Kb Electronics KBPW-240D User Manual

INSTALLATION AND OPERATION MANUAL
MODEL KBPW-240D
KB Part No. 8401 (Black Case) • Part No. 8402 (White Case)
NEMA 4X, IP-65
PWM DC Motor Speed Control For PM and Shunt Wound Motors
Rated 7.5 Amps DC, 11.5 Amps AC @ 115/230 VAC
The information contained in this manual is intended to be accurate. However, the manufacturer retains the
right to make changes in design which may not be included herein.
A COMPLETE LINE OF MOTOR DRIVES
© 2002 KB Electronics, Inc.
See back cover
See Safety Warning on Page 2
OLSTOPON
50
%
NEMA-4X / IP-65
60
70
80
90
100
RUN
JOG
TM
PENTA-DRIVE
PWM DC MOTOR SPEED CONTROL
40
30
20
10
0
FWD
REV
START
STOP
!
TABLE OF CONTENTS
Section Page
i. Safety Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
I. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
II. Simplified Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
III. Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
IV. Setting Selectable Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
V. Mounting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VI. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VII. AC Line Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VIII. Trimpot Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
IX. Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
X. Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
XI. Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Tables
1. Electrical Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. General Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Terminal Block Wiring Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Field Connection (Shunt Wound Motors Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. Setting Motor Current (SCR & PWM Motor Horsepower Ratings) . . . . . . . . . . . . . . . . . . . 10
Figures
1. Control Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3. Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Full Voltage Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. Half Voltage Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6. Remote Potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7A. Remote 3-Wire Start/Stop Switch with Normally Open Start Contact
and Normally Open Stop Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7B. Remote 3-Wire Start/Stop Switch with Normally Open Start Contact
and Normally Closed Stop Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7C. Remote 2-wire Start/Stop Switch with Normally Open Start/Stop Contact . . . . . . . . . . . . . . 8
8. Start/Stop Function Eliminated (Jumper Installed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
9. Voltage Following . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
10. Inhibit Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
11. Enable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
12. Enable Circuit Using Potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
13. DC Tach-Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
14. Motor Voltage Selection (J1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
15. Motor Current Selection (J2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
16. Removing Resistor R35 (for low current selection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
17. Current Limit Mode Selection (J3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
18. DC Tach-Generator Voltage Selection (J4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
19. DC Tach-Generator with Addition of RT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ii
20. Run Relay Output Mode Selection (J5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
21. Stop Switch Type Selection (J6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
22. Enable Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
23. ACCEL Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
24. DECEL Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
25. MAX Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
26. MIN Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
27. JOG Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
28. CL Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
29. TCL Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
30. IR Trimpot Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
iii
1
I. INTRODUCTION
Thank you for purchasing the KBPW-240D. KB Electronics, Inc. is committed to providing total customer satisfaction by producing quality products that are easy to install and operate. The KBPW-240D is manufactured with surface mount components incorporating advanced circuit­ry and technology.
The KBPW-240D is a Pulse Width Modulated (PWM) control in a NEMA-4X / IP-65 watertight and washdown enclosure designed to operate PWM and SCR rated Permanent Magnet and Shunt Wound motors ranging from 0.2 Amps DC to 7.5 Amps DC. It operates at a switching frequency greater than 16kHz to provide high motor efficiency and quiet operation.
Special cir­cuitry automatically accepts AC line input voltages of 115 Volts AC to 208/230 Volts AC (±10%, 50/60Hz) without having to make a jumper selection.
Standard panel mounted features include diagnostic LEDs (power on, stop, and overload), Start/Stop switch, and speed potentiometer. Other features include barrier terminal blocks (facilitate wiring of AC line, motor armature, motor field, tach-generator and run relay connec­tions), adjustable trimpots (acceleration, deceleration, maximum speed, minimum speed, jog speed [used with optional Run/Jog switch], current limit, timed current limit and IR Comp.)
i. SAFETY WARNING! Please read carefully
This product should be installed and serviced by a qualified technician, electrician, or electrical maintenance person familiar with its operation and the hazards involved. Proper installation, which includes wiring, mounting in proper enclosure, fusing or other overcurrent protection, and grounding can reduce the chance of electrical shocks, fires, or explosion in this product or products used with this product, such as electric motors, switches, coils, solenoids, and/or relays. Eye protection must be worn and insulated adjustment tools must be used when working with control under power. This product is constructed of materials (plastics, metals, carbon, silicon, etc.) which may be a potential hazard. Proper shielding, grounding, and filtering of this product can reduce the emission of radio frequency interference (RFI) which may adversely affect sensitive electronic equipment. If further information is required on this product, contact the factory. It is the responsibility of the equipment manufacturer and individual installer to supply this Safety Warning to the ultimate end user of this product. (SW effective 11/1992.)
This control contains electronic Start/Stop circuits that can be used to start and stop the control. However these circuits are never to be used as safety disconnects since they are not fail-safe. Use only the AC line for this purpose.
Be sure to follow all instructions carefully. Fire and/or electrocution can result due to improper use of this product.
!
PWM Safety Warning! This control contains a safety circuit which is designed to prevent
full speed runaway in the event the main power transistor fails. However, this safety cir­cuit is not infallible and may itself fail to operate and therefore allow a full speed runaway con­dition to exist. The installer of this product should take proper precautions to include other means to protect the operator or the machine involved (such as mechanical disconnects, warn­ing notices, etc.).
This product complies with all CE directives pertinent at the time of manufacture. Contact the
Sales Department for detailed installation and Declaration of Conformity. Installation of a CE approved RFI filter (KBRF-200A [P/N 9945C] or equivalent) is required. Additional shielded motor cable and/or AC line cables may be required along with a signal isolator (KBSI-240D [P/N 9431] or equivalent).
Electrical Hazard Warning Symbol: Failure to observe this warning could result in electrical shock or electrocution.
Operational Hazard Warning Symbol: Failure to observe this warning could result in serious injury or death.
!
!
