal converter 4/1-4/4
PLEASE NOTE
These concise instructions do not include the following: device description, technical data, standards, approvals, etc., nor conditions pertaining to product liability and warranty.
The operator is, however, obligated to take note of these sections in the detailed Installation and Operating Instructions.
IFC 020 E
No. 3175870200
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications technology
Engineering systems & solutions
Switches, counters, displays and recorders
Heat metering
Pressure and temperature
Page 2
Condensed instructions IFC 020
1/1
Part A System installation and start-up
1 Electrical connection: power supply
1.1 Important installation notes PLEASE NOTE !
1.1.1 Location
Electrical connection in accordance with VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V” or equivalent national regulations.
Do not cross or loop cables inside the terminal compartment.
Use separate cable entries (see below) for power supply, field current cables, signal lines,
outputs and inputs.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunlight. Fit a sunshade if necessary.
When installed in switchgear cabinets, signal converters must be adequately cooled, e.g. use fans or heat exchangers.
Do not expose signal converters to intense vibration.
1.1.2 Onl
y for separate systems/signal converters (F- and E versions)
Keep distance between primary head and signal converter as short as possible.
Refer to Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied Krohne signal cable A (Type DS), standard length 10 m (33 ft).
Always calibrate primary head and signal converter together. Therefore, when installing,
ensure primary constant GKL is identical; refer to instrument nameplate for the primary head. If the GKL is not identical, set the signal converter to the GKL of the primary head. Refer also to Sections 4.
Dimensions of signal converter; refer to Section 10.4.
1.1.3 Cable entries (K- and F- versions)
Number of cable entries: 2 for the compact flowmeters
4 for the seperate IFC 020 F signal converter
NOTE: Ensure gaskets are fitted correctly and maintain
the following max. torques!
1 Max. torques for PG 13.5,
1/2“ NPT or 1/2“ PF adapters: 4 Nm / 2.8 ft
x
lbf
2 Max. torques for PG 13.5 only: 3 Nm / 2.1 ft
x
lbf
3 Gasket
A) PG 13.5 cable entries
These cable entries may only be used for flexible electrical cables if the relevant electrical regulations so allow, e.g. National Electric Code (NEC). Do not fix rigid metal conduits (IMC) or flexible plastic conduits to the PG 13.5 cable entries, refer to “Point B, C” below (1/2” NPT or PF adapters).
B) 1/2“ NPT adapters C) 1/2“ PF adapters
For most North American systems the regulations require that electrical conductors be laid in conduits, particularly where power voltages > 100 V AC are concerned. In such cases, use the 1/2” NPT or 1/2” PF adapters to which flexible plastic conduits can be screwed. Do not use rigid metal conduits (IMC)! Lay conduits such that no moisture can penetrate into the converter housing. Should there be risk of any condensation water forming, fill the cross-section of the conduit around the cables at these adapters with a suitable sealing compound.
3
1
2
Page 3
Condensed instructions IFC 020
1/2
Connection to power 1.2
PLEASE NOTE !
Rated values:
The flowmeter housings protecting the electronic equipment from dust and moisture must always be kept closed. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage class II.
Safet
y isolation: the flowmeters (signal converters) must be provided with an
isolating facility.
1. AC V
ersion
2. AC Version
230/240 V AC (200 - 260 V AC) 200 V AC (170 - 220 V AC)
switch-selectable to switch-selectable to
115/120 V AC (100 - 130 V AC) 100 V AC (85 - 110 V AC)
Note information on instrument nameplate: supply voltage and frequency
The PE protective ground conductor for the power supply must be connected to the
separate U-clamp terminal in the terminal compartment of the signal converter. For exceptions (compact systems), refer to installation instructions for the primary head.
Connection diagrams for electrical connection between primary head and signal converter: refer to Section 1.3.5 and 1.3.6.
DC V
ersion (in preparation for IFC 020 E)
24 V DC (18 - 32 V DC)
Note information on instrument nameplate: supply voltage and frequency.
For measurement reasons, connect an FE functional ground conductor to the separate
U-clamp terminal in the terminal compartment of the signal converter.
If connected to a functional extra-low voltage source (24 V AC / DC, 48 V AC), provide for protective separation (PELV) in conformity with VDE 0100 / VDE 0106 or IEC 364 / IEC 536, or equivalent national regulations.
