Honeywell TH8320U, TH8321U User Manual

TH8320U and TH8321U Touch Screen

Programmable Thermostats

INSTALLATION INSTRUCTIONS

APPLICATION

The TH8320U and TH8321U Touch Screen Universal Programmable Thermostats provide electronic control of 24 Vac heating and cooling systems or 750 mV heating system. See Table 1 for a general description.

Table 1. TH832 Thermostats Description.

Model

Power

Changeover

System Selection

Fan Selection

Comments

Method

TH8320U

Batteries or

Automatic or

Heat-Off-Cool-

On-Auto-Circ

System and Fan selection

 

common wire

manual

Auto (Em. Heat for

 

vary based on system type

TH8321U

 

selectable

heat pumps)

 

System and Fan selection

 

 

 

 

 

 

 

 

 

vary based on System type.

 

 

 

 

 

Humidity sensor to control

 

 

 

 

 

dehumidification.

MERCURY NOTICE

If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After completing installation, use these instructions to check out the product operation.

Selecting Location

Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.

NO

 

YES

 

NO

NO

5 FEET

[1.5 METERS]

M19925

Fig. 1. Selecting thermostat location.

® U.S. Registered Trademark

 

Copyright © 2004 Honeywell International Inc. •

• All Rights Reserved

69-1706

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

Do not install the thermostat where it can be affected by:

Drafts or dead spots behind doors and in corners.

Hot or cold air from ducts.

Radiant heat from sun or appliances.

Concealed pipes and chimneys.

Unheated (uncooled) areas such as an outside wall behind the thermostat.

Installing Wallplate

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.

1.Position and level the wallplate (for appearance only).

2.Use a pencil to mark the mounting holes.

WALL

WIRES THROUGH WALL

AND WIRE SLOT

WALL ANCHORS (2)

MOUNTING

HOLES (2)

MOUNTING

SCREWS (2)

M19916

Fig. 2. Mounting wallplate.

3.Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.

4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.

5.Insert the mounting screws into the holes and tighten.

WIRING (FIG. 5-16)

All wiring must comply with local electrical codes and ordinances.

1.Select set of terminal identifications (Table 2) that corresponds with system type (conventional or heat pump in Fig. 3).

2.Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.

3.Securely tighten each screw.

4.Push excess wire back into the hole.

5.Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

HEAT PUMP

CONVENTIONAL

Y2

Y2

RC

RC

L

 

R

R

E

 

W

O/B

AUX

W2

Y

Y

S1

S1

G

G

S2

S2

C

C

 

SCREW TERMINALS

M19951

Fig. 3. Selecting terminal identifications for system type.

Table 2. Selecting Terminal Identifications for System Type.

 

 

 

 

Wallplate

Wiring

System Type

Terminal

Diagram

Identifications

Reference

 

 

 

Standard Heat/Cool

Conventional

5, 6

 

 

 

Heat Only

Conventional

7

 

 

 

Heat Only with Fan

Conventional

8

 

 

 

Heat Only Series 20

Conventional

9

 

 

 

Cool Only

Conventional

10

 

 

 

Standard Multistage

Conventional

11, 12

up to 2 Heat/2 Cool

 

 

 

 

 

Heat Pump with No

Heat Pump

13, 14

Auxiliary Heat

 

 

 

 

 

Heat Pump with

Heat Pump

15, 16

Auxiliary Heat

 

 

 

 

 

M19917

Fig. 4. Inserting wires in terminal block.

IMPORTANT

Use 18 gauge thermostat wire.

69-1706

2

Honeywell TH8320U, TH8321U User Manual

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

 

 

CONTACTOR

 

 

 

 

HEAT RELAY

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19895

Fig. 5. Typical hookup of conventional single-stage heat and cool system with single transformer (1H/1C conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

 

 

CONTACTOR

1

 

 

 

 

HEAT RELAY

C

 

 

 

 

 

 

R

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2REMOVE FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19896

Fig. 6. Typical hookup of conventional single-stage heat and cool system with two transformers (1H/1C conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

HEAT RELAY

 

 

 

 

OUTDOOR/INDOOR

 

 

 

TEMPERATURE

 

 

 

SENSOR

 

 

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19897

Fig. 7. Typical hookup of heat-only system (1H conventional).

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

OUTDOOR/INDOOR

 

RELAY

 

 

 

 

TEMPERATURE

 

 

 

SENSOR

 

HEAT RELAY

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19898

Fig. 8. Typical hookup of heat only system with fan (1H conventional).

3

69-1706

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

 

CONVENTIONAL

Y2

RC

2

 

 

 

R

 

1

 

 

 

 

W

 

 

R

W2

Y

 

 

C

S1

G

 

 

 

S2

C

 

 

 

3

 

 

 

 

OUTDOOR/INDOOR

 

W

B

R

TEMPERATURE

 

 

 

 

 

SENSOR

 

 

 

SERIES 20

 

 

 

 

 

 

 

MOTOR OR

 

 

TR

TR

VALVE

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M19899

 

 

CONVENTIONAL

 

Y2

RC

2

 

 

R

1

 

 

 

W

 

R

W2

Y

 

C

S1

G

 

 

S2

C

OPTIONAL

 

 

 

24 VAC

 

 

 

COMMON

 

 

 

CONNECTION

 

3

 

FAN

 

 

RELAY

 

 

 

 

OUTDOOR/INDOOR

 

 

 

TEMPERATURE

 

COMPRESSOR

 

SENSOR

 

CONTACTOR

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FACTORY INSTALLED JUMPER.