Optional accessories include On/Off AC Line Switch, FWD-BRK-REV Switch, Run-Stop-Jog Switch, Signal Isolator, and Anti-Plug Reversing Module. Quick-connect terminals are provid­ed for easy installation of all optional accessories. The control is available in black finish (P/N
8401) and FDA approved white finish (P/N 8402).
STANDARD FEATURES
Short Circuit Protection – Protects control from a short circuit at motor connections.
Electronic Motor Burnout Protection – Timed Current Limit shuts down the control if a pro-
longed overload condition exists.
Active Bridge – Limits the AC line inrush current when power is turned on and also prevents high speed runaway if the power transistor shorts.
Heat Spreader – Allows power transistor to operate safely during momentary overload condi-
tions.
Auto AC Line Select – Control automatically adjusts for 115 or 208/230 Volt AC line input.
Start/Stop Switch – Provides electronic start and stop functions.
Diagnostic LEDs – For power on (ON), stop (STOP) and motor overload (OL).
Trimpots – Provide adjustment for acceleration (ACCEL), deceleration (DECEL), maximum
speed (MAX), minimum speed (MIN), jog speed (JOG), current limit (CL), timed current limit (TCL), and IR compensation (IR).
Selectable Jumpers – Provide settings for armature voltage or tach-generator feedback (J1),
motor current (J2), timed or non-timed current limit (J3), tach-generator voltage (J4), and run relay output (J5).
Barrier Terminal Blocks – Facilitate wiring of AC line, motor armature and field, tach-genera­to, run relay output, and thermal or enable switch.
Quick-Connect Terminals – Facilitate connecting Start/Stop switch, Run-Stop-Jog switch,
FWD-BRK-REV switch, and Inhibit switch.
II. SIMPLIFIED OPERATING INSTRUCTIONS
A. Power Connection –
Connect the AC line to L1 and L2 terminals of TB1 and the ground wire (Earth) to the green ground screw as shown in Figure 3, on page 6, and as described in Section IIIA, on page 6, and Section IIIB, on page 6.
B. Permanent Magnet (PM) Motor Connection (Two-Wire Type) – Connect the motor arma-
ture to A1 (+) and A2 (-) terminals of TB1 as shown in Figure 3, on page 6, and as described in Section IIIC, on page 6. Be sure that jumper J3 is set to the corresponding motor voltage position as described in Section IVA, on page 10.
Do not use F1 and F2 terminals of TB2 for any purpose other than to power the field of a shunt wound motor. Do not use F1 and F2 terminals for PM motors.
Note: Motor performance and efficiency, including brush life, may be adversely affected
when operating the control in stepdown mode (208/230 Volt AC line with 90/130 Volt DC motors).
C. Shunt Wound Motors (Four-Wire Type) – Connect the motor armature as described in
Section IIIC, on page 6. Connect full voltage field wires (90 Volt DC motors with 100 Volt DC field and 180 Volt DC motors with 200 Volt DC field) to F1 (+) and F2 (-) terminals of TB2 as described in Section IIID, on page 7. Connect half voltage field wires (90 Volt DC motors with 50 Volt DC field and 180 Volt DC motors with 100 Volt DC field) to F1 (+) terminal of TB2 and L1 (-) terminal of TB1 as described in Section IIIE, on page 7.
Note: Do not connect motor armature leads to F1 and F2 terminals.
2
IMPORTANT – You must read these simplified operating instructions before proceeding. These instructions are to be used as a reference only and are not intended to replace the detailed instructions provided herein. You must read the Safety Warning, on page 1, before proceeding.
D. Motor Current – Jumper J2 is factory set for 7.5 Amp motors. For lower current motors, set
jumper J2 to the corresponding motor current as described in Section IVB, on page 10.
Note: The factory setting for Current Limit is 150% of the nominal current setting (example: if jumper J2 is set to “5A” position, the CL trimpot is calibrated for 7.5 Amps).
E. Trimpot Settings – All trimpots have been factory set as shown in Figure 1, on page 4.
Trimpots may be readjusted as described in Section VIII, on page 13.
F. Diagnostic LEDs – After power has been applied, observe the LEDs to verify proper con-
trol function as described in Section IX, on page 14.
G. Start/Stop Switch – The control is supplied with a prewired Start/Stop switch as described
in Section IIIG, on page 7. This switch must be used to start the control each time the AC power is lost or the control shuts down due to TCL. To override this function, see Section IIIG, on page 7.