Connection diagrams for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.6.
Connection to power (K- and F- versions only)
Power fuse F1
(see Sect. 8.2)
AC: 100 – 240 V DC: 24 V
Power supply
U-clamp terminal
PE protective conductor FE functional ground conductor
L N
1L = 0L =
for
internal
use only
For electrical connection of the IFC 020 E power supply see Section 1.3.6, connection diagrams III to VI.
Page 4
Condensed instructions IFC 020
1/3
Field current line C (single shielding with IFC 020 F)
Line 2 x 0.75 mm2(18 AWG) Cu, 2 x 1.5 mm2(14 AWG) Cu or 2 x 2.5mm2(12 AWG) Cu single shielding (Cu = copper cross section) The cross section depends on the required cable length, see table in Section 1.3.4.
1.3
Electrical connection of separate primary heads (F- and E- versions)
1.3.1
General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when Krohne signal lines A and B are used with foil screen and magnetic shield.
• Signal lines must be firmly installed.
• Shields are connected via stranded drain wires.
• Underwater or underground routing is possible.
• Insulating material flame-retardant to IEC 332.1 / VDE 0742.
• Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Si
gnal line A (type DS) with double shielding
1.3.2 Grounding of primary head
• All flowmeters must be properly grounded.
• The grounding conductor should not transmit any interference voltages.
• Do not ground any other electrical device together with this conductor.
• The primary head is connected to ground by means of an FE functional ground conductor.
• Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
• These instructions also contain detailed descriptions on how to use grounding rings and how to install primary heads in metal or plastic pipes or internally coated pipelines.
1 Stranded drain wire, 1st shield, 1.5 mm2 or AWG 14 2 Insulation 3 Stranded wire 0.5 mm
2
or AWG 20 (3.1 red/3.2 white) 4 Special foil, 1st shield 5 Insulation 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG 20
8 Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line), for IFC 020 E only
1 Dummy glider wire 2 Insulation (2.1 red/2.2 white) 3 Special foil, 1st shield (3.1/3.2) 4 Insulation (4.1/4.2) 5 Stranded wire 0.5 mm
2
or AWG 20 (5.1 red/5.2 white)
6 Stranded drain wire, 1st shield, 0.5 mm
2
or AWG 20
(6.1/6.2) 7 Special foil, 2nd shield 8 Stranded drain wire, 2nd shield, 1.5 mm
2
or AWG 14
9 Insulation
10 Mu-metal foil, 3rd shield
11 Stranded drain wire, 3rd shield, 0.5 mm
2
or AWG 20
12 Outer sheath
Page 5
Condensed instructions IFC 020
1/4
Stripping (preparation) of signal cable A and B 1.3.3
Please note the different lengths given in the table for signal converter and primary head.
Customer-supplied materials W
Insulation tubing (PVC), Ø 2.0 - 2.5 mm (dia. 1”)
X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
For cable fixation in signal converter housing IFC 020 F
see illustration in section 10.4
External shielding of signal cable A (Type DS) Wrap stranded drain wire (7) around the mu-metal foil (6) and clamp under the shield terminal in the signal converter terminal box (see also diagram in Sect. 1.3.5).
