Important: You must read these simplified instructions before proceeding. These instructions
are to be used as a reference only and are not intended to replace the details provided herein.
You must read the SAFETY WARNING, on page 5, before proceeding.
1.1. Connections (See Figure 3, on page 14).
Note: There are no AC Line or Armature fuses supplied with this control. See Section,
1.1.2.
1.1.1 AC Line – Connect AC line voltage (115 or 230 VAC) to terminals L1 and L2.
Connect ground wire (earth) to the green ground screw.
1.1.2 Fusing – The KBRG-212D does not contain AC line or armature fusing. It is
recommended that a 20 Amp fuse or circuit breaker be installed on each AC line
conductor not at ground potential. Do not fuse ground or neutral wires.
1.1.3 Ground Connection – Earth ground the control chassis using the green ground
screw that is provided on the control,s heat sink (near TB2).
1.1.4Motor (See Figure 3, on page 14).
a. Permanent Magnet (PM Type). Connect motor armature leads to M1+ and
M2-.
Note: Motor performance and efficiency, including brush life, can be adversely affected
when using 90 volt motors with a 230 VAC line. Contact motor manufacturer for
derating information.
b. Shunt Wound Motors.Connect motor armature leads as above. Connect
full voltage shunt field leads (90 volt motors with 100 volt fields and 180 volt
with 200 volt fields) to F+ and F-. Connect half voltage field leads (90 volt
motors with 50 volt fields and 180 volt motors with 100 volt fields) to F+ and
L1.
1.2 ENABLE/INHIBIT– The control can be electronically stopped and started with this circuit
function. To “Stop” the control, Terminals must be connected in the required position, by
selecting the type of mode, via J9. See Figure 8B and Section 6.10, on page 18.
In the Enable Mode, the control can also be started and stopped with an Enable circuit
(the Enable circuit functions opposite to that of the inhibit circuit; Inhibit: open to start,
close to stop, Enable: open to stop, close to start). The Enable function can also be
established by wiring a contact in series with the high side of the Main Speed
Potentiometer lead connected to Terminal P3. See Figure 8A and Section 6.10, on page
18.
1.3SPEED OR TORQUE MODE: Jumper J5 is factory set for Speed (SPD) control operation.
For torque control, set J5 to the Torque (TRQ) position. See Section 7.3, on page 20.
1.4 JUMPER SETTINGS: All jumpers are set for the KBRG-212D version. The control is
factory jumpered for the Enabled mode. See Section 7, on page 19.
1.5 TRIMPOT SETTINGS – All trimpots have been factory set. See Figure 1, on page 10 and
Section 10, on page 25.
1.6 SIGNAL INPUT – Connect potentiometer or analog input to TB1, terminals “-15,” “+15”
“SIG,” and “COM” according to Section 6, on page 16.
4
2 SAFETY WARNING
f
Definition of Safety Warning Symbols
Electrical Hazard Warning Symbol: Failure to observe this warning could result in
electrical shock or electrocution.
Operational Hazard Warning Symbol: Failure to observe this warning could result in
serious injury or death.
This product should be installed and serviced by a qualified technician, electrician, or electrical
maintenance person familiar with its operation and the hazards involved. Proper installation, which
includes electrical connections, mounting and adequate enclosure, fusing or other current protection, and
grounding can reduce the chance of electrical shocks, and/or fires in this product or products used with this
product, such as electric motors, switches, coils, solenoids, and/or relays. Do not use this drive in an
explosion-proof application. Eye protection must be worn and insulated adjustment tools must be used
when working with drive under power. This product is constructed of materials (plastics, metals, carbon,
silicon, etc.) which may be a potential hazard. Proper shielding, grounding, and filtering of this product can
reduce the emission of radio frequency interference (RFI) which may adversely affect sensitive electronic
equipment. The input circuits of this drive may not be isolated from the AC line. Be sure to read and follow
all instructions carefully. Fire and/or electrocution can result due to improper use of this product.
The drive may contain electronic start/stop circuits, which are used for "Start" and "Stop" functions.
However, these circuits are never to be used as safety disconnects since they are not fail-safe. Use only
the AC line for this purpose.
It is the responsibility of the equipment manufacturer and individual installer to supply this Safety Warning
to the ultimate end user of this product. (SW 7/2009)
SAFETY WARNING! Please read carefully before proceeding.
This product complies with all CE directives pertinent at the time o
manufacture. Contact our Sales Department for Declaration of Conformity. Installation
of a CE approved RFI filter is required. Additional shielded cable and/or AC line cables
may be required along with a signal isolator.
5
3 INTRODUCTION
Thank you for purchasing the KBRG-212D. KB Electronics is committed to providing total
customer satisfaction by producing quality products that are easy to install and operate. The
KBRG-212D is manufactured with Surface Mount Technology (SMT), incorporating advanced
circuitry, components and technology.