1. For low current operation, remove resistor R35 as described in section IVB, on page 10
2. Step-down operation.
3
115
AC Line Voltage (±10%, 50/60 Hz)
(Volts AC)
Motor Voltage
(Volts DC)
Maximum AC
Line Current (Amps RMS)
Maximum
Load Current
(Amps DC)
Maximum Horsepower
HP, (kW)
SCR Rated
Motors
PWM Rated
Motors
3/4, (0.5)
208 – 230
0 – 90, 130 11.5 7.5 1, (0.75)
Field Voltage
(Volts DC)
200
100
7.5 2, (1.5)11⁄2, (1)11.50 – 180, 260
TABLE 1 – ELECTRICAL RATINGS
0
100
Specification Factory SettingParameter
0 – 50
Operating Frequency (kHz)
0.5 – 10
Operating Temperature Range at Full Rating (ºC)
>16
Current Range (High Scale) (Amps DC)
0 – 50
1.7, 2.5, 3.5, 5.0, 7.5 7.5
Current Range (Low Scale) (Amps DC)
1
ACCEL and DECEL Range (Seconds)
Jog Speed (% Base Speed)
MIN Speed Range (% Base Speed [90VDC & 180VDC Motors])
MAX Speed Range (% Base Speed [90VDC & 180VDC Motors])
IR Comp Range at 90 Volts DC Output (∆Volts DC at Full Load)
IR Comp Range at 180 Volts DC Output (∆Volts DC at Full Load)
CL Range (% Range Setting)
Timed Current Limit (TCL) Range (Seconds)
AC Line Input Voltage (Volts AC, ±10%, 50/60 Hz)
Armature Voltage Range at 115 Volts AC Line Input (Volts DC)
Armature Voltage Range at 208/230 Volts AC Line Input (Volts DC)
Field Voltage at 115 Volts AC Line Input (Volts DC)
Field Voltage at 208/230 Volts AC Line Input (Volts DC)
Speed Range (Ratio) 50:1
0.2, 0.3, 0.4, 0.5, 0.8
0.5 – 10
0 – 30
50 – 140
0 – 15
0 – 30
0 – 200
115 – 208/230
0 – 130
0 – 1302, 0 – 260
100/50
200/100
150
1
15
4
8
5
90
90
Voltage Following Linearity (% Base Speed) ±0.5
TABLE 2 – GENERAL PERFORMANCE SPECIFICATIONS
AC Line Regulation (% Base Speed) 0.5
Armature Feedback Load Regulation (% Base Speed) 1
Tach-Generator Feedback Load Regulation (% Set Speed)
1–
4
FIGURE 1 – CONTROL LAYOUT
(Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings)
START/STOP SWITCH
RED
BLACK
WHITE
VIOLET
ORANGE
MAIN SPEED POTENTIOMETER
WHITE
To LED Board
INH1
INH2START
STOP COM
JOG
P3
P2
P1
J4
50V7V
INH1
INH2
START
COM
STOP
JOG
P3
P2
P1 TB3
K2
K1
T-
T+
EN2
EN1
CON1
J6
STOP
RELAY
TACH
ENABLE
J7
EN
DECELACCEL
NO
NC
RELAY
J5
NC
MINMAX JOG CL IRTCL
NO
TCL NTCL
J3
KBPW-240D
J1
90V
180VT
LH
AMP
J2
0.8
7.5
0.5
5.0
0.43.5
0.3
2.5
0.2
1.7
BLU WHT WHT
BLU
WHT
BLK
J7A
RED
ORN
A2B
A1A
A1B
CON2
TB1
TB2
F1 A1F2 A2 L2L1
A2A
L1B
L1A L2A
J7B
L2B
DECELACCEL MINMAX JOG CL IRTCL
Enlarged view of trimpots
5
FIGURE 2 – MECHANICAL SPECIFICATIONS (INCHES / mm)
127
5.00
241
9.49
5.89
150
5.47
139
0.36
80
60
70
90
OLSTOPON
50
PENTA-DRIVE
40
PWM DC MOTOR SPEED CONTROL
9
100
%
REV
FWD
0
BRK
10
30
20
209
8.23
225
8.88
NEMA-4X / IP-65
RUN
START
JOG
STOP
CONTROL SHOWN WITH OPTIONAL FWD-BRK-REV AND RUN-STOP-JOG SWITCHES
III. WIRING INSTRUCTIONS
WARNING! Read Safety
Warning, on page 1, before using this control. Disconnect the AC line before wiring.
Note: To avoid erratic operation, do not bundle AC line and motor wires with wires from signal following, start/stop switch, inhibit, or any other signal wires. Use shielded cables on all signal wiring over 12” (30cm). Shield should be Earth grounded on the control side only. Wire the control in accordance with the National Electrical Code requirements and other codes that may apply to your area. See Figure 3, Table 3 and Table 4, on page 7.
Be sure to properly fuse each conductor that is not at ground potential. Do not fuse neutral or grounded conductors. See Section VII, on page 13. A separate AC line switch or con­tactor must be wired as a disconnect so that each ungrounded conductor is opened. An acces­sory On/Off AC Line Switch (P/N 9341) may be used in lieu of, or in addition to, the Start/Stop switch. The switch can be wired for single pole or double pole operation, as required.
To maintain the watertight integrity of the control, be sure to use suitable watertight connectors and wiring which are appropriate for the application. Two 7/8” (22.2mm) knockout holes are provided for standard 1/2” knockout connectors (not supplied) for wiring. A watertight plug is provided if only one knockout is required.
Warning! Do not wire switches or relays in series with the armature. Armature switching
can cause catastrophic failure of motor and/or control. To avoid erratic operation, do not bundle AC line and motor wires with potentiometer wires, voltage following wires, Start/Stop switch wires, inhibit wires, or any other signal wires. Use shielded cables on all signal wiring over 12” (30cm) long. Shield should be Earth grounded on the control side only.
Warning! Do not use CON2 for any purpose other than to power the optional Anti-Plug Reversing Module APRM-PC (P/N 9378A).
A. AC Line Connection – Wire AC line input to L1 and L2 terminals of TB1 as shown in
Figure 3.
B. Ground Connection – Earth ground the control chassis using the green ground screw that
is provided on the inside of the control to the right side of TB1 as shown in Figure 3.
C. Permanent Magnet (PM) Motor Connection – Wire the motor armature leads to A1 (+) and
A2 (-) terminals of TB1 as shown in Figure 3. Be sure jumper J1 is set to the appropriate motor voltage and that J3 is set to the appropriate motor current. For step-down operation (230 Volt AC line input with 90 Volt DC SCR rated motor or 130 Volt DC PWM rated motor) set jumper J1 to “90V” position. However, in step-down operation the motor may have reduced brush life - consult motor manufacturer.
6
FIGURE 3 – POWER CONNECTION
3.5
12
Terminal
Block
TB1
TB1
TB2
TB3
Supply Wire Gauge
(AWG - Cu)
TB4
Designation Connections
Maximum
Tightening Torque
(in-lbs)
L1 & L2
A1 & A2
F1 & F2
T+ & T-
K1 & K2
Minimum Maximum
22
22
24
24
24
12
12
14
14
14
12
3.5
3.5
AC Line Input
Motor Armature
Motor Field (Shunt Wound Motors Only)
Tach-Generator
Run Relay
TABLE 3 – TERMINAL BLOCK WIRING INFORMATION
!
TB2
TB1
F2F1
L2A2A1 L1
+
M
-
AC LINE
MOTOR
!