Signal cable A (type DS) double shielding, for primary head and IFC 020 E
Signal cable A (type DS) double shielding, for IFC 020 F
Signal cable A
bending radius
50 mm (2“)
Signal cable A bending radius 50 mm (2“)
Signal line B (type BTS) with triple shielding (bootstrap), for IFC 020 E
Signal line B
bending radius 50 mm (2”)
Length
Converter Primary
mm IFC 020 F + E only IFC 020 E
head
(inch) Signalcable A Signalcable B a 55 (2.17) 70 (2.76) 90 (3.54) b 10 (0.39) 50 (1.97) 98 (0.31)
c 15 (0.59) 25 (0.98) 25 (0.98) d 58 (0.31) 78 (0.31) 98 (0.31) e 50 (1.97) 70 (2.76) f 78 (0.31) 98 (0.31)
Page 6
Condensed instructions IFC 020
1/5
Length
Cross section AF (Cu), minimum
0 - 150 m 5 - 500 ft 2 × 0.75 mm2Cu / 2 × 18 AWG 150 - 300 m 500 - 1000 ft 2 × 1.50 mm2Cu / 2 × 14 AWG 300 - 600 m 1000 - 1900 ft 2 × 2.50 mm2Cu / 2 × 12 AWG
Abbreviations and ex
planatory notes
used in the following tables, diagrams and connection diagrams
A Signal cable A (type DS), with double shielding, see diagram A for max. length B Signal line B (type BTS) with triple shielding, max. length see diagram B (IFC 020 E only)
C Field current cable min. cross-section (AF) and max. length,
(with single shielding for IFC 020 F), see Table
D High-temperature silicone cable, 3 × 1.5 mm
2
(14 AWG) Cu, (with single shielding,
max. length 5 m (16 ft)
E High-temperature silicone cable, 2 × 1.5 mm
2
(14 AWG) Cu, max. length 5 m (16 ft)
AFCross section of field current line C in Cu, see table L Cable length
κκ
Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
Recommended length of signal cable A (Type DS) and B (Type BTS) (Signal cable B, Type BTS, for IFC 020 E only)
1.3.4 Cable lengths (max. distance between signal converter and primary head)
Field current cable C: (for IFC 020 F single shielding!)
Primary head Meter size Signal cable
DN mm inch AB
AQUAFLUX F 010 - 10003/
8 -40 A1 B1
ECOFLUX IFS 1000 F 010 - 153/8 -1/2 A4 B3
025 - 150 1 - 6 A3 B2
ALTOFLUX IFS 2000 F 150 - 250 6 - 10 A1 B1 ALTOFLUX IFS 4000 F 010 - 1503/8 - 6 A2 B2
200 - 1000 8 - 40 A1 B1 PROFIFLUX IFS 5000 F 002.5 - 151/10 -1/2 A4 B3
025 - 100 1 - 4 A2 B2
VARIFLUX IFS 6000 F 002.5 - 151/10 -1/2 A4 B3
025 - 80 1 - 3 A2 B2
ALTOFLUX M 900 010 - 3003/8 -12 A1 B1
Diagram A Diagram B (for IFC 020 E only)
Page 7
Condensed instructions IFC 020
1/6
Im
portant information on connection diagrams PLEASE NOTE!
The figures in brackets indicate the stranded drain wires for the shields,
see cross-sectional drawing of signal cable in Section 1.3.1.
• Electrical connection to VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V“ or equivalent national regulations.
•PE= protective conductor FE = functional ground conductor
Connection diagrams I and II (IFC 020 F signal converter and primary head) 1.3.5
I II
Process temperature < 150°C (302 °F) Process temperature > 150°C (302 °F)
Primary heads
Primary heads
1 Signal cable A
(Type DS)
2 Shield terminal
for shielded signal cable
3 Field power cable
4 Shield terminal
for shielded field power cable
5 Housing wall,
signal converter
6 Cable entries
Connection of shields at the IFC 020 F
4
5
6
3
1
6
2
IFC 020 F IFC 020 F
Page 8
Condensed instructions IFC 020
1/7
III IV
Signal cable A (type DS) Signal cable B (type BTS)
IFC 020 E
IFC 020 E
Process temperature < 150°C (302°F)
Primary head Primary head
Important information on connection diagrams PLEASE NOTE!
The figures in brackets indicate the stranded drain wires for the shields
(see cross-sectional drawing of signal cable in Section 1.3.1).
• Electrical connection to VDE 0100 "Regulations governing heavy-current installations with line voltages up to 1000 V" or equivalent national regulations.
• 24 V DC power supply (in preparation): Functional extra-low voltage with protective separation in conformity with VDE 0100, Part 410 or equivalent national regulations.
For IFC 020 E, please note: The internal bridges marked with *
are needed for power supply > 100 V AC only.
•PE= Protective conductor FE = Functional ground conductor
1.3.6 Connection diagrams III to VI (IFC 020 E signal converter and primary head)
24 V DC FE
0L = 1L =
24 V DC FE
0L = 1L =
Page 9
Condensed instructions IFC 020
1/8
V
VI
Signal cable A (type DS) Signal cable B (type BTS)
IFC 020 E IFC 020 E
Process temperature > 150°C (302°F)
Primary head Primary head
24 V DC FE
0L = 1L =
24 V DC FE
0L = 1L =
Page 10
Condensed instructions IFC 020
2/1
• All operating data and functions can be set:
Operation
see section 4 and 5.
