Kb Electronics KBSI-240D User Manual

INSTALLATION AND OPERATING INSTRUCTIONS
MODEL KBSI-240D
Signal Isolator KB Part No. 9431
See Safety Warning on Page 1
The information contained in this manual is intended to be accurate. However, the Manufacturer retains the right to make
changes in design which may not be included herein.
A COMPLETE LINE OF MOTOR DRIVES
© 2000 KB Electronics, Inc.
P1
J1
VOLT CUR
MAX
1
2345678910
KBSI-240D
MIN
TABLE OF CONTENTS
Section Page
i. Safety Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
I. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
II. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
III. Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
IV. Output Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
V. Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Tables
1. General Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Voltage Input Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figures
1. Control Layout & Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2A. 115V Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2B. 230V Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Current Input Signal Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Voltage Input Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5A. Master/Multiple Slave Voltage Following System (Single Main Motor) . . . . . . . . . . . . . . . . . . . . . . 9
5B. Master/Multiple Slave Voltage Following System (Single Main Potentiometer) . . . . . . . . . . . . . . . . 9
6A Master/Slave Voltage Following System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6B. Process Control with Auto/Manual Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6C. Process Control with Auto (Ratio Pot)/Manual Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6D. Auto/Manual Operation with Potentiometer on KBSI Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
ii
1
This product complies with all CE directives pertinent at the time of manufacture. Contact factory for detailed installation instructions and Declaration of Conformity.
i. SAFETY WARNING! Please read carefully:
Be sure to follow all instructions carefully. Fire and/or electrocution can result due to improper use of this product.
This product should be installed and serviced by a qualified technician, electrician, or electrical maintenance person familiar with its operation and the hazard involved. Proper installation, which includes wiring, mounting in proper enclosure, fusing or other over current protection and grounding, can reduce the chance of electric shocks, fires, or explosion in this product or prod­ucts used with this product, such as electric motors, switches, coils, solenoids, and relays. Eye protection must be worn and insulated adjustment tools must be used when working with con­trol under power. This product is constructed of materials (plastics, metals, carbon, silicon, etc.) Which may be a potential hazard. Proper shielding, grounding, and filtering of this product can reduce the emission of radio frequency interference (RFI) which may adversely affect sensitive electronic equipment. If information is required on this product, contact our factory. It is the responsibility of the equipment manufacturer and individual installer to supply this safety warn­ing to the ultimate user of this product. (SW effective 11/92)
!
I. INTRODUCTION
The KBSI-240D Signal Isolator is used to isolate, amplify and condition DC voltage and current signals from any source (motors, tachs and transducers) which will drive most variable speed motor controls with a voltage following input. The maximum output voltage of the isolator is 10 volts, which is a linear function of the input signal.
The KBSI-240D is versatile since it can accommodate a wide range of input voltages (0 - 25*, 0 - 120 and 0 - 550V DC) and, in addition, a wide range of input current signals (4 - 20 mA, 10
- 50 mA and 1 - 5 mA). The Voltage/Current (“VLT/CUR”) jumper is used to change the KBSI-240D from a voltage to current input.
A built-in power supply enables the KBSI-240D to be controlled with a 5KΩ remote poten­tiometer (connect potentiometer to terminals “P1,” “5” and “6” – see page 9). The potentiome­ter can also be wired for Auto/Manual Operation.
*The input range of 0 - 25V is the maximum voltage that can be applied to terminals “5” and “6”. The minimum input voltage is 0 - 5 volts, which can achieve an output voltage of 0 - 10 volts. The unit is factory calibrated so that a 0 - 10V DC input yields a 0 - 10V DC output.
II. MOUNTING
Mount the Signal Isolator using (4) 6-32 screws (not included). Use the Control Layout and Mechanical Specifications drawing on page 3 to locate the mounting holes. The unit is designed to be mounted in any position providing its components do not come in contact with grounded or live wiring.
2
FIGURE 1 – CONTROL LAYOUT & MECHANICAL SPECIFICATIONS (INCHES / [mm])
(Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings)
3
4.843
0.276 [7.00]
[123.00]
4.291
[109.00]
0.276 [7.00]
P1
J1
VOLT CUR
MAX
1
2345678910
(4) mounting holes for #6 screws
KBSI-240D
2.244 [57.0]
MIN
2.795 [71.0]
Notes:
1. To achieve full specifications input voltage must be within ± 10% of nominal.
2. Floating (non-grounded) or grounded input signal may be used.
3. To change from 4 - 20mA to 1 - 5mA remove R3. To convert to 10 - 50mA add a 150Ω 1W resistor across terminals “5” and “6.” See figure 3.
