Honeywell TH8320U, TH8321U User Manual

Page 1
TH8320U and TH8321U Touch Screen
Programmable Thermostats
INSTALLATION INSTRUCTIONS

APPLICATION

The TH8320U and TH8321U Touch Screen Universal Programmable Thermostats provide electronic control of 24 Vac heating and cooling systems or 750 mV heating system. See Table 1 for a general description.
Table 1. TH832 Thermostats Description.
Model
TH8320U Batteries or
TH8321U System and Fan selection
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
Power
Method Changeover System Selection Fan Selection Comments
common wire
Automatic or manual selectable
Heat-Off-Cool­Auto (Em. Heat for heat pumps)
On-Auto-Circ System and Fan selection
vary based on system type
vary based on System type. Humidity sensor to control dehumidification.

Selecting Location

Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
® U.S. Registered Trademark Copyright © 2004 Honeywell International Inc. • • All Rights Reserved
NO
NO
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Selecting thermostat location.
M19925
69-1706
Page 2
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
CO
L
SC
S
H
UMP
S1
2
C
G
C
Do not install the thermostat where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall
behind the thermostat.

Installing Wallplate

CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Position and level the wallplate (for appearance only).
2. Use a pencil to mark the mounting holes.
WALL
WIRES THROUGH WALL AND WIRE SLOT
WALL ANCHORS (2)
MOUNTING HOLES (2)
MOUNTING SCREWS (2)
Fig. 2. Mounting wallplate.
3. Remove the wallplate from the wall and, if drywall,
drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.
5. Insert the mounting screws into the holes and tighten.
M19916
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
EAT P NVENTIONA
Y2
L
E
AUX
S1
S2
Fig. 3. Selecting terminal identifications for
Table 2. Selecting Terminal Identifications for
W2
S
system type.
System Type.
System Type
R
W
Y
REW TERMINAL
Wallplate
Terminal
Identifications
RC
R
O/B
Y
G
C
M19951
Wiring
Diagram
Reference
Standard Heat/Cool Conventional 5, 6
Heat Only Conventional 7
Heat Only with Fan Conventional 8
Heat Only Series 20 Conventional 9
Cool Only Conventional 10
Standard Multistage up to 2 Heat/2 Cool
Heat Pump with No Auxiliary Heat
Heat Pump with Auxiliary Heat
Conventional 11, 12
Heat Pump 13, 14
Heat Pump 15, 16

WIRING (FIG. 5-16)