7 function 1.06 and 1.07
.
• The pulse and status outputs can be operated in the active or passive mode.
Active mode: The current output is the internal voltage source,
connection of electronic totalizers (EC)
Passive mode: External DC or AC voltage source required, connection of electronic (EC)
or electromechanical (EMC) totalizers
• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or
cycle counters are connected, allow for minimum counting interval:
gate time, counter
1000
P
100% [ Hz]
Connection diagrams see Sect. 2.4: diagrams - pulse output
 
diagrams - status output  
2.1 Current output I
The current output is galvanically isolated from all input and output circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
Typical current output
All operating data and functions can be set: Operation see section 4 and 5.6 fuction 1.05.
The current output can also be used as an internal voltage source for the outputs.
U
int
= 15 V DC I = 23 mA when operated without receiver instruments at the current output
I = 3 mA when operated with receiver instruments at the current output
Connection diagrams,
see Sect. 2.4: diagrams    
For
Connection and operation with HART®-interface see section 6.1.
I+ approx. 15 V DC positive
voltage of current output
I current sink
I
chassis ground, current output
2 Electrical connection of outputs and inputs
2.2 Pulse output P and status output S
The pulse and status outputs are galvanically isolated from the current output and all input circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
• Typical pulse and status outputs
S status output
P⊥chassis ground
P pulse output
Page 11
2/2
Condensed instructions IFC 020
Switch open Switch closed
OFF (switched off) without function ON (e.g. operation indicator) Power supply OFF Power supply ON F/R INDICATOR (F/R mode) Forward flow Reverse flow TRIP POINT (Limit switch) Inactive Active ALL ERRORS (all errors) Errors No errors FATAL ERRORS (fatal errors only) Errors No errors
• Characteristics of the status outputs
Control input E (with IFC 020 E only) 2.3
The control inputs are galvanically isolated from the current output and all input circuits.
Setting data and functions can note down in section 5.16..
Please also refer to Sect. 3.2 “Factory settings”.
Typical current input E
All operating data and functions can be set:
Operation see section 4 and 5.18 Fct. 1.08.
The control inputs must be operated in the passive mode.
• Function of the control inputs
OFF switched off TOTAL.RESET reset totalizer(s) ERROR.RESET delete error messages OUTP. HOLD hold value of outputs
Connection diagram, see Sect. 2.4: diagram
Z10
Z11
Page 12
Condensed instructions IFC 020
2/3
2.4 Input / output connection diagrams
Terminal identification
IFC 020 E separated, 19” plug-in unit, connection
IFC 020 F separated, field housing
IFC 020 K compact
For connection and operation of the HART® interface, see section 6.1. Burden (load) at HART® operation ranges between min. 250 and max. 500 .
E: X2
F
K
I Current output C Control input (IFC 020 E only) P Pulse output S Status output RS 485 Interface
1 2
I = 0/4 - 20 mA U
ext
15...20 V DC 20...32 V DC
Ri0...500 250...750
U
ext
15 V DC
I = 0/4 - 20 mA Ri≤ 500
Current output
I
active
Current output I
passive
Active mode
The current output supplies the power for operation of the outputs and inputs.
Passive mode
External power source required for operation of the outputs and inputs.
3 4
Pulse output P
passive
for electronic (EC) or electromechanical (EMC) totalizers
U
ext
32 V DC/24 V AC
I
max
150 mA
(incl. status output S)
U
int
15 V DC from current output
Operation with current output:
I
max
3 mA
Operation without current output:
I
max
23 mA
R
15 V
I
max
Pulse output P
active (and current output I
active
) for electronic (EC) totalizers with and without current output I
Totalizer
- electronic (EC)
- electromechanical (EMC)
Milliammeter 0 or 4-20mA and others
Key, N/O contact
External voltage source (U
ext
), DC or AC voltage, connection polarity arbitrary
DC voltage, external power source (U
ext
),
note connection polarity
U
ext
U
ext
I
max
+
Page 13
2/4
Condensed instructions IFC 020
U
ext
30 V DC/24 V AC
I
max
6 mA
87
Control input E
passive
(IFC 020 E only)
RS 485 Interface
For connection and operation of the
Krohne RS 485 Interface,
see section 6.2.