The KBRG -212D has an Enable (EN) / Inhibit (INH) mode. The 212D version is factory set (J9
jumper) to Enable (EN). If the user requires the 213D Inhibit (INH) mode, the jumper, J9, is
moved to that position.
The KBRG-212D is a full-wave regenerative drive capable of operating DC PM (Permanent
Magnet) or Shunt motors in a bidirectional mode. Its 4-quadrant operation provides forward and
reverse torque in both speed directions. This allows the control to maintain constant speed with
overhauling loads and provides rapid instant reversing and controlled braking. Because of its
excellent controllability and response time, the KBRG-212D can replace servos in many
applications. The control is factory set for armature feedback, which can provide 1% load
regulation over a motor base speed of 50:1. However, tachometer feedback is also available if
superior regulation is required. By resetting mode jumper J5 to the “TRQ” position, the
KBRG-212D can be changed from a speed control to a torque control.
In addition, the KBRG-212D is used to isolate, amplify, and condition DC voltage signals from
any external source (power supplies, motors, tachometer generators, transducers, and
potentiometers). The KBRG-212D also provides isolation for motor direction switching and an
isolated power supply for transducer or potentiometer operation.
All input and signal connections are made via Terminal blocks and are electrically isolated from
AC line and motor wiring.
The KBRG -212D features an Enable (EN) and Inhibit (INH) function (J9). Having both these
features allows the drive to be used in applications that previously used the KBRG-212D
(Enable) or the KBRG-213D (Inhibit). The control can be electronically stopped and started with
the Enable / Inhibit circuit. (The Enable circuit functions opposite to that of the inhibit circuit;
Inhibit: open to start, close to stop, Enable: open to stop, close to start).
The drive contains a variety of “selectable” jumpers and adjustment trimpots to allow for
custom tailoring for exact requirements.
Another important feature is the LED indicators (PWR ON, OL), which indicate the mode of
operation the drive is in, and also serves as a diagnostic tool.
Reliability of the KBRG-212D is further enhanced with the use of high speed current limiting
and MOV transient protection. A 5kΩ remote potentiometer and full operating instructions are
supplied. See Figures 1 and 2, on pages 10 and 11. In addition, see Tables 1 – 6, on pages
7 – 9.
OR ELECTROCUTION CAN RESULT DUE TO IMPROPER USE OF THIS PRODUCT. READ
WARNING! BE SURE TO FOLLOW ALL INSTRUCTIONS CAREFULLY. FIRE
SAFETY WARNING ON PAGE 5.
6
TABLE 1 – STANDARD FEATURES
Feature Description
Terminal Blocks
(See Section 6, on page 13.)
Connectors
(See Section 7, on page 19.)
Facilitates wiring of AC line, motor armature and field,
TB1 (-15V, +15V, SIG, COM, EN), TB2 (L1, L2, M2, M1), TB3
(F+, F-).
J1, Tach-Generator Input – Connection point for an external
Tach-Generator.
J2 - Motor Armature Current
J3 - Motor Armature Voltage
Selectable Jumpers
(See Section 7, on page 19.)
J5 -SPD / TRQ – (Speed / Torque)
J6 -CTS/RTS – (Coast to Stop / Regenerate to Stop)
J8 -Signal Input Source (15V or 10V)
J9 - Enable (EN) / Inhibit (INH)
J17- Analog Signal Input (Voltage/Current)
Provide adjustment for Forward Acceleration (FACC), Reverse
(See Section 10, on page 25.)
Trimpots
Acceleration (RACC), Maximum (MAX), Forward Current Limit
(FCL), Reverse Current Limit (RCL), IR Compensation (IR),
Response (RESP), Deadband (DB), Offset (OFFSET), and
Scale (SCALE).
Diagnostic LEDs
(See Section 11, on page 30.)
For Power On (ON), and Current Limit (OL) indications.
(Current Overload gives indication that the control will trip).
TABLE 2 – SELECTABLE JUMPERS (See Section 7, on page 19)
Feature Description
J2-Motor Current, Refer to Section 7.1, on page
19.
J3 – Motor Armature Voltage, Refer to Section
7.2, on page 20.
J5-SPD / TRQ, Speed or Torque, Refer to
Section 7.3, on page 20.
J6-CTS/RTS. Refer to Section 7.4, on page 21.
J8-Signal Input (15V or 10V). Refer to Section
7.5, on page 22.
J17-Signal Input. Refer to Section 7.6, on page
22.
J9-EN (Enable) / INH (Inhibit). Refer to Section
7.7, on page 22.
For selection of the motor current being used.
For selection of the motor voltage being
used.
Jumper position is selectable for either Speed
(SPD) or Torque (TRQ) modes.
For selection of Coast to Stop (CTS) and
Regenerate to Stop (RTS). Works in
conjunction with the Enable circuit.
Used for selection of potentiometer (15V) or
use if the control is to be used from a
0 – ±10/±15VDC.