All wiring must comply with local electrical codes and ordinances.
1. Select set of terminal identifications (Table 2) that corresponds with system type (conventional or heat pump in Fig. 3).
2. Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.
69-1706 2
Fig. 4. Inserting wires in terminal block.
IMPORTANT
Use 18 gauge thermostat wire.
M19917
Page 3
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
CONVENTIONAL
RC
Y2
W2 S1
S2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 5. Typical hookup of conventional single-stage
heat and cool system with single transformer
Y2
W2 S1
S2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
REMOVE FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
2
R
W
Y
G
C
CONNECTION
FAN
RELAY
COMPRESSOR
CONTACTOR
HEAT RELAY
(1H/1C conventional).
CONVENTIONAL
RC
2
R
W
Y
G
C
CONNECTION
FAN
RELAY
COMPRESSOR
CONTACTOR
HEAT RELAY
OPTIONAL
24 VAC
COMMON
OPTIONAL
24 VAC
COMMON
M19895
M19896
CONVENTIONAL
RC
1
R
C
Y2
W2 S1
S2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 7. Typical hookup of heat-only system
Y2
W2
1
R
C
1
C
R
OUTDOOR/INDOOR
1
2
3
S1 S2
3
TEMPERATURE
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 8. Typical hookup of heat only system with fan
2
R
W
Y
G
C
HEAT RELAY
(1H conventional).
CONVENTIONAL
RC
2
R
W
Y G C
FAN
RELAY
HEAT RELAY
(1H conventional).
CONNECTION
OPTIONAL
24 VAC
COMMON
OPTIONAL
24 VAC
COMMON
CONNECTION
1
R
C
M19897
1
R
C
M19898
Fig. 6. Typical hookup of conventional single-stage
heat and cool system with two transformers
(1H/1C conventional).
3 69-1706
Page 4
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
C
G
CS2S1
CO
L
CONVENTIONAL
RC
Y2
W2 S1
S2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
2
R
W
Y
G
C
W BR
SERIES 20
MOTOR OR
TR
TR
1
VALVE
M19899
Fig. 9. Typical hookup of heat only Series 20 system.
NVENTIONA
R
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY 2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
COOL RELAY 2 COOL RELAY 1
HEAT RELAY 1
R
C
CONVENTIONAL
RC
Y2
W2 S1
S2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 10. Typical hookup of cool only system
COMMON CONNECTION
MUST COME FROM
2
R
W
Y G C
RELAY
COMPRESSOR
CONTACTOR
(1C conventional).
OPTIONAL 24 VAC
THE COOLING
TRANSFORMER.
FAN
OPTIONAL
24 VAC
COMMON
CONNECTION
FAN RELAY
M19901
1
R
C
M19900
1
R
C
Fig. 11. Typical hookup of conventional multistage two-stage heating and two-stage cooling
in a single transformer system (2H/2C or 2H/1C or 1H/2C conventional).
69-1706 4
Page 5
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
C
G
CS2S1
CO
L
C
O/
G
C
UX
SI
S2
P
3
COMMON CO
ON
NVENTIONA
R
OPTIONAL 24 VAC
COMMON CONNECTION
MUST COME FROM
THE COOLING
TRANSFORMER.
OUTDOOR/INDOOR
3
TEMPERATURE
SENSOR
HEAT RELAY 2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER REMOVED.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABL
3
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 12. Typical hookup of conventional multistage two-stage heating and two-stage cooling
in a two-transformer system (2H/2C or 2H/1C or 1H/2C conventional).
COOL RELAY 2 COOL RELAY 1
HEAT RELAY 1
FAN RELAY
HEAT PUM
R
1
R
C
M19902
1
R
C
1
R
C
B
A
OPTIONAL 24 VAC
NNECTI
OUTDOOR/INDOOR
4
TEMPERATURE
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
FACTORY INSTALLED JUMPER.
2
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
4
FROM THE THERMOSTAT CABLE.
CHANGEOVER
VALV E
Fig. 13. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).
5 69-1706
FAN RELAY
COMPRESSOR
M19903
Page 6
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
C
O/
G
C
UX
SI
S2
P
3
COMMON CO
ON
O/
G
C
UX
SI
S2
P
6
5
COMMON CO
ON
HEAT PUM
R
B
A
OPTIONAL 24 VAC
NNECTI
OUTDOOR/INDOOR
TEMPERATURE
5
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
FACTORY INSTALLED JUMPER.
2
MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24 VAC
3
OUTPUT. SEE "L TERMINAL" SECTION FOR MORE INFORMATION.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
5
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
CHANGEOVER
VALV E
Fig. 14. Typical hookup of multistage heat pump with no auxiliary/backup heat (2H/2C heat pump).
HEAT PUM
FAN RELAY
COMPRESSOR 1COMPRESSOR 2
EQUIPMENT
MONITOR
M19904
1
R
C
1
R
C
A
3
OUTDOOR/INDOOR
TEMPERATURE
4
SENSOR
HEAT 2 RELAY
(AUXILIARY HEAT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
FACTORY INSTALLED JUMPER.
2
OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
4
FROM THE THERMOSTAT CABLE.
MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
5
A 24 VAC OUTPUT. SEE "L TERMINAL" SECTION FOR MORE INFORMATION.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
6
Fig. 15. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
69-1706 6
EMERGENCY
HEAT RELAY
B
CHANGEOVER
VALV E
OPTIONAL 24 VAC
NNECTI
FAN RELAY
COMPRESSOR
RELAY
M19905
Page 7
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
O/
G
C
UX
SI
S2
P
6
5
COMMON CO
ON
HEAT PUM
EQUIPMENT
MONITOR
B
A
OPTIONAL 24 VAC
NNECTI
OUTDOOR/INDOOR
3
TEMPERATURE
4
SENSOR
HEAT 2 RELAY
(AUXILIARY HEAT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
FACTORY INSTALLED JUMPER.
2
OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
4
FROM THE THERMOSTAT CABLE.
MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
5
A 24 VAC OUTPUT. SEE "L TERMINAL" SECTION FOR MORE INFORMATION.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
6
EMERGENCY
HEAT RELAY
COMPRESSOR 2 COMPRESSOR 1
CHANGEOVER
VALV E
FAN RELAY
Fig. 16. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).