6
5
Status output S
passive
U
ext
30 V DC/24 V AC
I
max
150 mA
(incl. pulse output P)
Status output S
active
with and without current output I
U
int
15 V DC
from current output
I
max
3 mA
Operation with current output
I
max
23 mA
Operation without current output
Load
Load
Error messages in measuring mode 2.5
The following list gives all errors that can occur during process flow measurement. Errors shown in display when “YES“ set in Fct. 1.04 DISPLAY, subfunction “DISP. MSG.“.
Error messages Description of error Error clearance
LINE INT. Power failure Note:
Cancel error in RESET/QUIT. menu
no counting during power failure Reset totalizer if necessary.
CUR. OUTP. I Current output overranged. Check and if necessary correct
(Flow > measuring rage) instrument parameters. After
elimination of cause, error message deleted automatically.
PULSOUTP. P Pulse output overranged. Check and if necessary correct
Note:
instrument parameters. After
totalizer deviation possible. elimination of cause, error message
deleted automatically.
TOTALIZER Totalizer has been reset Cancel error message in
RESET/QUIT. menu, see section 4.6.
ADC Analog / digital Error message deleted automatically
converter overranged after elimination of cause.
FATAL. ERROR Fatal error, all outputs set Please consult factory.
to “min. values“
Page 14
Condensed instructions IFC 020
3/1
3 Start-up
Before powering the system, please check that it has been correctly installed according
to Sect. 1 and 2.
The flowmeter is delivered ready for operational use. All operating data have been factory set in accordance with your specifications.
Please refer to Sect. 3.2 “factory settings”.
Power the unit, and the flowmeter will immediately start process flow measurement.
When powered, the display shows in succession: START UP and READY.
This is followed by display of the current flow rate and/or the current totalizer count on either a continuous or alternating basis, depending on the setting under Fct. 1.04.
Refer to Sect. 4 and 5 for operator control of the “display version”.
3.1 Power-on and measurement
3.2 Factory setting
All operating data are factory set according to your order specifications.
If you have not made any particular specifications at the time of ordering, the instruments will be delivered with the standard parameters and functions listed in the Table below.
To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric flow counted independent of the flow direction. On instruments equipped with a display, measured values may possibly be shown with a “ – ” sign.
This factory setting for the current and pulse outputs may possibly lead to measuring errors, particularly in the case of volume flow counting:
for example, if pumps are switched off and a “backflow” occurs which is not within the range of the low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.
To avoid faulty measurements, therefore, it may be necessary to change the factory setting of some or all of the following functions: – low-flow cutoff SMU, Fct. 1.03, Sect. 5.3 – current output I, Fct. 1.05, Sect. 5.6 – pulse output P, Fct. 1.06, Sect. 5.7 – display (option), Fct. 1.04, Sect. 5.4
Operation see Section 4 and 5.
Standard factory settings
Function Setting
1.01 Full-scale range Q
100%
see nameplate
1.02 Time constant 3 s, for I, S and display
1.03 Low-flow ON: 1 %
cutoff SMU OFF: 2 %
1.04 Display (option)
flow rate m
3
/hr or US Gal/min
totalizer(s) m3 or US Gal
1.05 Current output I
function 2 directions range 4 - 20 mA error message 22 mA
1.06 Pulse output P
function 2 directions pulse value 1 pulse/s pulse width 50 ms
1.07 Status output S flow directions
Function Setting
1.08 Control input off
3.01
Language for display only
English
3.02 Flowmeter diameter see nameplate flow direction (see arrow
+ direction
on primary head)