GROUND
(EARTH)
Note: Do not connect motor armature leads to F1 and F2 terminals. Do not use F1 and F2 terminals for PM motors.
D. Full Voltage Field Connection (Shunt
Wound Motors Only) – Wire the motor
field leads to F1 (+) and F2 (-) terminals of TB2 as shown in Figure 4 & Table 4.
Note: Do not connect motor armature leads to F1 and F2 terminals.
Warning! Do not use F1 and F2 ter­minals of TB2 for any purpose other than to power the field of a shunt wound motor.
E. Half Voltage Field Connection (Shunt
Wound Motors Only) – Wire the motor
field leads to F1 (+) and L1 (-) terminals of TB2, as shown in Figure 5 & Table 4.
Note: Do not connect motor armature leads to F1 and F2 terminals.
Warning! Do not use F1 and F2 ter­minals of TB2 for any purpose other than to power the field of a shunt wound motor.
F. Remote Main Speed Potentiometer
Connection –
The control is supplied with a prewired main speed potentiometer mounted on the front cover. To operate the control from a remote potentiometer (5kΩ), remove the white, orange, and violet potentiometer leads from P1, P2, and P3 terminals, respec­tively. The leads may be taped and left inside the control. The potentiometer assembly may be removed if a watertight seal is used to cover the hole in the front cover. Connect the remote main speed potentiometer wires to terminals P1 (low side), P2 (wiper), and P3 (high side) as shown in Figure 6.
G. Remote Start/Stop Switch Connections – The control is supplied with a prewired
Start/Stop switch mounted on the front cover. To operate the control from a remote Start/Stop switch (type: (ON)-OFF-ON, SPDT), remove the white, black, and red wires from START, COM, and STOP terminals, respectively. The leads may be taped and left in the control. The switch itself may be removed if a watertight seal is used to cover the hole
7
FIGURE 4 – FULL VOLTAGE FIELD
FIGURE 5 – HALF VOLTAGE FIELD
Field Connections
F1 & L1
AC Line Voltage
(Volts AC)
Armature Voltage
(Volts DC)
Field Voltage
(Volts DC)
90 – 130115
115
230 180 – 260
230
230
90 – 130
180 – 260
90 – 130
100
50
200
100
100
F1 & F2
F1 & L1
F1 & F2
F1 & L1
TABLE 4 – FIELD CONNECTION (Shunt Wound Motors Only)
FIGURE 6 – REMOTE POTENTIOMETER
TB1
TB2
FIELD
+
-
F1 F2
+
M
-
MOTOR
L2L1A1 A2
AC LINE
TB1
TB2
F1 F2
+
FIELD
-
+
M
-
MOTOR
L2L1A2A1
AC LINE
GROUND
(EARTH)
GROUND
(EARTH)
High Side
Wiper
MAIN SPEED POTENTIOMETER (FRONT VIEW)
Low Side
P3 P2 P1
in the front cover. Connect the remote Start/Stop switch wires to START (momentary), COM (common), and STOP (constant) terminals as shown in Figure 7A. After applying power, momentari­ly set the Start/Stop switch to “START” position. The motor will operate at the set speed of the main speed potentiome­ter. To stop the motor, set the Start/Stop switch to “STOP” position.
For remote 3-wire Start/Stop Switch with normally open start con­tact and normally closed stop contact, see Figure 7B.
For remote 2-wire Start/Stop Switch with normally open start/stop contact, see Figure 7C.
Note: For automatic start when power is applied, the Start/Stop function can be bypassed. This can be accomplished by installing a jumper (provided with control) between the START and COM ter­minals. Jumper J6 must be in the “NO” position. See Figure 8.
CAUTION! Eliminating the Start/Stop function using a jumper will cause the motor to run at the main
speed potentiometer setting when the AC line is applied.
H. Run Relay Connection – Normally open (NO) or normal-
ly closed (NC) relay output contacts are provided at TB4, which will change state when the Start/Stop switch is set to “START” position or if the control shuts down and goes into STOP mode from TCL. The run relay is used to indi­cate the state of the control (run or stop). Normally open or normally closed run relay contact outputs can be select­ed depending on the position of jumper J5. If nor­mally open is selected (J5 in “NO” position), the run relay output contacts will close when the Start/Stop switch is set to “START” position. If nor­mally closed is selected (J5 set to “NC” position), the run relay output contacts will open when the Start/Stop switch is set to “START” position. When the control shuts down and goes into STOP mode from TCL, or the Start/Stop switch is set to “STOP” position, the Run Relay output contacts will return to their normal position.
Note: If relay output contacts are not required for your application, J5 may be in any position.
I. Voltage Following Connection – An isolated 0 - 10 Volt DC analog signal can also be used
to control motor speed. See Figure 9.
8
FIGURE 7A – REMOTE 3-WIRE START/STOP SWITCH
WITH NORMALLY OPEN START CONTACT
AND NORMALLY OPEN STOP CONTACT
FIGURE 9 – VOLTAGE FOLLOWING
N
FIGURE 7B – REMOTE 3-WIRE START/STOP SWITCH WITH
NORMALLY OPEN START CONTACT
AND NORMALLY CLOSED STOP CONTACT
FIGURE 7C – REMOTE 2-WIRE START/STOP SWITCH
WITH NORMALLY OPEN START/STOP CONTACT
FIGURE 8 –START/STOP
FUNCTION ELIMINATED
(JUMPER INSTALLED)
MOMENTARY
CONTACT
MAINTAINED
CONTACT
Start
Stop
START
COM
STOP
J6
STOP
NO
NC
MOMENTARY
NORMALLY OPEN
CONTACT
MOMENTARY
ORMALLY CLOSED
CONTACT
Start
Stop
START COM
STOP
J6
STOP
NO NC
J6
STOP
NO NC
MAINTAINED
NORMALLY CLOSED CONTACT
(CLOSE TO RUN, OPEN TO STOP)
START COM
STOP
!