Powering the Thermostat

There are two different ways to power the thermostat:
• Batteries (three AAA alkaline).
• 24 Vac Common wire.
M19906
1
R
C
Wiring 24 Vac Common
Wire the common side of the transformer to the C screw of the thermostat wallplate. When installing in a single transformer system, keep jumper wire between the R and Rc screws. When installed in a two-transformer system, use the common from the cooling transformer to connect to C screw and remove the jumper wire between the R and Rc screws.
Inserting Batteries (Optional)
If not using a 24 Vac Common to power the thermostat, install three AAA alkaline batteries (included) in the back of the thermostat. Make sure the positive and negative terminals are oriented correctly, as marked on the device. See Fig.17.
BATTERIES (3)
M19918
Fig. 17. Installing batteries on thermostat back.

Mounting the Thermostat

1. Align the terminal screw blocks with the pins on the back of the thermostat.
2. Push the thermostat straight onto the wallplate. See Fig. 18.
7 69-1706
Page 8
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
E
MON
UE
THUSASUN
E
MON
THUSASUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
USE ARROWS TO SET YEAR AND TIME
R
U
WALL
INSTALLATION
REMOVE DURING
M19919
Fig. 18. Mounting thermostat on wallplate.

Adjusting Real-Time Clock

Setting Calendar and Time
Locate and remove the tab labeled Remove in the lower left corner on the thermostat back. The tab must be removed to activate the real-time clock. See Fig. 19.
REMOVE TAB TO ACTIVATE REAL TIME CLOCK
INSTALLATION
REMOVE DURING
INSTALLATION
REMOVE DURING
M19920
Fig. 19. Removing tab to activate real-time clock.
This thermostat is designed to automatically keep the current time and day in memory for up to ten years under normal use once the calendar is set. When the thermostat is first powered, the display is ready for the calendar date to be entered. See Fig. 20.
SET CURRENT DAY SET MONTH
T
DON
DON
M19921
Fig. 20. Setting calendar and time after initial
IMPORTANT
The tab on the back of the thermostat in the lower left corner must be removed for this feature to be active.
powerup.

Using the Thermostat

The thermostat has a touch screen interface. Words or symbols appear, highlighting the keys, as necessary, to complete tasks. Always press the keys with your finger­tips. Sharp instruments like a pen or pencil point can damage the thermostat.
1. Use the arrow keys to set the Year, Month and Day, as shown in Fig. 20.
2. Press the Done key.
3. Use the arrow keys to set the current time. See
Fig. 20.
4. Press the Done key.
69-1706 8
Page 9
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
E
MON
UE
THUSASUN
SYSTEM
OFF
COOL
g
Schedule
de
Se
o

OPERATION

System and Fan Settings
The System default setting is Heat and the Fan default setting is Auto.
SYSTEM SETTINGS
Heat: Thermostat controls heating system. Off: Both heating and cooling are off. Cool: Thermostat controls cooling system. Auto: Thermostat automatically changes between heating and cooling systems, depending on indoor temperature. (See Installer Setup section.) Em Heat: Emergency heat cycles to maintain temperature. Compressor is locked out. (Used only for heat pump systems with backup heat.)
FAN SETTINGS
The Fan setting can be programmed into the thermostat schedule for each period (Wake, Leave, Return, Sleep). See the Owners’ Guide for additional information.
LED Indication (Requires 24 Vac Common Connection)
An LED indicator is located in the upper right corner of the thermostat. It is only visible when lighted:
• It indicates when the thermostat is in the Emergency Heat mode. When in Em. Ht. mode, the L terminal is continuously energized and the LED is on.
• When the L terminal is wired to an equipment monitor, the LED signals when a check or fail signal is sent to the thermostat from the system. See Fig. 21. (This can occur only when the thermostat is not in Em. Ht. mode.)
C
EQUIPMENT
MONITOR
L TO R
Fig. 21. L terminal switch to R (power) side of system
transformer.
TO C
M19907

INSTALLER SETUP

This Universal Thermostat works with many different system types. To operate correctly, the thermostat must be set up to operate the installed heating and/or cooling system.