}
3.04 Entry code no
3.05 User unit
Liter/hrorUSMGal/day
3.06 Application steady
3.07 Measuring point Altometer
3.08 Communication interface off
Page 15
4/1
Condensed instructions IFC 020
Operation of the signal converter 4
Teil B IFC 020 _/ D Signal converter
Krohne operator control concept 4.1
1 3 6. 4 9
m3/hr
Measuring mode
CodE 1
Menu column
Function column
Data column
3.00 INSTALL.
2.00 TEST
1.00 OPERATION
3.05 USER UNIT
3.06 APPLICATION
3.07 MES. POINT
3.08 COM
3.04 ENTRY CODE
3.03 ZERO SET
3.02 FLOWMETER
3.01 LANGUAGE
2.02 HARDW. INFO
2.01 TEST Q
1.07 STATUS. S
1.08 CONTROL E
1.06 PULS. OUTP. P
1.05 CUR. OUTP. I
1.04 DISPLAY
1.03 L.F. CUTOFF
1.02 TIMECONST.
1.01 FULL SCALE
Direction of movement
see
Sect.
4.4
When this display appears, press following keys:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
Page 16
4/2
Condensed instructions IFC 020
π
4
π
4
4.2 Table of settable functions
Fct. Text Description and settings
1.00 OPERATION Operations menu
1.01 FULL SCALE Full-scale range for flowrate Q
100%
Select unit
m3
/hr • Liter/Sec • US.Gal/min
user unit, factory set is “Liter/hr” or “US MGal/day” (see Fct. 3.05)
Press → key to transfer to number setting.
Setting ranges The ranges are dependent on the meter size (DN) and the flow
velocity (v): Q
min
= DN2x v
minQmax
= DN2x v
max
Nom. dia.
/meter size v
min = 0,3 m/s (1 ft/s) vmax = 12 m/s (40 ft/s)
DN 2.5–1000 /
1
/10”–40”: 0.0053 – 033 900 m3/hr
0.0237 – 152 000 US.Gal/min
Press key to return to Fct. 1.01 FULL SCALE.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
) has been changed. With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
min
= F
min
/ Q
100% Pmax
= F
max
/ Q
100%
Check new values!
1.02 TIMECONST. Time constant
Select:
ALL (applies to display and all outputs)
ONLY I+S (only display, current and status outputs)
Press ↵ key to transfer to number setting.
Range: • 0.2 – 99.9 Sec
Press ↵ key to return to Fct. 1.02 TIMECONST.
1.03 L.F.CUTOFF Low-flow cutoff (SMU)
OFF (fixed values: ON = 0.1% / OFF = 0.2%
at 100Hz and 1000Hz, see Fct. 106, 1% resp. 2%)
PERCENT (variable values) ON OFF
1 – 19% 2 – 20%
Press → key to transfer to number setting.
Note: Cutoff “off” value must be greater than cutoff “on” value.
Press ↵ key to return to Fct. 1.03 L.F. CUTOFF.
1.04 DISPLAY Display functions
DISP.FLOW Select flow display
NO DISP. •
user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
m3/hr PERCENT
Liter/Sec BARGRAPH (value and bargraph display in %)
US.Gal/min
Press key to transfer to subfunction “DISP. TOTAL.”.
DISP.TOTAL. Select totalizer display
NO DISP. (totalizer switched on but not displayed)
OFF (totalizer switched off)
+TOTAL TOTAL ±TOTAL SUM (Σ)
ALL (single totalizer or all)
Press ↵ key to transfer to display unit
m3 Liter US.Gal
user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).
Press → key to transfer to format setting.
Format setting
• Auto (exponent notation)
# . ####### ##### . ###
## . ###### ###### . ##
### . ##### ####### . #
#### . #### ########
Press key to transfer to subfunction “DISP.MSG”.
DISP.MSG. Additional messages required in measuring mode?
NO YES (cyclic change with displays of measured values)
Press ↵ key to return to Fct. 1.04 DISPLAY.
Page 17
Condensed instructions IFC 020
4/3
Fct. Text Description and settings
1.05 CURRENT I Current output I
FUNCT. I Select function for current output I
OFF (switched off)
1 DIR. (1 flow direction)
2 DIR. (forward/reverse flow, F/R flow measurement)
Press key , transfer to subfunction “RANGE I”;
RANGE I Select measuring range
0 - 20 mA 4 - 20 mA (fixed ranges)
mA (user-defined range) I
0%
- I
100%
(Value I0%< I
100%
!) 0 - 16 mA 4 - 20 mA
To transfer to number setting, press key →! Press key to transfer to subfunction “I ERROR“.