4. Specifications are based on an output of 10 volts.
AC Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 115 or 208 - 230V AC, 50/60 Hz
(1)
Signal Input Voltage
(2)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 25, 0 - 120, 0 - 550V DC
Signal Input Current
(2)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 5, 4 - 20, 10 - 50mA
(3)
Maximum Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Volts
Maximum Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10mA
Range of “MIN” Trimpot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3 Volts
Range of “MAX” Trimpot . . . . . . . . . . 0 to 2 times the input voltage with maximum of 10 Volts
Linearity
(4)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0.1%
Temperature Drift
(4)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 mV per ºC
Temperature Operating Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 50 ºC
4
TABLE 1 – GENERAL PERFORMANCE SPECIFICATIONS
III. WIRING.
Warning! Read Safety Warning on page 1 before attempting to use this control.
A.
AC Power – The KBSI-240D is powered with either 115 or 230V AC, 50/60 Hz by arranging the jumpers between terminals “1” to “4” properly. See figures 2A and 2B. Be sure unit is wired in accordance with the National Electric Code and other codes that may apply. It is recommended that a 1 amp fuse be installed in series with the AC line.
B. Input Terminals – A voltage or current signal from a
microprocessor, tachometer, transducer, etc. is to be connected to terminals “5” through “8.” The selection of the proper terminal is based on the maximum level of the input signal. See figures 3 and 4.
5
FIGURE 2A – 115V CONNECTION
FIGURE 2B – 230V CONNECTION
Warning! To avoid erratic operation do not bundle AC Line and motor wires with potentiometer, voltage fol­lowing, enable, inhibit or other signal wiring. Use shielded cables on all signal wiring over 12” (30 cm) – Do not ground shield.
!
1234
Jumper Jumper
115V AC
1A
FUSE
1234
Jumper
230V AC
1A
FUSE
i. Current Input Signal
Warning! Read Safety Warning on Page 1 before attempting to use this control.
Note:
The Voltage/Current (VLT/CUR) jumper must be in “CUR” position. Connect the negative current signal input to terminal “5” and the positive to terminal “6.” The KBSI-240D is factory calibrat­ed so that a 4 - 20mA signal will provide a 0 - 9 Volt output. The input range can be converted to a 10 - 50mA range by attaching a 150Ω 1W resistor across the current input terminals “5” and “6.” See figure 3. Control must be recalibrated when the 150Ω resistor is installed. The range of signal input can be changed to 1 - 5mA by removing resistor R3 from the printed circuit board.
Recalibrate the Signal Isolator to follow a 4 - 20mA current signal input as follows:
1. Connect a 10V DC meter (digital DC meter is suggested) to terminals “9”(-) & “10” (+).
2. Apply the minimum input current (4mA) at terminals “5” and “6.”
3. Adjust the “MIN” trimpot to an output voltage of 0 volt DC.
4. Set the input current to 20mA and adjust the “MAX” trimpot so that the output voltage is at
the desired level (9V DC).
5. Repeat steps 3 and 4 if extreme accuracy is required. The Signal Isolator is now cali-
brated to provide 0 - 9V DC output with a 4 - 20mA input.
6. Use the “MIN” and “MAX” trimpot if other than 0 - 9V DC output is required with the respec-
tive input current range.
6
FIGURE 3 – CURRENT INPUT
SIGNAL CONNECTION
!
56
4 - 20mA
+
150 Resistor Converts 4 - 20mA to 10 - 50mA
ii. Voltage Input Signal
Warning! Read Safety Warning on Page 1 before attempting to use this control.
Note: The Voltage/Current (VLT/CUR) jumper must be in the VLT position (factory setting). The KBSI-240D is designed to accept a wide range of input voltage signals as follows:
Connect input voltage signal to proper input terminals as indicated in figure 4.
1. Connect a 10V DC meter (digital meter is suggested)
to terminals “9” (-) and “10” (+).
2. Apply the maximum input voltage that would be supplied from tach, transducer, etc.
3. Adjust the “MAX” trimpot to the desired output voltage.
Example: A slave motor is to follow the output of a main motor with an armature voltage range of 0 - 90V.
7
Minimum Input Voltage Range
Input Terminals
5, 6
Maximum Input
Voltage Range
0 - 5 0 - 25
5, 7 0 - 25 0 - 120
5, 8 0 - 120 0 - 550
TABLE 2 – VOLTAGE INPUT SIGNAL
FIGURE 4 – VOLTAGE INPUT
SIGNAL CONNECTIONS
!
56
0 - 25V
+
0 - 120V
0 - 550V
78
+
+
a) Connect the armature of the main motor to the SI input terminals “5” (-) and “7” (+).
b) Set the armature voltage of the main motor to zero (0). Adjust the “MIN” trimpot so that
the output at terminals “9” and “10” reads zero (0) volts.
c) Reset the armature voltage of the main motor to 90V. Adjust the “MAX” trimpot so that
the output voltage is 9V DC.
Notes:
1. When setting the output voltage using the “MIN” and “MAX” trimpots the voltage or speed of the driven motor can be read directly instead of using the output of the KBSI.