Installer Setup Menus

Main Menu: Offers the most commonly used options.
It is necessary to enter this menu to set the thermostat to the type of system it is operating. Many applications use only the Main Menu.
Regional Menu: Offers choices often changed due to a particular area or region. For example, temperature display in Fahrenheit or Celsius is offered in this menu.
Advanced Settings Menu: Offers more settings to fully customize the thermostat. Many of these settings do not require changing from the factory settings.
Entering Installer Setup
1. Thermostat must be powered either with Alkaline AAA batteries or with 24 Vac Common wire.
2. From the home screen, press System key. (Press Done or Cancel key to return to home screen.)
3. Five blank touch keys show on the bottom of the screen between the Done and Cancel keys. Press and hold the two blank keys on either side of the center blank key for approximately five seconds until screen changes. See Fig. 22.
T
Insi
DON
t T
Followin
CANCEL
Preprogrammed Settings
Table 3 shows the default program settings. See Owners’ Guide for complete instructions on changing the program.
Table 3. Default Program Settings.
70 (21
62 (16.5
70 (21
62 (16.5
Setpoints
°
F
°
C)
°
F
0
C)
°
F
°
C)
°
F
°
C)
°
78 (25.5
°
85 (29.5
°
78 (25.5
°
82 (28
F
F
F
F
°
C)
Schedule
Period Time
Wake 6:00AM
Leave 8:00AM
Return 6:00PM
Sleep 10:00PM
M19923
Fig. 22. Entering Installer Setup.
Fan
SettingHeat Cool
Auto
°
C)
Auto
0
C)
Auto
°
C)
Auto
9 69-1706
Page 10
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
DONE
MON
THUSASUN
A
4. The Installer Setup Number is displayed in the lower left. It is a four-digit code beginning with zero. The factory setting or other choice selection is dis­played in the lower right. See Fig. 23. This is a two­digit code shown in the Option column of Table 4.
ADVANCE TO NEXT
INSTALLER SETUP NUMBER
PRESS TO EXIT INSTALLER SETUP
Fig. 23. Installer Setup Number and factory setting
selection locations.
INSTALLER SETUP
FACTORY SETTING
CHANGE THE FACTORY SETTING
M19922
Changing Installer Setup Selections
1. Advance to the next Installer Setup Number by pressing the up and down arrow keys to the right of the four-digit Installer Setup Number. See Fig. 23.
2. Change the factory Setting Options by pressing the up and down arrow keys to the right of the two-digit code selection. See Fig. 23.
Exiting Installer Setup
1. Press the Done key to exit the Installer Setup screen.
IMPORTANT
The three Installer Setup Menus (Tables 4-6) show all the available options. These options customize themselves as you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are available to change.
Table 4. Main Installer Setup Menu.
Factory Setting Other Choices
Installer
Select
Setup
Number
Not used. 1 thru 0099 —
Date (Year Upper)
Date (Year Lower)
Date (Month) 0140 6 Digit(s) represents
Date (Day)
Schedule Options
0120 20 Set first two digits of
0130 04 Represents last two
0150 15 Digit(s) represents
current calendar year (20 for year 2005, etc)
digits of current calendar year (2004).
current calendar month.
current calendar date.
21 21 —first two digits of
00 -99 Select last two digits of
1-12 Select number that
1-31 Select number that
current calendar year (21xx)
current calendar year.
represents current calendar month.
represents current calendar date.
0160 4 7-day programming 0 0 —nonprogrammable
CommentsOption Description Options Description
2000 -2178 available
2001-2178 available
69-1706 10
Page 11
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 4. Main Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
System Type Selection
Fan Operation 0180 0 Conventional
Reversing Valve (O/B) Operation
Backup Heat Source (Auxiliary Heat)
External Fossil Fuel Kit
Cycles per hour (cph) for 1st Stage Compressor
Cycles per hour (cph) for 2nd Stage Compressor
Setup
Number
0170 1 1 Heat/1Cool 1-12 1— 1 h e a t / 1 c o o l
applications where equipment controls fan operation in heat mode.
0190 0 O/B terminal is
0200 0 Heat pump backup
0210 1 External fossil fuel kit
0220 3 Compressor Stage 1
0230 3 Compressor Stage 2
energized for reversing valve in cooling
heat source is electric.
is controlling heat pump backup heat
cycles per hour (cph)
cycles per hour (cph)
2—single-stage heat p u m p ( n o a u x . h e a t )
3— h e a t o n l y ( n o f a n ) 4— h e a t o n l y ( w i t h f a n ) 5—hot water Series 20
(3-wire or normally open z o n e v a l v e s )
6— c o o l o n l y 7—2 heat/1cool heat
pump 8—2 heat/2 cool multistage conventional 9—2 heat/1cool multistage conventional 10—1 heat/2 cool multistage conventional 11—2 heat/2 cool heat pump (with no auxiliary hea t) 12—3 heat/2 cool heat pump (with auxiliary heat)
1 Heat pump or electric
1 O/B terminal is energized
1 Heat pump backup heat
0 No external fossil fuel kit
1-6 1-6 available;
1-6 1-6 available;
heat applications where thermostat controls fan operation in heat mode.
for reversing valve in heating
source is fossil fuel.
is controlling heat pump backup heat. This thermo­stat controls the backup fossil fuel heat with outdoor sensor (C7089U).