START COM
STOP
J6
STOP
NO NC
0 - 10V DC
(ISOLATED)
+-
P3 P2 P1
Note: If an isolated signal voltage is not available, an optional signal isolator can be installed (KBSI-240D, P/N 9431). Connect the isolated signal voltage to P2 (+) and P1 (-) terminals. Adjustment of the MIN trim­pot may be necessary to achieve a 0 Volt DC output.
J. Inhibit Connection – The control is supplied with
inhibit terminals (INH1 and INH2) to con­nect an Inhibit switch. See Figure 10. These terminals are used to electronical­ly stop the control. When the Inhibit switch is closed, the control will coast to stop. When the Inhibit switch is opened, the control will accelerate to the main speed potentiometer setting.
Warning! Do not use Inhibit as a safety disconnect. Use only the
AC line for this purpose.
K. Enable Connection –
The Enable is used to electronically start and stop the control. When the Enable contact is closed, the control will accelerate to the Main Speed Potentiometer setting. When the Enable contact is opened, the control will coast to stop. Wire the Enable contacts to Terminals EN1 and EN2 of Terminal Block TB3 as shown in Figure 11. The contacts must be isolated and Jumper J7 must be removed.
Note: The control can also be started and stopped with an Enable contact in the Main Speed Potentiometer circuit. The Enable function is established by wiring a switch in series with the violet Main Speed Potentiometer lead which connects to the P3 terminal. See Figure 12.
Warning! Do not use Enable as a
safety disconnect. Use only the AC line for this purpose. The Enable Circuit is not isolated and is not to be Earth grounded.
L. DC Tach-Generator Connection –
Wire the tach-generator to T+ (+) and T- (-) ter­minals of TB4 as shown in Figure 13. Jumper J1 must be in “T” position. Jumper J4 must be in “7V” position for 7 Volt per 1000 RPM tach-generators or “50V” posi­tion for 50 Volt per 1000 RPM tach-gener­ators. See section IVD on page 11.
Note: When using a tach-generator, the IR trimpot should be set fully counterclockwise.
IV. SETTING SELECTABLE JUMPERS
The KBPW-240D has customer selectable jumpers which must be set before the control can be used. See Figure 1, on page 4 for location of jumpers.
9
FIGURE 10 – INHIBIT CIRCUIT
FIGURE 12 – ENABLE CIRCUIT
USING POTENTIOMETER
FIGURE 13 – DC TACH-GENERATOR
FIGURE 11 – ENABLE CONNECTION
!
!
INHIBIT
(CLOSE TO STOP)
(OPEN TO RUN)
INH1
INH2
TB3
K2
RELAY
K1
T-
T+
EN2
EN1
ENABLE
TACH
(CLOSE TO RUN) (OPEN TO STOP)
ENABLEEN
J7
Note: Jumper J7 must be removed for Enable to operate.
ENABLE (CLOSE TO RUN) (OPEN TO STOP)
Main Speed Potentiometer
Violet
Orange
White
P3 P2 P1
TB3
K2
RELAY
K1
DC TACH-GENERATOR
T-
T+
EN2
EN1
TACH
ENABLEEN
J7
G
10
A. Motor Voltage Selection (J1) – Jumper
J1 is factory set to “90V” position for 90 Volt SCR rated motors (or 130 Volt PWM rated motors). For 180 Volt SCR rated motors (or 220 Volt PWM rated motors), set jumper J1 to “180V” position. See Figure 14.
Note: If jumper J1 is set to “T” position, a tach-generator must be wired to TB3. If a tach-gener­ator is not used, jumper J1 must be in either “90V” or “180V” posi­tion. If jumper J1 is in “T” position and a tach-generator is not used, the motor will accelerate to full speed and the main speed poten­tiometer will not control speed.
B. Motor Current Selection (J2) –
Jumper J2 is factory set to “7.5A” position for 7.5 Amp motors.
For motors of lower amper­age, set Jumper J2 to the corresponding position for the motor being used. See Figure 15 and Table 5.
Note: For low (L) motor current settings (0.8A, 0.5A,
0.4A, 0.3A, and 0.2A), it is necessary to remove resis­tor R35. Cut the leads at the locations shown in Figure 16.
WARNING! Disconnect AC line
before cutting out resistor R35. Use an insulated cutter and wear safety glasses.
FIGURE 16 – REMOVING RESISTOR R35
1/2, (0.37)
SCR Rated Motor Horsepower
HP, (kW)
PWM Rated Motor Horsepower
HP, (kW)
J2 Setting
(Amps DC)
130 Volts DC Motors
1/4, (0.18)
1/2, (0.37)
90 Volts DC Motors 180 Volts DC Motors 220Volts DC Motors
7.5
5.0
3.5
2.5
1.7
0.8*
3/4, (0.5)
1/2, (0.37)
1/3, (0.25)
1/4, (0.18)
1/6, (0.1)
1/12, (0.06)
0.5*
0.4*
0.3*
0.2*
1/20, (0.04)
1/20, (0.04)
11⁄2, (1)
1/25, (0.03)
1/30, (0.02)
1/50, (0.01)
1, (0.75)
3/4, (0.5)
1/3, (0.25)
1/6, (0.1)
1/10, (0.08)
1/12, (0.06)
1/15, (0.05)
1/25, (0.03)
1, (0.75)
3/4, (0.5)
1/2, (0.37)
1/3, (0.25)
1/4, (0.18)
1/8, (0.09)
1/15, (0.05)
1/20, (0.04)
1/25, (0.03)
1/30, (0.02)
2, (1.5)
11⁄2, (1)
1, (0.75)
3/4, (0.5)
1/6, (0.1)
1/8, (0.09)
1/10, (0.08)
TABLE 5 – SETTING MOTOR CURRENT (SCR & PWM Motor Horsepower Ratings)
*Note: For low (L) motor current range settings (0.8A, 0.5A, 0.4A, 0.3A and 0.2A), it is necessary to remove resistor R35 as
shown in figure 16.