I ERROR Select error value
22 mA 0.0 to I0%mA (variable, see above if I0%> 1 mA)
To transfer to number setting, press key →! Press key to revert to Fct. 1.05 CURRENT. I.
1.06 PULS B1 Pulse output B1 (see Fct. 3.07 HARDWARE)
FUNCT. P Select function for pulse output P
OFF (switched off)
1 DIR. (1 flow direction)
2 DIR. (forward/reverse flow, F/R flow measurement)
Press key to transfer to subfunction “SELECT P”.
SELECT P Select pulse type
100 HZ PULSE/VOL. (pulses per unit volume, flowrate)
1000 HZ PULSE/TIME (pulses per unit time for 100% flowrate)
Press key to transfer to subfunction “PULSWIDTH”. With selection 100 HZ and 1000 HZ, return to Fct.1.06 pulsoutput P (pulswidth 50% cyclic).
PULSWIDTH Select pulse width
50 msec 100 msec 200 msec 500 msec 1 sec
Press key to transfer to subfunction “VALUE P”.
VALUE P Set pulse value per unit volume (appears only when
“PULSE/VOL.” set under “SELECT P” above)
xxxx PulS/m3 xxxx PulS/Liter xxxx PulS/US.Gal
xxxx PulS/
user-defined unit, factory-set is “Liter” or “US M.Gal” (see Fct. 3.05) Setting range “xxxx” is dependent on the pulse width and the full-scale range: P
min
= F
min
/ Q
100%Pmax
= F
max
/ Q
100%
Press key to return to Fct. 1.06“PULS. OUTPUT P”.
VALUE P Set pulse value per unit time (appears only when “PULSE/TIME”
set under “SELECT P” above)
xxxx PulSe/Sec (=Hz) xxxx PulSe/min xxxx PulSe/hr
xxxx PulSe/user-defined unit, factory-set is “hr” (see Fct. 3.05)
Setting range “xxxx” is dependent on the pulse width, see above Press key to return to Fct. 1.06“PULS. OUTPUT P””.
1.07 STATUS. S Status output S
ALL ERROR FATAL ERROR • OFF • ON
F/R INDIC. (F/R indication for forward/reverse measurement)
TRIP. POINT Settin
g range: 002 - 115 PERCENT
EMPTY PIPE (appears only when this option is installed)
Press ↵ key to transfer to number setting Press ↵ key to return to Fct. 1.07 “STATUS. S“.
1.08 CONTROL E Control input E (IFC 020 E only) (IFC 020 E only) OFF (switched off)
OUTP. ZERO (set outputs to “min.values”)
TOTAL. RESET (reset totalizers)
ERROR. RESET(delete error messages)
Press key to return Fct. 1.08 “Control E”.
Page 18
Condensed instructions IFC 020
4/4
Fct. Text Description and settings
2.00 TEST Testmenu
2.01 TEST Q Test measuring range Q
Precautionar
y query
SURE NO Press key to return to Fct. 2.01 “TEST Q”.
SURE YES Press key, then use key to
select value: -110 / -100 / -50 / -10 / 0 / +10 / +50 / +100 / +110 PCT.
of set full-scale range Q
100%
.
Displayed value present at outputs I and P.
Press ↵ key to return to Fct. 2.01 “TEST Q”.
2.02 HARDW. INFO Hardware information and error status
Before consulting factory, please note down all 6 codes.
MODUL ADC X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press key to transfer to “MODUL IO“.
MODUL IO X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press key to transfer to “MODUL DISP.“.
MODUL DISP. X . X X X X X . X X Press key to transfer to “MODUL RS
Y Y Y Y Y Y Y Y Y Y
MODUL RS X . X X X X X . X X Press key to return to Fct. 2.02
Y Y Y Y Y Y Y Y Y Y “HARDW. INFO“.
Fct. Text Description and settings
3.00 INSTALL. Installation menu
3.01 LANGUAGE Select language for display texts
GB / USA (English) F (French)
D (German) others on request
Press ↵ key to return to Fct. 3.01 “LANGUAGE”.
3.02 FLOWMETER Set data for primary head
DIAMETER Select size from meter size table
DN 2.5 - 1000 mm equivalent to
1
/10- 40 inch
Select with key. Press ↵ key to transfer to subfunction “FULL SCALE ”.