3 is recommended.
3 is recommended.
CommentsOption Description Options Description
Available options and defaults vary by thermo­stat. System selection automatically modifies some default settings and/ or hides other Installer Set­up options.
Only shown if conventional system is selected. If heat pump is chosen, fan defaults to electric.
Only shown if heat pump system is chosen.
Only shown if 2 heat/1 cool or 3 heat/2 cool heat pump is chosen.
Only shown if fossil fuel is chosen as backup heat source.
Only shown if two stages of cool are selected.
11 69-1706
Page 12
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 4. Main Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Select
Cycles per hour (cph) for 1st Stage Conventional Heat
Cycles per hour (cph) for 2nd Stage Heat
Setup
Number
0240 5 Conventional Heat
0250 5 Cycles per hour (cph)
Stage 1 cycles per hour (cph)
for 2nd Stage Conventional Heat or Auxiliary Heat for 2 H/1C Heat Pump Systems
1-12 1-12 available; typical
1-12 1-12 available; typical
s e t t i n g s : 1—1 cph used for steam o r g r a v i t y s y s t e m . 3—3 cph used for hot water systems or high efficiency (90% or better) fossil fuel forced air s y s t e m s. 5—5 cph used for standard fossil fuel forced air systems. 9—9 cph used for electric forced air heat systems.
s e t t i n g s : 1—1 cph used for steam or gravity system. 3—3 cph for hot water systems or high efficiency (90% or better) fossil fuel forced air systems. 5—5 cph for standard fossil fuel forced air s y s t e m s. 9—9 cph used for electric forced air heat systems (electric auxiliary heat for heat pump systems).
CommentsOption Description Options Description
Not shown if system selection is heat pump. Selection in this stage changes default cph for 2nd stage heat.
Only shown if two stages of heat are selected.
69-1706 12
Page 13
Select
Cycles per hour (cph) for 3rd Stage Heat
Cycles per hour (cph) for Em Heat
Continuous Backlight
Additional Menu Choices
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 4. Main Installer Setup Menu. (Continued)
Factory Setting Other Choices
Installer
Setup
Number
0260 9 Cycles per hour (cph)
0270 9 Cycles per hour (cph)
0280 0 Backlight not on
0290 0 Only main menu
for Auxiliary Heat in 3H/2C Heat Pump Systems
for Emergency Heat
continuously. Thermostat backlight comes on with each key press.
options are shown. Installer Test Options shown next (Table 7).
1-12 1-12 available; typical
1-12 1-12 is available; typical
1 Backlight is on
1,2 1—Main Menu and
s e t t i n g s : 1—1cph for steam or g r a v i t y s y s t e m . 3—3 cph for hot water systems or high efficiency (90% or better) fossil fuel forced air systems. 5—5 cph for standard fossil fuel forced air s y s t e m s . 9—9 cph for electric forced air heat systems. (electric auxiliary heat for heat pump systems).
s e t t i n g s : 3—3 cph for hot water systems or high efficiency (90% or better) fossil fuel f o r c e d a i r s y s t e m s . 5—5 cph for standard fossil fuel forced air s y s t e m s . 9—9 cph for electric heat systems.
continuously (thermostat must have a common wire attached for this function).
Regional Settings are shown plus Installer Test (Tables 5 and 7 only).
2—All remaining Menu/ Options shown plus Installer Test (Tables 5, 6 and 7).
CommentsOption Description Options Description
Only shown if 3H/2C heat pump system is selected.
Only shown if 2 heat/1 cool or 3 heat/2 cool heat pump is selected.
Option is always shown; however, continuously on backlight works only if thermostat is wired with 24 vac Common.
The majority of application require only the Main Menu Options.
13 69-1706
Page 14
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 5. Regional Settings Menu.
Installer
Select
Setup
Number
Changeover 0300 0 Manual changeover 1 1—auto
Deadband 0310 3 Heating and cooling
Temperature Indication Scale
Daylight Savings
0320 0 Temperature is
0330 1 Daylight savings
Factory Setting Other Choices
changeover
setpoints can be set no closer than 3
°
(1.5
C)
displayed in
enabled (United States).
°
F
°
F.
2 thru 9 Heating and
1 Temperature is
0 0—daylight savings
cooling setpoints can be set no c l o s e r t h a n c h o s e n v a l u e :
°
2—2
°
3—3
°
4—4
°
5—5
°
6—6
°
7—7
°
8—8
°
9—9
displayed in °C.
is disabled.
F (1°C ) F (2°C ) F (2.5°C ) F (3°C ) F (3.5°C ) F (4°C ) F (4.5°C ) F (5°C)
CommentsOption Description Options Description
Shown only if automatic changeover is selected.
Set to 0 in areas that do not follow daylight savings.
69-1706 14
Page 15
Select
Remote Temperature Sensor (Outdoor or Indoor)
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 5. Regional Settings Menu. (Continued)
Installer
Setup
Number
0340 0 No remote
Factory Setting Other Choices
temperature sensor
1-3 1—outdoor
temperature sensor for display only. 2—outdoor temperature sensor for control. Used for select heat pump systems. (See Special Heat Pump Features section for more details.) 3—indoor temperature sensor