FIGURE 14 – MOTOR VOLTAGE SELECTION
*Note: For low (L) motor current range settings (0.8A, 0.5A, 0.4A,
0.3A and 0.2A), it is necessary to remove resistor R35 by cutting it out of the circuit as shown in figure 16 on page 10.
0.2
7.5
5.0
3.5
2.5
1.7
0.8
0.5
0.4
0.3
Low Scale
Current Range*
(Amps DC)
High Scale
Current Range
(Amps DC)
J2 Set for 7.5 Amp Motor
(Factory Setting)
FIGURE 15 – MOTOR CURRENT SELECTION
J1 Set for 90 Volt Motors
(Factory Setting)
J1
T
90V
180V
J1 Set for 180 Volt Motors
J1
T
90V
!
TO REMOVE RESISTOR R35
CUT THE LEADS HERE
R35
D6
D20
TB2
CON2
F1 F2
RED WHT
ORG
J6A A1A A2B
A1B
TB1
WHT WHTBLU BLU
J7B
J7A
BLK
J6B
A2A
L1 L2A2A1
Q4
L2AL1B L2BL1A
Q5
180V
11
C. Timed and Non-Timed Current Limit
Selection (J3) – Jumper J3 is factory set
to “TCL” position for timed current limiting operation. See Figure 17. For non-timed current limiting operation, set jumper J3 to “NTCL” position.
TCL (Timed Current Limit) – When Jumper J3 is in the “TCL” position, the control will go into “STOP” after it is in overload for a predetermined amount of time (set by the TCL trimpot).
Resetting the Control After TCL – To reset the control after it has gone into TCL, momen­tarily set the Start/Stop switch to “START” position or disconnect and reconnect the AC line. If an On/Off AC Line Switch is installed, set it to “OFF” position and then back to “ON” posi­tion. If the Start switch is jumpered (START and COM terminals connected), the control must be restarted by disconnecting and reconnecting the AC line.
NTCL (Non-Timed Current Limit) – When jumper J3 is set to “NTCL” position, the control will not go into “STOP” after it is in overload.
Note: TCL trimpot will have no affect when jumper J3 is in “NTCL” position.
D. DC Tach-Generator Voltage Selection (J1 and J4) – For a tach-generator wired to TB3,
set jumper J1 to “T” position. See Figure 18. Jumper J4 is factory set to “7V” position for 7 Volt per 1000 RPM tach-generators wired to TB3. For a 50 Volt per 1000 RPM tach-gener­ator, set jumper J4 to “50V” position.
Note: When using a tach-generator, the IR trimpot should be set fully counterclockwise. Note: The tach-generator input is designed for 7 Volt or 50 Volt per 1000 RPM tach-gen-
erators used with 1800 RPM motors. For tach-generators other than 7 Volt or 50 Volt per 1000 RPM or for motors other than 1800 RPM, an external 1/2 watt resistor (RT) must be used. Install R
T in series with the tach-generator as shown in Figure 19, on page 12.
Jumper J4 must be set to “7V” position.
The value of RT in Ω can be calculated using the following formula:
RT = (1.46 x VT x S) - 19,000
Where VT is the tach-generator voltage (in Volts per 1000 RPM) and S is the base speed of the motor (in RPM).
FIGURE 17 – CURRENT LIMIT
MODE SELECTION
FIGURE 18 – DC TACH-GENERATOR VOLTAGE SELECTION
Suppose you have a 20 Volt per 1000 RPM tach-generator with a 3600 RPM motor:
RT = (1.46 X 20 X 3600) - 19000 = 86120Ω.
Choose the closest 1/2W resistor value, which is 82000Ω (82kΩ) or 91000Ω (91kΩ). Readjustment of the MAX trimpot may be necessary to achieve the desired maximum output voltage.
Example:
J3 Set for TCL Mode
(Timed Current Limit)
(Factory Setting)
J3 Set for NTCL Mode
(Non-Timed Current Limit)
J3
J3
NTCLTCL
TCL NTCL
Jumper J1 Settings Jumper J4 Settings
J1 Set for 90 Volt Motors
(Factory Setting)
J1
T
180V
90V
J1 Set for
Tach-Generator Input
J1
T
180V
90V
J4 Set for 7V per 1000RPM
Tach-Generator Input
(Factory Setting)
J4 J4
50V
J4 Set for 50V per 1000RPM
Tach-Generator Input
50V
7V7V
E. Run Relay Output Mode Selection (J5)
Jumper J5 is factory set to “NO” position
for normally open relay output at TB4. For normally closed relay output, set jumper J5 to “NC” position. See Figure 20.
F. Stop Switch Type Selection (J6) –
Jumper J6 is factory set to the “NO” position for a normally open stop switch, as used on the front cover. If a remote normally closed stop switch is used, set Jumper J6 to the “NC” position. If a remote normally open stop switch is used, set Jumper J6 to the “NO” position. See Figure 21.
G. Enable Selection (J7) – Jumper J7 is fac-
tory installed to enable the control. If con­necting Enable contacts to Terminals EN1 and EN2 of Terminal Block TB3, remove Jumper J7. See Figure 22.
V. MOUNTING INSTRUCTIONS
Warning! The KBPW-240D is not designed to be used in an explo-
sion-proof application.
It is recommended that the control be mount­ed vertically on a flat surface with adequate ventilation. Leave enough room below the control to allow for AC line, motor connec­tions, and any other wiring. Although the control is designed for outdoor and wash­down use, care should be taken to avoid extreme hazardous locations where physi­cal damage can occur. If the control is mounted in a closed, unventilated location, allow enough room for proper heat dissipa­tion. If operating the control at full rating, a minimum enclosure size of 12”W x 24”H x 12”D is required. See Figure 2, on page 5.
The KBPW-240D is designed with a hinged case so that when the front cover is open, all wiring stays intact. To open the cover, the four screws must be loosened so they are no longer engaged in the case bottom. After mounting and wiring, close the cover and make sure that wires will not get caught or crimped as the cover is closed. Tighten all four cover screws so that the gasket is slightly compressed.