Input signal connection for the use with the
Main Speed Potentiometer. Used for
accepting a 0 – ±10V or 0 – ±25V signal or
4 – 20 ma.
For selection of electronically starting and
stopping the motor. Used in conjunction with
J6, CTS/RTS.
7
TABLE 3 – TRIMPOT ADJUSTMENTS(See Section 10, on pages 25)
Trimpot Description
Sets the amount of time for the motor to
Forward Acceleration (FACC). Refer to Section
10.1, page 25.
Reverse Acceleration (RACC). Refer to Section
10.1, on page 25.
Maximum Speed (MAX SPD). Refer to Section
10.2, on page 26.
Forward Current Limit (FCL). Refer to Section
10.3, on page 26. *
Reverse Current Limit (RCL) Refer to Section
10.3, on page 26. *
IR Comp (IR COMP). Refer to Section 10.4,
page 27.
Response (RESP). Refer to Section 10.5, on
page 28.
Deadband (DB). Refer to Section 10.6, on page
28.
Offset (OFFSET). Refer to Section 10.7, on
page 29.
Scale (SCALE). Refer to Section 10.8, on page
29.
* FCL and RCL also determine the maximum amount of regenerative breaking torque
depending on which direction is braking.
8
accelerate from zero speed to full speed in the
forward direction and the time it takes to
decelerate in the reverse direction (FACC =
Reverse Deceleration). Factory adjusted to 1
second. (Maximum of 15 seconds).
Sets the amount of time for the motor to
accelerate from zero speed to full speed in the
reverse direction and the time it takes to
decelerate in the forward direction (RACC =
Forward Deceleration). Factory adjusted to 1
second. (Maximum of 15 seconds).
The MAX trimpot is used to set the maximum
output voltage of the control which, in turn, sets
the maximum speed of the motor. In the
Torque Control Mode. The MAX trimpot setting
determines the unloaded motor speed.
Sets the maximum amount of DC current that
the motor can draw. This determines the
amount of maximum motor torque in both the
Speed Control Mode and Torque Mode.
Sets the maximum amount of DC current that
the motor can draw. This determines the
amount of maximum motor torque in both the
Speed Control Mode and Torque Mode.
The IR Comp is used to stabilize motor speed
under varying loads.
This trimpot determines the dynamic response
of the control.
The DB trimpot sets the amount of main speed
potentiometer rotation required to initiate
control voltage output. It is factory set to
approximately 0%. The DB trimpot also
determines the amount of delay that will occur
before regeneration starts.
This trimpot determines the amount of bias in
the forward or reverse direction. The trimpot is
factory set to provide approximately zero
offset, which means neither the forward nor
the reverse speed is favored.
This trimpot works in conjunction with the
MAX potentiometer for fine tuning of the
(voltage or current) of the incoming analog
signal.
TABLE 4 B ELECTRICAL RATINGS
Input Voltage
(VAC)
115 12 0 – ±90 7.5 ¾, (0.5)
208/230 12 0 – ±180 7.5 1.5, (1)
AC Line Input Voltage (VAC, ±10%, 50/60 Hz) 115 or 208/230 208/230
Armature Voltage Range at 115 VAC Line (VDC) 0 – ±90 —
Armature Voltage Range at 230 VAC Line (VDC) 0 – ±90, 0 – ±180 0 – ±180
Maximum AC
Line Current
(Amps RMS)
TABLE 5 B GENERAL PERFORMANCE SPECIFICATIONS
Parameter
Field Voltage at 115 VAC Line (VDC)100 / 50
Field Voltage at 230 VAC Line (VDC) 200 / 100 —
Max Load Capacity (% for 2 Minutes) 150 —
Ambient Temperature Range (ºC / °F) 0 – 40 / 32 – 104 —
Speed Range (Ratio) 50:1 —
Arm Feedback Load Regulation (% Base Speed) ±1 —
Tach Feedback Load Regulation (% Set Speed) ±1 —
AC Line Regulation (% Base Speed) ±0.5 —
Current Ranges (Amps DC) 1.7, 2.5, 5.0, 7.5 7.5
FWD and REV Accel Range (Seconds) 0.1 – 15 1
Deadband Range (% Base Speed) 0 – ±5 0
Max Speed Trimpot Range (% Base Speed) 55 – 110 100
IR Comp Range at 115 VAC Line (VDC) 0 – 20 5
IR Comp Range at 230 VAC Line (VDC) 0 – 40 10
FCL and RCL Range (% Range Setting) 0 – 175 150
Voltage Following Input Range (VDC) ±5 – ±25 0 – ±10, 0 – ±15
Voltage Following Linearity (% Base Speed) ±0.5 —
Output
Voltage
(Volts DC)
Maximum
DC Output
Current (ADC)
Specification Factory Setting
Maximum
Horsepower
HP, (KW)
—
9
FIGURE 1 B CONTROL LAYOUT
10
M1M2L1L2
F-F+
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.