CommentsOption Description Options Description
Defaults and Options depend on System Type selection. Indoor Temperature Sensor uses an averaging network and does not include on-board sensor.
When number 0210 is set to zero, this item is automatically selected to number 2 and not shown.
Heat Pump Compressor Lockout or (Balance Point)
Heat Pump Auxiliary Lockout
Indoor Dehumidifi­cation Control
0350 0 No compressor
0360 0 No heat pump
0380 0 No indoor
lockout.
auxiliary lockout
dehumidification control
15, 20, 25, 30, 35, 40, 45
40, 45, 50, 55, 60
1 1—dehumidi-
N o l o c k o u t .
°
F (-9.5°C )
15
°
20
F (-6.5°C )
°
25
F (-4°C )
°
30
F (-1°C )
°
35
F (1.5°C )
°
40
F (4.5°C )
°
45
F (7°C)
N o l o c k o u t .
°
F (4.5°C )
40
°
45
F (7°C )
°
50
F (10°C )
°
55
F (13°C )
°
60
F (15.5°C)
fication droop control. (See Advanced Features section for more information.)
Default depends on other selections. Shown if Outdoor Temperature for control is selected. (See Advanced Features section for more information.)
Shown if electric is chosen for backup heat source and outdoor temperature sensor for control is selected. (See Advanced Features section for more information.)
Available on models with humidity sensor.
15 69-1706
Page 16
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 6. Advanced Settings Menu.
Select
Furnace Filter Change Reminder
Humidifier Pad Replace-ment Reminder
UV Lamp Replace-ment Reminder
Adaptive Intelligent Recovery™
Number of Periods
Installer
Setup
Number
0500 0 Furnace filter change
0510 0 Humidifier pad
0520 0 UV Lamp
0530 1 Adaptive Intelligent
0540 4 Four periods
Factory Setting Other Choices
reminder off
replacement reminder off
replacement reminder off
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
available (Wake, Leave, Return, Sleep)
1-6 1—10 run time
1-3 1—90 calendar
1 1—365 calendar
0 0—conventional
2Two periods
d a y s 2—30 run time d a y s 3—60 run time d a y s 4—90 run time d a y s 5—120 run time d a y s 6—365 run time d a y s
d a y s 2—180 calendar d a y s 3—365 calendar d a y s
days
recovery (system starts recovery at programmed time)
available (Wake and Sleep)
CommentsOption Description Options Description
Run time based on call for fan.
Not shown if non­programmable is selected. 2 or 4 applies to all days of the week.
Minimum Compressor Off Time
Heat Temperature Range Stop
Cool Temperature Range Stop
Clock Format 0640 12 12-hour clock format 24 24-hour clock
Extended Fan on time Heat
Extended Fan on time Cool
69-1706 16
0580 5 Five minute minimum
0600 90 Highest heating
0610 50 Lowest cooling
0650 0 No extended fan
0660 0 No extended fan
off time for compressor
setpoint.
setpoint.
operation after call for heat ends
operation after call for cool ends
0, 2, 3, 4 Minimum number
40 to 89 Temperature range
51 to 99 Temperature range
of minutes compressor is off between calls for compressor
(1°F increments) of heating setpoint.
(1°F increments) of cooling setpoint.
format
90 Fan operation is
90 Fan operation is
extended 90 seconds after call for heat ends.
extended 90 seconds after call for cool ends.
Shown in 1/2 °C.
Shown in 1/2 °C.
Not shown if fan operation is set to fossil fuel or in Cool Only Systems
Not shown in Heat Only Systems.
Page 17
Select
Keypad Lockout
Temperature Control in Heat
Temperature Control in Cool
Temperature Display Offset
Reset Thermostat
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
Table 6. Advanced Settings Menu. (Continued)
Installer
Setup
Number
0670 0 Unlocked keypad 1, 2 1— p a r t i a l l y l o c k e d
0680 2 Standard
0690 2 Standard
0700 0 No difference in
0710 0 No thermostat reset. 1 Resets all Installer
Factory Setting Other Choices
k e y p a d 2—fully locked keypad
temperature control in heating
temperature control in cooling
displayed temperature and actual room temperature
1, 3 1—less aggressive
1, 3 1—less aggressive
-3, -2, -1, 0, 1, 2, 3
temperature control (could cause temperature u n d e r s h o o t ) 3—more aggressive temperature control (could cause temperature overshoot)
temperature control (could cause temperature u n d e r s h o o t ) 3—more aggressive temperature control (could cause temperature overshoot)
°
F (-1.5°C )
-3
- 2 ° F ( - 1 ° C )
- 1 ° F ( - . 5 ° C ) 0 F ( 0 . ° C ) 1 ° F ( . 5 ° C ) 2 ° F ( 1 ° C ) 3°F (1.5°C)
Setup Options to default values and resets schedule to default setting.
CommentsOption Description Options Description
Unlocked—all functions are available. Partially locked— only temperature up and down keys and ability to enter and modify Installer Setup mode are a va i l a b l e. Fully locked—only ability to enter and modify Installer Setup mode are available.
Applies to recovery ramp and use of auxiliary heat during recovery.
Choose 1 if getting temperature overshoot.
Choose 3 if getting temperature undershoot.
Applies to recovery ramp.
Choose 1 if getting temperature overshoot.
Choose 3 if getting temperature undershoot.
Only calendar settings and time are retained.
17 69-1706
Page 18
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