FULL SCALE Full-scale range for flow Q
100%
To set, refer to Fct. 1.01 “FULL SCALE” above.
Press key to transfer to subfunction “GK VALUE”.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
) has been changed. With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
min
= F
min
/ Q
100% Pmax
= F
max
/ Q
100%
Check new values!
GK VALUE Primary head
- Set primary constant GK
see primary head nameplate. Range: 1.0000 - 9.9999
Press key to transfer to subfunction “FIELD. FREQ.”.
FIELD FREQ. Magnetic field frequency
Values: 1/6
and 1/18 of power frequency, see nameplate.
Press ↵ key to transfer to subfunction “FLOW DIR.”; DC units only: to transfer to subfunction “LINE FREQ.”.
LINE FREQ. Normal line frequency in your country
Please note:
This function is only provided for units with DC power supply to suppress line-frequency interference. Values: 50 Hz and 60 Hz
Press key to transfer to subfunction “FLOW DIR.”.
FLOW DIR. Define flow direction (in F/R mode: forward flow).
Set according to direction of arrow on primary head:
+ DIR. – DIR. Select using key. Press ↵ key to return to Fct. 3.02 “FLOWMETER ”.
Page 19
Fct. Text Description and settings
3.03 ZERO SET Zero calibration
Note: Carry out only at “0” flow and with completely filled
measuring tube!
Precautionar
y query
CALIB. NO Press key to return to Fct. 3.03 “ZERO SET”.
CALIB. YES Press key to start calibration.
Duration approx. 15-90 seconds, (depends on frequency of magnetic field) current flowrate
displayed in the selected
unit (see Fct. 1.04 “DISP. FLOW”).
A “WARNING” sign appears when flowrate “> 0“; acknowledge by pressing key.
STORE NO (do not store new zero value)
STORE YES (store new zero value)
Press key to return to Fct. 3.03 “ZERO SET”.
3.04 ENTRY CODE Entry code required to enter setting mode?
NO (= entry with only)
YES (= entry with and Code 1: → → → ↵ ↵ ↵ ↑ ↑ ↑ )
Press to return to Fct. 3.04 “ENTRY CODE”.
3.05 USER UNIT Set any required unit for flowrate and counting
TEXT VOL. Set text for required flowrate unit (max. 5 characters)
Factory-set: “Liter” or “MGal”. Characters assignable to each
place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press key to transfer to subfunction “FACT. VOL.”
FACT. VOL. Set conversion factor (F
M
) for volume
Factory set “1.00000 E+3” for “Liter” or “2.64172E-4” for “US MGal” (exponent notation, here: 1x103or 2.64172x10-4). Factor FM= volume per 1m3. Setting range 1.00000 E-9 to 9.99999 E+9 (= 10-9to 10+9)
Press key to transfer to subfunction “TEXT TIME”.
TEXT TIME Set text for required time unit (max. 3 characters)
Factory-set: “hr” (=hour). Characters assignable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press key to transfer to subfunction “FACT. TIME”
FACT. TIME Set conversion factor (FT) for time
Factory-set: “3.60000 E+3” for “hour” or “8.64000 E+4” for “day” (exponent notation, here: 3.6 x103or 8.64 x10-4). Set factor FTin seconds. Settin
g range
1.00000 E-9 to 9.99999 E+9 (= 10-9to 10+9)
Press key to return to Fct. 3.05 “USER UNIT”.
3.06 APPLICAT. Set overload point for A/D converter
FLOW STEADY (150% of Q
100%
) PULSATING (1000% of Q
100%
)
Press key to return to Fct. 3.06 “APPLICAT.“,
3.07 MEASURING POINT Set measuring point no. Factory setting: ALTOMETER Characters assi
gnable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character). Press key to return to Fct. 3.07”MEASURING POINT”
3.08 COM Set comminucation interface
OFF (switched off)
HART (HART-interface switched on)
KROHNE (RS 485 interface switched on)
Address:”HART” 00-15 / “KROHNE” 000-239
BAUD RATE: -1200 -2400 -4800 -9600 -19200
(appeare with selection “KROHNE”)
Press key to return to Fct. 3.08 “COM”.
4/5
Condensed instructions IFC 020
Loading...