Do not over tighten.
VI. OPERATION
Caution!
It is recommended that the bus capacitors be reconditioned if this product has been in storage for over one year. To recondition the capac­itors, apply the AC line, with the drive in Stop Mode, for a minimum of one hour.
After the control has been properly set up (jumpers set to desired positions and wiring com­pleted), the startup procedure can begin. If AC power has been properly brought to the con­trol, the ON and STOP LEDs will be illuminated. Before starting, be sure the main speed
12
FIGURE 19 – DC TACH-GENERATOR
WITH ADDITION OF RT
FIGURE 20 – RUN RELAY OUTPUT
MODE SELECTION
FIGURE 21 – STOP SWITCH
TYPE SELECTION
FIGURE 22 – STOP SWITCH
TYPE SELECTION
TB3
K2
K1
T-
T+
EN2
EN1
RELAY
DC TACH-GENERATOR
G
TACH
R
ENABLEEN
J7
!
J5 Set for Normally Open
(NO) Output Contacts
(Factory Setting)
J5
J5 Set for Normally Closed
(NC) Output Contacts
J5
NONC
NC NO
J6 Set for
Normally Open Stop Switch
(Factory Setting)
J6
NO NC
STOP
J6 Set for
Normally Closed Stop Switch
J6
STOP
J7 Installed to
Enable the Control
(Factory Setting)
EN
J7 Removed to
Connect Enable Contacts
J7
T
NO NC
J7
EN
potentiometer is fully counterclockwise. To start the control, momentarily set the Start/Stop switch to “START” position and release it. The STOP LED should no longer illuminate. The motor should begin to rotate, as the main speed potentiometer is rotated clockwise.
Note: If the motor rotates in the incorrect direction, it will be necessary to disconnect the AC line, reverse the motor leads, and repeat the startup procedure.
VII. AC LINE FUSING
This control does not contain AC line fuses. Most electrical codes require that each unground­ed conductor contain circuit protection. Installation of a 20 Amp fuse or circuit breaker in series with each ungrounded conductor is recommended. Check all electrical codes that apply to the application.
VIII. TRIMPOT ADJUSTMENTS
The KBPW-240D contains trimpots, which are factory set for most applications. The trimpots are shown in the approximate calibrat­ed positions. Some applications may require readjustment of the trimpots in order to tailor the control for a specific requirement. Readjust trimpots as described below.
Warning! If possible, do not adjust trimpots with
main power applied. If adjustments are made with main power applied, an insulated adjustment tool must be used and safety glasses must be worn. High voltage exists in this control. Fire and/or electrocution can result if caution is not exercised. Safety Warning, on page 1, must be read and understood before proceeding.
A. Acceleration (ACCEL) –
Sets the amount of time for the motor to accelerate from minimum speed to maximum speed. The ACCEL trimpot is factory set for one (1) second, as shown in Figure 23. For more rapid acceleration time, rotate the trimpot counterclockwise. For longer acceleration time, rotate the trimpot clockwise.
Note: Rapid acceleration settings may cause the current limit circuit to activate, which will extend the acceleration time.
B. Deceleration (DECEL) – Sets the amount of time for the
motor to decelerate from maximum speed to minimum speed. The DECEL trimpot is factory set for one (1) second, as shown in Figure 24. For more rapid deceleration time, rotate the trimpot counterclockwise. For longer deceleration time, rotate the trimpot clockwise.
Note: Deceleration time will not be shorter than the maximum coast time of the motor under actual load.
C. Maximum Speed (MAX) – Sets maximum speed of the
motor. The MAX trimpot is factory set for 100% of base motor speed, as shown in Figure 25. For a higher maximum speed setting, rotate the trimpot clockwise. For a lower maximum speed setting, rotate the trimpot counterclockwise.
D. Minimum Speed (MIN) – Sets minimum speed of the motor.
The MIN trimpot is factory set for 0% speed, as shown in Figure 26. For a higher minimum speed setting, rotate the trimpot clockwise
13
FIGURE 23 – ACCEL
TRIMPOT RANGE
FIGURE 24 – DECEL
TRIMPOT RANGE
5
FIGURE 25 – MAX TRIMPOT RANGE
FIGURE 26 – MIN
TRIMPOT RANGE
!
5
1
0.5 10
Seconds
5
1
0.5 10
Seconds
95
100
0 140
% Base Speed
15
030
% Base Speed
E. Jog Speed (JOG) – Sets “jog” speed of the motor. The JOG
trimpot is factory set for 15% of motor base speed, as shown in Figure 27 . For a higher jog setting, rotate the trimpot clockwise. For a lower jog setting, rotate the trimpot counter­clockwise.
Note: The Jog feature requires installation of the Run-Stop-Jog Switch assembly (P/N 9340).
F. Current Limit (CL) – Sets current limit (overload), which limits
the maximum current to the motor. The current limit set point is established by the setting of jumper J2 and the setting of the CL trimpot. The CL trimpot is factory set for 150% of J2 range set­ting, as shown in Figure 28. For a higher current limit setting, rotate the trimpot clockwise. For a lower current limit setting, rotate the trimpot counterclockwise. Two modes of current lim­iting operation are provided: Non-Timed Current Limit (NTCL) and Timed Current Limit (TCL). See Section IVC, on page 11.
CAUTION! Adjusting the CL above 150% of motor rating can cause overheating and demagnetization of some PM motors. Consult the motor manufacturer. Do not leave the motor in a locked condition for more than a few seconds since armature damage may occur.
G. Timed Current Limit (TCL) – Sets the time for the control to
shut down after being in current limit (provides electronic motor overload protection). The TCL trimpot is factory set for 5 sec­onds, as shown in Figue 29. For increased TCL time, rotate the trimpot clockwise. For decreased TCL time, rotate the trimpot counterclockwise. If the control remains in CL for a predeter­mined amount of time (set by the TCL trimpot and if jumper J3 is in the “TCL” position), the control will shut down. To reset the control after it has shut down, momentarily set the start/stop switch to the “START” position or disconnect and then recon­nect the AC line.