SYSTEM CHECKOUT

Installer System Test

The Installer System Test mode is used to test the HVAC system(s). See Table 7. While in System Test mode, minimum off -time for compressors is bypassed.
The Installer Test is part of the Installer Setup options. Entering the Installer Setup screen and pressing the down arrow key to bring up the test selection(s) accesses it quickly. See Fig. 22.
Table 7. System Test(s).
Select
Installer Test Cool
Installer Test Fan
Installer Test Heat
Installer Test Em Ht
Installer
Setup
Number
Test 1 0 Cool is off 1,2 0—cool off
Test 2 0 Fan is off 1 0— f a n o f f
Test 3 0 Heat is off 1-3 0— h e a t o f f
Test 4 0 Emergency heat is
Factory Setting Other Choices
off
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling compressor quickly.
CommentsOptions Description Options Description
1—cool stage 1
tu rns on 2—cool stages 1 and 2 on
1—fan turns on
1—stage 1 heat
o n 2—stages 1 and 2 h e a t o n 3—stages 1, 2 and 3 (Aux Ht) on
1 0—emergency
heat off 1—emergency heat on
System selection determines which tests are available and the number of stages shown.
Available only if heat pump with auxiliary heat is selected.
69-1706 18
Page 19

ADVANCED FEATURES

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

Outdoor or Indoor Temperature Sensor

Allow outdoor or indoor temperature sensor to absorb the air for a minimum of five minutes before taking a reading. See the Sensor instructions for more information.