3 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19900

Fig. 10. Typical hookup of cool only system

(1C conventional).

Fig. 9. Typical hookup of heat only Series 20 system.

CONVENTIONAL

 

1

 

 

R

Y2

RC

C

 

R 2

 

 

W

 

W2

Y

 

S1

G

OPTIONAL 24 VAC

S2

C

COMMON CONNECTION

MUST COME FROM

 

 

 

 

THE COOLING

 

 

TRANSFORMER.

OUTDOOR/INDOOR

 

FAN RELAY

TEMPERATURE

 

 

SENSOR

COOL RELAY 2

COOL RELAY 1

 

HEAT RELAY 2

HEAT RELAY 1

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST

HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M19901

Fig. 11. Typical hookup of conventional multistage two-stage heating and two-stage cooling in a single transformer system (2H/2C or 2H/1C or 1H/2C conventional).

69-1706

4

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

CONVENTIONAL

 

 

 

1

 

 

 

 

 

R

 

Y2

RC

2

 

C

 

 

R

 

 

 

 

W

 

 

 

 

W2

Y

 

 

 

 

S1

G

 

OPTIONAL 24 VAC

 

 

S2

C

 

COMMON CONNECTION

 

 

 

MUST COME FROM

 

 

 

 

 

 

 

 

 

 

THE COOLING

 

 

 

 

 

TRANSFORMER.

 

3

OUTDOOR/INDOOR

 

 

FAN RELAY

 

TEMPERATURE

 

 

 

1

 

SENSOR

COOL RELAY 2

COOL RELAY 1

R

 

 

 

 

 

 

 

 

 

C

HEAT RELAY 2

 

HEAT RELAY 1

 

 

 

 

 

 

 

 

 

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER REMOVED.

3OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABL SEPARATE FROM THE THERMOSTAT CABLE.

M19902

Fig. 12. Typical hookup of conventional multistage two-stage heating and two-stage cooling in a two-transformer system (2H/2C or 2H/1C or 1H/2C conventional).

 

 

HEAT PUMP

 

 

1

 

 

 

 

 

 

 

 

 

 

R

 

Y2

 

RC

 

C

 

2

 

 

 

L

 

R

 

 

 

E

 

O/B

3

 

 

AUX

 

Y

 

 

 

SI

 

G

 

 

 

S2

 

C

 

OPTIONAL 24 VAC

 

 

 

 

 

COMMON CONNECTION

4

OUTDOOR/INDOOR

 

 

 

FAN RELAY

TEMPERATURE

 

 

 

 

 

SENSOR

 

CHANGEOVER

COMPRESSOR

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.

4OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M19903

Fig. 13. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).

5

69-1706

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

 

 

HEAT PUMP

 

1

 

 

 

 

 

 

 

 

R

 

Y2

 

RC

C

 

2

 

3

L

 

R

 

 

E

 

O/B

4

 

AUX

 

Y

 

 

SI

 

G

 

 

S2

 

C

OPTIONAL 24 VAC

 

 

 

 

 

 

 

 

COMMON CONNECTION

 

OUTDOOR/INDOOR

 

 

FAN RELAY

5

TEMPERATURE

 

 

 

 

SENSOR

 

CHANGEOVER

 

 

 

 

 

COMPRESSOR 2

VALVE

COMPRESSOR 1

 

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24 VAC OUTPUT. SEE "L TERMINAL" SECTION FOR MORE INFORMATION.

4"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.

5OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE

THERMOSTAT CABLE.

M19904

Fig. 14. Typical hookup of multistage heat pump with no auxiliary/backup heat (2H/2C heat pump).

 

 

HEAT PUMP

EQUIPMENT

 

 

MONITOR

 

 

 

1

 

 

 

R

 

Y2

 

C

 

2

 

5

L

R

 

 

E

O/B

6

 

AUX

Y

 

 

SI

G

 

 

S2

C

OPTIONAL 24 VAC

 

 

 

 

 

 

COMMON CONNECTION

3

OUTDOOR/INDOOR

 

FAN RELAY

 

 

 

4

TEMPERATURE

 

 

SENSOR

CHANGEOVER

 

 

 

VALVE

HEAT 2 RELAY

EMERGENCY

COMPRESSOR

(AUXILIARY HEAT)

HEAT RELAY

RELAY

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2FACTORY INSTALLED JUMPER.

3OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.

4OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

5MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24 VAC OUTPUT. SEE "L TERMINAL" SECTION FOR MORE INFORMATION.

6 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.

M19905

Fig. 15. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).

69-1706

6

Loading...
+ 14 hidden pages