Warning! When the control shuts down in TCL, the AC line voltage is still present in the control.
H. Non-Timed Current Limit (NTCL) – When jumper J3 is set to
“NTCL” position and an overload condition exists, the control will remain in current limit and will not shut down.
I. IR Compensation (IR) – Sets the amount of compensating
voltage required to keep the motor speed constant under changing loads. The IR trimpot is factory set for 4 Volts (for 90 Volt DC output) and 8 Volts (for 180 Volt DC output), as shwon in Figue 30. For higher compensating voltage, rotate the trimpot clockwise. For lower compensating voltage, rotate the trimpot counterclockwise.
Note: If the IR compensation is set too high, unstable (oscillatory) operation will result. If the control is used with a tach-generator, the IR trimpot should be set fully counterclockwise.
IX. DIAGNOSTIC LEDs
The KBPW-240D is designed with LEDs mounted on the front cover to display the control’s operational status.
A. Power On (ON) – The ON LED will illuminate green when the AC line is applied to the
control.
Note: When removing power to the control, the POWER LED will remain illuminated for a few seconds until the DC bus voltage discharges.
14
FIGURE 27 – JOG TRIMPOT RANGE
FIGURE 28 – CL
TRIMPOT RANGE
FIGURE 29 – TCL TRIMPOT RANGE
4
FIGURE 30 – IR
TRIMPOT RANGE
25
15
050
% Base Speed
100
0 200
% Range Setting
5
0.5 10
Seconds
!
7.5, 15
, 8
0 15, 30
Volts
150
B. Stop (STOP) – The STOP LED will illuminate yellow when the Start/Stop switch is set to
“STOP” position. When AC line is applied, this LED will also be illuminated until the Start/Stop switch is set to “START” position.
C. Overload (OL) – The OL LED will illuminate red when the control goes into current limit, indi-
cating that the current limit set point has been reached (set by the CL trimpot and the posi­tion of jumper J2). This LED will remain illuminated if the control times out in TCL (jumper J3 set to “TCL” position). The control can be reset by either setting the start/stop switch to “START” position or by disconnecting and reconnecting the AC line. If the overload condi­tion still exists when the control is restarted or AC line reapplied, the OL LED will illuminate again. If the OL LED remains illuminated during control operation, a fault condition may exist. Possible causes for this condition are as follows:
• Motor is overloaded. Check motor current. If the motor is a shunt wound type, the field
may be open or not receiving proper voltage.
• Motor may be defective. Check motor for shorts or grounds.
• CL may be set too low. Check position of CL trimpot and setting of jumper J2.
Note: In some applications, especially those requiring the motor to cycle on and off, or from one speed to another, or from stop to high speeds, the OL LED may blink, indicating a transient overload. This may be a normal condition for the application.
X. OPTIONAL ACCESSORIES
Complete instructions and connection diagrams are supplied with all accessories to facilitate installation.
A. On/Off AC Line Switch (P/N 9341) – Disconnects the AC line. Mounts on the enclosure
cover and is supplied with a switch seal to maintain watertight integrity.
B. FWD-BRK-REV Switch (P/N 9339) – Provides motor reversing and dynamic braking. This
switch is equipped with a center off hesitation mechanism, which assures that the motor is fully stopped before it can be reversed. Mounts on the enclosure cover and is supplied with a switch seal to maintain watertight integrity.
C. Run-Stop-Jog Switch (P/N 9340) – Selects speed setting from either main potentiometer
or JOG trimpot. Mounts on the enclosure cover and is supplied with a switch seal to main­tain watertight integrity.
D. Signal Isolator KBSI-240D (P/N 9431) – Provides isolation from non-isolated signal
sources. Mounts on the inside of the enclosure cover.
E. Auto/Manual Switch (P/N 9377) – When used with the KBSI-240D (P/N 9431), it selects
either an isolated signal from the KBSI-240D or from the main speed potentiometer. Mounts on the enclosure cover and is supplied with a switch seal to maintain watertight integrity.
F. Anti-Plug Reversing Module APRM-PC (P/N 9378A) – Provides electronic braking and
reversing. Mounts on the inside of the enclosure cover.
Note: For use with this control, the APRM-PC must be Revision A or newer.
G. RFI Filters and Chokes – RFI Filters and Chokes are available to provide suppression for
conducted radio frequency interference (RFI). They comply with the CE Directive 89/336/EEC relating to the EMC Class A Industrial Standard and Class B Residential Standard. See RFI Filters and Chokes Selection Guide (Publication No. D-321).
15
– NOTES –
16
XI. LIMITED WARRANTY
For a period of 18 months from the date of original purchase, KB Electronics, Inc. will repair or replace, without charge, devices which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized per­sons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. The foregoing is in lieu of any other warranty or guarantee, expressed or implied. KB Electronics, Inc. is not responsible for any expense, including instal­lation and removal, inconvenience, or consequential damage, including injury to any person, caused by items of our manufacture or sale. Some states do not allow certain exclusions or lim­itations found in this warranty and therefore they may not apply to you. In any event, the total liability of KB Electronics, Inc., under any circumstance, shall not exceed the full purchase price of this product. (rev 2/2000)
(A40360) – Rev. B – 8/2002
KB Electronics, Inc.
12095 NW 39th Street, Coral Springs, FL 33065-2516 • (954) 346-4900 • Fax (954) 346-3377 Outside Florida Call TOLL FREE (800) 221-6570 • E-mail – info@kbelectronics.com www.kbelectronics.com
Copyright © 2002 by KB Electronics, Inc.
All rights reserved. In accordance with the United States Copyright Act of 1976, no part of this publication may be reproduced in any form or by any means without permission in writing from KB Electronics, Inc. (8/22/02)
Loading...