2. When readjusting the “MIN” and “MAX” trimpots, always set the minimum voltage first and then the maximum voltage.
3. Trimpots allow approximately 20 turns for the full range of adjustment. If during the adjust­ment procedure the output stops changing, try reversing the direction of rotation of trimpot.
IV. OUTPUT SIGNAL
The output signal from the SI is obtained from terminals “9” (-) and “10” (+). Connect the out­put directly to the signal following input terminal of the speed control. For multiple slave motors, several controls can be driven from a single KBSI-240D. Be sure the AC line connections to the slave control are to the same phase (eg, L1 to L1 and L2 to L2 of all controls.)
The output from the KBSI-240D can be scaled to control the speed control over any desired speed range. Adjust the “MIN” trimpot to provide the desired minimum speed and the “MAX” trimpot to provide the desired maximum speed.
8
9
Isolation Diode
F(–)
A(–)
A(–)
A(+)
A(+)
Additional
Slaves
Slave
Motor #1
Slave
Motor #2
Slave
Motor #3
A(–)
A(+)
P2
F(–)
P2
F(–)
P2
Ratio 5K
9(–)
10(+)
KBSI-240D
5
7
Main Motor
A(–)
A(+)
DC
Speed
Control
Speed
Control
Speed
Control
Speed
Control
FIGURE 5 – MASTER/MULTIPLE SLAVE VOLTAGE FOLLOWING SYSTEM
A) From a Single Main Motor
WARNING! If Signal Isolator is connected to multiple speed controls;
1) Multiple controls must be powered from the same phase of AC line.
2) The positive input terminal to each speed control must be installed with a 1 amp - 600V isolation diode as shown.
3) Multiple speed controls can not be used with PWM, Regenerative or Variable Frequency Drives (Inverters).
B) From a Single Main Potentiometer
A 10K ratio poten­tiometer is used to control up to ten (10) slave motors.
If a 5K ratio poten­tiometer is used, up to five (5) slave motors can be con­trolled.
P1*
5K Pot
6
KBSI-240D
5
*Connect high side of potentiometer to terminal "P1" (1/4" QD)
10 (+)
Connect as above
9 (–)
10
The KBSI-240D can be wired in an Auto/Manual mode which will allow man­ual override of an automatic process. See figure 6B.
FIGURE 6B – PROCESS CONTROL WITH AUTO/MANUAL SWITCH
AC Line
FIGURE 6A – MASTER/SLAVE VOLTAGE FOLLOWING SYSTEM
DC Speed Control
A(+)
A(–)
Speed
Pot
90V DC
Main Motor
7
KBSI-240D
5
AC Line
10(+)
9(–)
AC Line
L1 L2
P2
Speed
F-
Control
Manual 5K Speed Pot
Auto/Man
5K Pot
P3
10(+)
KBSI-240D
P2
P1
9(–)
F(–)
KB
CONTROL
A(+)
A(–)
Slave
Motor #1
A(+)
A(–)
Motor
Note: The preceding circuit provides for the speed pot to be used in “MAN” mode only. In “AUT0” mode, the process control signal is supplied directly to the signal isolator.
11
The following circuit provides for dual pur­pose usage of the speed pot. In the “AUTO” mode it is used for ratio control and in the “MAN” mode it is used for manual speed adjust­ment.
FIGURE 6C – PROCESS CONTROL WITH AUTO (RATIO POT)/MANUAL SWITCH
FIGURE 6D – AUTO/MANUAL OPERATION WITH POTENTIOMETER ON KBSI INPUT
KBSI-240D
Auto W/Ratio
10(+)
9(–)
Manual
5K Pot
P3
P2
F(–)
KB
CONTROL
A(+)
A(–)
Motor
Process
Signal
0 - 10V DC
Auto/Man 5K Pot
6 5
P1
KBSI-240D
10(+)
9(–)
P2
F(–)
KB
CONTROL
A(+)
A(–)
Motor
– NOTES –
12
– NOTES –
13
V. LIMITED WARRANTY
For a period of 18 months from the date of original purchase, KB Electronics, Inc. will repair or replace, without charge, devices which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized per­sons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. The foregoing is in lieu of any other warranty or guarantee, expressed or implied. KB Electronics, Inc. is not responsible for any expense, including instal­lation and removal, inconvenience, or consequential damage, including injury to any person, caused by items of our manufacture or sale. Some states do not allow certain exclusions or lim­itations found in this warranty and therefore they may not apply to you. In any event, the total liability of KB Electronics, Inc., under any circumstance, shall not exceed the full purchase price of this product.
(Rev 2/2000)
KB Electronics, Inc.
12095 NW 39th Street, Coral Springs, FL 33065-2516 • (954) 346-4900 • Fax (954) 346-3377 Outside Florida Call TOLL FREE (800) 221-6570 • E-mail – info@kbelectronics.com www.kbelectronics.com
(A40255) – Rev. B – 5/2000
Loading...