Special Heat Pump Features

Heat Pump with Fossil Fuel Auxiliary Heat (Dual Fuel) and Outdoor Temperature Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) installed; the thermostat controls this function.
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option is controlling back up heat in Installer Setup Number
0210.
4. Outdoor Temperature Sensor for Control Option is automatically chosen in Installer Setup
Number 0340 (0340 is not shown).
5. Choose appropriate Balance Point Temperature in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected Balance Point Temperature (ISU 0350), only the compressor operates and the fan (G terminal) energizes when the thermostat calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected Balance Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary heat) operates and the fan (G terminal) does not energize when the thermostat calls for heat.
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the Emergency heat mode. When the thermostat is moved to the Emergency Heat position, the compressor is locked out. The first stage of heat is whatever is connected to the E terminal. The second stage of heat is what is connected to the Aux. terminal. Often there is only one source of non-compressor heat and the E terminal is jumped to the Aux. terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup Number 0170.
2. Choose Electric as Auxiliary (Backup) Heat Source in Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor for Control Option in Installer Setup Number 0340.
4. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer Setup Number 0360.
NOTE: There is a 5°F deadband between the
Compressor and Auxiliary Heat Lockout Temperatures
Operation in Heat Mode
When the outdoor temperature is below the Compressor Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout Temperature, only the Compressor operates. See Fig. 24.
COMPRESSOR ONLY
50
BOTH COMPRESSOR AND
AUXILIARY HEAT
35
OUTDOOR TEMPERATURE
Fig. 24. Heat Pump Operation with Lockout
When the outdoor temperature is between the two temperatures, both the Compressor and Auxiliary Heat operate.
AUXILIARY ONLY
Temperatures Set.
AUXILIARY LOCKOUT TEMPERATURE
COMPRESSOR LOCKOUT TEMPERATURE
M19950
Operation in the Emergency Heat Mode
Once the thermostat is placed into the Emergency Heat mode, the compressor and auxiliary lockout features are turned off. In the Emergency heat mode, the compressor is locked out. The first stage of heat is whatever is connected to the E terminal. The second stage of heat is connected to the Aux. terminal. Usually the emergency and auxiliary heat sources are electric strip heat in these cases.
Dehumidification Droop Control
The dehumidification control attempts to control to the user's humidity setpoint by turning on the air conditioner. In extremely high humidity conditions, the thermostat keeps the air conditioner running for up to 3 temperature setpoint. It does this while trying to achieve the desired humidity setpoint and balancing that with the temperature setpoint.
°
F below the
19 69-1706
Page 20
TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

TROUBLESHOOTING (SEE TABLE 8)

Table 8. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Thermostat is not being
Temperature settings do not change.
powered.
The upper or lower temperature limits were reached.
The keypad is fully locked. Check Installer Setup Number 0670 to
Heating or cooling does not come on.
Thermostat is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running.
Thermostat does not respond when touch areas are pressed.
Thermostat minimum off-time is activated.
System selection is not set to Heat or Cool.
O/B terminal is not set correctly (Heat Pumps only).
System type Selection is incorrect.
Heating or cooling equipment is not operating.
The keypad is locked. Check Installer Setup Number 0670 to
Check for 24 Vac between C and Rc. Check that AAA batteries are installed correctly and are good.
Check temperature setpoints. Check Installer Setup Numbers 0600 and 0610; modify as needed.
change keypad locked options.
Wait up to five minutes for the system to respond.
Set system Selection to correct position.
Check Installer Setup Number 0190 and set correctly.
Check Installer Setup Number 0170 and make sure correct System type is chosen.
Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode.
change keypad locked options.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
69-1706 G.H. 01-04 www.honeywell.com/yourhome
M1V 4Z9
Loading...